SP-8470-0300-0004
SP-8470-0300-0004
SP-8470-0300-0004
TABLE OF CONTENTS
PAGE
1.0 SCOPE 3
1.0 SCOPE
The work includes the design, manufacture, erection, and installation of all mechanical,
electrical, instrumentation and control equipment on skid and ready for installation on site
by others. It also includes labor, supervision, inspection and testing required for the
activated carbon filters, as outlined in this specification and other technical specifications.
The equipment shall be suitable for outdoor operation in tropical southeastern China. All
material, equipment supplied and work carried out including calculation sheets, drawings,
quality and class of goods, methods of inspection, constructional peculiarities of
equipment shall comply in every respect with the following technical specification. If
there seems to be a conflict between a specific code and this document, the matter shall
be referred to the Owner's Authorized Representative.
All items furnished by the Vendor shall be new, complete, and functional, as required by
this specification. Each carbon filter system shall include, but not be limited to, the fol-
lowing items:
Vendor shall specify Codes, Standards, and Procedures that the proposed equipment will
be designed and built. As a minimum requirement, the equipment shall be designed in
accordance with the latest editions of all local, state, and federal codes, standards and
practices including the following organizations. In the event of conflict between various
codes and standards, the design shall be based on the most stringent requirements.
The system shall be capable of transferring and treating 50 m 3/hr of feed water (See Table
1, Influent Water Data) from the storage tank by others. The complete system shall
include all necessary equipment, all interconnecting piping, and instrumentations, etc. for
efficient unit operation.
Al (mg/l) 0.03
pH 7.26
The Contractor shall provide a guarantee that the equipment shall continuously meet the
specified performance requirements as on Table 2 –Effluent Water Data.
* After chlorination.
a. The unit shall be designed to remove residual organics from the feed water of 50
m3/hr to comply with World Health Organization (WHO) Drinking Water Standards.
The normal hydraulic loading rate shall be approximately 5.0 gpm/sq. ft.
b. The filter shall produce a continuous filtrate stream and an intermittent
backwash stream. Backwash valves, instrumentation shall be required for
backwash cycles.
c. The carbon bed shall be backwashed when pressure drop across the bed
exceed the preset value.
d. The effluent from the carbon filter shall subject to chlorination to ensure that the water
quality is suitable for human consumption.
e. Filtered water is stored in a potable water storage tank by others prior to distribution to
the potable water grid. A pressurized vessel shall be provided to allow the
potable water to maintained under 4 kg/cm 2 pressure using oil free
compressed air for distribution to the potable water grid. Potable water will be
pumped into the pressurized vessel from the potable water storage tank via
another transfer pumps by others.
4.1 Materials
4.2 Equipment
Vessels shall be cylindrical, carbon steel constructed of 3/16" thick sidewalls and bottom,
1/4" top dish ASTM A-36 carbon steel. The vessel shall be provided with the liquid inlet
on top and outlet on the bottom side. The vessel shall have one 20" quick open manway
that shall provide for carbon filling and vessel access.
The vessel shall be sized to provide 10 minutes contact time at full rated capacity with a
minimum surface loading of 5gpm/sq. ft.
The carbon bed support shall consist of 1" thick type A-36, 19W-4 carbon steel grating,
and supported on the side walls with angle supports and with intermediate supports from
the vessel bottom.
The grating shall be 316 stainless steel 40 mesh screen, held in place with a carbon steel
retainer band held against the vessel wall.
The activated carbon will be virgin grade material, manufactured in a facility from
domestic mined bituminous coal, or coconut shell suitable for potable water treatment. All
granular activated carbon shall be acid-washed prior to shipment. All granular activated
carbon shall conform to the following specifications:
The delivery of the granular activated carbon shall be accompanied by an analysis sheet.
The activated carbon filter system provided by the contractor shall include all
instrumentation and controls required for proper functioning, monitoring, alarming, and
controlling of the complete carbon filter system.
a) The system shall be operated from a local control panel with system status and
operational controls.
Piping and pipe supports shall not be located where they obstruct access to unit
components. Piping shall be designed and arranged for complete drainage.
All equipment furnished for the Carbon Filter System shall be installed on one galvanized
structural steel skid complete with all junction boxes; wiring; conduits; instruments; panels;
piping and valves; skid decking; access ladders, platforms, toeplate and hand rails, etc..
The spacing of mechanical equipment shall provide adequate clearance between any
projection of adjacent equipment, piping, flanges, or valve stems.
The structural steel skid shall be A-36 steel or better. All skid joints shall be continuously
seal welded and skip welding or crevices shall not be permitted. There shall be no
projection of equipment outside the skid edge. Lifting lugs shall be located so that the skid
is balanced during lifting.
Interior and exterior surface preparation shall be in accordance with SSPC-10 and SSPC-
6, respectively. The interior surfaces shall be coated with coal tar epoxy enamel to a
minimum of 16 mil DFT, applied in two (2) 8 mil DFT coats. The exterior and other surface
protection shall meet the project specification.
All tests, inspections and verifications shall be carried out in accordance with each items
specific section as detailed in this specification.
5.1 Inspection
The Owner's Authorized Representative shall be notified prior to the shipment of any
equipment from a manufacturer in order for the Owner's Authorized Representative to
perform a shop inspection of said equipment in the manufacturer's shop. Upon approval
by the Owner's Authorized Representative, equipment may be shipped to the site for
storage.
5.2 Tests
The Contractor shall submit performance test reports in booklet form showing all field
tests performed to adjust each component and all field tests performed to prove
compliance with the specified performance criteria, upon completion and testing of the
installed system.
The environmental design conditions, including climate conditions, are described in the
Project specification, SP-8820-0000-0001, Basic Engineering Design Data.
Specification No. SP-8470-0300-0004
Page 11 of 12
All equipment shall meet noise standard of less than 85 dBA (10X10 -6 N/m2) at 1 meter.
Any deviations shall be clearly stated. Instrument, electrical and other equipment tags
shall be impression stamped stainless steel with 5mm (minimum) characters and
permanently mounted with stainless steel drive screws.
6.1 Demonstration
Field training course shall be provided for designated operating and maintenance staff
members. Training shall be provided for a total period of 5 man-days of normal working
time and shall start after the system is functionally complete but prior to final acceptance
tests. Field training shall cover all of the items contained in the operating and
maintenance manuals.
6.3 Protection
All of the Contractor's work is the responsibility of the Contractor prior to final
acceptance by the Owner's Authorized Representative. Therefore, protection of all
equipment up to the approval point is the responsibility of the Contractor.
All equipment shall be packed, securely anchored and protected for the shipment method
called for in the purchase order. Miscellaneous parts, if any, shall be tagged with
equipment number of equipment to which it belongs. All such parts shall be boxed and
shipped with the unit. Equipment shall be free from scale, dirt, and foreign materials. All
instrumentation, electrical components, piping and valve shall be secured and braced for
shipment. Protection shall be provided against atmospheric corrosion while in transit and
during outdoor storage in a salty water environment. Exposed finished and machined
surfaces, including bolts, shall be given a heavy coat of rust inhibiting compound. All
flanged openings shall be protected with steel cover plates to prevent damage during
shipment. The cover and flange shall be taped for waterproof protection. All other
openings shall be adequately capped for protection.