System 800xA Training

Chapter 5 OPC Connectivity

TABLE OF CONTENTS

Chapter 5 OPC Connectivity ......................................................................................................................................................... 1


5.1 General Information ............................................................................................................................................................. 1
5.1.1 Objectives ..................................................................................................................................................................... 1
5.1.2 Legend .......................................................................................................................................................................... 1
5.1.3 Reference Documentation ............................................................................................................................................. 1
5.2 OPC Communication ........................................................................................................................................................... 2
5.2.1 OPC Standard ............................................................................................................................................................... 2
5.2.2 Structure and Data Flow ............................................................................................................................................... 3
5.2.3 MMS Server.................................................................................................................................................................. 4
5.2.4 OPC Terms ................................................................................................................................................................... 4
5.2.5 Controller CPU Load .................................................................................................................................................... 5
5.2.6 AfW OPC Service Model ............................................................................................................................................. 5
5.3 OPC Server Configuration ................................................................................................................................................... 7
5.3.1 Setting up Data Access Connection .............................................................................................................................. 7
5.3.2 Setting up Alarm and Event Connection ....................................................................................................................... 9
5.3.3 Loading Configuration Automatically at Startup .......................................................................................................... 9
5.4 OPC Configuration in System 800xA ................................................................................................................................ 10
5.4.1 Setting up OPC Data Access Connectivity ................................................................................................................. 10
5.4.2 Setting up OPC Alarm and Event Connectivity .......................................................................................................... 13
5.5 Check OPC Connectivity ................................................................................................................................................... 17
5.5.1 Check Control Object Properties ................................................................................................................................ 17
5.5.2 Check the System Services ......................................................................................................................................... 19

Chapter 5 - 1
System 800xA Training

5.1 General Information

5.1.1 Objectives
On completion of this chapter you will be able to:
 Describe communication structure and data flow
 Set up OPC connectivity
 Verify communication (live data)
 Explain the Name Uploader

5.1.2 Legend
> Indicates when you go from one menu to a sub-menu
Italic Indicates object and file names
“ “ Indicates dialog box buttons, tabs, menus etc.
Bold Indicates important topics
Indicates start/explanation of student activity

5.1.3 Reference Documentation


3BSE041880 System 800xA Control
AC 800M Getting Started
3BSE035983 AC 800M - OPC Server
3BSE041434 System 800xA
System Guide – Technical Data and Configuration
3BSE043732 AC 800M - Planning

Chapter 5 - 1
T314-05 OPC Connectivity - RevG.docx

5.2 OPC Communication

5.2.1 OPC Standard


OPC stands for OLE for Process Control. OLE (Object Linking and Embedding) is a
Microsoft technology for objects to interact with each other. OLE is based on COM or
DCOM.
OLE allows placement of “embedded objects” and “linked objects” in a document that
retains the native data used to create them (or a “link” to that data) as well as format
information. In simpler terms, the ‘clipboard’ metaphor of ‘cut’, ‘copy’, and ‘paste’.
A double-click allowed the object data to be automatically brought back into the
original editor.
The OPC Foundation is a non-profit corporation that has established a set of standard
OLE/COM interface protocols advancing interoperability between automation/control
applications, field system/devices and business/office applications in the process
control world.

While OLE was originally designed for office applications (e.g. Word, Excel). OPC
technology is an extension of that protocol for industrial applications.
NOTE! OPC is an open standard.
www.opcfoundation.org
OPC provides a mechanism to provide data from a data source and communicate the
data to any client application in a standard way.
OPC is a group defined protocol for process control data communication. It has three
interfaces as follows:
 OPC Data Access for real time data
 OPC Alarm and Event for event data
 OPC Historical Data Access for historical data

Chapter 5 - 2
System 800xA Training

5.2.2 Structure and Data Flow


The OPC Server for AC 800M is needed for reading run-time data or alarms and
events from controllers. The OPC Server for AC 800M consists of the following parts:
OPC Data Access Server
The OPC Data Access Server provides data from controllers programmed with
Control Builder through an OPC Data Access 2.0 and 1.0A interface.
OPC Alarm and Event Server
The OPC Alarm and Event Server generate a stream of information, mostly event
notifications, and distribute them to the Alarm and Event clients. OPC Alarm and
Event 1.02 standard is supported.

Aspect
Server

Connectivity
Server

The OPC Server must be installed in the same physical node as the Connectivity
Server.
There are a number of basic rules that applies:
 One OPC Server is allowed to subscribe to data from a maximum of 24 AC800M
controllers, or the equivalent number of variables from other controller types.
 A maximum of three OPC Servers are allowed to subscribe to Data Access and/or
Alarm and Event from one controller.
 Multiple OPC Clients can subscribe to data or event notifications from the same
OPC Server.
 A third-party OPC Client should, if possible, be installed on the separate
connectivity server as the OPC Server.

Chapter 5 - 3
T314-05 OPC Connectivity - RevG.docx

5.2.3 MMS Server


The MMS Server resembles a switchboard between the OPC Server and the Control
Network. The server is automatically installed when the Control Builder M, or the
OPC Server is installed, so no further action is required.

MMS stands for “Manufacturing Message Specification” and is an ISO 9506 standard.
For further information look at:
www.nettedautomation.com/standardization/ISO/TC184/SC5/WG2

The protocol defines communication messages transferred between controllers as well


as between the engineering station (such as Control Builder) and the controller (e.g.
downloading an application or reading/writing variables).
It has been developed especially for industrial applications. The protocol can be used
on many different networks, but preferably on the TCP/IP network, which is the most
commonly used network today.

5.2.4 OPC Terms


Data is passed between OPC Servers and OPC Clients via subscriptions made to OPC
Items (tags).

OPC Server
OPC Server is a software application that establishes a connection to the field device
and serves data to OPC compliant applications.

OPC Item
This is the syntax (tag name) used to reference a register or bit location in the field
device (PLC, valve, power monitor meter etc…)

OPC Client
OPC Client is a software application that attaches to an OPC Server application and
establishes the OPC Items it wishes to read/write.

Chapter 5 - 4
System 800xA Training

5.2.5 Controller CPU Load


Communication handling has the lowest priority in an AC 800M controller. It is
therefore important to consider controller CPU load if the communication handling is
vital to the application.
Running at the maximum cyclic load will result in poor capacity and response times
for peer-to-peer and OPC Server for AC 800M communication. It is recommended
that peak cyclic controller load will be kept below 65%, and static cyclic load below
60%, under all conditions. Even lower cyclic loads (30-40%) are desirable if high
communication throughput is important.

5.2.6 AfW OPC Service Model


An Afw Service is designed to run around the clock. It is portioned into several
service groups, each group handling part of the scope of the service. For redundancy
each group can contain several service providers running on different servers.

Aspect 800xA
Directory Clients

Client/Server
Network
Afw OPC Service
Service Group Service Group
Service Service Service Service
Provider Provider Provider Provider

redundant redundant
Connectivity Connectivity
Servers Servers

AC 800M
controllers Controller XXX

Using information from the Aspect Directory, a service handler provides one uniform
interface to the service, relieving the client applications from having to deal with
issues such as how the service is partitioned, redundant service providers, etc.
NOTE! A Service Provider resides always in a dedicated node.

Chapter 5 - 5
T314-05 OPC Connectivity - RevG.docx

A typical example is the OPC communication:

The Afw OPC server concept allows many different OPC servers to be placed under
one common server that unifies access to data from different sources.
This common server provides one set of OPC compliant interfaces, eliminating the
need for client applications to know which OPC server to use for each data item.

Chapter 5 - 6
System 800xA Training

5.3 OPC Server Configuration


All configuration steps in this section must take place in the Connectivity Server.
Start the OPC Server from the Windows Start menu:
ABB Start Menu > ABB Industrial IT 800xA > Control and IO > OPC Server for
AC 800M > OPC Server for AC 800M”.

5.3.1 Setting up Data Access Connection


1. Select the tab card “Data Access”.

2. Type in the controllers IP-Address into the Controller Identity input field. To
simplify the connection of controllers, there is a function to find all available
controllers on the Control Network. Select “View > Available Controllers” to get
a list of controllers.

The controller addresses can be “dragged and dropped” from the list to the OPC
Server Configuration panel.

Chapter 5 - 7
T314-05 OPC Connectivity - RevG.docx

3. Press “Connect”. The “Smiley” indicates that the connection is up and running.

Chapter 5 - 8
System 800xA Training

5.3.2 Setting up Alarm and Event Connection


1. Select the tab card “Alarm and Event”. Choose the controller in the same way as
for the Data Access connection.
2. Press “Connect”. The Alarm and Event connection to the controller exists if the
“smiley” face is shown.

5.3.3 Loading Configuration Automatically at Startup


Once the OPC Server is running and all controllers configured and operational, the
OPC Server configuration can be stored into a configuration file. This file is then
loaded automatically loaded whenever the computer reboots.
1. Select “Settings > Autoload Configuration…” and enable “Autoload
Configuration” by clicking the check box.

2. Click onto the browse button and select the configuration file from disc.

3. Accept all dialogs.

Chapter 5 - 9
T314-05 OPC Connectivity - RevG.docx

5.4 OPC Configuration in System 800xA


To get connectivity to the AC 800M OPC Server some settings are necessary in the
Engineering Workplace. Although the configuration is slightly different between the
DA and AE configuration, the result in the Service Structure is the same.

5.4.1 Setting up OPC Data Access Connectivity


These adjustments are located on the Control Network object, which is placed in the
Control Structure.
1. Click onto the Control Network object and select the OPC Data Source Definition
aspect of this object. Select the tab card “Connectivity”.

2. Press “New” to create a new Service Group. The new Service Group is named
SG_Control_Network by default.

Chapter 5 - 10
System 800xA Training

3. To get a connection from the Service Group to the OPC Server Node, click onto
the “Add” button.

4. Select the OPC Server Node from the list and click “OK”. Press “OK” to create
the new Service Group.

5. Click onto the “Apply” button to finish the setup after you selected the service
group from the name list.

Chapter 5 - 11
T314-05 OPC Connectivity - RevG.docx

6. To get a view about the kind of OPC Server which is used in the System 800xA,
click onto the tab card “OPC Configuration”. This is configured by default as
ABB.AC800MC_OpcDaServer.3.

Chapter 5 - 12
System 800xA Training

5.4.2 Setting up OPC Alarm and Event Connectivity


Prior to configuring the Alarm and Event List display, you must setup the service. You
have to connect to an OPC Alarm Server (collector) before you can get any alarms and
events. The services for Alarm and Event are found in the Service Structure.

1. Go to the Service Structure and select Event Collector, Service.

Chapter 5 - 13
T314-05 OPC Connectivity - RevG.docx

2. Right-click and select “New Object” from the context menu. Select Service Group
and enter a name, such as AC800M OPC AE Collector and click “Create”.

3. Right-click on the newly created Service Group object and select “New Object”
again. Enter a name, such as AC800M OPC AE nodename (where nodename is a
Connectivity Server name) and click “Create”.

Chapter 5 - 14
System 800xA Training

4. Select the “Configuration” tab of the Service Provider Definition aspect for the
Service Provider object. Select the name of the AC 800M Connectivity Server in
the Node drop-down list box and click “Apply”.

5. Navigate to the Service Group object previously created. Select the “Special
Configuration” tab of the Service Group Definition aspect.

6. Select as Alarm Server the OPC Server that is your collector (supplier of alarm
and event information) and click “Apply”.
Usually it is called OPC AE Server for AC 800M.

Chapter 5 - 15
T314-05 OPC Connectivity - RevG.docx

7. Verify that OPC AE Server for AC 800M is set in the Collection Definition drop-
down list box.

Chapter 5 - 16
System 800xA Training

5.5 Check OPC Connectivity

5.5.1 Check Control Object Properties


To check the connectivity you can verify that live data are received from the controller
for a control object in the Control Structure, e.g. a program or an object like a valve.
In this example we use the valve Sxx_V1 to check if the OPC connection is working.

Open the Config View for the Function Block aspect of an object in the Control
Structure. Select the tab card “Property View”. Enable the option “Subscribe for live
data” to get the live data from the OPC-Server.
If the Quality column displays “Good”, then the connection to the OPC Server is ok.

Chapter 5 - 17
T314-05 OPC Connectivity - RevG.docx

Right-click on the object S01Prg_V1 and select “Main Faceplate” to call up the
faceplate for the valve.
If the OPC connection works well, you can switch for instance the valve to Auto
mode. The variable AutoMode will change from “False” to “True”.

Mode
indication

A bad OPC connection is displayed on the faceplate as shown below and you will
not be able to operate the valve. Also the Quality column shows “Bad
communication” in the Property View.

Chapter 5 - 18
System 800xA Training

5.5.2 Check the System Services


The System Status Viewer is an aspect in the Service Structure (located at the
Services object).

This aspect provides knowledge about the services of System 800xA. The OPC
connection is one of the services. The Event Collector service handles the OPC Alarm
and Event stream coming into the system.
The green color indicates that the service is running well. In case of problems a red
color indicates a failed service.

In this example, the OPC connection to Connectivity Server CS21 has some problems
whereas the connection to Connectivity Server CS22 is fine.

 Exercise 5.1

Chapter 5 - 19