SIZING CALCULATIONS FOR RUPT

Input Parameters
Units
Flow kg/hr 2000.00
Set Pressure barg 9.50
Over Pressure % 10%
Atmospheric Pressure psia 14.70
Cp/Cv (k) - 1.33
Downstream Pressure psia 14.70
Inlet Temperature Deg C 182.00
Back Pressure bara 1.00
Compressibility factor (Z) - 1
Molecular weight of fluid (M) - 18.01
Specific Gravity of fluid - 0.622
Napier Eqn. Correction Factor (Kn) - 1
Coefficient of Discharge (Kd) - 0.62
Superheat Correction Factor (KSH) - 1

Notes:
1) Value of Kn specified is for P1<1500 psia. In case of higher value of P1, refer formula on Backup Data sheet to calcul
2) If the pressure downstream of the nozzle is less than, or equal to, the critical flow pressure, Pcf, then critical flow w
subcritical flow will occur.
3) If a calculated compressibility factor is not available, a Z value of 1.0 should be used.
4) For saturated steam at any pressure, KSH = 1.0
5) For Rupture Disc, Coefficient of Discharge Kd = 0.62
SIZING CALCULATIONS FOR RUPTURE DISC

Output Parameters
Units Option 1 Option 2
Flow (W) lb/hr 4410.00 4410.00
Set Pressure psia 137.79 137.79
Upstream Relieving Pressure (P1) psia 166.27 166.27
Critical Flow Pressure (Pcf) psia 89.84 89.84
Type of Flow - Critical Flow Critical Flow
Type of Fluid - Steam Gas & Vapour - Subcritical
Inlet Temperature (T) Deg R 819.27 819.27
Back Pressure (P2) psia 14.50 14.50
Ratio of Back Pressure (r) - 0.09 0.09
F2 - 0.23 0.23
C - 349.77 349.77
Required Discharge Area in2 0.8307 1.8162
Equivalent Diameter in 1.0287 1.5211

er value of P1, refer formula on Backup Data sheet to calculate K n


equal to, the critical flow pressure, Pcf, then critical flow will occur & If the downstream pressure exceeds the critical flow pressure, Pc

value of 1.0 should be used.


Option 3
4410.00
137.79
166.27
89.84
Critical Flow
Gas & Vapour - Critical
819.27
14.50
0.09
0.23
349.77
0.8249
1.0251

he critical flow pressure, Pcf, then


SIZING CALCULATIONS FOR PRESSU

Input Parameters
Units
Flow kg/hr 32.00
Set Pressure barg 13.72
Over Pressure % 10%
Atmospheric Pressure psia 14.70
Cp/Cv (k) - 1.40
Downstream Pressure psia 14.70
Inlet Temperature Deg C 40.00
Back Pressure bara 1.50
Compressibility factor (Z) - 1
Molecular weight of (M) - 28.01
Specific Gravity of fluid - 1
Napier Eqn. Correction Factor (Kn) - 1
Coefficient of Discharge (Kd) - 1
Superheat Correction Factor (KSH) - 1
Combination Correction Factor (Kc) - 1.00
Back Pressure Correction Factor (Kb) - 1

Notes:
1) Value of Kn specified is for P1<1500 psia. In case of higher value of P1, refer formula on Backup Data sheet to ca
2) If the pressure downstream of the nozzle is less than, or equal to, the critical flow pressure, Pcf, then critical flo
subcritical flow will occur.
3) If a calculated compressibility factor is not available, a Z value of 1.0 should be used.
4) For saturated steam at any pressure, KSH = 1.0
5) For PRV, Combination Correction Factor Kc = 1 when Rupture Disc is not installed & Kc = 0.9 when Rupture Disc i
SIZING CALCULATIONS FOR PRESSURE RELIEF VALVE

Output Parameters
Units Option 1 Option 2
Flow (W) lb/hr 70.56 70.56
Set Pressure psia 198.99 198.99
Upstream Relieving Pressure (P1) psia 233.59 233.59
Critical Flow Pressure (Pcf) psia 123.40 123.40
Type of Flow - Critical Flow Critical Flow
Type of Fluid - Steam Gas & Vapour - Subcritical
Inlet Temperature (T) Deg R 563.67 563.67
Back Pressure (P2) psia 21.76 21.76
Ratio of Back Pressure (r) - 0.09 0.09
F2 - 0.25 0.25
C - 356.06 356.06
Required Discharge Area in2 0.0060 0.0078
Equivalent Diameter in 0.0875 0.1000
Required Discharge Area mm2 3.8801 5.0622
Required Discharge Area cm 2
0.0388 0.0506

value of P1, refer formula on Backup Data sheet to calculate K n


qual to, the critical flow pressure, Pcf, then critical flow will occur & If the downstream pressure exceeds the critical flow pressure, P

alue of 1.0 should be used.

ure Disc is not installed & Kc = 0.9 when Rupture Disc is installed.
Option 3
70.56
198.99
233.59
123.40
Critical Flow
Gas & Vapour - Critical
563.67
21.76
0.09
0.25
356.06
0.0039
0.0705
2.5176
0.0252

e critical flow pressure, Pcf, then


Type of Fluid
Gas & Vapour - Critical
Gas & Vapour - Subcritical
Steam