Protection System PGDC
Protection System PGDC
Contact designation
• NO (Normally open) Contact
• NC Normally closed) Contact
• Time delayed contact – Delay in pickup
• Delay in drop off
Types of relays
Based on Operating time Characteristic
• Definite time
• IDMT Inverse definite mean time
• Instantaneous
Contactors
Operating supply
• AC Contactors
• DC Contactor
Application
• Control contactors
• Power contactors
Aux Contacts
With Aux contact
Without Aux contact
Abnormal Operating Conditions
Over votage
Under voltage
Over current
Under current
Over frequency
Under frequency
Negative phase sequence current/voltage
Combination of above
Protection scheme
Differential protection
Restricted earth fault protection
Carrier aided protection
Impedance based protection
Over/under current
Over/under voltage
Over/under frequency
Over fluxing
Protection
In
Transmission system
Transmission System/Switchyard Fault
• Over current protection ( Directional / Non Directional)
• Over Voltage Protection
• Synchronization relay
• Differential Protection
• Distance Protection
• Carrier aided protection
• Direct inter trip
• Power swing Blocking
• Revers zone
• Busbar / T Point Differential protection
• LBB
• Pole Discrepancy
Generator Protection
Fault Originated from Grid/Switchyard
Transformer Feeder
Over current protection
Earth fault protection
Motor Feeder
• Thermal Over current
• Over Current IDMT/DT
• Earthfault DT
• Differential
• NPS
• UV
• Block rotor
Revers Blocking Scheme
• Fault in the outgoing feeder of a board is sensed by it’s relays.
• Two out puts will be generated
1. Trip the faulty feeder
2. Send the blocking signal to up stream breaker (I/C or Tie I/C)
• Same fault will be sensed by the upstream feeder relays also
• It will process the trip as follows –
1. If reverse blocking signal is present trip with 300 mSec Delay
2. If reverse blocking signal is not present Trip in 100 mSec