1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick To display target set point; in programming mode it selects a parameter or confirm
reference. an operation.
The instrument shall not be used for purposes different from those described hereunder. It cannot (UP) To see the max stored temperature; in programming mode it browses the
be used as a safety device. parameter codes or increases the displayed value.
Dixell Srl reserves the right to change the composition of its products, even without notice, (DOWN) To see the min stored temperature; in programming mode it browses the
ensuring the same and unchanged functionality. parameter codes or decreases the displayed value.
1.2 SAFETY PRECAUTIONS
To switch the instrument on and off (when onF=oFF).
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding (AGT) To switch on and off the light (when oA3=LiG).
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
KEY COMBINATIONS:
Warning: disconnect all electrical connections before any kind of maintenance.
The instrument must not be opened.
Fit the probe where it is not accessible by the end user.
+ To lock & unlock the keyboard.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” + To enter in programming mode.
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data). + To return to the room temperature display.
Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining. 5.1 USE OF LEDS
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel
with inductive loads could be useful. Each LED function is described in the following table.
1. Push the SET key more than 2 sec to change the Set point value. CF Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
2. The value of the set point will be displayed and the “°C” or “°F” LED will start blinking. WARNING: When the measurement unit is changed the SET point and the values of
3. To change the Set value push the UP or DOWN arrows within 10 sec. the parameters HY, LS, US, ot, ALU and ALL have to be checked and modified (if
To save the new set point value, push the SET key again or wait for 10 sec. necessary).
rES Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display.
7.3 HOW TO CHANGE A PARAMETER VALUE
AGITATION CYCLE
To change a parameter value, operate as follows:
1. Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec (the °C or °F LED will AGC Agitator configuration: (EL; in) EL = switched ON and OFF with the compressor;
start blinking). in = switched ON according to parameter iAG.
2. Select the required parameter. Press the SET button to display its actual value. tiC Resolution for the Agt parameter: nP = the Agt parameter is in minutes
3. Use UP or DOWN buttons to change its value. Pb = the Agt parameter is in seconds.
4. Press SET button to store the new value and move to the following parameter. iAG Interval between agitation cycles: (1 to 120 min) Determines the time interval
between between two agitation cycles. NOTE: when a continuous agitation cycle is
To exit: Press SET+UP buttons or waiting for 15 sec without pressing any key. started, the time counting is reset and starts from zero.
AGt Length for agitation cycle: (0 to 255 min/sec) It sets the agitation cycle duration.
NOTE: the set value is stored even when the procedure is exited by waiting for the time-out to expire. APO First agitation cycle after start-up: Y = immediately; n = after the iAG time.
7.4 THE HIDDEN MENU ALARMS
The hidden menu includes all the parameters of the instrument. ALC Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred
7.4.1 HOW TO: ENTER THE HIDDEN MENU
to the set point. Temperature alarm is enabled when the temperature exceeds the
1. Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec (the °C or °F LED will [SET+ALU] or [SET-ALL] values.
start blinking). ALU MAXIMUM temperature alarm:
2. Released the buttons and then push again the SET+DOWN buttons for more than 7 sec. The Pr2 If ALC=Ab: [ALL to 150.0°C or ALL to 302°F]
label will be displayed immediately followed from the HY parameter. If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
Now it is possible to browse the hidden menu. when this temperature is reached the alarm is enabled, after the ALd delay time.
3. Select the required parameter. ALL Minimum temperature alarm:
4. Press the SET button to display its value.
If ALC=Ab: [-100°C to ALU; -148 to ALU]
5. Use UP or DOWN to change its value.
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
6. Press SET to store the new value and move to the following parameter.
when this temperature is reached the alarm is enabled, after the ALd delay time.
To exit: Press SET+DOWN or wait 15 sec without pressing a key. ALd Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
NOTE1: if no parameter is present in Pr1 menu, after 3 sec the “noP” message will be displayed. Keep dAo Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time
the buttons pushed till the Pr2 message will be displayed. interval between the detection of the temperature alarm condition after instrument power
on and alarm signalling.
NOTE2: the set value is stored even when the procedure is exited by waiting for the time-out to expire DIGITAL INPUTS
7.4.2 HOW TO: MOVE A PARAMETER FROM THE HIDDEN MENU TO THE i1P First digital input polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
FIRST LEVEL AND VICEVERSA.
i1F Digital input configuration:
Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing EAL = external alarm, “EA” message is displayed.
SET+DOWN buttons. If a parameter is part of the user level, when showed in the hidden menu the bAL = serious alarm, “CA” message is displayed.
decimal point will be lit. PAL = pressure switch alarm, “CA” message is displayed.
7.5 HOW TO LOCK THE KEYBOARD dor = door switch function.
AGt = agitator cycle activation.
1. Keep both UP and DOWN buttons pressed for more than 3 sec. AUS = not enabled.
2. The “PoF” message will be displayed and the keyboard will be locked. At this point it will be Htr = kind of action inversion (cooling – heating).
possible only to see the set point or the MAX o Min temperature stored FAn = not set it.
1. If a button is pressed more than 3 sec the “PoF” message will be displayed ES = Energy saving.
did Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
7.6 TO UNLOCK THE KEYBOARD alarm condition and its signalling.
Keep pressed together for more than 3 sec the UP and DOWN keys till the “Pon” message will be When i1F=PAL, it is the interval of time to calculate the number of pressure switch
displayed. activation.
nPS Number of pressure switch activation: (0 to 15) Number of activation, during the did
7.7 THE CONTINUOUS CYCLE interval, before signalling an alarm event (i1F=PAL).
If the nPS activation during did time is reached, switch off and on the instrument to
When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec. The restart normal regulation.
compressor operates to maintain the CCS set point for the time set through the CCt parameter. The odC Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
cycle can be terminated before the end of the set time using the same activation key UP for 3 sec. FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
7.8 THE ON/OFF FUNCTION rrd Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.
Y = outputs restart with a door open alarm.
With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” HES Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it
message is displayed. In this configuration, the regulation is disabled. sets the increasing value of the set point [SET+HES] during the Energy Saving cycle.
To switch the instrument on, push again the ON/OFF key.
OTHER
WARNING: Loads connected to the normally closed contacts of the relays are always supplied
PbC Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:
and under voltage, even if the instrument is in stand by mode.
PtC = PTC probe, ntC = NTC probe.
8. LIST OF PARAMETERS onF On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it.
rES Real Set Point: SET+ES+SETd (read only).
REGULATION rEL Software release for internal use (read only).
Ptb Parameter table code (read only).
HY Differential: (0.1 to 25.5°C; 1 to 45°F) intervention differential for set point. Compressor
Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the temperature 9. DIGITAL INPUTS
reaches the set point.
LS Minimum set point: (-100°C to SET; -148°F to SET) sets the minimum value for the set The free voltage digital inputs are programmable by the i1F parameter.
point.
9.1 GENERIC ALARM (i1F = EAL)
US Maximum set point: (SET to 150°C; SET to 302°F) set the maximum value for set point.
ot Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL
offset of the thermostat probe. alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
odS Outputs activation delay at start up: (0 to 255min) this function is enabled at the initial activated.
start up of the instrument and inhibits any output activation for the period of time set in the
parameter.
15. CONNECTIONS
11. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the power
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a
suitable external relay.
11.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration.
It is recommended to place the thermostat probe away from air streams to correctly measure the
average room temperature. Place the defrost termination probe among the evaporator fins in the coldest
place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent
premature defrost termination. 110Vac supply: connect to the terminals 6 and 7.
12. HOW TO USE THE HOT KEY
16. DEFAULT SETTING VALUES
12.1 HOW TO: PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
Label Description Range Value Menu
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “HOT-KEY” and push UP button; the “uPL” message SEt Temperature Set Point LS to US 2.0 ---
appears followed a by a flashing “End” label. [0.1°C to 25.5°C]
3. Push SET button and the “End” will stop flashing. Hy Differential 2.0 Pr1
[1°F to 45°F]
4. Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again. [-55.0°C to SET]
LS Minimum set point -30.0 Pr2
[-67°F to SET]
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again [SET to 150.0°C]
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. US Maximum set point 20.0 Pr2
[SET to 302°F]
12.2 HOW TO: PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) [SET to US]
SrS Second set point 5.0 N.V.
[SET to US]
1. Turn OFF the instrument. Compressor off time with
Srt 0 to 255 min 0 N.V.
2. Insert a pre-programmed “HOT-KEY” into the 5-PIN receptacle and then turn the Controller SrS set point
ON. [-12.0°C to 12.0°C]
ot Thermostat probe calibration 0.0 Pr1
3. The parameter list of the “HOT-KEY” will be automatically downloaded into the Controller [-21°F to 21°F]
memory. The “doL” message will blink followed a by a flashing “End” label. odS Outputs delay at start up 0 to 255 min 0 Pr2
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “HOT-KEY”. AC Anti-short cycle delay 0 to 50 min 1 Pr1
NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then on
Compressor ON time with
if you want to restart the download again or remove the “HOT-KEY” to abort the operation. Con 0 to 255 min 15 Pr2
faulty probe
Compressor OFF time with
CoF 0 to 255 min 30 Pr2
faulty probe
Temperature measurement
CF °C(0); °F(1) °C Pr2
unit