QUINT-UPS/ 24DC/ 24DC/ 5
Uninterruptible power supply
Technical data
Input data
Nominal input voltage 24 V DC
DC input voltage range 18 V DC ... 30 V DC
Buffer period 2 h ()
Current consumption mains mode
Max. 9.4 A
No load 60 mA
Charging process 1.9 A
Fixed connect threshold ≤ 22 V DC
Output data
Nominal output voltage 24 V DC
Output voltage range 18 V DC ... 30 V DC
Nominal output current 5A
Derating 60 °C ... 70 °C (2.5%/K)
Output current limit (In mains mode according to connected upstream current limiting device)
> 7.5 A (Battery operation)
Power dissipation (mains mode)
Idle 1.4 W
Nominal Load 2.1 W
BOOST 2.4 W
Power dissipation (battery operation)
Idle 1.3 W
Nominal Load 3.3 W
BOOST 4.1 W
Output power 120 W
Efficiency > 98.7 %
Connection in parallel Yes, up to 2 modules with redundancy module
Connection in series No
Output data (mains operation)
Nominal output voltage 24 V DC
Output voltage range 18 V DC ... 30 V DC
Output current (according to connected upstream power supply unit)
Nominal output current IN 5 A (-25 °C ... +60 °C)
POWER BOOST IBOOST 7.5 A (-25 °C ... +40 °C)
SFB technology ISFB 30 A (-25 °C ... +60 °C)
Duration 12 ms (SFB technology)
Output data (battery operation)
Nominal output voltage 24 V DC
Output voltage range 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0.5 V DC)
Output current
Nominal output current IN 5 A (-25 °C ... +60 °C)
POWER BOOST IBOOST 7.5 A (-25 °C ... +40 °C)
SFB technology ISFB 32.5 A (-25 °C ... +60 °C)
Duration 15 ms (SFB technology)
QUINT-UPS/ 24DC/ 24DC/ 5
Power storage device
Nominal voltage UN 24 V DC
End-of-charge voltage 24 V DC ... 29 V DC (temperature compensated)
Temperature compensation 42 mV/K (preset)
Nominal capacity range 0.8 Ah ... 140 Ah
Charge current 0.2 A ... 1.36 A
Battery presence check (time interval) 1 min
Power In OK
Status display LED / Static to / green
Alarm
Inverting with the UPS-CONF configuration and management software
Switching output Relay
Maximum switching voltage ≤ 30 V AC/DC
Maximum switching current ≤ 100 mA
Status display LED / Static to / red
Battery charge
Signal options are adjustable with the UPS-CONF configuration and management software
Switching output Relay
Maximum switching voltage ≤ 30 V AC/DC
Maximum switching current ≤ 100 mA
Status display LED bar graph / dynamic / green
Battery mode
Signal options are adjustable with the UPS-CONF configuration and management software
Switching output Relay
Maximum switching voltage ≤ 30 V AC/DC
Maximum switching current ≤ 100 mA
Status display LED / Static to / yellow
General data
Mounting position horizontal DIN rail NS 35, EN 60715
Housing material Steel sheet, zinc-plated
Dimensions W / H / D 35 mm / 130 mm / 125 mm
Dimensions W / H / D (90° turned) 122 mm / 130 mm / 38 mm
Weight 0.5 kg
Security
Degree of protection IP20
Protection class III
Connection data
Connection method Pluggable screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 20 ... 12
Stripping length 7 mm
Screw thread M4
Tightening torque 0.5 Nm ... 0.6 Nm
2
QUINT-UPS/ 24DC/ 24DC/ 5
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3 g tv = 90 min.
Shock 30g in all directions in acc. with IEC 60068-2-27
Climatic class 3K3 (in acc. with EN 60721)
Standards
Electrical safety (of information technology equipment) EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
Approvals
UL approvals UL/C-UL Recognized UL 60950
UL Listed UL 508
3
QUINT-UPS/ 24DC/ 24DC/ 5
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
EN 61000-6-2 requirement Tested
Electrostatic discharge EN 61000-4-2
Housing contact discharge 4 kV (Test intensity 2) 8 kV (Test intensity 4)
Housing air discharge 8 kV (Test intensity 3) 15 kV (Test intensity 4)
Comments Criterion B Criterion A
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 1 GHz
Test field strength 10 V/m 20 V/m
Frequency range 1.4 GHz ... 2 GHz 1 GHz ... 3 GHz
Test field strength 3 V/m (Criterion A) 10 V/m (Test intensity X / 3)
Fast transients (burst) EN 61000-4-4
Input 2 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 3 - asymmetrical)
Output 2 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 3 - asymmetrical)
Signal 1 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 4 - asymmetrical)
Comments Criterion B Criterion A
Surge current loads (surge) EN 61000-4-5
Input/Output +/- 0.5 kV (Asymmetrical) 1 kV (symmetrical)
0.5 kV (symmetrical) 2 kV (Asymmetrical)
Signal +/- 1 kV (Asymmetrical) 1 kV (Asymmetrical)
Comments Criterion B Criterion A
Conducted interference EN 61000-4-6
Input/Output/Signal asymmetrical asymmetrical
Frequency range 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz
Voltage 10 V (Test intensity 3) 10 V (Test intensity 3)
Comments Criterion A Criterion A
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential