B.electrical Motor Starting Methodologies.
B.electrical Motor Starting Methodologies.
When running back emf oppose the applied voltage and thus a small current flows.
Problems of heavy inrush current at the starting time
✈ Heavy sparking at the commutator and even flashovers.
✈ Damage to the armature windings.
✈ Damage to rotating parts of the motor.
✈ Large drop in supply voltage.
Hence for the protection of the motor from high current during starting period (say 5
to 10 seconds), it is necessary to connect a high resistance in series with the armature
of motor at the starting period. The resistance should gradually cut in steps as the
motor gains speed and develop back emf.
The start the motor, the handle is slowly moved against the
control spring force, to make contact with first stud (on position)
of the variable starting resistance. At this point field winding gets
supply through the metal rod and the No-Volt coil is energized.
The metal rod forms parallel path with the starting resistance.
The this point entire starting resistance is available in the
armature circuit. As the handle moved further, it goes on making
contact with divisions 2, 3, 4 etc. When starter handle is at
division 3, the division to 1 and 2 are removed from the circuit.
Solution-
Given Data
V=230V, IL=32A, Ra=0.2 Ω, Rsh=115 Ω
Eb=?
Ish= V/Rsh
=230/115
=2A
Eb=V-IaRa
=230-30*0.2
=224V
Automatic DC starters
Automatic DC starters
The Automatic DC Motor Starter is designed to allow the automatic
starting of the DC Motor/Generator, Model 8501, by sensing the motor
counter electromagnetic force (CEMF) to control the armature current.
In the event of loss of field, the control circuit protects the motor
against overspeed by removing power from the armature.
Thermal/magnetic circuit breakers completely protect the starter.
Connections are made through 4 mm color-coded jacks.
Note that the field rheostat is shorted out until the final starting resistor
is shorted. This keeps the field current at a maximum value to help
create torque to accelerate the motor and load.
1.2 Electrical motor starting methodologies for
AC Motors
1.2.1 Explain the following starting methods for A.C. motors and its
characteristics:
2) It is used for large motors, in which start by direct connection to the network
is not possible. For large motors also the star-delta starter cannot be used,
especially if they are started with a significant load.
• If any fault occurs, the auxiliary coil gets de-energized, and hence the
starter disconnects the motor from supply mains.
Working of DOL Starter
• The above wiring connection is of DOL starter. The DOL starter connects the 3-
phase main with the motor.
• The control circuit is connected to any two phases and energized from them
only.
• When we press the start button, the current flows through contactor coil
(Magnetizing Coil) and control circuit also. The current energizes the contactor
coil and leads to close the contacts, and hence 3-phase supply becomes
available to the motor.
• If we press the stop button, the current through the contact becomes
discontinued, hence supply to the motor will not be available, and the similar
thing will happen when overload relay operates, Since the supply of motor
breaks, the machine will come to rest.
• The contactor coil (Magnetizing Coil) gets supply even though we release start
button because when we release start button, it will get supply from the primary
contacts as illustrated in the diagram of the Direct Online Starter.
• Overload Protection When motor draws excessive current to meet the load requirement and If load
requirement goes beyond the rated limit, termed as Overload.
• Overload protection is a type of security when motor draws over current or excessive current and
causes overheating of the equipment. Overload is also the type of over current. So overload relays are
employed to limit the amount of current drawn. But that does not mean that protects the short circuit.
• Fuse or MCB used in the system protects the over current. Overload protection opens a circuit at
relatively low currents that are a little higher than the rating of the motor.
• Overload currents are likely to damage if they persist for a long time, i.e. it will not trip if a high value
of current flows for a short period such as starting of the motor.
• We often provide the overload protection by an overload relay. Overload relays may be solid-state
devices with adjustable trip setting also called as the electronic relay or by interacting with related
temperature sensors called as a thermal relay or if only operates for excess current flow then called
as a magnetic relay.
• For most motors, the maximum rating of the overload protection device is 125% of the full load
ampere rating.
Advantages of DOL Starter
• Simple and most economical starter.
• More comfortable to design, operate and control.
• Provides nearly full starting torque at starting.
• Easy to understand and troubleshoot.
• DOL starter connects the supply to the delta winding of the motor.
• Induction motors (IMs) are currently the most widespread motors. This is
due to their low cost, simple manufacturing, reliability, and robustness,
while their efficiency is up to 96%.
Electrical Faults : These faults are further sub divided into types such as,
• Single Phasing Fault: Single phasing fault is occurred when any one phase of
supply voltage is getting lost because three phases voltage supply is must require
for normal working of three phase induction motor. Due to this fault the motor could
be burned or heat up.
• Under or Over Supply Voltages Fault: This fault is occurred when supply voltages
are under or over the specific limit. The limit of three phase ac supply voltages is
380 to 440 so when supply voltages are crossed this limit then motor could be
burned or heart up.
• Over Load Fault: This fault is occurred when motor is over loaded means the
higher load is connected at output side of motor and due to this load motor
could be heat up or excessive vibration .
• Earth Fault: Earth fault is occurred when any one phase of supply voltages is
connected to the housing of the motor then motor is totally shorted. In this
condition when any one will touch this motor then he will feel the heavy shock
beside this, the motor would take over current that could be dangerous for
induction motor.
• Inter Turn Short Circuit Fault: Inter turn short circuit fault is the such type of
fault when two turns of same phase or different phases are short circuited.
During this fault the motor could be totally damaged, or coils of that specific
phase could be damaged.
• The lightning energy moves in both directions on the power lines, much like a
rapidly moving wave. This traveling surge causes a large voltage rise in an
extremely short period of time. The large voltage does the most damage on the first
few turns of the motor windings, destroying the insulation and burning out the
motor.
The main faults in the a forementioned electric machines can be classified as
• stator faults resulting in the open or short circuits on one or more stator
windings
• broken rotor bar or end-ring faults on induction motors
• static or/and dynamic air-gap irregularities (rotor eccentricity)
• bearing and gearbox failures
• short circuit in the rotor field windings
• defects of the permanent magnets of PM motors.
• A relay that operates or picks up when it’s current exceeds a predetermined value
(setting value) is called Over Current Relay.
• The input section consists of input terminals where a small control signal is
to be applied. The control section has an electromagnetic coil which gets
energized when control input signal is applied to the input terminals and
the output section consists of an movable armature and mechanical
contacts – movable and stationary, the movement of the armature makes
or breaks the electrical circuit.
For instance, a 125A circuit breaker tripping point (magnetic trip) rated for 200% is
connected to a 100A load circuit. When the load current increase and reach the limit of
125A, it will trip eventually. If the current increase up to 200A, the breaker will operate
instantly and protect the circuit from overcurrent due to short circuit etc.
Overcurrent Protection:
Overcurrent protection is generally a protection against short circuit where excessive current
starts to flow in the circuit which leads to damage the connected equipment.
Fuses, circuit breakers, overcurrent relays, current limiters, temperature sensors and solid
state power switches are used against overcurrent protection devices. In addition, a thermal
magnetic circuit breaker is used for both overcurrent and overload protection.
What is Overload?
• An electrical overload is the condition where the load takes more current than
the normal or rated current.
• For example, a #12 gauge wire can safely carry 20 amperes current. The circuit can
be protected by minimum of 20A or 125% of load amperage i.e. (20A of load current x
125% = 25A). In this case, we must use maximum of 25A circuit breaker for
protection. Now if we use 30A – 35A circuit breaker instead of the rated CB, it means
the circuit breaker will allow about 30 to 35 amperes current to the load circuit which
flows in the wires rated for 20A. In other words, the circuit breaker may allow more
current than the nominal current which can only handle up to 20A. In this case, the
wires may heats up and caught fire or damage the circuit and connected appliances
while the breaker won’t trip as we didn’t use the proper size and rating of circuit
breaker for protection.
• Another example of overload is connecting a 1.5kW load to the 1kW alternator,
inverter or transformer etc or when up to 1.5 times higher current flows through the
circuit rather than the rated current.
• Overload is the overcurrent flow in the circuit which causes overheating in the
connected device hence, overload is a type of overcurrent.
Overload Protection:
• Overload protection is actually a protection against overheat due to the
flow of overcurrent in the circuit for specific time.
• Slow blow fuses and overload relays are used against overload protection
whereas, thermal magnetic circuit breaker are used for both overcurrent
and overload protection. The “magnetic” element provides protection
against overcurrent and “thermal” element protects the circuit from
“overload” where it operate on inverse time curve i.e. the tripping time
becomes less when current increases.
• Typically, overload protection circuit activated when 120% – 160% greater
current starts to flow in the circuit than the rated current by power supply.
What is Overvoltage?
• Overvoltage is the condition where the operating or supply voltage is higher than
the rated voltage of the system specified by the manufacturer.
• As the name suggests, overvoltage is the higher supply voltage to a device than its nominal
rated voltage. In short, voltage higher than the permissible voltage is known as overvoltage.
• Generally, when the supply voltage increases up to 1.1 (which is 110%) of the rated voltage of
a device is known the overvoltage unless specified by the manufactures.
• For instance, if the rated voltage printed on the nameplate data rating of a machine is 230V
AC ±10%. Now, If the supply voltages increase up to 250V+, the system becomes unstable
due to overvoltage (iron losses) which leads to excessive heat and may damage the device
and equipment.
• Overvoltage Protection:
• overvoltage caused by lightning strikes, power system and switching surges and insulation
failure etc can be protected by avalanche diodes, voltage dependent resistors (VDR), gas
discharge valves, lightning rods, arcing horns etc.
• Generally, zener diode based electronic circuit are mostly used for small level overlarge
protection. An overvoltage protection circuit will operate when the supply voltage increases up
to 110% to 130% above the rated voltage of a device. This way, it will cut off the power supply
to protect the device from overvoltage which may cause to damage the connected device.
1.6 Describe the function of overcurrent trip, time delays and fuses
with both overload and fault currents
What is the function of the over current trip?
• 1. To protect components, equipment and people from risk of fire and electric shock
2. To isolate sub systems from the main system.
• The fusing action begins when the circuit current is high enough to heat the fuse element
and starts it to melt. Once melting begins, a gap is created that the current will “arc”
across. Melting continues and the gap grows wider until it is too wide to sustain the arc. At
that point, current ceases to flow and the overcurrent event is “cleared,” opening and
making the circuit safe.
• It can be seen from the above figure that metal having greater coefficient of thermal
expansion has more expansion when heated. Now we want to use this feature in the
protection of a Motor.
• A bimetallic overload relay consists of a small heater element wired in series with the motor
and a bimetal strip that can be used as a trip lever. The bimetal strip is made of two dissimilar
metals bonded together. The two metals have different thermal expansion characteristics, so
the bimetal strip bends at a given rate when heated. Under normal operating conditions, the
heat generated by the heater element will be insufficient to cause the bimetal strip to bend
enough to trip the overload relay.
• As current rises, heat also rises. The hotter the bimetal strip becomes, the more it bends. In
an overload condition, the heat generated from the heater will cause the bimetal strip to bend
until the mechanism is tripped, stopping the motor. Some overload relays equipped with a
bimetal strip are designed to reset the circuit automatically when the bimetal strip has cooled
and reshaped itself, restarting the motor. If the cause of the overload still exists, the relay will
trip again and reset at given intervals. Care must be exercised in the selection of this type of
overload relay, since repeated cycling will eventually damage the motor.
• It should be noted that the bimetallic strip of Overload Relay will not instantly heat up to bend
rather will take some finite time to heat up and bend and therefore Thermal Overload Relay is
proffered where overcurrent for some short duration is permitted.
• If overload or over current falls down to normal value before this predetermined time, the relay
will not be operated to trip the protected equipment. A typical application of thermal relay is
overload protection of electric motor.
• 1.1.7 Explain what is meant by single phasing and its effects on a motor:
- when running
- when starting
- if continued attempts to start are made
• For proper working of any 3 phase induction motor, it must be connected to a 3
phase alternating current (ac) power supply of rated voltage and load. Once
these three-phase motors are started, they will continue to run even if one of the
three-phase supply lines gets disconnected. The loss of current through one of
these phase supplies is described as single phasing.
• The ship is fitted with hundreds of motors which are responsible for running
different pumps, machinery, and systems. The critical machinery such as steering
gear, main engine, generator, boiler etc. have 3 phase motors attached to them
which run one or the other main or auxiliary system for them.
• Causes of Single Phasing
• Single phasing is a power supply-related electrical fault in case of an induction motor. It occurs
when one of the 3 phase circuits in a three-phase motor is opened; hence the remaining
circuits carry excess current. This condition of Single Phasing is usually caused when:-
• – One or more out of the three back up fuse blows (or fuse wire melts if the fuse is of wire
type)
• – The motor circuit has contactors which supply the current. One of the contactors is open
circuited.
• – A wrong or improper setting of any of the protection devices provided on the motor can
also lead to single phasing
• – If contactor routines are not performed regularly, they might get covered or get coated
with oxidation layer leading to single phasing.
• – The relay contacts for the motor is damaged or broken
• -- One of the wire for the motor circuit is broken
• – Due to equipment failure of the supply system
• – Due to the short circuit in one phase of the star-connected or delta-connected motor
• Effect of Single Phasing
• If the motor is in a stopped condition, it cannot be started as a single phase motor
cannot be a self-starter and also due to the safety system provided in 3 phase
motor to protect it from overheating
• If the single phasing faults occur while the motor is operating, it will continue to
run (unless provided by additional safety cut-out system) because of the torque
produced by the remaining two phases which is produced as per the demand by
the load
• – As the remaining two phase are doing additional work of the one default phase,
they will be overheated which might result in critical damage to the windings
• – The single phasing will lead to increase in the current flow by 2.4 times the
average current value in the remaining two phases
• Single Phasing reduces the speed of the motor, and its rpm will fluctuate
• – The noise and vibration from the motor will be abnormal. This is the result of
uneven torque produced by the remaining two phases
• – Almost all the motor system in the ship has a standby arrangement. If
the motor is selected for standby, with single phasing problem – It will not
start leading to failure of the related system
• – If the problem is not addressed and motor operation is continued,
windings will melt due to overheating and can lead to short-circuiting or
earthing
• In such condition, if the crew of a ship comes in contact with the motor,
he will get an electrical shock which can even be fatal. Overheating of
winding is primarily due to the flow of negative sequence current.
• – It may cause overloading of the power generation machine, i.e.
auxiliary engine, and its alternator
1.1.9 Describe the principle the protection against running with a phase
open circuited
How to Protect Motor from Damage Due to Single Phasing?
• Such a condition requires that the motor is provided with protection that
will disconnect it from the system before the motor is permanently
damaged.
• All motors above 500 KW are to be provided with protection devices or
equipment to prevent any damage due to single phasing.
• The rule stated above does not apply to motors of the steering gear
system installed on the ship. Only on the detection of the single phasing,
an alarm will be sounded; however, the motor will not stop as the
continued operation of the steering motor is essential for safety or
propulsion of the ship, especially when the vessel is in congested waters
or under manoeuvring.
• 1) Electromagnetic Overload Device
• In this device, all the three phases of the motor are fitted with an overload relay. If there is
an increase in the value of the current, then this relay activates automatically and the
motor trips.
• This device works on the principle of the electromagnetic effect produced due to the
current.
• As the current value increases, the electromagnet in the coil also increases which pulls the
relay and activates the trip relay, and the motor is stopped.
• The time delay is provided in this system because while starting the motor draws a lot of
currents which can trip the motor.
• 2) Thermistors
Thermistors are small thermal devices which are used together with an electromagnetic
overload relay. The thermistors are inserted in the three windings of the motor. Any
increase in the current will cause heating in the windings, which is detected by the
thermistors that send signals to the amplifier.
The amplifier is connected to the electromagnetic relay. As soon as a signal is received from
thermistor about overheating, this amplifier increases the current value in the coil of an
electromagnetic relay which activates the trip and the motor stops or trips.
• 3) Bi-metal strip
In this method, the bimetallic strip is placed in such a way that it detects the
overheating in the circuit. As soon as overheating is detected, this bimetallic strip tries
to expand due to two different metal used and because they have a different
coefficient of expansion. The strip attempts to bend towards the metal having a high
coefficient of expansion and finally completes the trip circuit and the motor trips.
4) Standard motor starter overload protection
• It is provided in 3 phase motor to takes care of the single phasing condition.
Overload heaters are provided in all the phases which detect any overload in
the phase, and if the load goes far above spec for the motor, the heaters trip
the starter off before the motor winding is damaged
1.10 Explain why under voltage trips are necessary
1.11 Suitable Operating conditions with respect to speed
1.1.1 State applications where the following speeds are suitable:
• In this case, you can call an induction motor, which is defined as a constant
speed motor. The rotor flux rate lags slightly behind the stator flux and there is a
relative velocity between the stator and the rotor. The difference in engine speed
changes slightly with increasing engine load. In a vacuum, this is called sliding
speed(slip speed). There is very little slip at idle and the torque generated by the
engine matches idle and friction losses. Consequently, at idle speed, the motor
rotates at almost synchronous speed (Ns = 120f / P).
• When the load increases, the motor tries to transfer the load to the mechanical
load, and in this process the motor speed decreases. Decreasing the motor speed
causes slip to increase and the motor draws a large current from the rotor to
transmit torque, which tends to return the motor speed to its original speed.
• The slip of the induction motor ranges from 3% to 5% of the synchronous speed.
As the inductive load increases, the slip decreases within the specified slip range.
Therefore, an induction motor can be called a constant speed motor.
What is two or three fixed speeds Motors?
Dual-speed motors are a cost-effective choice for applications that
only require two speeds, while also lowering the chance of failure.
These motors are often constructed with an operational speed and a
slower speed for easier starting. Without the need of a frequency
converter, dual speed motors may push fans, pumps, hoists, and
other machinery at two distinct speeds.
This sort of motor uses coils to create two distinct magnetic fields, resulting in two
separate speeds. A two-speed motor with two windings can be used to obtain
almost any combination of normal motor speeds, and the two different speeds do
not need to be related to each other by a 2: 1 speed ratio. Thus, a two-speed
motor requiring 1750 rpm and 1140 rpm would need to be a dual-winding motor.
Advantages and Disadvantages of Dual-Speed Motors
motors offer an advantage over other speed control technologies, such as variable
frequency drives, in that they lose less power. This is because the motor consumes
the majority of the power and no electrical pulse switching is performed. In
comparison to other alternative speed control solutions, the system is significantly
simpler and easier to operate.
motor, on the other hand, has the disadvantage of rapid mechanical wear and tear
as a result of changing speeds in such a drastic ratio; this type of connection also
produces high harmonic distortion during pole shifting as the angular distance
between the power generated increases as the poles are decreased in the motor;
this type of connection also produces high harmonic distortion during the shifting of
poles as the angular distance between the power generated increases as the poles
are decreased in the motor.
1.12 Describe briefly how stepped speeds can be provided
• A stepper motor is an electromechanical device which
converts electrical pulses into discrete mechanical
movements.
• The shaft or spindle of a stepper motor rotates in discrete
step increments when electrical command pulses are
applied to it in the proper sequence.
• The motors rotation has several direct relationships to
these applied input pulses. The sequence of the applied
pulses is directly related to the direction of motor shafts
rotation.
• The speed of the motor shafts rotation is directly related
to the frequency of the input pulses and the length of
rotation is directly related to the number of input pulses
applied
• A stepper motor is a digital device. Digital information is processed by the stepper motor
to accomplish an end result, in this case, controlled motion. One may assume that a
stepper motor will dependably follow digital instructions, just as a computer is expected.
This is the distinguishing feature of a stepper motor.
• The stepper motor is an electrical motor that is driven by digital pulses rather than a
continuously applied voltage. Inherent in this concept is open-loop control, wherein a
train of pulses translates into so many shaft revolutions, with each revolution requiring a
given number of pulses.
• Each pulse equals one rotary increment, or step (hence named, stepper, stepping, or step
motor), which is only a portion of one complete rotation.
• Therefore, counting pulses can be applied in the stepper motor to achieve a desired
amount of shaft rotation. The count automatically represents how much movement has
been achieved, without the need for feedback information, as would be the case in servo
systems, and other technologies.
• Although not required, most stepper motors can accommodate an encoder when
desired.
VARIABLE RELUCTANCE STEPPER
MOTORS
• Variable reluctance stepper motors have the simplest design of the three
types, with a soft iron, non-magnetic, toothed rotor and a wound,
electromagnetic stator. Because the rotor is not magnetized, there’s no
attraction between the rotor and stator when the windings aren’t
energized, so variable reluctance motors don’t produce detent torque.
• Their dynamic torque production is relatively low, but they have less
torque drop-off at higher motor speeds, so for mid- to high-speed
applications, they are often a better choice than permanent magnet
designs. Variable reluctance steppers are known, however, for their
relatively high noise levels, so they’re not suitable for applications where
noise is a concern.
•
VARIABLE RELUCTANCE
STEPPER MOTOR
1.13 Basic Speed Control Methods
• The Speed of Induction Motor is changed from Both Stator and
Rotor Side.
• The speed control of three phase induction motor from stator
side are further classified as :
➢ V / f control or frequency control.
➢ Changing the number of stator poles.
➢ Controlling supply voltage.
➢ Adding rheostat in the stator circuit.
• For regenerative braking, the output voltage of generator G is reduced below the induced
voltage of motor M by decreasing the generator field current. This reverses the current
flowing through the armatures of machines G and M. Now machine M works as a
generator and G as a motor. Mechanical energy provided to machine M, either from the
kinetic energy of rotating parts or due to an active load acting on its shaft, is converted into
electrical energy. Electrical energy supplied by Machine M is converted into mechanical
energy by machine G. The ac motor, which now works as a generator, converts the
mechanical energy to electrical energy and feeds it to the ac source.
• Advantages of Ward Leonard System
1. It is a very smooth speed control system over a very wide range (from
zero to normal speed of the motor).
2. The speed can be controlled in both the direction of rotation of the motor
easily.
3. The motor can run with a uniform acceleration.
4. Speed regulation of DC motor in this Ward Leonard system is very good.
5. It has inherent regenerative braking property.
• Rectifier:
• It is the first stage of a variable frequency drive. It converts AC power
fed from mains to DC power. This section can be unidirectional or
bidirectional based on the application used like the four-quadrant
operation of the motor. It utilizes diodes, SCR’s, transistors, and other
electronic switching devices.
• If it uses diodes, converted DC power is uncontrolled output while using
SCR, DC output power is varied by gate control. A minimum of six
diodes are required for the three-phase conversion, so the rectifier unit
is considered as six pulse converter.
• DC bus:
• DC power from the rectifier section is fed to the DC link. This section
consists of capacitors and inductors to smooth against ripples and store
the DC power. The main function of the DC link is to receive, store and
deliver DC power.
• Inverter:
• This section comprises of electronic switches like transistors, thyristors,
IGBT, etc. It receives DC power from DC link and converts into AC which is
delivered to the motor. It uses modulation techniques like pulse width
modulation to vary output frequency for controlling the speed of induction
motor.
• Control circuit:
• It consists of a microprocessor unit and performs various functions like
controlling, configuring drive settings, fault conditions, and interfacing
communication protocols. It receives a feedback signal from the motor as
current speed reference and accordingly regulates the ratio of voltage to
frequency to control motor speed.
1.3 Effect of varying frequency and voltage of A.C. motors
• 1.3.1 Explain Speed