9460 Analog Input Module - en
9460 Analog Input Module - en
1
Series 9460
A4
> 8 channels for 2-wire
transmitters and 4 channels
for 3- and 4-wire transmitters
and current sources
A4
> Intrinsically safe inputs Ex ia IIC
> Galvanic separation between
the inputs and the system
> Open-circuit and short-circuit A4
monitoring for each field circuit
> Module can be replaced
in operation (hot swap)
> New version: Type 9468/32 A4
A4
www.stahl.de
A4
Series 9460 A4
02084E00
A4
The Analog Input Module is used for the connection and supply
of up to 8 x 2-wire or 3-wire transmitters with 0 ... 20 mA or
4 ... 20 mA signals. Each input is individually monitored for open
and short circuits. A4
Inputs and power supplies are short-circuit proof and
intrinsically safe.
The power supply for 4-wire transmitters is provided by an external
voltage source. A4
The interface of the Analog Input Module with the internal data bus
of the BusRail is designed with redundancy.
For operation of HART field devices see Series 9461.
A4
ATEX / IECEx NEC 505 NEC 506 NEC 500
Class I Class I Class II Class III
Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 Division 1 2 1 2 1 2
Ex interface x x x x x x Ex interface x x x x x x Ex interface x x x x x x A4
Installation in x x x*) x*) Installation in x x x*) x*) Installation in x x x*) x*) x*) x*)
*) Restrictions see table explosion protection
A4
A4
WebCode 9460A
A4
2013-06-26·AK00·III·en Remote I/O A4/1
Analog Input Module Ex i / I.S. Inputs, 8 Channels for Zone 1 / Div. 1
Series 9460
Selection Table
Version Description Order number Weight
kg / lbs
Analog Input Module 8 channels for 2-wire transmitters and 4 channels 9460/12-08-11 0.321 / 0.708
for 3- and 4-wire transmitters and current sources
Note Please order terminal separately - see Accessories
Explosion Protection
Global (IECEx)
Gas PTB 06.0001X
Ex ib [ia] IIC/IIB T4
Europe (ATEX)
Gas and dust PTB 99 ATEX 2175
E II 2 (1) G Ex ib [ia] IIC T4 E II (1) D [Ex ia] IIIC
Certificates
Certificates IECEx, ATEX, Brazil (Inmetro), Canada (CSA), Kazakhstan (GOST K),
Russia (GOST R), Serbia (SRPS), USA (FM), Belarus (operating authorisation)
Ship approval ABS, BV, ClassNK, DNV, GL, LR
Safety data
Maximum values 2-wire transmitter 3-wire transmitter 4-wire transmitter
max. voltage Uo / Voc 26.2 V 26.2 V 0V
max. voltage Ui / Vmax -- -- 28 V
max. current Io / Isc 86 mA 86 mA 0 mA
max. current Ii / Imax -- -- 150 mA
max. power Po 561 mW 561 mW 0 mW
Cable parameters (ATEX) 2-wire transmitter 3-wire transmitter 4-wire transmitter
(for inductive or max. capacitance Co / Ca for IIC 97 nF 97 nF --
capacitive circuits) max. capacitance Co / Ca for IIB 0.75 mF 0.75 mF --
max. inductance Lo / La for IIC 2.71 mH 2.71 mH --
max. inductance Lo / La for IIB 15.8 mH 15.8 mH --
effective internal capacitance Ci 0 0 0
effective internal inductance Li 37 mH 73 mH 73 mH
Further parameters
Installation in Zones 1 & 2, Div. 1 & 2, Zones 21 & 22
Further information see respective certifcate and operating instructions
Grounding
(3-wire, 4-wire transmitters, or active mA sources occupy 2 channels)
The field circuits must not be grounded
A4
Signal
Signal range 0 ... 20 mA, 4 ... 20 mA
(adjustable parameters for each channel)
Minimum signal 0 mA
Maximum signal 23.5 mA A4
Supply voltage 16.0 V at 20 mA for 2-wire and 3-wire transmitters
Maximum input 14 Ω
resistance (for 4-wire transmitter / active mA source)
Signal transmission Filter time constant (adjustable parameters)
small medium 50 Hz, 60 Hz A4
Resolution in the range 12.75 bit 14.75 bit 14.75 bit
4 ... 20 mA
Maximum delay from the 32 ms 120 ms 840 ms
input to the internal bus,
0 ... 90 % of the
signal span A4
Max. short-circuit 35 mA for 2-wire and 3-wire transmitters
current
Accuracy of measurement
Note All values in % of the signal span, at 23 °C / 73.4 °F
Measurement Filter time constant (adjustable parameters) A4
deviation small medium 50 Hz, 60 Hz
Maximum measurement 0.075 % 0.05 % 0.05 %
deviation
Ambient temperature 0.1 % / 10 K
influence A4
Operator interface
Operation LED green "RUN"
Fault LED red "ERR"
Settings
Open-circuit and short- ON, OFF (for each channel) A4
circuit monitoring
Value to fieldbus during -10 %, 0 %, 100 % of the signal, alarm code, hold last value
open circuit, short
circuit
Diagnostics
Retrievable Manufacturer, type, version, serial number
A4
parameters
Module faults • Internal primary bus faults
• Internal redundant bus faults
• No response
• Module does not correspond to configuration A4
• Hardware fault
Signal errors for
each channel
Open circuit < < 2.4 / < 3.6 mA (adjustable parameters, 4 ... 20 mA)
Short circuit
Measuring range
> > 23.5 / > 22.8 / > 21 mA (adjustable parameters, 0/4 ... 20 mA)
Over range / under range
A4
Galvanic separation
between power supply 1500 V AC
and system
components
between two input / 500 V AC A4
output modules
between inputs and 500 V AC
system components
The inputs and outputs of an I/O module have a common negative conductor.
A4
2013-06-26·AK00·III·en Remote I/O A4/3
Analog Input Module Ex i / I.S. Inputs, 8 Channels for Zone 1 / Div. 1
Series 9460
Technical Data
Electrical data
Electrical connection
Ex i field signals Plug-in terminals 16-pole with catch, 2.5 mm2 / up to 14 AWG, screw or spring type
Connection diagram X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
0 / 4 ... 20 mA
0 1 2 . . . 7
U
U
06301E00
Ambient conditions
Ambient temperature -20 ... +65 °C / -4 ... +149 °F
Storage temperature -40 ... +70 °C / -40 ... +158 °F
Maximum relative 95 % (no condensation)
humidity
Sinusoidal vibration 1 g in frequency range between 10 ... 500 Hz
(IEC EN 60068-2-6) 2 g in frequency range 45 ... 100 Hz
Semi-sinusoidal shock 15 g (3 shocks per axis and direction)
(IEC EN 60068-2-27)
Electromagnetic Tested according to the following standards and regulations:
compatibility EN 61326-1 (1998) IEC 1000-4-1...6, NAMUR NE 21
Mechanical data
Module enclosure Polyamide 6GF
Fire resistance (UL 94) V2
Degree of protection
(IEC 60529)
Modules IP30
Connections IP20
Mounting / installation
Installation conditions
Mounting type on 35 mm DIN rail NS 35/15
Mounting orientation horizontal and vertical
05869E00
DIN A4 sheet For label plate on I/O modules; 6 labels on each sheet;
print-out using IS Wizard; packaging unit = 20 sheets
162832
A4
A4
09900E00
05872E00
A4
Partition For assembly between intrinsically safe and non-intrinsically safe 162740
connectors of the I/O modules, in order to adhere to the required
50 mm / 2 in distance
02078E00
A4
Dimensional Drawings (All Dimensions in mm / inches) - Subject to Alterations
A4
67 mm / 2.64 "
A4
09879E00
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice.