Power network configuration TN-S system Type coordination for panel design Type 2 for efficiency clas IE-3 Breaker / Contactor rating AC3 / AC4 Duty Class Continuous Incoming power supply 415 V +/-10% Frequency 50 Hz, +/-5% Control / Operating voltage 110 V AC, 50 Hz Fault Level 50 kA for 1 Sec Ambient conditions Minimum ambient temperature 5 Deg. C Maximum ambient temperature 45 Deg. C Design Ambient Temperature 50 Deg. C A. General Metal clad, Indoor, Floor mounted, Air Insulated Panel Type Board with internal arc flash proof Modular construction, Fully compartmentalized with metal/ Construction insulating material partition. Enclosure class IP55 Insulation and access Live parts shall be finger proof with shrouding. Technical Data sheet for MCC Electrical System UTCL REQUIREMENT B. Constructional Features :- Sheet steel CRCA 2.0 mm for load bearing members. Thickness 1.6 mm for non load bearing members. Incomer: Bottom cable entry. Cable entry Outgoing: Bottom cable entry. All the components shall be accessible from front side & Design Minimum 1.5 meter clearance to maintain in front of panel Related SFU and suggest MCC as per KW required. Module door interlocked with main power isolating devices. Interlocking & protection Power circuit isolation device to have pad locking in the OFF position with door closed. Undrilled removable bottom gland plates (3 mm thick at Gland plate incomer and 2mm at other locations), Same shall be segregated in the length having size of 500 mm Clear and legible identification labels with letter sizes of readable 25-50 mm for MCC panel 5 mm for components and module name plates. Labelling In all the feeders, Description of feeder, Feeder No., equipment No., kW rating shall be labeled. Danger board on front and rear sides in English, Hindi and Gujarati. Two separate earthing terminals will be provided. Bolted joints with tooth spring washers for good earth Earthing continuity. Earth bus to run in all cable alley of the panel . Paint shade RAL 7032, Powder coated. Paint thickness > 80 microns C. Bus-bars (i) Main horizontal & vertical bus-bars Arrangement Three phase & neutral (3 Ph, 4 W) High conductivity electrolytic Aluminium confirming to Material grade E91E as per IS-5082 -1981. Shall be able to carry continuously the connected load Phase Bus-bar Rating (considering diversity factor) plus a 25% margin. Max. current density shall be 0.80 A/sq.mm Neutral Bus-bar Rating 50 % of phase bus-bar rating Red-yellow-blue from front to back or top to bottom or left Bus-bar configuration to right as viewed from front. Heat shrinkable PVC Bus-bar insulation R,Y,B coloured sleeves for phases Black colour for neutral. Non-hygroscopic, Flame retarded, Track resistant, High Bus-bar supporting insulators strength, Sheet moulded compound or equivalent polyster fibre glass moulded type . Max. temp. rise of bus Not to exceed 40 deg. C. above ambient of 45 Deg. C. Technical Data sheet for MCC Electrical System UTCL REQUIREMENT Phase to phase :- 25.4 mm (minimum) Air clearance for bare Bus-bar Phase to earth :- 19.0 mm (minimum) Bus-bar joints and tap off points shall be shrouded and bolted (with cadmium coated bolts with plain and spring washers and locknuts). Joints and tap off points Bimetallic connectors for connection between dissimilar metals. Anti-oxide grease for all bus connections. Neutral bus isolation Through disconnecting link . (ii) Earth bus Material Cu Size Size as per design fault level (iii) Control bus Material Copper. Size Minimum 25 x 3 mm strip D. Insulation level Rated insulation voltage 1100 V Impulse withstand voltage 4 kV One minute power frequency withstand voltage 2.5 kV E. Incoming Feeder arrangement Circuit breaker Siemens Pad lockable with Lock-out and Tag-out so that without Interlocking removing the lock, one can not work on the feeder. LED cluster type indicating lamps for :- Indication Lamps ACB ON/OFF/TRIP/ Spring Charge/ Trip circuit Healthy. Power ON R / Y / B. Meters and selector switches Siemens Vendor to specify as per metering & protection of the Current transformer complete system Simocode Basic Unit 2 SIMOCODE PRO V, Series:3UF7, Profibus Communication, Aux Supply: 110 - 240V AC/DC SIEMENS K91B 3UF7010-1AU00-0. Current/Voltage Protection relays Measuring Device for Motor Protection & Control Device current setting range 3 to 40A SIEMENS K91M 3UF7111- 1AA01-0 1 H. Outgoing feeder arrangements Circuit breaker As per load required suggest. AC3/AC4 as per requirement. 3 pole. Minimum 16 A rated. Power contactor Contactor coil rating for 110 V AC. 2NO + 2NC auxiliary contacts. Mechanically interlocked for reversible drives. Auxiliary contactors Required nos. as per scheme. Control supply isolation device 2 Pole MCB Inside module for testing of power contactor when the Test PB module incoming power breaker is OFF For motor feeders of 45 KW and above through separate Space heater power provision MCB and interlock with main power contactor Electronic protection relay for motors protection For all motors Technical Data sheet for MCC Electrical System UTCL REQUIREMENT I. Panel wiring 1.1kV grade single core, black colour PVC insulated, stranded copper conductor of minimum size 2.5 sq.mm. Power / current (As per feeder rating) For feeder rating 100A and above all the power circuit shall be through rigid Bus-bar. Grey colour PVC insulated. Control and potential circuit Stranded copper conductor of minimum size 1.5 sq.mm. CT wiring shall be 2.5 sq.mm multi-stranded copper wires Numbered plastic/ceramic ferrules Ferrules Self locking type. All spare contacts of relays selector switches & contactors will be wired up to the terminal block in feeder Spare contacts Each components shall have at least 1 NO + 1 NC potential free spare contacts. Power & control terminals shall be segregated by insulating material Power terminals will be stud type. Control terminals will be suitable for connecting two cores of 2.5 sq.mm wires. Terminals Minimum 20 % spare terminals will be provided. Minimum rating of control terminal shall be 10 Amps. Color coded wires, TB’s of different voltage rating to be provided. Uniform color-coding to be followed for cabling, TB,Numbering on TB etc. J. Control Supply Control transformer Included Input side :- MCCB Input and output side isolation device Output side :- MCB, 2 Pole K. Miscallaneous Components of panel Breaker Control Switch ( TNC ) Included Local / Remote Selector Switch Included Emergency Push Button , Stay Put type Included 3 pin Power Socket with Switch, 15 Amp Included Auxiliary Contactor, 4NO + 4NC Included Common Hooter / Buzzer Included