TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 auxiliary boiler specification RevE

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

DOCUMENT SUBMISSION STATUS: AP

NOTE:

E May. 18, 2015 FOR APPROVAL Xue rong Liu liyuan Wu afeng

D Jan. 30, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng

C Nov. 14, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng

B Aug. 06, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng

A May. 04, 2014 FOR APPROVAL Xue rong Liu liyuan Wu afeng

REV. DATE DESCRIPTION DRAWN CHECKED APPROVED APPROVED


OWNER OWNER’S CONSULTANT

VIETNAM OIL AND GAS GROUP (PVN) FICHTNER PVPOWER PCC


EPC CONTRACTOR EPC CONSTRACTOR’S CONSULTANT

PETROVIETNAM CONSTRUCTION JOINT


WORLEYPARSONS
STOCK CORPORATION (PVC)
POWER ISLAND PACKAGE SUPPLIER

SOJITZ CORPORATION DAELIM INDUSTRIAL CO., LTD.


PROJECT TITLE

THAI BINH 2 THERMAL POWER PLANT 2 x 600MW


DRAWING / DOCUMENT TITLE

AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS


BIP SUPPLIER: FUNCTION NAME SIGN DATE
DRWN Xue rong May. 18, 2015

CHKD Liu liyuan May. 18, 2015

BABCOCK & WILCOX BEIJING COMPANY LTD. APPD Wu afeng May. 18, 2015

DOCUMENT NO:TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 No of page: 4 Scale Rev.E


P.O NO. 110180-1600-101-001-A01

ITEM NO. ALL

ITEM DESCRIPTION BOILER AND BOILER BOP

DOCUMENT NO. TB2-SDC.VP101-00QZA-M-M1A-DAS-5001

AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA


DOCUMENT TITLE
SHEETS

REV NO. E

Daelim's Approval Status

Daelim Industrial Co., Ltd.


Job No. 110180

A - APPROVED

B - APPROVED WITH COMMENTS

C - RETURNED FOR CORRECTION

D - REJECTED

N - NOT APPLICABLE(REFERENCE ONLY)

SIGNED BY : DATE :

DIC'S PERMISSION TO PROCEED OR REVIEW TAKEN ON VENDOR


PRINTS SHALL NOT RELIEVE VENDOR FROM ITS RESPONSIBILITIES
OR LIABILITIES UNDER THE PURCHASE ORDER.

BIP SUPPLIER:

BABCOCK & WILCOX BEIJING COMPANY LTD.


Document Review Comment Sheet
PEB Ref. No : TB2-DIC-BWBC-T-1930
Review Status
No. Document No. Rev Title Purpose In Out
AUXILIARY BOILER SPECIFICATION AND
1 TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 D AP - C
TECHNICAL DATA SHEETS
No. Comments Item status Contractor’s Response

1 Is it economizer outlet temperature? Yes. It is economizer outlet temperature.

2 Please add the deaerator length. Noted and revised.

Noted and revised. It has been added operating pressure, design pressure and
3 Is it same as design pressure? If then, it seems quite low.
revised the maximum allowable operating pressure.

4 It means stainless steel? Yes. It means stainless steel.

5 It need to controlled by aux.boiler deaerator or aux.boiler chemical injection system such as hydrazine. Noted. The dissolved oxygen will be controlled by aux.boiler deaerator.

Because supplied demi.water's pH is 6.5~7.5, ammonia injection to aux.boiler BFP inlet line is Noted. It has been set up a ammonia injection nozzle on the pipe from
6
required by aux.boiler chemical injection system. deaerator outlet to feed pump inlet line.

* Legend
Contractor Purpose: Approval Status:
AP - For Approval A - Approved
RE - For Reference B - Approved with Comments
FC - For Construction C - Returned for Correction
AB - As Built D - Rejected
INFO - For Information I - Accepted for Reference / IB - Accepted for Reference with Comments / R - Returned for Correction

1 / 1
Thai Binh 2 Thermal Power Plant Project - PEB Comment for Transmittal Ref. No TB2-SDC-PEB-TV-6685

Document Review Comment Sheet Ref. No TB2-PEB-SDC-M1A-TVI-08794


Approval
No. Document No. Rev Title Purpose
In Out
AUXILIARY BOILER SPECIFICATION AND TECHNICAL
1 TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 D AP - B
DATA SHEETS
Item
No TB2PEB's Comments Contractor's Response
status
I General comment
1 No comment.
1 TB2-SDC.VP101-00QZA-M-M1A-DAS-5001
The water quality please kindly refer to AUXILIARY BOILER
SECTIONAL VIEWS, No.TB2-SDC.VP101-00QZA-M-M1A-DSE-5001. The
Water Quality (Boiler) - Information is lacking. What are limits for conductivity, dissolved oxygen are not required in the boiler water
conductivity, dissolved oxygen, etc. New Response:
1.5 OPEN
PEB Response - Understand response. However, provide water quality The water quality limits for both feed water and boiler water had been included in the
limits for both feed water and boiler water. data sheet TB2-SDC.VP101-00QZA-M-M1A-DAS-5001 Rev.D. The information was
shown in the bottom of the datasheet.

Owner/PMC's Comments
1 No comment.

Legend
Contractor Purpose: TB2PEB Approval Status:
AP = For Approval For AP:
FC = For Construction A = Approved
AB = As Built B = Approved with Comments
INFO = For Information C = Returned for Correction
D = Rejected
For RE:
I=Accepted for Reference
IB=Accepted for Reference with Comments
R= Returned for Correction

1 of 1
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS

AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS


Thai Binh 2 Thermal Power Plant
AUXILIARY BOILER
Units
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Type / Number per 600 MW Unit SZS35-1.3/350-Y / 1 set for 2 units
Boiler parameters:
Evaporiztion Rate at BMCR 35 t/h
Rated steam pressure 1.27 MPa(g)
Rated steam temperature 350 ℃
LFO Consumption 2768 kg/h
HFO Consumption 2899 kg/h
Boiler efficiency ≥91.5 %
Blowdown rate 2 %
Economizer inlet/outlet water temperature 104/154 ℃
Economizer inlet/outlet water pressure 1.55 MPa(g)
Economizer inlet/outlet gas temperature 335/159 ℃
Economizer inlet/outlet gas pressure 2000 Pa(g)
Flue gas flow (160℃) 59549 m3/h
Furnace:
Width 2.4 m
Depth 10.8 m
Height 2.6 m
Design pressure (+/-) 5.5 kPa(g)
Volume 70.2 m3
Effective Projected Radiant Surface (Including Vertical Furnace Exit Plane over Nose) 97.1 m2
Drum:
Material SA-516 Gr70
Thickness (steam drum/water drum) 18/16 mm
ID (steam drum/water drum) 1100/800 mm
Maximum allowable operating pressure 1.5 MPa(g)
Design Temperature 250 ℃
Volume (Normal operation) 20 m3
Volume (Hydraulic test) 25 m3
Total weight(including drum internals) 11198 kg
Safety valve (DRUM)
Quantity 2 Number
Manufacturer Hangzhou World Wides Vavle Co.,Ltd
Model A48Y-300LB
KKS Code 09QHA10AA601/09QHA10AA602
Type Spring
Material SA-216 WCB
Capacity 14516 kg/h
Set pressure 1.59 MPa(g)
Heat Transfer Surface Areas:
Furnace 97.1 m2
Convection pass tubing 414 m2
Superheater 67 m2
Economizer 440 m2
Safety valve (Superheater)
Quantity 1 Number
Manufacturer Hangzhou World Wides Vavle Co.,Ltd
Model A48Y-300LB
KKS Code 09QLB10AA601
Type Spring
Material SA-216 WCB
Capacity 43062 kg/h
Set pressure 1.352 MPa(g)
Safety valve (Deaerator)
Quantity 1 Number
Manufacturer Hangzhou World Wides Vavle Co.,Ltd
Model A28Y-150LB
KKS Code 09QLA10AA601
Type Spring
Material SA-216 WCB
Capacity 1035 kg/h

TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS

Set pressure 0.09 MPa(g)

Tubes/Headers - Material: ASME II A Article 2013 O.D. x Thickness

Header SA-106B OD168.3x7.11


Front water cooling wall
Tube SA-210 A-1 OD60.3x3.91
Header SA-106B OD168.3x7.11
Rear water cooling wall
Tube SA-210 A-1 OD60.3x3.91
Middle water cooling wall Tube SA-210 A-1 OD60.3x3.91
Side of water cooling wall Tube SA-210 A-1 OD60.3x3.91
Convection tubes SA-210 A-1 OD48.3x3.68
Condensation slage bank SA-210 A-1 OD48.3x3.68
Pipe system SA-213 T22 OD42.2x3.56
Superheater
Headers SA-106B OD273.0x9.27
Pipe system SA-106B OD33.4x3.38
Economizer
Headers SA-106B OD168.3x7.11
Deaerator:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material SA-516 Gr70
Thickness 10 mm
ID 2400 mm
Length 6279 mm
Operating Pressure 0.02 MPa(g)
Maximum allowable operating pressure 0.2 MPa(g)
Design Pressure 0.2 MPa(g)
Design Temperature 150 ℃
Total volume 26 m3
Total weight 4960 kg
FD Fan:
Quantity 1 Number
Manufacturer Jiangsu Nantong Zhongnan Blower Co.,Ltd
Type Centrifugal
Model 9-26 No.11.2D
Material
Casing Q235
Bearing AISI52100
Impeller Q235
Main shaft 45
Air inlet temperature 20 ℃
Flow 42221 m3/h
Total pressure 6382 Pa
Rotational speed 1450 r/min
Motor power 132 Kw
Boiler Feedwater Pump:
Quantity 2 Number
Manufacturer Shandong Sure Boshan Pump Industry Co.,Ltd
Model 80DG50×4
Material
Casing QT500-7
Bearing AISI52100
Impeller HT200
Main shaft 40CrV
Flow 50 m3/h
Head 2 MPa(g)
NPSH 3.4 m
Maximum allowable water temperature 110 ℃
Rotational speed 2950 r/min
Motor power 55 Kw
Sewage Sump Pump:
Quantity 1 Number
Manufacturer NANFANG PUMP INDUSTRY CO.,LTD
Model CDLF4-8
Material
Casing 304
Bearing SUJ2
Impeller 304
Main shaft 304

TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS

Flow 5 m3/h
Head 0.54 MPa(g)
NPSH 1 m
Maximum allowable water temperature 120 ℃
Rotational speed 2900 r/min
Motor power 1.5 Kw
Burner:
Quantity 1 Number
Manufacturer EBICO
Model EC12NQR
Capacity 33500 kW
Construction Split Type
Regulation Proportion Modulating
Fuel LFO/HFO
LFO atomizing Compressed air
HFO atomizing Steam
Compressed air pressure ~0.8 MPa(g)
LFO pressure for burner inlet 1 MPa(g)
HFO pressure for burner inlet 1 MPa(g)
Ignitor gun
Quantity 1 Number
KKS No. 09QHL10 AA001
Model 10000001006-10-2
Flow 80 kg/h
Main oil gun
KKS No. 09QHL10 AA002
Quantity 1 Number
Model 20009901039-10
Flow 4500 kg/h
Main Steam Piping:
Material SA-106B
O.D. x Thickness OD273.0x10 mm
Outlet steam flow 35 t/h
Feed Water Piping:
Material SA-106B
O.D. x Thickness OD88.9x5.49 mm
Feed water flow 40 t/h
Blowdown Tank:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material SA-516 Gr70
Thickness 8 mm
ID 900 mm
Maximum allowable operating pressure 0.6 MPa(g)
Design Temperature 200 ℃
Total volume 1.5 m3
Total weight 643 kg
Ammonia Dosing Device
Quantity 1 Number
Manufacturer Zhejiang Alipu Technology Co.,Ltd
Solution Tank (It is a component of Ammonia Dosing Device)
Quantity 1 Number
Volume 0.5 m3
Diameter 805 mm
Design Pressure Atmospheric pressure
Design Temperature 5~50 ℃
Material 304L
Metering pump (It is a component of Ammonia Dosing Device)
Quantity 2 Number
Flow 38 L/h
Head 1 MPa(g)
Material of Over-flow part 316
Phosphate Dosing Device:
Quantity 1 Number
Manufacturer Zhejiang Alipu Technology Co.,Ltd
Solution Tank (It is a component of Phosphate Dosing Device)

TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE
THAI BINH 2 THERMAL POWER PLANT 2x600MW AUXILIARY BOILER SPECIFICATION AND TECHNICAL DATA SHEETS

Quantity 1 Number
Volume 0.5 m3
Diameter 805 mm
Design Pressure Atmospheric pressure
Design Temperature 5~50 ℃
Material 304L
Metering pump (It is a component of Phosphate Dosing Device)
Quantity 2 Number
Flow 38 L/h
Head 1.6 MPa(g)
Material of Over-flow part 316
Sampling Cooler Device
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Cooler Tank (Produced by pipeline)
Cooler Tank Quantity 3 Number
Cooler Tank Material 304
Cooler Tank Diameter 159 mm
Cooler Tank Thickness 4.5 mm
Ductwork:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material Q235B
Size 549x358x4 mm
Insulation & Lagging:
Insulation material Rock wool/Aluminum silicate
Outter protective plate Aluminum alloy pressed plate
Stack:
Quantity 1 Number
Manufacturer Hangzhou Runpaq Energy Equipment Co.,Ltd
Material Q235A
Diameter 1200 mm
Thickness 8 mm
Height 20 m
Water quality requirement (Feed water):
Hardness ≤2.0 umol/L
PH(25ºC) 8.8~9.3
Dissolved oxygen ≤15 ug/L
Iron ≤50 ug/L
Copper ≤10 ug/L
SiO2 ≤20 ug/kg
Water quality requirement (Boiler water):
PH(25ºC) 9.0~11.0
PO4-3 5~15 mg/L
SiO2 ≤2.0 ug/kg

TB2-SDC.VP101-00QZA-M-M1A-DAS-5001.RevE