SAU-300

User Manual

SINENG Electric Co., Ltd.


Version A02
Revision Date 2022-3-20
BOM Code 28010152
SINENG Electric Co., Ltd.
This manual is the user manual of the SAU-300 of SINENG Electric Co., Ltd., and is applicable to
qualified electrical technicians. This manual mainly introduces SAU-300 device, including
installation, cable connection, debugging and maintenance. Get familiar with the functions and
features of the SAU-300 before installation or maintenance, and carefully read the safety
information in this manual.
Product name Model Remarks
SAU-300-BASE Include Fun :DO(60)、DI(26)
、SAU、Switch
SAU-300
SAU-300-PRO SAU-300-BASE + Relay Protection Fun

Note: if you want Relay Protection function, The SAU-300-PRO needs to be selected.

This manual uses the symbols listed below for different purposes, and different symbols can be used
in combination.
Symbols Definition
Warning sign, must be installed in strict accordance with the instructions in this
manual, otherwise it may cause equipment damage or endanger the safety of
operators!
There is a danger of electric shock, which may cause personal injury. It requires
professional personnel to install or maintain it. Others may not operate it
without authorization! Otherwise there is a danger of death due to electric
shock!

Highly dangerous, need special attention!

This manual may be upgraded from time to time due to product upgrades and other reasons without
prior notice.
This manual is copyrighted by SINENG Electric Co., Ltd. and may not be reproduced without
authorization.

SAU-300 User Manual A01 1


SINENG Electric Co., Ltd.
Contents
Chapter 1 Product Introduction ...................................................................................................................4
1. Product Introduction .....................................................................................................................4
2. Product Models .............................................................................................................................4
2.1 Description of the board ...........................................................................................................4
3. Physical Interfaces .........................................................................................................................5
3.1 Switch board ............................................................................................................................5
3.2 Data acquisition board .............................................................................................................6
3.3 Power board .............................................................................................................................7
3.4 X1 board ..................................................................................................................................8
3.5 X2|X3 board .............................................................................................................................8
3.6 X4 board ..................................................................................................................................9
3.7 CPU board ............................................................................................................................. 10
3.8 AI sampling board.................................................................................................................. 11
4. Product application interfaces ..................................................................................................... 12
4.1 Supported Network Protocol Types ........................................................................................ 12
4.2 Supported RS485 Protocol Types ........................................................................................... 12
4.3 Supported CAN Protocol Types.............................................................................................. 12
4.4 Relay Protection Fun.............................................................................................................. 12
4.5 Auxiliary debugging function ................................................................................................. 16
5. Product application interfaces ......................................................................................................... 18
5.1 Centralized photovoltaic grid scenario ................................................................................... 18
5.2 String-type PLC networking scenario .................................................................................... 19
Chapter 2 Product Specifications ............................................................................................................... 20
1. Power Supply Mode ........................................................................................................................ 20
2. External Interfaces .......................................................................................................................... 20
3. Specification List ............................................................................................................................. 21
4. Environmental Reliability ............................................................................................................... 22
5. EMC Related................................................................................................................................... 22
5.1 EMI ....................................................................................................................................... 22
5.2 EMS ....................................................................................................................................... 23
6. Dimensions and Weight ................................................................................................................... 23
7. Installation Method ......................................................................................................................... 23
Chapter 3 Product Installation ................................................................................................................... 24
1. Installation Introduction ................................................................................................................. 24
2. Installation Wiring .......................................................................................................................... 24
2.1 Power Wiring ......................................................................................................................... 24
2.2 Wiring of Input and Output Dry Contacts: ............................................................................ 25
2.3 RS485 Communication Cables ............................................................................................... 25
2.4 CAN Communication Cables ................................................................................................. 26
2.5 Ethernet Port Wiring ............................................................................................................. 28
2.6 Voltage and current sampling lines ......................................................................................... 28
Chapter 4 Trouble Handling....................................................................................................................... 30
Chapter 5 Product Maintenance................................................................................................................. 31
1. Periodic Inspection .......................................................................................................................... 31
2. Daily Maintenance .......................................................................................................................... 31

SAU-300 User Manual A01 2


SINENG Electric Co., Ltd.

Introduction

Please read this manual thoroughly before unpacking and installing the product. This
manual contains the following chapters:
Description of Symbols—This chapter summarizes the various symbols that appear
in the manual and explains them for better reading.
Safety Precautions—Important safety issues to be aware of before proceeding.
Chapter 1 Product Introduction—This chapter describes the main functions and
applications of this product.
Chapter 2 Product Specifications—This chapter provides product specifications for
this product.
Chapter 3 Product Installation—This chapter describes the installation of this
product and the connection of cables.
Chapter 4 Troubleshooting—This chapter provides the abnormal phenomena that
may occur during the debugging of this product and how they are handled.
Chapter 5 Product Maintenance—This chapter describes product maintenance,
including periodic maintenance and routine maintenance.
After-sales service information—This chapter provides contact information for
after-sales service.

SAU-300 User Manual A01 3


SINENG Electric Co., Ltd.
Chapter 1 Product Introduction

This chapter mainly introduces the model, optional interfaces, and functional descriptions of the
SAU-300, and describes the functions for different application scenarios.

1. Product Introduction

The device is an edge gateway used in the photovoltaic and energy storage domain, which can
enhance the perception and control over new energy stations, meeting the control demands for the
safe and stable operation of large power grids. The device also features AC sampling capabilities,
fulfilling basic requirements for relay protection. Depending on different application scenarios, the
device can perform functions such as data collection, protocol conversion, rapid power dispatch, fiber
ring networks, relay protection, and deployment of energy storage EMU strategies.

2. Product Models
Product name Model Configuration Description
Basic version: 60 DO channels, 26 DI channels,
SAU-300-BASE
SAU-300 data collector, switch.
SAU-300-PRO Enhanced version: BASE + Relay Protection Fun.

2.1 Description of the board


Product Configuration Description remark
Hardware name
number
Two optical and six electrical, 100 Gigabit, Optional
01 Switch board
support optical fiber ring network
02 SAU board Six-channel RS485, dual CAN, dual RJ45 Required
03 Power board Dual RS232 interfaces, 10 output dry contacts Required
20 channels 220VAC electrical characteristics Choose
04 InputDry board one of the
20 channels 24VDC electrical characteristics
two
05 Same as board 4
06 Same as board 4
07 OutputDry board 16 passive output dry contacts 220VAC Required
08 CPU board Four-channel RS485, dual CAN, RJ45 Required
Voltage : 100V 
400V 
690V  Default
AC Sampling 800V 
09 800V、
Board Current : Measuring type 1(1.2)A 
5(6)A
Measuring type 5(6)A 
Protective type 1(20)A 
Protective type 5(100)A 

SAU-300 User Manual A01 4


SINENG Electric Co., Ltd.
3. Physical Interfaces

3.1 Switch board


Port Description Remark Diagram
7-Tx、7-Rx Fiber optic 2 CH 100Base-FX、SC、
8-Tx、8-Rx interface Single-mode and dual-fiber
1、2、3、 6 CH RJ45
RJ45 interface
4、5、6 10/100M self-adaptive

8 LED arrays
The lights are arranged sequentially from
left to right
Status Running Light (RUN), Onboard
Light
indication Heartbeat Light, Factory Mode Light,
Power Light (POW)
7, 8: link lamp and speed lamp of optical
fiber port 7 and optical fiber port 8

SAU-300 User Manual A01 5


SINENG Electric Co., Ltd.
3.2 Data acquisition board
Port Description Remark Diagram
USB2.0 interface,
USB USB port
can be connected to U disk

RS232 Debug port For commissioning purposes only


1A、1B 6 CH
2A、2B Galvanic isolation
3A、3B Built-in GDT protection
RS485 port
4A、4B Built-in 120 ohm matching resistor
5A、5B It is recommended that no more than 12
6A、6B devices be connected to each channel
2 CH
Galvanic isolation
Built-in GDT protection
CAN1 Built-in 120 ohm matching resistor
CAN port
CAN2 It is recommended to maintain the
internal resistance of the bus at 60 ohms
when forming a CAN communication
network
2 CH
ETH0 Built-in GDT protection
Ethernet port
ETH1 RJ45 interface
10/100 adaptive

RUN: the system running light


POW: Power Indicator
L1~L6: 6 application status lights
Status
Light 485-1~6: 6 sets of RS485 transceiver
indication
status lights
CAN-1&2: Dual CAN transceiver status
lights

SAU-300 User Manual A01 6


SINENG Electric Co., Ltd.
3.3 Power board
Port Description Remark Diagram
Supports dual DC redundant power
supply.
Built-in overvoltage protection and
Power supply
P1、P2 reverse connection protection.
interface
Power Voltage : 2A at 24VDC ±10%.
No-load power: 10W at 24VDC.
Full load power: 30W at 24VDC.
POW1 Power status
Light on: 24V power supply normal
POW2 indication

Dual-channel RS232 interface


PLC1 Dual PLC
Only compatible with our company's
PLC2 interfaces
PLC option

DO1-1 250Vac [email protected]


single-phase
DO1-2 DO1-1: Remote close
circuit breaker
COM1 DO1-2: Remote open

DO2-1 250Vac [email protected]


Two-phase
DO2-2 DO2-1: Remote close
circuit breaker
COM2 DO2-2: Remote open

High-voltage
DO3-1 250Vac [email protected]
load switch
DO3-2 DO3-1: Remote close
opening and
COM2 DO3-2: Remote open
closing

Single-phase
DO4-1
protection trip

Two-phase Four groups of common COM ports


DO4-2
protection trip for digital outputs (DO)
Single contact continuous current
capacity: 5A @ 250Vac
COM port continuous current
DO4-3 Alarm signal capacity: 10A @ 250Vac

Among them, DO4-1 and DO4-2


have a pulse output of 2.5 seconds.
DO4-4 Trip signal

DO4 common
COM2
terminal

SAU-300 User Manual A01 7


SINENG Electric Co., Ltd.
3.4 X1 board
Before ordering this product, it is necessary to specify the electrical specifications of the input
signal, defaulting to 220VAC.
Port Description Remark Diagram
X1-01 Remote/local signal
X1-02 Maintenance status 24V version, common
X1-03 Reset signal cathode:
X1-04 Heavy gas signal 24VDC wiring diagram
X1-05 Light gas signal
24V+ 开关量
X1-06 Ultra-high temperature
X1-07 High temperature X1-01

X1-02
X1-08 Low oil level
X1-09 High oil level X1-03

X1-10 Pressure release ...

X1-11 High-voltage fuse X1-19

X1-12 One branch Open status X1-20


X1-13 One branch Close status
X1-14 One branch Fault status
24VDC
X1-15 Two branch Open status
X1-16 Two branch Close status 24V- X1-COM

X1-17 Two branch Fault status


220Vac version, common
X1-18 Load switch Open status neutral
X1-19 Load switch Close status 220VACwiring diagram
X1-20 BOX Door Open signal 开关量
220Vac-L
X1- X1-01
Common terminal
COM X1-02

X1-03

...

X1-19

X1-20
Status indicator light
LED POW: Power indicator
indicat light 220VAC
or light RUN: Running indicator
X1-COM
light 220Vac-N

3.5 X2|X3 board


Consistent with X1 board, interface description only
Port Description Remark Diagram
X2-01 Non-electrical trip 09 X3-01 X3-1 input dry contact
X2-02 Non-electrical trip 10 X3-02 X3-2 input dry contact
X2-03 Non-electrical trip 11 X3-03 X3-3 input dry contact
X2-04 Non-electrical trip 12 X3-04 X3-4 input dry contact
X2-05 Non-electrical trip 13 X3-05 X3-5 input dry contact
X2-06 Non-electrical trip 14 X3-06 X3-6 input dry contact
X2-07 Non-electrical trip 15 X3-07 X3-7 input dry contact
X2-08 Non-electrical trip 16 X3-08 X3-8 input dry contact
X2-09 X2-9 input dry contact X3-09 X3-9 input dry contact
X2-10 X2-10 input dry contact X3-10 X3-10 input dry contact
X2-11 X2-11 input dry contact X3-11 X3-11 input dry contact
X2-12 X2-12 input dry contact X3-12 X3-12 input dry contact
SAU-300 User Manual A01 8
SINENG Electric Co., Ltd.
X2-13 X2-13 input dry contact X3-13 X3-13 input dry contact
X2-14 X2-14 input dry contact X3-14 X3-14 input dry contact
X2-15 X2-15 input dry contact X3-15 X3-15 input dry contact
X2-16 X2-16 input dry contact X3-16 X3-16 input dry contact
X2-17 X2-17 input dry contact X3-17 X3-17 input dry contact
X2-18 X2-18 input dry contact X3-18 X3-18 input dry contact
X2-19 X2-19 input dry contact X3-19 X3-19 input dry contact
X2-20 X2-20 input dry contact X3-20 X3-20 input dry contact
X2-COM X2 common point X3-COM X3 common point

3.6 X4 board
220Vac output dry contact board
Port Description Remark Diagram

16 channels
Common dual COM ports
Single contact continuous current
capacity: 5A @ 250Vac
Dual COM port continuous current
capacity: 20A @ 250Vac
Single contact pulse current
capacity: 10A @ 2.5S
220VAC接线示意图
Passive 负载端
DO5-01
DO5-01~16 output dry
contact DO5-02

DO5-03

...

DO5-15

DO5-16

220VAC

DO5-COM
DO5-COM

LED Status
indicator indicator
light light

SAU-300 User Manual A01 9


SINENG Electric Co., Ltd.
3.7 CPU board
Port Descript Remark Diagram
ion
1A、1B 4-channel, electrical isolation
2A、2B Built-in GDT protection
RS485
Built-in 120 ohm matching resistor
3A、3B port
Recommended maximum of 12 devices
4A、4B per channel
2-channel, electrical isolation
Built-in GDT protection
CAN1 CAN Built-in 120 ohm matching resistor
CAN2 port Recommended total bus impedance of 60
ohms when forming a CAN
communication network
Built-in GDT protection
Ethernet
NET RJ45 interface
port
10/100 adaptive
Supports the acquisition of 4 channels of
4-20mA DC current, while also
DC1+、DC1- DC compatible with 0-10V voltage sampling.
DC2+、DC2- analog Wiring example for DC1 & 2:
1#Sensor Device
DC3+、DC3- sampling (4~20mA)
DC4+、DC4- interface
2#Sensor Device
(4~20mA)

Supports the acquisition of 2 channels of


PT100 signals.
PT100 Wiring example for PT-1:
Pt-1-A\B\C
sensor
Pt-2-A\B\C Pt-1-A
interface
Pt-1-B
Pt-1-C
POW: Power indicator light
RUN: Running indicator light
485-1~4: Status lights for 4 sets of RS485
transmission and reception
CAN1 & 2: Status lights for 2 sets of CAN
transmission and reception
Status
LED L1: Alarm light, L2: Fault light
indicator
indicator light L3: Open position 1, L4: Close position 1
light
L5: Open position 2, L6: Close position 2
L7: Remote (on) Local (off)
L8: Maintenance indicator light (on) Non-
maintenance mode (off)
L9: PT disconnection (any line)
L10: CT disconnection (any line)

SAU-300 User Manual A01 10


SINENG Electric Co., Ltd.
3.8 AI sampling board
Port Descript Remark Diagram
ion
Ua1

Ub1 One
Branch
Uc1 Voltage Voltage selection: Rated voltage (Ue)
100V 
Un1
400V 
Ua2 690V 
800V 
Ub2 Two Overload capacity: 2*Ue continuous operation
Branch
Uc2 Voltage

Un2

IA1 Ia1’
One
IB1 Ib1’ Branch Current selection: Rated current (Ie)
Current Measurement type: 1(1.2) A 
IC1 Ic1’ Measurement type: 5(6) A 
Protection type: 1(20) A 
IA2 Ia2’ Protection type: 5(100) A 
Overload capacity:
Two Protection type: 20*Ie allowed for 1 second
IB2 Ib2’ Branch 2*Ie continuous operation
Current
IC2 Ic2’

Note: Note:
Measurement accuracy: Voltage sampling supports three-phase four-
Voltage and Current < 0.5% wire, if three-phase three-wire connection, N
AP and RP < 1.0% phase and B phase need to be shorted.
PowerFactor < 0.5%
Frequency < 0.01Hz A相
B相
Protection Accuracy: C相
voltage : class 1 N相
Ua1
current : class 1
Ub1
Line loss: IA1 Ia1
Uc1
AC voltage loop: <0.5VA/phase IB1
IC1
Ib1
Ic1
AC current loop: <1.0VA/phase @ In=5A, Un1 IA2 Ia2
IB2 Ib2
<0.5VA/phase @ In=1A Ua2 IC2 Ic2
When ordering, specify the input specifications of Ub2
voltage and current, default 800V, 5A. Uc2
Un2

SAU-300 User Manual A01 11


SINENG Electric Co., Ltd.
4. Product application interfaces

4.1 Supported Network Protocol Types

Protocol Type Service Port Max Links Remarks


1. Support multi master station access
IEC60870-104
2404(default) 10 2. Support service port mapping
slave station
3. Support multi point table submission
1. Support multi master station access
2. Support service port mapping
Modbus TCP slave 502(default) 5
3. Support data exchange between
Modbus TCP and RTU
1. Support standard Modbus TCP
Modbus TCP host / /
protocol
IEC61850-MMS 102(default) 4 1. Support dual network redundant
Multicast communication
IEC61850-GOOSE / 2.Support multi master station access
communication
NTP time
/ / /
synchronization
4.2 Supported RS485 Protocol Types

Protocol Type Service Port Max devices Remarks


Number
1. It is recommended that a single RS485
Modbus RTU host interface be connected to no more than 12
SAU board: slave devices, supporting a total of 120
10*12
RS485 1~6 device connections
(default)
DLT645-2007 CPU board: 2. It is recommended that devices of the
Metering protocol RS485 1~4 same type be connected to the same port
and have unique device IDs
Modbus RTU slave / /
4.3 Supported CAN Protocol Types

Protocol Type Service Port Max Remarks


Number devices
SAU board:
It is recommended to maintain a total
CAN1&2
SAE J1939 4*6 bus impedance of 60Ω for a single
CPU board:
CAN bus.
CAN1&2
4.4 Relay Protection Fun

Parameter Setting Range Constant Range


AC Current:0.1A~100A Current:< ±2.5%*Ie Or ±0.01*Ie
AC Voltage:10V~1600V Voltage:< ±2.5%*Ue Or ±0.01*Ue
Response Delay:0s~100s DelayTime:≤SetTimeValue*1% + 40ms

4.4.1 Three-stage Overcurrent Protection


The device is configured with three-stage overcurrent protection with low-voltage interlocking.
The three stages of protection are independently configured, and the protection logic is the same.
Explanation of directional elements:
SAU-300 User Manual A01 12
SINENG Electric Co., Ltd.
The device specifies that the positive direction is from the busbar to the line, The directional
elements adopt a 90°connection(𝐼𝑎 → 𝑈𝑏𝑐 /𝐼𝑏 → 𝑈𝑐𝑎 /𝐼𝑐 → 𝑈𝑎𝑏 ), The positive direction characteristic
equation is as follows (maximum error range in parentheses):
Ir e  j 45

 
 90 (10 )  arg  90  (10  )

Ur
In the equation: 𝐼𝑏̇ and𝑈̇𝑟 represent the current and voltage quantities corresponding to the 90°
connection method respectively.
The voltage restoration interlocking component is subjected to PT disconnection interlocking.
When a PT disconnection occurs in a branch, the selection of whether to interlock the voltage
restoration component can be made through the "PT disconnection interlocking protection" setting.
When the "PT disconnection interlocking protection" is activated, the current protection will
directly trip upon "PT disconnection alarm";
When the "PT disconnection interlocking protection" is deactivated, the directional current
protection will switch to pure overcurrent protection upon "PT disconnection alarm".
The specific logic diagram is as shown in the following figure:

N OverCurrent Fun Enable


& N Warn Signal

Max(Ia,Ib,Ic)>N Set Current


& & N Time Delay

N Trip Fun Enable


& N Trip Signal
PT Clock Enable

≥1
PT Disconnect

Setting parameters:
Set values Range and precision Default values
0: Withdraw
Protection plate Withdraw
1: Engage
Stage 1: 20A
Current setpoint 0.05A~100.00A Stage 2: 15A
Stage 3: 7.5A
Delay time 0~180 seconds 0.5
0: Alarm
Operation mode Trip
1: Trip
4.4.2 Zero sequence overcurrent protection

3𝐼0 is the zero sequence current, obtained by adding the vector sum of the three-phase currents
inside the device.
Zero Sequence & Zero Sequence Warn
Enable & Delay Time
3Io>Izero (set)

Trip Enable
& Zero Sequence Trip

Setting parameters
Set values Range and precision Default values
0: Withdraw
Protection plate Withdraw
1: Engage
Current setpoint 0.05A~99.99A 6A
Delay time 0~180 seconds 0.5
SAU-300 User Manual A01 13
SINENG Electric Co., Ltd.
0: Alarm
Operation mode Trip
1: Trip
4.4.3 Overvoltage protection
When any line voltage exceeds the overvoltage setpoint, the overvoltage protection trips.
Overvoltage & Overvoltage Warn
Enable?
Delay Time
Max(Uab,Ubc,Uca)>Vol(set)
&
Trip Enable ?
& Overvoltage Trip

Setting parameters:
Set values Range and precision Default values
0: Withdraw
Protection plate Withdraw
1: Engage
Current setpoint 100~1500Vac 1000Vac
Delay time 0~180 seconds 0.5
0: Alarm
Operation mode Trip
1: Trip
4.4.4 Low voltage protection
Low voltage protection must operate or alarm only when the h ighest line voltage is below the
set value, provided that the circuit breaker is closed and there is no PT disconnection.
Low voltage Enable
& Low voltage Warn

Min(Uab,Ubc,Uca)<Vol(set) & DelayTime


HWJ=1
PT disconnect Lock Trip Enable?
& Low voltage Trip

Setting parameters:
Set values Range and precision Default values
0: Withdraw
Protection plate Withdraw
1: Engage
Current setpoint 100~1500Vac 650Vac
Delay time 0~180 seconds 0.5
0: Alarm
Operation mode Trip
1: Trip
4.4.5 Overload protection
Three-stage overcurrent protection is designed to protect against short-circuit faults, while
overload protection has setpoints much lower than those of overcurrent protection but higher than
normal load levels to prevent equipment from operating in overload conditions. When overcurrent
protection fails to operate for some reason, overload protection can act as a backup protection for
overcurrent protection.
& Overload Warn
Overload Enable
Delaytime
Max(Ia,Ib,Ic)>Iover(set)
&
Trip Enable?
& Overload Trip

Setting parameters:
Set values Range and precision Default values

SAU-300 User Manual A01 14


SINENG Electric Co., Ltd.
0: Withdraw
Protection plate Withdraw
1: Engage
Current setpoint 0.05A~99.99A 5.5A
Delay time 0~180 seconds 0.5
0: Alarm
Operation mode Trip
1: Trip
4.4.6 Ground fault alarm
Ground fault on the bus is determined based on the unbalanced voltage of the bus. The
unbalanced voltage is calculated by the software, and the fixed setpoint for bus ground fault
unbalanced voltage is 18V with a delay of 10 seconds.
Ground Fault Enable Ground Fault
& 10S
3Uo>18V Warn

4.4.7 TWJ abnormal alarm


If the switch is in the open position but current is detected in the circuit, it is considered TWJ
abnormal after a delay of 10 seconds.
TWJ abnormal Enable
TWJ=1 & 10S TWJ abnormal alarm
Max(Ia、Ib、Ic)>0.04In

4.4.8 Abnormal switch position alarm


If both TWJ and HWJ are either closed or both are open at the same time, or if they are both not
operated, an abnormal switch position alarm will be issued after a delay of 10 seconds.
Switch Position
abnormal alarm Enable
HWJ Switch Position
& & 10S
abnormal alarm
TWJ ≥1
&

4.4.9 DC protection
The DC signals are: 1# PT100, 2# PT100, and CH1~4#4-20mA sampling channels.
When any of the DC temperature measurements exceed the set value, a delay is initiated before
the protection action.

DC protection Enable
& DC Protection Warn

Delay time
Iz>Idc(set)
&
Trip Enable?
& DC Protection Trip

4.4.10 PT disconnection alarm


Bus PT disconnection check uses criteria such as line voltage drop and negative sequence voltage
rise. An alarm is triggered after a delay of 10 seconds. The negative sequence voltage is calculated
by the software from the three-phase voltages.
When a phase is disconnected, the PT's abnormality can be determined if Max(𝐼𝑎 、𝐼𝑏 、𝐼𝑐 ) is
greater than 0.04𝐼𝑛 (adjustable).
SAU-300 User Manual A01 15
SINENG Electric Co., Ltd.
When the "Bus PT disconnection interlocking protection" is triggered, the protection function
dependent on the PT signal will be interlocked.
PT disconnection Enable

Max(Uab、Ubc、Uca)<0.7Un(0.8Un) & PT disconnect Warn


≥1 & 10S
U2>0.1Un(0.07Un)

& Clock PT disconnect signal


Max(Ia、Ib、Ic)<0.04In
&
PT disconnect clock Enable
PT disconnect clock Enable

4.4.11 CT disconnection alarm


CT disconnection alarm is determined by zero sequence current and zero sequence voltage. An
alarm is triggered after a delay of 10 seconds.
During normal operation, the sum of the three-phase currents is zero. When the CT is
disconnected, the sum of the three-phase currents is not zero, and the current of the disconnected
phase is zero. To exclude line faults, the zero sequence voltage must be zero.
CT disconnection Enable
I0 > 0.05In 10S CT disconnection Warn
MIN(Ia,Ib,Ic)< 0.05In &
U0 < 0.05Un

4.4.12 Non-electrical protection


The device supports up to 30 groups of non-electrical inputs, labeled as Non-electrical 1 to 30.
During program initialization, the specified input dry contacts (DI) can be associated with the inputs
either through configuration or hard-coding.
When the corresponding non-electrical protection is activated, and the trigger conditions for
Non-electrical 1 are met, the protection action will be executed after the necessary delay. This
function can only be triggered if both circuit breakers in the two branches are in the closed position;
otherwise, the non-electrical protection will be interlocked.
If the trigger signal persists, the output signal will remain active. After the trigger signal
disappears, it needs to be reset before the trip signal or alarm signal can be cleared.
Non-electrical N Enable & Non-electrical N Warn

Non-electrical N Signal = 1 & Delay Time

HWJ1=1
≥1 Trip Enable?
& Non-electrical N Trip
HWJ2=1

Setting parameters:
Set values Range and precision Default values
0: Withdraw
Protection plate Withdraw
1: Engage
Delay time 0~180 seconds 0.5
0: Alarm
Operation mode Trip
1: Trip
4.5 Auxiliary debugging function

SAU-300 User Manual A01 16


SINENG Electric Co., Ltd.
4.5.1 Support SMV waveform output
Facilitates the observation of real-time voltage and current waveforms, enabling visualization of
the grid waveform.
4.5.2 Support fault recording
Individual waveform resolution is 1ms, with a recording duration of 1000ms, supporting up to
10 fault waveforms.
4.5.3 Support operation recording function
Supports 256 cycle erasures
4.5.4 Support event sequence recording function
Supports 2048 cycle erasures

SAU-300 User Manual A01 17


SINENG Electric Co., Ltd.
5. Product application interfaces
5.1 Centralized photovoltaic grid scenario

This solution seamlessly integrates with our inverters, allowing power to be emergency
controlled within milliseconds compared to traditional ground stations. It supports more than 10
RS485 interfaces with electrical isolation, enabling a greater number of devices to be connected more
stably.
We recommend using switches from the same brand for both the sub-array ring switch and the
control room switch, ensuring a more stable and reliable network.
It supports multiple master stations simultaneously, such as solar power prediction, AGC master-
slave machines, AVC master-slave machines, centralized control centers, and fast frequency servers.
It is recommended not to exceed 12 devices per RS485 bus.

SCADA
PPC Dispatch Center Work Station Printer Control Center

Main Switch

Fiber Box
SAU-300
SAU-300

Optical Ring Network

SAU-300

SAU-300 SAU-300
N Station
RS485

1 2 34
... ...

Digital Tracking Meter


PV Box Inverter Transformer Box
thermometer Bracket

SAU-300 User Manual A01 18


SINENG Electric Co., Ltd.

5.2 String-type PLC networking scenario

The PLC (Power Line Communication) solution can save the cost of long-distance 485 cable
work on-site, simplify the complexity of on-site communication deployment, and reduce the
construction cost of the power station.
The SAU-300 virtualizes multiple inverters belonging to the same array into a single adjustable
power device, simplifying the complexity of northbound communication remote control and remote
adjustment. It can be integrated with a panoramic monitoring system, enabling emergency control of
power within milliseconds.

SCADA
PPC Dispatch Center Work Station Printer Control Center

Main Switch

Fiber Box

SAU-300

SAU-300
光纤环网

SAU-300
SAU-300

String Inverter String Inverter String Inverter


Internal bus
SAU-300
N Station
PLC选件 RS485
A B C
PLC

String Inverter String Inverter String Inverter


1 2 34
... ...

Transformer Box Tracking Bracket Meter


Digital
thermometer

SAU-300 User Manual A01 19


SINENG Electric Co., Ltd.
Chapter 2 Product Specifications

This chapter mainly introduces the external interfaces and specifications met by the SAU-300.

1. Power Supply Mode


Table 2-1 Power Supply Mode
External model Power Supply Mode Power consumption
SAU-300-BASE
Input Voltage: 24VDC±10%, dual redundant 2A@24V
SAU-300-PRO

2. External Interfaces
Table 2-2 External interfaces
Interfaces Descriptions Performances
RS485 RS485 port 1. Supports up to 10 channels
2. Electrical isolation, all SELV circuits
3. It is recommended that each RS485 connection should not exceed 12
devices
4. Communication baud rate supports 2400, 4800, 9600, 19200, 38400,
57600, 115200bps
5. The data format supports 1 start bit, 5-8 data bits, 1-2 stop bits, and 0-1
check bits
6. Verification methods support: no verification, odd verification, even
verification, Mark verification, Space verification
7. Support Modbus RTU (host, slave) and DL/T645 protocol
8. Communication point table configurable
CAN CAN port 1. Supports up to 4 channels
2. Electrical isolation, all are SELV circuits
3. It is recommended not to exceed 12 devices per RS485 channel
4. Communication baud rates supported: 250K, 500K, 1Mbps
100M port Ethernet port 1. 3 independent network cards
2. 10/100M adaptive
3. Supports Modbus TCP, IEC60870-104 protocol, MMS
4. Supports GOOSE, NTP time synchronization
5. Communication point table is configurable
DI Input dry 1. Supports up to 60 channels
contact 2. Electrical isolation
DO Output dry 1. 26 channels.
contact 2. 250VAC normally open relay.
3. Single contact pulse current carrying capacity of 10A @ 2.5S.
USB USB 1. one Host
2. USB2.0, compatible with USB1.1
3. Supports a capacity of no less than 32GB
4. Support data export, such as log files, statistical data, record information,
and other functions
5. Support program upgrade function
4~20mA 4~20mA 1. 4 channels
Analog Analog 2. Compatible with ± 10V voltage sampling
sampling sampling 3. Signal isolation
interface
PT100 PT100 1. 2 channels
Temperature 2. Sampling range -30~240 ℃
sampling 3. Signal isolation
interface

SAU-300 User Manual A01 20


SINENG Electric Co., Ltd.
3. Specification List
Table 2-3 Specification List Table
Setting Name Remarks Setting Range Factory
Setting
System Frequency - 50Hz  60Hz  50Hz
- Three-Phase Four-Wire  Three-
Wiring Method Three-Phase Three-Wire  Phase Four-
Disabled  Wire
Single Phase, Two Phases Positive Sequence  Positive
CT Polarity
Negative Sequence  Sequence
Primary Side of PT Single Phase, Two Phases 1.0~330.0Kv 1.0Kv
Secondary Side of PT Single Phase, Two Phases 1~2000V 1000V
Primary Side of CT Single Phase, Two Phases 1~6000A 1A
Secondary Side of CT Single Phase, Two Phases 1~20A 1A
Output Pulse Width - 1-100.000s 2.5s
Delay Reset Operation Disable/Enable Disable
Auto-reset Function
Delay Reset Time Limit 1-60000s 60000s
Non-electrical Protection Protection Pressure Plate Disable/Enable Disable
Parameters Action Mode Alarm/Trip Trip
1~16 Delay 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
PT100 Protection Parameters Action Mode Alarm/Trip Trip
CH1, CH2 Temperature Upper Limit 50~300℃ 300℃
Delay 0~180S 10S
Protection Pressure Plate Disable/Enable Disable
20mA Protection Parameters Action Mode Alarm/Trip Trip
CH1, CH2, CH3, CH4 Current Upper Limit 4~20mA 20mA
Delay 0~180S 10S
Protection Pressure Plate Disable/Enable Disable
Overcurrent First Stage Action Mode Alarm/Trip Trip
Protection Current Setting Value 0.05A~100.0A 20A
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Overcurrent Second Stage Action Mode Alarm/Trip Trip
Protection Current Setting Value 0.05A~100.0A 15A
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Overcurrent Third Stage Action Mode Alarm/Trip Trip
Protection Current Setting Value 0.05A~100.0A 7.5A
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Action Mode Alarm/Trip Trip
Overload Protection
Current Setting Value 0.05A~100.0A 5.5A
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Action Mode Alarm/Trip Trip
Zero Sequence Overcurrent
Current Setting Value 0.05A~100.0A 6A
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Action Mode Alarm/Trip Trip
Overvoltage Protection
Overcurrent Setting Value 100~1500V 1000V
Delay Time 0~180S 0.5S
Protection Pressure Plate Disable/Enable Disable
Undervoltage Protection Action Mode Alarm/Trip Trip
Overcurrent Setting Value 100~1500V 650V
SAU-300 User Manual A01 21
SINENG Electric Co., Ltd.
Delay Time 0~180S 0.5S
PT Disconnection Alarm
Disable/Enable Disable
Operation
PT Disconnection Alarm
PT Disconnection Lockout
Disable/Enable Disable
Operation
CT Disconnection Alarm
Disable/Enable Disable
Operation
CT Disconnection Alarm
CT Disconnection Lockout
Disable/Enable Disable
Operation

4. Environmental Reliability
Table 2-4 Environmental reliability standard
Items Normal range
Operating temperature -40 to 60ºC
Storage temperature -40 to 70ºC
Relative humidity 5 to 95%, no condensation
Altitude <5000m
Protection level IP20
MTBF 500,000 hours
MTTR 1 hour
Design life 20 years

5. EMC Related
5.1 EMI

Table 2-5 Complied EMI standard


Test items Test standard Test level and criterion
Conduction EN 55022 485 port、Ethernet port: Class B

Radiation CISPR22/GB/T 9254/EN 55022 Class B

SAU-300 User Manual A01 22


SINENG Electric Co., Ltd.
5.2 EMS

Table 2-6 Complied EMS standard


Test items Test standard Test level Criterion
IEC61000-4-2 ±6kV contact discharge
Electrostatic discharge immunity Criterion B
GB/T 17626.2 ±8kV air discharge
Radio frequency electric field IEC61000-4-3
10V/m(80MHz~1GHz) Criterion A
radiation immunity GB/T 17626.3
Electrical fast transient burst IEC61000-4-4
Data terminal: ±2kV Criterion B
immunity GB/T 17626.4
IEC61000-4-5
Surge (impact) immunity Data terminal: ±2kV Criterion B
GB/T 17626.5
Conducted disturbance IEC61000-4-6
3V(150kHz~230MHz) Criterion A
immunity of RF field induction GB/T 17626.6
Power frequency magnetic field IEC61000-4-8 100A/m continuous
Criterion A
immunity GB/T 17626.8 1000A/m 1s~3s
IEC61000-4-9
Pulsed magnetic field 1000A/m(peak) Criterion A
GB/T 17626.9
Damped oscillatory wave IEC61000-4-10
100A/m Criterion A
immunity GB/T 17626.10
Voltage sag: 0% for 0.5
cycles, 0% for 1 cycle, 40% for
Immunity of voltage dips, short 10 cycles, 70% for 25 cycles,
IEC61000-4-11
interruptions and voltage 80% for 250 cycles; Criterion B
GBT 17626.11
changes Short interruption: 0% lasts
250 cycles
Duration: 10s
IEC61000-4-12 Common mode 1kV, differential
Ringing wave immunity Criterion B
GB/T 17626.12 mode 0.5kV
IEC61000-4-14
Voltage fluctuation immunity Level3 Criterion A
GBT 17626.14
Common mode conducted IEC61000-4-16 Continuous: 30V
Criterion A
disturbance immunity GBT 17626.16 Short time 1s: 300V

6. Dimensions and Weight


Table 2-7 Dimensions and weight
Model Dimensions (mm*mm*mm) Weight (kg)
SAU-300 472*177*220 <9

7. Installation Method
Plug-in installation

SAU-300 User Manual A01 23


SINENG Electric Co., Ltd.
Chapter 3 Product Installation

This chapter introduces the environmental conditions required for the storage and reliable
operation of the SAU-300 device in the field, the installation steps of the SAU-300 device, and other
related instructions.

1. Installation Introduction
The device is installed using a plug-in frame method. Structurally, the SAU-300 chassis has a
standard height of 4U. After inserting the plug-in frame, it is fixed to the rack side by tightening the
combination bolts of 4 * M6 * 12 flat washers on both the left and right sides, as shown in the diagram
below.

2. Installation Wiring
2.1 Power Wiring

The SAU-300 device adopts redundant dual 24VDC DC power supply, and the power interface
uses 2-pin Phoenix terminals with a 5.08 spacing. It requires reliable grounding, as shown in the
diagram below.

Power Ports Ground Ports


Please pay attention to the following points when wiring:
1. In order to ensure stable and reliable data collector communication, please ensure that the PE
is reliably connected to the earth.
SAU-300 User Manual A01 24
SINENG Electric Co., Ltd.
2. It is recommended to use a cable of 1.0~2.5mm*mm.
3. In addition to the bayonet, the terminal has a screw for locking. Since high voltage is involved,
please ensure that the screw is securely locked to prevent personal injury when the terminal is
disconnected.

2.2 Wiring of Input and Output Dry Contacts:

The X1, X2, and X3 boards each integrate 20 channels of DI with a common COM connection,
using a 5.08mm pitch 21-pin phoenix terminal. The X4 board integrates 16 channels of DO with a
common COM connection, also using a 5.08mm pitch terminal. See the diagram below for reference.

DI/DO Ports
Please pay attention to the following points when wiring:
1. 220Vac version DI is connected with common neutral line, and 24Vdc version DI is connected
with common negative pole.
2. Recommended to use 0.5~2.5mm²cables.
3. The output dry contact adopts a common COM port connection method, with a single-contact
continuous current carrying capacity of 5A at 250Vac and an instantaneous current carrying capacity
of 10A for 2.5 seconds. The current carrying capacity for a single COM port is 10A at 250Vac.

2.3 RS485 Communication Cables

The RS485 communication ports total 10, with 6 on the SAU board and 4 on the CPU board.
They all use terminals with a 5.08mm pitch, where 'A' represents the positive of the RS485
communication port, and 'B' represents the negative, as shown in the diagram below.

SAU-300 User Manual A01 25


SINENG Electric Co., Ltd.

RS485 Ports
Please pay attention to the following points when wiring:
1. Default built-in 120 ohm matching resistor
2. Please pay attention to the positive and negative ends of the RS485 cables, which cannot be
reversed.
3. It is recommended to use a cable of 0.5~2.5mm*mm.
4. When wiring, try to clearly indicate the direction of the cable.
5. The length of the communication cable should not exceed 1000m.
6. It is recommended to connect no more than 12 devices under each RS485 port.
7. It is recommended that each RS485 port be connected to the same device (same
communication protocol).
8. The communication speed of each device under the RS485 port is the same, the data format
is the same, and the device address is different.
9. Each communication line that comes from RS485 adopts single point grounding method, and
its shielding layer should be connected to the earth at the data collector.
10. Each RS485 bus needs to be shielded together at the node where the device is hand-in-hand.
11. It is recommended to use RS485 communication cable specification: ZC-DJYP2VP2-
2*2*1.0
"C" in "ZC" is Class C flame retardant grade
D: computer cable
J: twisted
Y: The insulating material is polyethylene
P: Shield (here, the line is shielded from copper).
V: The sheath material is PVC
p: shield (total shield, copper wire), if P2, it is copper tape shield
2*2*1.0: The front "2" refers to two pairs, the rear "2" refers to the number of cores of each pair,
and the "1.0" refers to the cross-section mm*mm of each core conductor.
12. It is recommended that the communication cable be laid at a distance of 0.1 m and 0.25 m
from the minimum clearance of 0.4 kV and 35 kV cables, respectively, and 0.5 m when cross-laying.

2.4 CAN Communication Cables

The CAN communication ports total 4, with 2 on the SAU board and 2 on the CPU board. They
all use terminals with a 5.08mm pitch, where 'H' represents the positive of the CAN port, and 'L'

SAU-300 User Manual A01 26


SINENG Electric Co., Ltd.
represents the negative, as shown in the diagram below.

CAN communication ports


Please pay attention to the following points when wiring:
1. The default built-in 120 ohm matching resistor maintains an internal resistance of 60 ohms
when building a CAN bus network.
2. Please pay attention to the H and L wire sequence of the CAN cable and do not reverse it.
3. It is recommended to use cables of 0.5~2.5mm * mm.
4. When wiring, try to clearly indicate the direction of the cable.
5. The length of the communication cable should not exceed 40m.
6. The communication rate of devices under each CAN bus is consistent.
7. Each CAN bus needs to be shielded and connected together at the nodes of the device handle.
8. It is recommended to use CAN communication cables with the same specifications as 485.

SAU-300 User Manual A01 27


SINENG Electric Co., Ltd.
2.5 Ethernet Port Wiring

There are three Ethernet ports available, each with its own physical MAC address. They support
10/100 Mbps auto-negotiation and utilize standard RJ45 interfaces, connecting to external devices
via standard Ethernet cables.
Please pay attention to the following points when wiring:
1. Standard cable, crystal connector, line order is white orange, orange, white green, blue, white
blue, green, white brown, brown.
2. The network cable uses Super Category 5 cable.
3. The length of the network cable does not exceed 80m.
4. To ensure the reliability of the network cable connection, it is recommended to use CAT 5E
outdoor shielded network cable and shielded crystal head.

2.6 Voltage and current sampling lines

Voltage sampling lines should be connected to the tubular cold-pressed terminal before insertion
into the terminal. The cable requirements are 24~8 AWG.
Current sampling lines should be connected to the U-shaped cold-pressed terminal before
insertion. The wire pressing range is 18~12 AWG.
Specifications for the U-shaped terminal are as follows:

For three-phase three-wire voltage sampling line connection, the N phase and B phase should be
shorted.
The connection method for three-phase four-wire system is as follows:
A相
B相
C相
N相
Ua1
Ub1
Uc1 IA1 Ia1
IB1 Ib1
IC1 Ic1
Un1 IA2 Ia2
IB2 Ib2
Ua2 IC2 Ic2
Ub2
Uc2
Un2

SAU-300 User Manual A01 28


SINENG Electric Co., Ltd.
The connection method for three-phase three-wire system is as follows:
A相
B相
C相

Ua1
Ub1
Uc1 IA1 Ia1
IB1 Ib1
IC1 Ic1
Un1 IA2 Ia2
IB2 Ib2
Ua2 IC2 Ic2
Ub2
Uc2
Un2

SAU-300 User Manual A01 29


SINENG Electric Co., Ltd.
Chapter 4 Trouble Handling

This chapter mainly introduces the abnormalities that may occur during the debugging or use of
the SAU-300, as well as their handling methods. Some of these abnormalities may be caused by
inappropriate configurations.
Abnormal
Cause analysis and checking procedures
phenomenon
Check whether power cable terminals are connected to incorrect positions.
After power on, the Check whether the polarity of power cable terminals is reversed.
power indicator light
is off Check whether the power cable voltage is 24V
Contact our customer service staff.
Check if the RS485 communication line is disconnected, broken away, reversed or
shorted, and the shield is grounded at a single point.
Check whether the connected device is powered on.
Check whether the RS485 communication port parameter configuration, such as
RS485
communication baud rate, data format, and communication address, matches the connected device.
failure Check if there is a 120-ohm matching resistor at the beginning and end of the RS485
communication line: the farthest ends need, but not in the middle, otherwise the bus
load is too heavy.
Check if the point table configuration matches the connected device
Contact our customer service staff.

Input dry contact Check if the input dry contact line is disconnected, broken away, reversed or shorted.
detection error Contact our customer service staff.
Check if the output dry contact line is disconnected, broken away, reversed or
Output dry contact shorted.
detection error
Contact our customer service staff.
Check whether the network cable is connected reliably.
Check if the IP and gateway settings are correct
Ethernet
communication error Check whether the network is connected through the ping command.
Check if the point table configuration is correct, including data points, data formats
Contact our customer service staff.

SAU-300 User Manual A01 30


SINENG Electric Co., Ltd.
Chapter 5 Product Maintenance

This chapter describes the maintenance of the SAU300, including the maintenance cycle and
maintenance methods. Be sure to read the instructions in this section carefully before maintenance.

Danger

Only professionals can maintain the SAU300, others can not operate!

Warning

Be sure to use qualified spare parts supplied by our company. If the use of spare parts supplied by
our company causes damage to the equipment, it has nothing to do with our company.

Danger

In order to ensure the safety of maintenance personnel, it is not allowed to touch any live parts of the
data collector while the data collector is running, and it is necessary to check the grounding point of
the product frequently for reliable connection.

Danger

After the data collector is completely powered down, the hazardous voltage still exists in the
product! Please wait 1 minute before maintaining the product!

1. Periodic Inspection
The periodic inspection and maintenance of the data collector can confirm the status of the SAU200
in time to improve the reliability of the product. It is recommended to perform periodic inspection
every three months to confirm whether the working environment is normal, check whether the RS485
and dry contact wiring are reliable, whether the cable connection terminal is loosened, check whether
the RS485 cable shielding layer is reliably grounded, and check whether the equipment enclosure is
well grounded.

2. Daily Maintenance
Check whether the RS485 and dry contact wirings are reliable, whether the cable connection terminal
is loosened, check whether the RS485 cable shielding layer is reliably grounded, and check whether
the equipment enclosure is well grounded.

Warning

Unauthorized removal of the data collector enclosure may result in equipment damage. This type of
equipment damage has nothing to do with our company!

SAU-300 User Manual A01 31


SINENG Electric Co., Ltd.

Service After Sales Information

SINENG ELECTRIC CO.,LTD provides customers with technical support.


Users may contact the nearest SINENG local sales office or service center.

SINENG ELECTRIC CO., LTD.

Address: #6 Hehui Road, Huishan Economic Development Zone, Wuxi, Jiangsu


Post Code: 214174
Customer service hotline: 0510-88888118
Fax: 0510-85161899

SAU-300 User Manual A01 32


SINENG Electric Co., Ltd.
Product Warranty Card
Thank you for selecting our energy storage convertor!
Product Model:
Product Serial Number:
Please refer to the descriptions in the User Manual for the product specifications,
standards and technical conditions.
The warranty of this product is years. Within the warranty period, SINENG
will provide free repair or replacement services for any faults that are not caused by
human error or force majeure (including but not limited to earthquake, mudslides,
flood, typhoon and war).
User Name:
User Address:

Contact Person:
Telephone:
E-Mail:

SINENG Electric Co., Ltd.


Address: #6 Hehui Road, Huishan Economic Development Zone, Wuxi, Jiangsu
Post Code: 214174
Customer service hotline: 0510-88888118
Fax: 0510-85161899
Website: www.si-neng.com