Modbus Ascii
Modbus Ascii
MODBUS ASCII
Supported Series: MODBUS ASCII CONTROLLER
Website: http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS ASCII
PLC I/F RS485 RS232/RS485
9600/19200/38400/
Baud rate 9600
57600/115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus ASCII protocol
Device Address:
Bit/Word Device type Format Range Memo
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 0x DDDDD 1 ~ 65535 Output bit
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
W 6x DDDDD 1 ~ 65535
Note: EBPro V6.03.02 or later supports 64 bits data type, but please note that the address
limit range is 48 bits in maximum.
PLC Connection Guide
Modbus RTU function code:
0x 0x01 Read coil 0x05 write single coil
1x 0x02 Read discrete input N/A for write operation
3x 0x04 Read input register N/A for write operation
4x 0x03 Read holding register 0x10 write multiple registers
3xbit is equivalent to 3x
4xbit is equivalent to 4x
Wiring Diagram:
Diagram 1
RS-232
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS232
Rx TXD
Tx RXD
GND GND
RTS
CTS
PLC Connection Guide
Diagram 2
RS-485 4W
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS485 4W
Rx- Tx-
RX+ Tx+
Tx- Rx-
Tx+ Rx+
GND GND
PLC Connection Guide
Diagram 3
RS-485 2W
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS485 2W
Data- D-
Data+ D+
GND GND