Marine Suppression System: Pneumatic Actuator
Marine Suppression System: Pneumatic Actuator
NUMBER
ACTUATOR 1172
P/N C70-233
Marine Suppression System N70-233
Architect and Engineering Specification
UL - Ex 4447
FM 3002238
USCG - 162.161/2/0 (HFC-227ea)
USCG - 162.038/12/0 (CO2)
Pneumatic Actuators, P/N C70-233 and N70-233, allow in the cylinder. The valves are also equipped with a safety
manual actuation of a Fike HFC-227ea or CO2 System for relief disc that will rupture if the cylinder pressure exceeds
industrial or marine applications. Actuator C70-233 is a single- 3,000 psi (20,685 kPa).
step actuator and N70-233 is a two step actuator that is
housed in a weather proof enclosure. These actuators can Both manual actuators include a sturdy mounting bracket
be mounted up to 300 linear feet away from the cylinder to affix the actuator to wall or other structure. Two u-bolts
valves. The actuator connects to the cylinder valve(s) via are used to connect the pressure vessel to the bracket.
1/4" O.D. stainless steel tubing (.035" wall thickness) or The overall dimensions of the actuator P/N C70-233, in-
1/4" galvanized schedule 40 or 80 pipe. For Marine HFC- cluding the bracket, are 5 1/2"w x 24"h x 3"d. The overall
227ea systems actuator N70-233 must be used to fulfill the dimensions of the two-step actuator N70-233, are 24"w x 30
requirements of the United States Coast Guard and NFPA 1/2"h x 8"d.
2001.
September, 2001
Revised Issue
704 S. 10th St l PO Box 610 l Blue Springs, MO 64013-0610 U.S.A. l (816) 229-3405 l Fax (816) 229-0314 l E-mail: [email protected]
OPERATION
The Pneumatic Actuator P/N N70-233 is operated by opening the enclosure door, removing the safety pin, pulling the
lever and turning the accompanying ball valve. The actuator tubing connects directly to the appropriate control valve in a
HFC-227ea or CO2 system.
SPECIFICATIONS
3 1/2" MAX
(89 mm)
2"
(51 mm)
20 1/4"
30 1/2 27 3/4 1/8"(4 mm) Fem
NPT Outlet (510 mm)
(775 mm) (705 mm)
17"
432 mm) 6"
NITROGEN (N2) PNEUMATIC
ACTUATOR CYLINDERASSEMBLY
(152 mm)
WARNING RECHARGE
INSTALLATION
FM
9/32" DIA
(7 mm)
1/4"(6 mm) TYP. 4 PLCS.
Diameter
5 1/2" 4 1/4"
1.00(25 mm) (140 mm) (108 mm)
5 1/2 13.00
(140 mm) (330 mm)
24
(610 mm)
FORM NO. D1172 Copyright 2001 by Fike Corporation All rights reserved PRINTED IN U.S.A.