Gtd Lecture Notes Itt
Gtd Lecture Notes Itt
GENERATION
TRANSMISSION
&
DISTRIBUTION
5 EHV TRANSMISSION
6 DISTRIBUTION SYSTEM
7 UNDERGROUND CABLE
8 ECONOMICS ASPECTS
9 TYPES OF TARIFF
10 SUBSTATION
CHAPTER-1
GENERATION OF ELECTRICITY
Hydro Electric Power – The power obtained from Energy of Falling water is Known as hydro
Electric Power. Generation of electricity by hydropower (potential energy in stored water) is one of the
cleanest methods of producing electric power. In 2012, hydroelectric power plants contributed about
16% of total electricity generation of the world. Hydroelectricity is the most widely used form of
renewable energy. It is a flexible source of electricity and also the cost of electricity generation is
relatively low.
STORAGE:
Generally water flows excess during one seasons & less during another.So it is made to
PONDAGE:
The water storage if present at far away from power plant then a small pond is required
a. Storage reservoir
It stores water during excess flow periods (Rainy Seasons) & supplied the same
during least flow of periods i.e. (dry seasons)
It can be either natural i.e. lake or artificial made by construction dam across the
river.
b. Dam :– It is the most expensive & important part which is built up concrete or stone
masonry earth or rock fill. It is not only raise the water surface by creating artificial head
but provide pondage or storage.
c. Fore bay :- It serves as regulating reservoir storing water temporary during light load
period & providing same during increased load period i.e. it is either a pond behind the
diversion dam or an enlarge section of canal spread out to accommodate required with of
intake.
d. Spillway :- These are constructed to discharge the over flow water to the downstream.
When the reservoir is full. Generally it acts as safety valve during flood situation.
e. Intake :- Generally intake includes head works i.e. structure at the intake the
conduits & tunnel or flumes which are res possible for diverting & preventing entry of debris
& ice into the turbines. These structures includes booms, screams, rocks or sluices.
SURGE TANK:
Surge tank regulates & maintains required pressure in the penstock. Because during light
load pressure in the penstock becomes more even if which can burst the penstock but surge tank
reduces the pressure by raising water level inside it. Similarly during the low pressure additional
water flows provided by it. So search tank stabilize the velocity & pressure in the penstock.
Generally these are fitted at Entrance to the turbine during in section & repairing these
are shut off.
TAIL RACE :
The water from turbine is discharged to the tail race generally tail race may be same
stream or another one but design & size of tail race should be search that water are free exist.
In hydro power plant water turbines are used as prime movers which convert kinetic
Energy of water into mechanical energy which is further utilized to drive the alternators
generating electric at energy.
Merits :-
1. No fuel is required by such plant because water is the source of energy.
2. It is highly reliable & cheapest & operation & maintenance
3. No. Stand by loss & variable load demand can meet easily
4. Good longer life & robust.
5. Efficiency does not fall with age & it has neat & clean environment due to absence of
smoke & ask.
6. In addition to generation of provides irrigation flood control on navigation.
Demerits :-
1. It covers large area.
2. Constructional cost is very high along with it requires long transmission line as it far
away from load centre.
3. Its O/P is uncertain
STEAM POWER PLANT OR THERMAL POWER PLANT :
The power plant which generates electrical energy from the combustion of coal called
steam power plant
ELEMENTS OF THERMAL POWER PLANT :
Those are such devices which recover the heat from the flue gases on their way to
chimney & raise the temp. of feed water. & air supplied for combustion.
2. CONDENSER:
Steam after explanation through prime movers goes through condenser which
condenses the exhaust steam & also removes air & other unwanted gases from steam
while passing through them.
It is up two types.
These heat the feed water by means of bled steam before supply to the boiler
which dissolves improve efficiency.
5. PRIME MOVER:-
Generally heavy amount of fuel i.e. coal is stored in coal storage his again transfer to
boiler furnace through coal handling plant. Where gates pulverization. After combustion the
resulting ash get transfer to ash storage to ash handling plant.
Here, atmospheric air is drawn by forced draught fan or induced draught fan through air
preheated in which air is heated by heat of flue gases passing to chimney & finally air is passed
to furnace. Similarly, flue gas after passing through boiler & super heater drawn by induced
draught fan via dost collector (Precipitator). Economizer & Airpre heater) Finally Exhausted to
the atmosphere to the chimney.
Generally steam coming from boiler is wet & having high pressure, which again dried &
further super heated by super heater & supply to steam turbine through main valve where it gives
heat energy & passes through condenser.
Now, the condensate steam is extracted from the condenser to the low pressure feed
water by condensate extraction pump.
Where is gets heats up at low pressure & pump to high pressure water heater through
deaerator & finally to boiler through economizer where it get again heat of by heats of flue gas
passing it on the way of chimney.
Here the function deaerator reduces dissolved oxygen in the condensate steam.
Generally a small part of steam & water is passing through different components are
lossed. So water is added to feed water as make up water by makeup water treatment.
The cooling water is supply from the natural source of supply i.e. river, lake canal etc
through screens to remove the matter that might choke condenser tube. The circulation of
cooling water maintenance low pressure in condenser.
These facilities most be available for trans potation of heavy equipment & fuels i.e. near
railway station.
Merits :-
Demerits :-
The power plant which generates electricity by utilizing the vast energy released from
nuclear fission reaction is known as nuclear power.
NUCLEAR FISSION :-
The nuclear reaction in which a heavy nucleus is splited in to small nucleus is splited in
to small nuclei with liberation of vast energy by bombardment of neutron is known as Nuclear
Fission Reaction.
92U
235
+ 0n1 56Ba139 +36Kr94+30n1 + Energy
235
92U + 0n1 92MO106+50Sn128 + 20n1 + Energy.
Note :-
It may be defined as a fission reaction where the neutrons from a previous step continuity
propagate & repeat the reaction i.e.
a. Nuclear Reactor :-
It is the main part of nuclear power plant which is very similar to boiler of thermal power
plant it has following component.
1. Reactor core :-
It contains a number of fuel rods made of U235, U 234
, U233 etc. as uranium gets oxidised
rapidly so fuel rods clad with aluminum stainless steel or zirconium.
2. Moderator :
The moderator moderate or reduces the neurons speed to a value that increase the
probability or fission reactor. The elements which are used as moderator in nuclear
reactor are hydrogen deuterium He , Li, oxygen ,carbon heavy water etc.
3. Control Rods:
The control rods which are made of Boron-10 cadium or Hafnium are inserted in to
nuclear reactor from the top of reactor vessels. The control rods control rate of the
nuclear fission reaction by absorbing neutrons. It can be inserted or taken out as
according to requirement i.e. if we need increased rate of reaction we have to taken out &
vice verse.
4. Coolant :-
It is the medium through which heat generated in the reactor is transferred to the heat
exchanger & it also keeps the reactor at desired temp.
a. The material like air He, H & CO2 amongst the gases light or heavy water amongst the
liquid or molten sodium or lithium amongst the metal used as coolant.
b. Heat Exchanger :-In heat Exchanger the gas is heated or steam is generated by utilizing
heat from nuclear reactor, here heat is connected by heat exchanger tube by circulation.
c. Steam turbine :- The Steam produce in heat exchanger is transferred to steam turbines
through steam valve where heat energy is converted in to mechanical energy.
d. Condenser : The exhausted steam from steam turbine is condensed by condenser &
again feed to heat exchanger by feed water pump.
e. Alternator :- It is coupled to steam turbine & it generate electricity by converting
mechanical energy to convert in to electrical energy.
The factor to be considered while selecting a site for nuclear power plant for economical
deficient generation.
1. It requires more water i.e. two times of thermal power plant of same rating. So it located
near the river, sea side or lake.
2. Distance from populated area:-
Generally these are located for away from populated area due to danger of radio activity.
3. Nearness to load center :-
Those plants can be located near the load center because of absence of transportation.
4. Availability of space for disposal of water :-
Their should have adequate space & arrangement for the disposal of radio activity waste.
5. Types of land :
The land should be strong enough to support the heavy reactor i.e. 10,000 tones weight
with imposed boarding pressure around 50 tones /m2
Merits :-
Disadvantages:
Solar Energy:
Introduction: Solar energy is an important, clean, cheap and abundantly available
renewable energy. It is received on Earth in cyclic, intermittent and dilute form with very low
power density 0 to 1 kW/m2.Solar energy received on the ground level is affected by atmospheric
clarity, degree of latitude, etc. For design purpose, the variation of available solar power, the
optimum tilt angle of solar flat plate collectors, the location and orientation of the heliostats
should be calculated. Units of solar power and solar energy: In SI units, energy is expressed in
Joule. Other units are angley and Calorie where 1 angley = 1 Cal/cm2.day 1 Cal = 4.186 J For solar
energy calculations, the energy is measured as an hourly or monthly or yearly average and is
expressed in terms of kJ/m2/day or kJ/m2/hour. Solar power is expressed in terms of W/m2 or
kW/m2.
Essential subsystems in a solar energy plant:
1. Solar collector or concentrator: It receives solar rays and collects the energy. It may be of
following types: a) Flat plate type without focusing b) Parabolic trough type with line focusing c)
Paraboloid dish with central focusing d) Fresnel lens with centre focusing e) Heliostats with
centre receiver focusing.
2. Energy transport medium: Substances such as water/ steam, liquid metal or gas are used
to transport the thermal energy from the collector to the heat exchanger or thermal storage. In
solar PV systems energy transport occurs in electrical form.
3. Energy storage: Solar energy is not available continuously. So we need an energy storage
medium for maintaining power supply during nights or cloudy periods. There are three major
types of energy storage: a) Thermal energy storage; b) Battery storage; c) Pumped storage hydro-
electric plant.
4. Energy conversion plant: Thermal energy collected by solar collectors is used for
producing steam, hot water, etc. Solar energy converted to thermal energy is fed to steam power
plant.
CHAPTER-2
Here power system generally composed of transmission system and distribution system, which
again divided in to primary and secondary (or sub) Generally voltage is generated in 33kv ( in
advanced countries) 11 kv ( in India) which if transmitted results heaving current and power
loss
Which if transmitted results heavy current and power losses. So there are stepped up to a
higher value i.e. 66kv 132kv 220/230kv and 400kv step up transformer present near generating station
and transfer to primary transmission system. Where it step down and transmitted to secondary
transmission. Again voltage is step down to 33kv or 11kv and transmitted to primary distribution
system from where medium large consumers connected and finally voltage step down to 400v at
secondary distribution system and fed to small consumers.
Voltage regulation :
It is defined as the difference of supply end voltage and relieving end voltage to the receiving end
voltage in other word.
The voltage drop i.e. difference of secondary end voltage and receiving end voltage expressed as a
percentage of receiving end voltage called regulation.
Mathematically
It is defined as the ratio of power delivered at the receiving end to the power sent from the sending end.
= PR/PR + PL X 100
power
An overhead 3-d Transmission line delivers 5000kw at 22kv at 0.8 p.f lagging with
resistance and reactance of 4-2 and 6-2 respectively. Calculate (1) percentage regulation (2) efficiency.
Solution:
VR = 22KV
ZPH = 4+6J
I = 164 -36.86
= 13813.4 + J 393.6
= 13819 1.6
= 13819-12700/12700x100 = 8.825%
Pl = Line wesses
Kelvin’s Law :
The law states that the most economical area of conductor is that for which the total
annual cost of transmission is minimum
Generally annual cost splited into two part
a. Annual charge on capital out lay i.e. P1 + P2 a
b. Annual cost of energy wasted i.e. P3/a
Where P1, P2 and P3 are constants and „A‟ area of X- section of the conductor.
So, total annual cost (C) = P1+P2a+P3/a
For minimum
=P2-P3/a2 = 0
P2.a = P3/a
In other word it can be stated that the most economical area of conductor is that for which the
variable part of annual charge is equal to the cost of energy losses per year.
Graphically :
Limitation :
(i) Difficult to estimate the energy loss in the line without load curve, which is not
available at the time of estimation.
(ii) Annual charge on capital out day i.e. P1+P2 a not true Eg.- neither the cost of cable
dielectric and heath in underground cables the cost of laying vary in this manner.
(iii) Current density, mechanical strength, corona loss are not considered.
(iv) By this low conductor size may be too small to carry the necessary current safely.
(v) Interest and depreciation not determined accurately.
CORONA :
The phenomenon of violet glow, hissing noise and production of zone gas in an overhead
transmission line is known as corona.
In case of polished and smooth, the corona glow will be uniform throughout the length of
the conductor, otherwise the rough points will appear brighter.
In case of D.C. Supply the TVC wire has uniformly glow. While the -ve conductor has spotty
glow.
Formation of corona :
Under normal condition, the air around the conductors contain some ionized particles like free
electrons and +ve ions and neutral molecules. Due to altra-violet ray and radioactivity applied,
the potential gradient is setup in the air. When the potential gradient at the conductor surface
reaches abut 30 kv per cm the velocity acquired by the free electrons is sufficient to strike a
neutral molecule with enough force to dislodge one or more electrons from it. This produce
another ion and one or more free electrons. Those electrons again collides with the other neutral
molecules and produces other dons. This process of ionization is cumulative. As a result corona
is formed.
1. Atmosphere : In stormy weather corona occurs more than in normal weather due to more
ions than the normal weather.
2. Conductor size :
The rough and irregular surface will produce more corona.
3. Spacing between conductors:
If the spacing between the conductor is made very large as compare to their diameter,
there may not be any corona effect
4. Line voltage : In low voltage no corona is formed
It is the minimum phase neutral voltage at which corona glow appears all along the line
conductors.
Due to corona electric energy is lost. Which is dissipated in the form of light, heat, sound and
chemical action. Power loss due to corona is
LINE SUPPORTS
1. High mechanical strength to withstand the weight of conductor and wind loads.
2. Light in weight
3. Long life
4. Cheap in cost
5. Easy accessibility of conductors maintenance.
The line supports used for transmission and distribution of electric power are made in ether wood
,steel, R.C.C. or lattice steel.
WOODEN POLE : Wooden poles are made of woods. this type of poles are used for shorter
spans up to 50 meters. These are mainly used in rural areas.
2. SHACKLE INSULATORS:
For low voltage line less than 11KV shackle insulators are used as strain inhalators. this is also
known as spool insulators. it is used in low voltage distribution limes. Such insulators can be
used either in a horizontal position or in a vertical position. They can be directly fixed to the pole
with a bolt or cross arm. The conductor in the groove is fixed with soft binding wire.
Coesote oil are impregnated in the ground level of the wooden pole for better foundation. these
wooden poles has smaller life 20 to 25 years. Also it has less mechanical strength. it can‟t be
used for voltage higher than 20kv.
Steel poles :
The steel poles are used generally for the distribution purpose in the city areas it has high
mechanical purpose in the city areas. It has high mechanical strength with longer life poles. The
outer surface of the pole is painted for longer life.
1. Rail poles
2. Tabular poles
3. Rolled steel joints
R.C.C. POLES :
STEEL TOWERS:-
TYPES OF INSULATOR
INSULATORS :-
An electrical insulator is a material whose internal electric charges do not flow freely.
In overhead transmission or distribution lines insulators are used to insulate the current flowing
in the conductor to earth through the poles or towers.
The most commonly used materials for insulator of over head line is porcelain.
There are mainly three types of insulator used overhead lines for high voltage.
1. Pen type insulator
2. Suspension type insulator
3. Strain type insulator
There are two other type insulators are used for low voltage over head lines. These are.
1. Pen type insulators : This type of insulator is popularly used in power network up to
33kv system. The pen type insulator is secured to the cross arm on the pole. The live
conductor attached to the top of the pen insulator the shortest distance between conductor
and earth, surrounding the insulator body along which electrical discharge may take place
through air is known as flash over distance.
When the insulator is wet, its outer surface becomes almost conducting. Hence the
flesh over distance of insulator is decreased. So the design of the electrical insulator (pin
type) is umbrella type on the upper part, so that it can protect the rest lower part of the
insulator from rain.
3. Strain insulator :
When there is a dead end of the line or
there is a sharp carve the line is subjected
to greater tension.
In order to relive the line of excessive
tension, strain insulators are used. Strain
insulator consists of an assembly of
suspension insulators. It has considerable
mechanical strength.
1. Stay insulator :
For low voltage range lines, the stays are to be insalated from ground at a height.
Stay Insulator
Calculation of sag :
The sag should be so adjusted that tension in the conductor is within safe limits.
The tension is governed by conductor weight, effects of wind, ice loading and temperature
variations.
1. When supports are at equal levels :
The above figure shows a conductor is placed between two equilevel supports A and B. The
point O is the lowest point.
If L= Length of span
Consider point „P‟ on the conductor let the distance between poin „O‟ and p in horizontal
projection is X.
We get Ty = Wx (x/2)
Y = WX2/2T
S= WL2/8T
CALCULATION OF SAG
H= Difference in levels
between two supports
Sag S2 = WX22/2T
By subtracting S2 from S1
We know X2+X1 =L
Then S2-S1 = WL/2T (X2-X1)
Equation-3 becomes
X1-X2 = 2TH/WL
In some cases the conductor may have ice coating and simultaneously subjected to wind pressure
– At this time the weight of the ice acts vertically down word as the same direction as the weight
of conductor the force due to the wind is assumed to act horizontally as shown in fig. „b‟
The total force on the conductor due to wind and ice coating is the vector sum of horizontal and
vertical forces as shown in fig „C‟
= wind pressure per unit area x projected area per unit length.
Tan = Ww/W+We
By S = Wt L2/2T
In EHV-AC line series inductance (L) and shunt capacitance C influence the performance of line
(Voltage regulation power flow, stability etc.) Significantly and they can‟t be neglected. Here the
a. Increase in size of generating units : In order to reduce the investment cost per kw, The
size of generating units has been constantly increased, thus this increased large amount of
power over long distances can be transmitted technically and economically in EHV
transmission.
b. Pithead steam plants and remote hydro plants :-
Generally steam and hydro-power plants are located accordingly their favourable
characteristics like availability of coal, water, land ,labour, transportation etc. Generally
these are very far away from load centre. Hence transmission of large amount of power
over long distances can only be technically and economically possible by EHV –
Transmission.
c. Surge impedance loading :- Surge impedance loading is the power that line carries
when each phase terminated by a load equal to surge impedance of the line
i.e.ZC=√(L/C)
where L= Series inductance per unit length
C= shunt capacitance per unit length. Hence,
SIL = 3V2/ZC
Therefore voltage at higher value makes large power transmission at economic.
d. Transmission : - The number of circuits and the land requirement for transmission
decreases with adoption of EHV AC transmission. E.g. for transmitting 600MW over
250km at 480 line using two conductor per phase and requiring a right of way of about
40m giving 600/40 = 15mw per meter right of way but if it transmitted by two double
circuit lines at 200kv then it requires a right of 60m giving 600/60 = 10 mw per meter
right of way. So double circuit 400kv line gives this ratio as about 30mw per meter right
of way. Hence EHV line reduces right of way requirement quite substantially.
e. Line cost : The line installation cost per MW per km decreases with increase in voltage
level. Moreover the impact of the cost of losses on the overall transmission costs can be
substantially different at different voltage levels. The total line cost including the cost of
losses per mw per km decreases considerably by use of EHV AC transmission.
a. Corona loss and Radio Interference : Generally corona appears in High voltage
transmission line which not only a source of power loss but it is also a source of
interference with radio and television.
b. Heavy supporting structure and erection difficulties :-
Generally EHV –AC transmission uses bundle conductor, Which results large mechanical
loading on tower. Similarly large air and ground clearances, dynamic forces due to
broken conducts etc makes large mechanical load. Hence strength of tower should be
heavy.
c. Insulation requirement:- Generally EHV – AC transmission requires high insulation to
withstand the voltage surges due to internal sources i.e. switching operation or due to
external sources i.e lightning etc. which produces very high voltage generally 2-3 times
of normal voltage. Hence insulation level depends upon switching over- voltages,
temporary over- voltages and atmospheric over voltages.
ADVANTAGES : HVDC transmission has many technical and Economics advantages over ac
transmission as follows.
1. Cheaper in cost : Bipolar HVDC Transmission lines require two pole conductors which
is very cheap.
2. No skin effect : As there is uniform current distribution in dc so no skin effect in HVDC.
3. Lower transmission losses : HVDC Transmission system needs only two conductors
and therefore the power losses in a dc line is less.
4. Voltage regulation : Due to absence of inductance it has better voltage regulation.
5. Line loading : Generally loading on AC line limited by transient stability limit and line
reactance but no such limit in HVDC lines. It also has no SIL with greater reliability.
6. Low short circuit current : It has no short circuit.
7. Lesser corona loss and radio interference : It has lesser corona loss due to zero
frequency.
8. Higher operating voltages and no reactive power compensation : Generally HVDC
system has high operating voltage with absence of reactive power compensation.
9. No stability limit : There is no stability limit in HVDC transmission system.
LIMITATIONS OF HVDC TRANSMISSION : HVDC Transmission system has following
limitations as follows:
1. Costly terminal equipment : The converters are used in HVDC are very costly along
with the converters produce lot of harmonics both on dc and ac sides, which requires
filtering and smoothing equipment resulting extra additional expense. It also require
complex cooling system and circuit breaker, which again adds cost.
2. More maintenance of line insulators : It requires more maintenance for in insulation
3. Circuit breaking in multi terminal dc system is difficult and costlier.
4. Voltage Transformer: Voltage transformation is not easier in case of dc and hence it has
to be accomplished on the ac side of the system. DC System can‟t be employed for
distribution sub transmission and back bone transmission.
CHAPTER-6
DISTRIBUTION SYSTEM
An electric power distribution system is the final stage in the delivery of electric power. It carries
electricity from transmission system to individual consumer. Distribution lines mainly sub
divided in to two types.
The figure shows the line diagram of a distribution system with the connection of feeders,
distributor and service mains.
1. Feeders : It is a conductor which conduct electricity from substation to the area where
the power is to be distributed. The feeders carries same current because no tapping are
taken from the feeder. The feeder is designed according to the current carrying capacity.
2. Distributor : Consumers take supply from the distributor by tapping. In the above figure
PQ, QR, RS, and PS are the distributor. The voltage drop along its length is considered
before designing a distributor.
3. Service mains : It is a cable which connects the distributor to the consumer‟s energy
meter.
In early days of electrical power distribution system, different feeders were radially come
out from the substation and connected to the primary of distribution transformer directly.
But radial electrical power distribution system has one major drawback that in case of any
feeder failure, the associated consumers would not get any power as there was no alternative path
to feed the transformer. In case of transformer failure also, the power supply is interrupted. In
other words the consumer in the radial electrical distribution system would be in darkness until
the feeder or transformer was rectified.
RING MAIN ELECTRICAL POWER DISTRIBUTION SYSTEM
The drawback of radial electrical power distribution system can be overcome by introducing a
ring main electrical power distribution system. Here one ring network of distributors is fed by
more than one feeder. In this case if one feeder is under fault or maintenance, the ring distributor
is still energized by other feeders connected to it. In this way the supply to the consumers is not
affected even when any feeder becomes out of service .
In this way, supply to the consumers connected to the healthy zone of the ring, can easily be
maintained even when one section of the ring is shutdown. The number of feeders connected to
the ring main electrical power distribution system depends upon the following factors.
1. Maximum demand of the system : If it is more, then more numbers of feeders feed the
ring.
2. Total length of the ring main distributors : If it length is more, to compensate the
voltage drop in the line, more feeders to be connected to the ring system.
3. Required voltage regulation : The number of feeders connected to the ring also depends
upon the permissible allowable, voltage drop of the line.
The sub distributors and service mains are taken off may be via distribution transformer at
different suitable points on the ring depending upon the location of the consumers. Sometimes,
instead of connecting service main directly to the ring, sub distributors are also used to feed a
group of service mains where direct access of ring distributor is not possible.
The most general method of classifying d.c. distributors is the way they are fed by the feeders.
On this basis, d.c. distributors are classified as :
In this type of feeding, the distributor is connected to the supply at one end and loads are taken at
different points along the length of the distributor.
The current in the various sections of the distributor away from feeding point goes on decreasing.
Thus current in section AC is more than the current in section CD and current in section CD is
more than the current in section DE.
The voltage
across the loads away from the feeding point goes on decreasing. In case a fault occurs on any
section of the distributor the whole distributor will have to be disconnected from the supply
mains. Therefore, continuity of supply is interrupted.
RING MAINS:
USE OF DC DISTRIBUTION
supply is required for the operation of variable speed machinery (e.g. d.c. motors),
electrochemical work and electric traction. For this purpose, a.c. power is converted into
d.c. power at the sub-station by using converting machinery e.g. mercury arc rectifiers,
rotary converters and motor–generator sets. The d.c. supply from the sub-station is
conveyed to the required places for distribution.
METHODS OF SOLVING A.C. DISTRIBUTION PROBLEMS :-
The current in different sections of the distributor will be the vector sum of load currents and not
the arithmetic sum in a.c. distribution. Hence the power factor of various load currents have to be
considered when solving A.C. distribution problems.
= VC LR
IAC = I1+I2
= I1 as (Q-L_)-I sin (Q1-L)
+I2 [ as Q2-JsinQ2]
+ Vol + dropin AC
INTRODUCTION
Since the loads having the trends towards growing density. This requires the better
appearance, rugged construction, greater service reliability and increased safety. An underground
cable essentially consists of one or more conductors covered with suitable insulation and
surrounded by a protecting cover. The interference from external disturbances like storms,
lightening, ice, trees etc. should be reduced to achieve trouble free service. The cables may be
buried directly in the ground, or may be installed in ducts buried in the ground.
Advantages
Disadvantages :
The major drawback is that they have greater installation cost and introduce insulation
problems at high voltages compared with equivalent overhead system.
1. High resistivity
2. High mechanical strength
3. High dielectric strength
4. Not affected by acid or alkalis
5. Non- inflammable
6. High tensile strength
7. Low cost
1. Rubber
2. VIR
3. Impregnated paper
4. PVC
5. Varnished cambric
1. Rubber :
It is the most commonly used insulating material. Natural rubber is produced from the
latex of the rubber tree. Synthetic rubber is produced from alcohol or oil products. It
absorbs moisture slightly and is soft. Therefore pure rubber cannot be used as an
insulating material.
It is used for low voltage power distribution systems only. It is prepaired by mixing pure rubber
with mineral matter such as sulphur, zink oxide, red lead etc. it has greater mechanical strength
than pure rubber. The advantages of using this type of rubber for cable is that, the cable becomes
strong and more curable before using VIR as insulation, the copper conductor must be tunnel
well because it attacks copper. (Reacts copper) its use is limited because of its low melting point
and short span of life.
IMPREGNATED PAPER :
It has low capacitance, high dielectric strength and economical. The paper is manufactured with
wood pulp, rags or plant fiber by a suitable chemical process. It has high resistance due to high
resistivity center dry condition. It absorbs a small amount of moisture only, which reduced the
insulation resistance. For this drawback it requires some sort of protective covering. It is
impregnated in insulating oil before used.
POLYVINYL CHLORIDE (PVC):
VARNISHED CAMBRIC :-
It is the cotton cloth impregnated and coated with varnish. The cambric is lapped on the
conductor in the form of a tape and its surface are coated with petroleum jelly compound to
allow for the sliding of one turn over another as the cable is bent.
CLASSIFICATION OF CABLES :
CLASSIFICATION OF CABLES
Things may be classified on many aspects and similar is the case with cables. There are several
ways of classifying cables. These includes classification of cables on the basis of
• 3 Core Cable
• HT Cables : Cables from 1001 volts to 11000 Volts or 11kV are called HT (High
Tension) or HV (High Voltage) cables.
• ST Cables : Cables from 11001 volts to 33000 Volts or 33kV are called ST (Super
Tension) cables.
• EHV Cables : Cables from 33001 volts to 66000 Volts or 66kV are called EHT (Extra
High Tension) or EHV
• Oil & Gas Filled Cables : From 66 kV to 132 kv Oil and Gas Filled cables are used.
• EST Cables : Cables used above 132 W are called EST (Extra Super Tension) cables.
Cables are also classified on the basis of insulation provided in the cable. Following are the type
of cables on the basis of insulation used in the cable -
PIC or PILC : Paper Insulated Cable - Paper is used as insulation to the conductor.
PVC : Poly Vinyle Chloride Cable - PVC is used as insulation to the conductor.
PE : Poly Ethylene - Poly Ethylene is used as insulation to the conductor
PTFE : Poly Tetra Fluoro Ethylene - PTFE is used as insulation to the conductor
XLPE : Cross Linked Poly Ethylene - Cross Linked Poly Ethylene is used as insulation.
This is most commonly used cable in Industry.
On the basis of amount of power to be transferred through the cable. cables are classified into
two categories. These are
• Power Cables : If large amount of power is to be transferred then these are called power
cables. These are further classified on the basis of voltage at which power is to be
delivered.
1. Low Voltage Power Cable : If the voltage in the cable is less then 1000 Volts or I kV
then the cable is called Low Voltage Power Cable.
2. High Voltage Power Cable : If the voltage in the cable is above 1000 Volts or l kV then
the cable is called High Voltage Power Cable.
• Control Cables: If the cable is used to carry very low power signal generally for
controlling equipments then the cables are called control cables.
H.T. Cable :-
H.T. cables are the cables which are used for voltage levels up to 11kv.
Construction :-
Cores or Conductors- A cable may have one or more than one core (conductor) depending
upon the type of service for which it is intended. The conductors are made of tinned copper or aluminium and
are usually stranded in order to provide flexibility to the cable.
Insulation- Each core or conductor is provided with a suitable thickness of insulation, the
thickness of layer depending upon the voltage to be withstood by the cable. The commonly used materials for
insulation are impregnated paper, varnished cambric or rubber mineral compound.
Metallic sheath- In order to protect the cable from moisture, gases or other damaging liquids
(acids or alkalies) in the soil and atmosphere, a metallic sheath of lead or aluminium is provided over the
insulation.
Bedding- Over the metallic sheath is applied a layer of bedding which consists of a fibrous
material like jute or hessian tape. The purpose of bedding is to protect the metallic sheath against corrosion
and from mechanical injury due to armouring.
Armouring- Over the bedding, armouring is provided which consists of one or two layers of
galvanized steel wire or steel tape to protect the cable from mechanical injury. Armouring may not be done
in the case of some cables.
Serving- In order to protect armouring from atmospheric conditions, a layer of fibrous material
(like jute) similar to bedding is provided over the armouring. This is known as serving.
METHODS OF CABLE LYING :
There are three main methods used for laying underground cables.
1. Direct laying.
2. Draw-in system
3. Solid system
2. Direct laying :
The above figure shows how the cable is laying in this method. A trench of about 1.5
meter deep and 45cm wide is dug. Then the trench is covered with a layer of fine sand,
about 10cm thick the cable is laid over the sand. The sand does not allow the entry of
moisture from the ground. Then the cable is covered with another layer of sand of about
10cm thickness.
After that the trench is covered with bricks and other materials to protect the cables from
mechanical injury. When more than one cable is to be laid in the same trench, a
horizontal or vertical inter axial spacing of at least 30cm is provided in order to reduce
the effect of mutual heating. This method of laying under ground cables is simple and
cheap.
3. Draw- in system :
This method of cable laying suitable for congested areas where excavation is
inconvenient. In this method a line of conduits, ducts or tubes made of either iron, glazed
stoneware clay or cement concrete are laid in ground with manholesat suitable positions
along the cable rotate. The cables are then pulled in to position. Separate pipes and ducts
are provided for each cable laid in the same duct. Care must be taken that where the duct
line changes direction, depths, dine so that a large cable may be pulled easily between the
manholes. The distance between the manholes should not be too long so as to simplify
the pulling in the cables.
SOLID SYSTEM :
In this method the cable is laid in open pipes or troughs dug out in earth along the cable route.
The toughing is of cast iron, stoneware, asphalt or treated wood. After laying the cable in
position, the toughing is filled with a bituminous and covered over.
Several methods are used for locating the faults in underground cables. The most popular
methods for locating faults in underground cables known as loop tests. These are as follows.
Let R= Resistance of the conductor loop from the test end to the point „F‟ where the fault occur
X = Resistance from fault point „F‟ to the rest of the faulty cable„C‟
The resistance P and Q are varied till the galvanometer indicates zero.
The balanced position of the Wheatstone bridge where P,Q,R & X are the four arms is P/Q =
R/X
Or P/Q +1 = R/X +1
Or P+Q/Q = R+X/X
Then R+X = 2r
So P+Q/Q = 2r/X
X= Q/P+Q x 2r
D= x/(r/l)
D = Q/P+Q x 2r x L/r
= Q/P+Q x 2L
P/Q = R/X
P/Q+1 = R/X +1
P+Q/Q = R+X/X
If „R‟ is the resistance of each cable
Then R+X = 2r
So P+Q/Q = 2r/X
X = Q/P+Q X 2r
P+Q/Q =( R+X+S1)/(X+S1)
If „r‟ is the resistance of the cable per meter length. The distance of fault from the test end is D =
X/r meters.
CHAPTER-8
The main cause of low Power factor is Inductive Load. As in pure inductive circuit Current lags
900 from Voltage, this large difference of phase angle between current and voltage causes zero
power factor. Basically, all those circuit having Capacitance and inductance (except resonance
circuit (or Tune Circuit) where inductive reactance = capacitive reactance (XL = Xc), so the
circuit becomes a resistive circuit), power factor would be exist over there because Capacitance
and inductance causes in difference of phase angle (ⱷ) between current and voltage.
1. Single phase and three phase induction Motors (Usually, Induction motor works at
poor power factor i.e. at:
2. Varying Load in Power System (As we know that load on power system is varying.
During low load period, supply voltage is increased which increase the magnetizing
current which cause the decreased power factor)
4. Electrical discharge lamps (High intensity discharge lighting) Arc lamps (operate a very
low power factor)
5. Transformers
6. Harmonic Currents
You may also read about:
• Power Factor
• Active, Reactive, Apparent and Complex Power. Simple explanation with formulas.
• How to Calculate the Suitable Capacitor Size in Farads & kVAR for Power factor
improvement (Easiest way ever)
• How to Convert Capacitor Farads into kVAR and Vice Versa (For Power factor
improvement)
Power factor play an important role in AC circuits and power dissipation depends on this factor.
For instant, we know that;
Also,
It is clear from both equations (1) and (2) that Current “I” is inversely proportional to Cosⱷ i.e.
Power Factor.
In other words, When Power Factor increases, Current Decreases, and when Power Factor
Now, in case of Low Power Factor, Current will be increased, and this high current will cause to
the following disadvantages.
Power Loss = I2xR i.e., the larger the current, the greater the line losses i.e. I»Line Losses
In other words,
Thus, if Power factor = 0.8, then losses on this power factor =1/Cos ⱷ2= 1/0.82 = 1.56 times will
be greater than losses on Unity power factor.
As we know that almost all Electrical Machinery (Transformer, Alternator, Switchgears etc)
rated in kVA. But, it is clear from the following formula that Power factor is inversely
proportional to the kVA i.e.
Cos ⱷ = kW / kVA
Therefore, The Lower the Power factor, the larger the kVA rating of Machines also, the larger
the kVA rating of Machines, The larger the Size of Machines and The Larger the size of
Machines, The Larger the Cost of machines.
In case of low power factor, current will be increased, thus, to transmit this high current, we need
the larger size of conductor. Also, the cost of large size of conductor will be increased.
4.) Poor Voltage Regulation and Large Voltage Drop:
Now in case of Low Power factor, Current will be increased. So the Larger the current, the
Larger the Voltage Drop.
Also Voltage Regulation = V.R = (VNo Load – Vfull Load )/ Vfull Load
In case of Low Power Factor (lagging Power factor) there would be large voltage drop which
cause low voltage regulation. Therefore, keeping Voltage drop in the particular limit, we need to
install Extra regulation equipments i.e. Voltage regulators.
In case of low Power Factor, there would be large voltage drop and large line losses and this will
cause the system or equipments efficiency too low. For instant, due to low power factor, there
would be large line losses; therefore, alternator needs high excitation, thus, generation efficiency
would be low.
6.) Penalty from Electric Power Supply Company on Low Power factor
Electrical Power supply Company imposes a penalty of power factor below 0.95 lagging in
Electric power bill. So you must improve Pf above 0.95.
The following devices and equipments are used for Power Factor Improvement.
1. Static Capacitor
2. Synchronous Condenser
3. Phase Advancer
I. STATIC CAPACITOR
We know that most of the industries and power system loads are inductive that take lagging
current which decrease the system power factor (See Disadvantages of Low Power factor) . For
Power factor improvement purpose, Static capacitors are connected in parallel with those devices
which work on low power factor. These static capacitors provides leading current which
neutralize (totally or approximately) the lagging inductive component of load current (i.e.
leading component neutralize or eliminate the lagging component of load current) thus power
factor of the load circuit is improved. These capacitors are installed in Vicinity of large inductive
load e.g Induction motors and transformers etc, and improve the load circuit power factor to
improve the system or devises efficiency.
Suppose,here is a single phase induction load which is taking lagging current (I) and the load
power factor is cosⱷ as shown in fig-1.
In fig-2, a Capacitor (C) has been connected in parallel with load. Now a current (Ic) is flowing
through Capacitor which lead 90° from the supply voltage ( Note that Capacitor provides leading
Current i.e., In a pure capacitive circuit, Current leading 900 from the supply Voltage, in other
words, Voltage are 90° lagging from Current). The load current is (I). The Vectors combination
of (I) and (Ic) is (I') which is lagging from voltage at ⱷ2, as shown in fig 3.
It can be seen from fig 3 that angle of ⱷ2 < ⱷ1 i.e. angle of ⱷ2is less than from angle of ⱷ2 .
Therefore Cosⱷ2, is less than from Cosⱷ1 (Cos ⱷ2> Cos ⱷ1). Hence the load power factor is
improved by capacitor.
Also note that after the power factor improvement, the circuit current would be less than from
the low power factor circuit current. Also. before and after the power factor improvement, the
active component of current would be same in that circuit because capacitor eliminates only the
re-active component of current. Also, the Active power (in Watts) would be same after and
before power factor improvement.
Advantages:
Capacitor bank offers several advantages over other methods of power factor
improvement.
Losses are low in static capacitors
There is no moving part, therefore need low maintenance
It can work in normal connotations (i.e. ordinary atmospheric conditions)
Do not require a foundation for installation
They are lightweight so it is can be easy to installed
Disadvantages:
2. SYNCHRONOUS CONDENSER
When a Synchronous motor operates at No-Load and over-excited then it's called a synchronous
Condenser. Whenever a Synchronous motor is over-exited then it provides leading current and
works like a capacitor. When a synchronous condenser is connected across supply voltage (in
parallel) then it draws leading current and partially eliminates the re-active component and this
way, power factor is improved. Generally, synchronous condenser is used to improve the power
factor in large industries.
Advantages
Disadvantages
It is expensive (maintenance cost is also high) and therefore mostly used by large power
users.
An auxiliary device has to be used for this operation because synchronous motor has no
self starting torque
It produces noise
3. PHASE ADVANCER
Phase advancer is a simple AC exciter which is connected on the main shaft of the motor
and operates with the motor's rotor circuit for power factor improvement. Phase advancer is used
to improve the power factor of induction motor in industries. As the stator windings of induction
motor takes lagging current 90° out of phase with Voltage, therefore the power factor of
induction motor is low. If the exciting ampere-turns are excited by external AC source, then
there would be no effect of exciting current on stator windings. Therefore the power factor of
induction motor will be improved. This process is done by Phase advancer.
Advantages
Lagging kVAR (Reactive component of Power or reactive power) drawn by the motor is
sufficiently reduced because the exciting ampere turns are supplied at slip frequency (fs).
The phase advancer can be easily used where the use of synchronous motors is
Unacceptable
1. Over Loading
2. Improve System Stability
LOAD CURVE
Load curve is a graph with time on x-axis & load megawatt on y-axis.
Load curves are drawn for a generating station are group of generating station connected to each
other to feed a group of load.
Note :- Here time can be taken as hour, Day, week, month or year.
Here during early morning hours demand low & around 5 am. The load starts increasing
because of increasing industrial & traction load around 9 am the load reaches at high value &
remain almost constant till evening except lunch hours & load again starts increasing due to
residential & traction load 7 to 9 pm peak occurs load starts decreasing but Sunday load demand
less as compared any other week days.
The information obtained from daily load curve if we plot the load against hour in a day
for a power station we will gate following below.
The following information can be obtained from daily load curve.
DEMAND FACTOR :
The ratio of the actual maximum demand on the system to the total rated load connected
to the system called demand factor.
Mathematically
Demand factor = maximum demand / connected loads
NOTES :
Generally maximum demand of a group of devices will be always less than the some of
KW & KVA .
The minimum capacity of a generating plant must be such that it meets the maximum demand so,
demand factor determines the capacity & the cost of power requirement to serve gain load.
MAXIMUM DEMAND :
The greatest of all short time interval averaged i.e. 15 minute, 30 min or 60min during a given
period. (A day, a month, OR a year) on the power stations called maximum demand it is called
system peak.
Note :
The maximum demand is not the greatest instantaneous maximum demand but it is the greatest
short time average demand occurring during along period of time under consideration.
LOAD FACTOR :
The ratio of average load to the maximum demand during a certain period of time such as a day,
or a month or a year.
Mathematically,
As, average load < Maximum demand so, load factor is always less than one. In other word load
factor may be also defined as the ratio of no. of units actually generated in a given period to the
no of units which could have been generated had the load or demand remain the maximum valve
throughout this period.
Mathematically,
Load factor = units generated in a given period / maximum demand x No. of hrs operation in that
given period.
DIVERSITY FACTOR :-
As the maximum demands of all the consumers supplied from an installations don‟t occur the
same time. So the maximum demand is always less than some of individual maximum demands
of all consumers connected to it. So the ratio of the individual maximum demand of all the
consumer connected to it so, the ratio of the individual maximum demand of the power station.
Mathematically.
Diversity factor = sum of individual maxm demand / maximum demand on the power station.
[ DIVERSITY FACTOR > 1 ]
Every plant has to have a reserve capacity for the future explanation an increase in load.
Therefore the total install capacity of the plant is usually greater than actually required
(Maximum demand) so the capacity of the plant factor is defined as the average load to the rated
capacity of the power plant i.e.
Capacity / plant factor = Average load / rated capacity of the power plant
In other word capacity factor may also be defined as the actual energy generated / maximum
possible energy that the plant might have generated during a given period i.e.
Plant factor = units are generated in given period/( rated capacity of power plant X no. Of hrs in
the given period)
= (units generated in a given period x maximum demand) / (max demand x rated capacity of
power plant x no. of hrs in the given period)
Capacity of the plant daily energy produced maximum energy that could be produced daily. if
the plant while running as per schedule were fully loaded.
1. Base load :-
The unvarying load which occurs almost the whole day on the stations is known as base
load.
2. Peak load :-
The various peak demands of load & above the base load of the station is known as peak
load.
CHAPTER-9
TARIFF
Tariff means schedule of rates or charges. Tariff in case of Electricity supply is the
schedule/rates frames or supply electrical energy to various classes of consumers.
Objective of tariff: The main objective is to distribute equitably the cost of supplying energy
amount various classification of used. hence tariff consider the following items.
Types of Tariff:
Flat rate tariff: Generally this tariff is schedule by taking in to account load factor & diversity
factor of each category of consumers. So in this tariff the different consumers are charged at
different rate i.e. flat rate for light & fan load are slightly higher than that of power load. This
method is most popular & easily under stood & simple calculation i.e. if energy consumed
during billing period = x unit.
Disadvantages
BLOCK RATE TARIFF: The tariff in which block of energy is charged at higher rate &
succeeding block of energy are charged at progressively reduce rate called block rate tariff.
Advantages :
1. In this tariff consumer gets incentive for consuming more electrical energy which
increases the load factor resulting reduction in generating cost.
In this tariff the total charges are splited into two component i.e. fixed charge & running charges.
Fixed charge : It is independent of energy consumed & proportional to the maximum demand
i.e. it is made at a certain amount per kw of maximum demand & on the basis of the ratioable
values. Of the premises or no. of room excluding bathroom or the connected load or the total
combine kw capacity of all devices of consumers.
Running charge : It is made at a certain amount per kw for the total energy consumed.
Mathematically:
Disadvantage :
Eg.- If company remains closed for a month but company Owner has to pay fixed charge
mandatory.
Problem-1
Compute the cost of electrical energy for consuming 375 kw under block rated tariff quoted as
follows.
Daily load of an industry is 200 kw for 1st hrs, 150kw for next 7 hour, 50 kw for 8 hour & 1kw
for the remaining time. If the tariff is force Rs. 1000 per kw of maximum demand per annum
plus Rs. 2.25 per kwh find the electricity expenditure per year.
POLE-MOUNTED SUB-STATION
The 11 kV line is connected to the transformer ( 11kV / 400 V) through gang isolator and
fuses. The lightning arresters are installed on the H.T. side to protect the sub-station from
lightning strokes. The transformer steps down the voltage to 400V, 3-phase, 4-wire supply. The
voltage between any two lines is 400V whereas the voltage between any line and neutral is
230V. The oil circuit breaker (O.C.B.) installed on the L.T. side automatically isolates the
transformer from the consumers in the event of any fault. The pole-mounted
transformers can also be used. The use of 3-phase transformer (instead of 3 single phase bank of
transformers) permits two advantages. Firstly, only one 3-phase load-tap changing mechanism
can he used. Secondly, its installation is much simpler than the three single phase transformers.
The power transformer is generally installed upon lengths of rails fixed on concrete slabs having
foundations I to 1.5 in deep. For ratings upto 10 MVA, naturally cooled oil immersed
transformers are used. For higher ratings, the transformers are generally air blast cooled.
Bus-bars are the important components in a sub-station. There are several bus-bar
arrangements that can he used in a sub-station. The choice of a particular arrangement depends
upon various factors such as system voltage, position of sub-station, degree of reliability, cost
etc. The following are the important bus-bar arrangements used in sub-stations
(i) Single bus-bar system. As the name suggests, it consists of a single bus-bar and all
the incoming and outgoing lines are connected to it. The chief advantages of this type
of arrangement are low initial cost, less maintenance and simple operation. However,
the principal disadvantage of single bus-bar system is that if repair is to be done on
the bus-bar or a fault occurs on the bus, there is a complete interruption of the supply.
This arrangement is not used for voltages exceeding 33kV. The indoor 1 I kV sub-
stations often use single bus-bar arrangement.
Fig-1
Fig-1 shows single bus-bar arrangement in a sub-station. There are two I l kV incoming
lines connected to the bus-bar through circuit breakers and isolators. The two 400V outgoing
lines are connected to the bus bars through transformers (1 1 kV/400 V) and circuit breakers.
66KV SUB STATION
(i) There are two 66 kV incoming lines marked `incoming 1' and `incoming 2' connected to
the bus-bars. Such an arrangement of two incoming lines is called a double circuit. Each
incoming line is capable of supplying the rated sub-station load. Both these lines can be
loaded simultaneously to share the sub-station load or any one line can be called upon to
meet the entire load. The double circuit arrangement increases the reliability of the
system. In case there is a breakdown of one incoming line, the continuity of supply can
be maintained by the other line.
(ii) The sub-station has duplicate bus-bar system: one 'main bus-bar' and the other spare bus-
bar. The incoming lines can be connected to either bus-bar with the help of a bus-coupler
which consists of a circuit breaker and isolators. The advantage of double bus-bar system
is that if repair is to be carried on one bus-bar, the supply need not be interrupted as the
entire load can be transferred to the other bus.
(iii) There is an arrangement in the sub-station by which the same 66 kV double circuit supply
is going out i.e. 66 kV double circuit supply is passing through the sub-station. The
outgoing 66 kV double circuit line can be made to act as incoming line.
(iv) There is also an arrangement to step down the incoming 66 kV supply to I 1 kV by two
units of 3-phase transformers; each transformer supplying to a separate bus-bar.
Generally, oils transformer supplies the entire sub-station load while the other
transformer acts as a standby unit. If need arises, both the transformers can be called
upon to share the sub-station load. The I 1 kV outgoing lines feed to the distribution sub-
stations located near consumer‟s localities.
(v) Both incoming and outgoing lines are connected through circuit breakers having isolators
on their either end. Whenever repair is to be carried over the line towers, the line is first
switched off and then earthed.
(vi) The potential transformers (P.T.) and current transformers (C.T.) and suitably located for
supply to metering and indicating instruments and relay circuits (not shown in the figure).
The P.T. is connected right on the point where the line is terminated. The CTs are
connected at the terminals of each circuit breaker.
(vii) The lightning arresters are connected near the transformer terminals (on H.T. side) to
protect there from lightning strokes.
viii) There are other auxiliary components in the sub-station such as capacitor bank for power
factor improvement, earth connections, local supply connections, d.c. supply connections
etc. However, these have been omitted in the key diagram for the sake of simplicity.