MM1013-24V/230V (48X96)

selec Operating Instructions


FUNCTIONAL BLOCKS
Timer Operational Modes On Delay, Off Delay, Pulse Special (Up / Down)Timer

Timer Resolution 1 ms
FEATURES
Sec, Min, Hr, Day, Min. Sec, Hr.Min, Day.Hr,
Timer Display Format Hr.Min.Sec, Day.Hr.Min.Sec
Ø Upto 8 Digital inputs
Ø Upto 5 Relays / Digital outputs Counter (8 digits) Up Counter, Down Counter, Up / Down Counter

Communication Ports RS485 ports (slave)

Communication Protocol MODBUS RTU


SPECIFICATIONS
Memory Retention 10 years
Display 7 segment led
24V DC for MM1013-1-24V
Digits 3 digit + (4 + 4) digit Supply Voltage
90 - 270 VAC / DC for MM1013-2-230V
No. of Keys 5
Operating: 0 to 50oC
Temperature Storage: -20 to 60oC
No. of Configurable Keys 4

DIGITAL INPUT Humidity (non-condensing) 95%

No. of Digital Inputs Weight 258 gms


8

Input Type PNP


TERMINAL CONNECTIONS
Input Voltage Range 11 - 28 VDC (abs. max.: 30 VDC)

Response Time Programmable from 1 to 255ms from Front End MM1013-24V MM1013-230V
(Inputs other than fast counter) (Default 10ms)(Also depends on ladder execution time)
I5 I4 I3 I2 I1 I0 I5 I4 I3 I2 I1 I0

Isolation 2 kV 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
DIGITAL OUTPUT - Relay 22 I6 RS485 + 24 22 I6 RS485 + 24
No. of Relay Outputs 5 21 I7 RS485 - 23 21 I7 RS485 - 23
Relay (NO Type) Contact rating NO type; 3 A resistive@240V AC 11 12 13 14 15 16 17 18 19 20 11 12 13 14 15 16 17 18 19 20
NO0 NO1 NO2 NO3 NO4 COM +24V GND +24V GND NO0 NO1 NO2 NO3 NO4 COM
Isolation 2 kV L(+) N(-)

Response Time 20 ms
ORDERING INFORMATION
FUNCTIONAL SPECIFICATIONS
Windows based software for ladder program Product Order Code Accessories Order Code
Programming Method & HMI configuration (ordered seperately)
MM1013-24V Communication cable ACH-001.
Memory Data memory: 16K, Code memory: 223K MM1013
MM1013-230V
No of Objects Maximum 5000 (as per memory) Windows-based software
for ladder programming ACD-003

Minimum Scan Time 200 µsec


Power Supply Module AP-24V-500mA-NS131
Typical Scan Time 1 ms
Note : Select product MM1013 in RS485 to RS232 AC - RS485 - RS232 - 01
Selpro software converter
AC - RS485 - RS232 - ISO

Selec Controls Pvt. Ltd.


Specifications are subject to change, since development is a continuous process.
Telephone: +91-22-40394200 / 40394202
Fax: +91-22-28471733 | Toll free: 1800 227 353
Website: www.selec.com | Email: [email protected] Operating/1008/MM1013-24V/230V/OP313 -V01 (Page 1 of 1)