TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 auxiliary boiler specification RevE
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 auxiliary boiler specification RevE
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 auxiliary boiler specification RevE
NOTE:
E May. 18, 2015 FOR APPROVAL Xue rong Liu liyuan Wu afeng
D Jan. 30, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng
C Nov. 14, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng
B Aug. 06, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng
A May. 04, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng
BABCOCK & WILCOX BEIJING COMPANY LTD. APPD Wu afeng May. 18, 2015
REV NO. E
A - APPROVED
D - REJECTED
SIGNED BY : DATE :
BIP SUPPLIER:
Noted and revised. It has been added operating pressure, design pressure and
3 Is it same as design pressure? If then, it seems quite low.
revised the maximum allowable operating pressure.
5 It need to controlled by aux.boiler deaerator or aux.boiler chemical injection system such as hydrazine. Noted. The dissolved oxygen will be controlled by aux.boiler deaerator.
Because supplied demi.water's pH is 6.5~7.5, ammonia injection to aux.boiler BFP inlet line is Noted. It has been set up a ammonia injection nozzle on the pipe from
6
required by aux.boiler chemical injection system. deaerator outlet to feed pump inlet line.
* Legend
Contractor Purpose: Approval Status:
AP - For Approval A - Approved
RE - For Reference B - Approved with Comments
FC - For Construction C - Returned for Correction
AB - As Built D - Rejected
INFO - For Information I - Accepted for Reference / IB - Accepted for Reference with Comments / R - Returned for Correction
1 / 1
Thai Binh 2 Thermal Power Plant Project - PEB Comment for Transmittal Ref. No TB2-SDC-PEB-TV-6685
Owner/PMC's Comments
1 No comment.
Legend
Contractor Purpose: TB2PEB Approval Status:
AP = For Approval For AP:
FC = For Construction A = Approved
AB = As Built B = Approved with Comments
INFO = For Information C = Returned for Correction
D = Rejected
For RE:
I=Accepted for Reference
IB=Accepted for Reference with Comments
R= Returned for Correction
1 of 1
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS
Flow 5 m3/h
Head 0.54 MPa(g)
NPSH 1 m
Maximum allowable water temperature 120 ℃
Rotational speed 2900 r/min
Motor power 1.5 Kw
Burner:
Quantity 1 Number
Manufacturer EBICO
Model EC12NQR
Capacity 33500 kW
Construction Split Type
Regulation Proportion Modulating
Fuel LFO/HFO
LFO atomizing Compressed air
HFO atomizing Steam
Compressed air pressure ~0.8 MPa(g)
LFO pressure for burner inlet 1 MPa(g)
HFO pressure for burner inlet 1 MPa(g)
Ignitor gun
Quantity 1 Number
KKS No. 09QHL10 AA001
Model 10000001006-10-2
Flow 80 kg/h
Main oil gun
KKS No. 09QHL10 AA002
Quantity 1 Number
Model 20009901039-10
Flow 4500 kg/h
Main Steam Piping:
Material SA-106B
O.D. x Thickness OD273.0x10 mm
Outlet steam flow 35 t/h
Feed Water Piping:
Material SA-106B
O.D. x Thickness OD88.9x5.49 mm
Feed water flow 40 t/h
Blowdown Tank:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material SA-516 Gr70
Thickness 8 mm
ID 900 mm
Maximum allowable operating pressure 0.6 MPa(g)
Design Temperature 200 ℃
Total volume 1.5 m3
Total weight 643 kg
Ammonia Dosing Device
Quantity 1 Number
Manufacturer Zhejiang Alipu Technology Co.,Ltd
Solution Tank (It is a component of Ammonia Dosing Device)
Quantity 1 Number
Volume 0.5 m3
Diameter 805 mm
Design Pressure Atmospheric pressure
Design Temperature 5~50 ℃
Material 304L
Metering pump (It is a component of Ammonia Dosing Device)
Quantity 2 Number
Flow 38 L/h
Head 1 MPa(g)
Material of Over-flow part 316
Phosphate Dosing Device:
Quantity 1 Number
Manufacturer Zhejiang Alipu Technology Co.,Ltd
Solution Tank (It is a component of Phosphate Dosing Device)
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS
Quantity 1 Number
Volume 0.5 m3
Diameter 805 mm
Design Pressure Atmospheric pressure
Design Temperature 5~50 ℃
Material 304L
Metering pump (It is a component of Phosphate Dosing Device)
Quantity 2 Number
Flow 38 L/h
Head 1.6 MPa(g)
Material of Over-flow part 316
Sampling Cooler Device
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Cooler Tank (Produced by pipeline)
Cooler Tank Quantity 3 Number
Cooler Tank Material 304
Cooler Tank Diameter 159 mm
Cooler Tank Thickness 4.5 mm
Ductwork:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material Q235B
Size 549x358x4 mm
Insulation & Lagging:
Insulation material Rock wool/Aluminum silicate
Outter protective plate Aluminum alloy pressed plate
Stack:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material Q235A
Diameter 1200 mm
Thickness 8 mm
Height 20 m
Water quality requirement (Feed water):
Hardness ≤2.0 umol/L
PH(25ºC) 8.8~9.3
Dissolved oxygen ≤15 ug/L
Iron ≤50 ug/L
Copper ≤10 ug/L
SiO2 ≤20 ug/kg
Water quality requirement (Boiler water):
PH(25ºC) 9.0~11.0
PO4-3 5~15 mg/L
SiO2 ≤2.0 ug/kg
TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE