Guidance Note 3 Inspection and Testing 2022
Guidance Note 3 Inspection and Testing 2022
The Institution of
Engineering and Technology
0.06
Guidance Note 3
Inspection & Testing
Updated to BS7671:2018+A2.2O22
IET Wiring Regulations
The Institution of
Engineering and Technology
0.06
Guidance Note 3
Inspection & Testing
Updated to BS 7671:2018+A2:2022
lETWiring Regulations
Published by the Institution of Engineering and Technology, London, United Kingdom
The Institution of Engineering and Technology is registered as a Charity in England & Wales (no. 211014) and
Scotland (no. SC038698).
This publication is copyright under the Berne Convention and the Universal Copyright Convention. All rights
reserved. Apart from any fair dealing for the purposes of research or private study, or criticism or review, as
permitted under the Copyright, Designs and Patents Act, 1988, this publication may be reproduced, stored or
transmitted, in any form or by any means, only with the prior permission in writing of the publishers, or in the case
of reprographic reproduction in accordance with the terms o f licences issued by the Copyright Licensing Agency.
Enquiries concerning reproduction outside those terms should be sent to the publishers at The Institution of
Engineering and Technology, Michael FaradayHouse, Six Hills Way, Stevenage, SGI 2AY, United Kingdom.
While the author, publisher and contributors believe that the information a n d guidance given i n this work are
correct, all parties must rely upon their own skill and judgement when making use of them. The author, publisher
and contributors d o n o t assume any liability to anyone for any loss or damage caused by any error or omission
in the work, whether such a n error or omission is the result of negligence or any other cause. Where reference is
m a d e to legislation it is n o t to be considered as legal advice. Any and all such liability is disclaimed.
Permission to reproduce extracts from British Standards is granted by BSI. No other use of this material is
permitted. British Standards can be obtained i n PDF or hard copy formats from the BSI online shop:
https://shop.bsigroup.com/.
Cooperating organizations 6
Acknowledgements 7
Preface 8
Introduction 11
Chapter 1 General requirements 13
1.1 Safety 13
1.2 Required competence 15
1.3 The client 16
1.3.1 Certificates and reports 16
1.3.2 Rented domestic and residential accommodation 16
1.3.3 The Construction (Design a n d Management) Regulations 2015 17
1.4 Additions and alterations 17
1.5 Departures and non-compliance 18
1.6 Record-keeping 18
1.7 Installations requiring specialist knowledge, training or experience 19
G u i d a n c e N o t e 3: I n s p e c t i o n & Testing 3
© The Institution of Engineering and Technology
2.6.14 Protection by automatic disconnection o f supply (ADS) 85
2.6.15 Earth fault loop impedance (EFLI) verification 85
2.6.16 Prospective fault current (Ipf) 88
2.6.17 Phase sequence testing 93
2.6.18 Operation a n d functional testing o f RCDs 95
2.6.19 Other functional testing 102
2.6.20 Verification o f voltage drop 102
2.6.21 Verification o f protection of low voltage (LV)
installations against temporary overvoltages
due to faults i n the high voltage (HV) or LV system 103
2.6.22 Verification o f protection against overvoltages of atmospheric
origin or due to switching 104
2.6.23 Verification of measures against electromagnetic
disturbances 105
2.6.24 Prosumer's electrical installations (PEIs) 106
Chapter 3 Periodic inspection and testing 109
3.1 Purpose of periodic inspection and testing 109
3.2 Necessity for periodic inspection and testing 109
3.3 Electricity at Work Regulations (EAWR) 110
3.3.1 The need for appropriate inspection and testing 110
3.3.2 Safety in inspection and testing 111
3.3.3 Diverted neutral currents 111
3.4 Design 111
3.5 Routine checks 112
3.6 Required information 113
3.7 Frequency of periodic inspections 114
3.8 Requirements for periodic inspection and testing 117
3.8.1 Process: prior to carrying out inspection a n d testing 117
3.8.2 General procedure 118
3.8.3 Setting inspection and testing samples 119
3.9 Periodic inspection 123
3.9.1 Example checklist of items that require inspection 123
3.10 Periodic testing 128
3.10.1 General 128
3.10.2 Tests to be made 128
3.10.3 Additional notes on periodic testing 130
3.11 Electrical Installation Condition Report (EICR) 133
3.12 Periodic inspection of installations constructed to an earlier edition
of BS 7671 or the IEE Wiring Regulations 135
Chapter 4 Test instruments and equipment 137
4.1 Instrument standard 137
4.2 Instrument accuracy 138
4.3 Low-resistance ohmmeters 139
4.4 Insulation resistance testers 140
4.5 EFLItesters 140
4.6 Earth electrode resistance testers 143
4.7 RCD testers 143
4.8 Phase rotation instruments 144
4.9 Thermographic equipment 144
Chapter 5 Forms 149
5.1 Initial verification (inspection and testing) forms 149
5.2 Minor works 150
We would like to thank the following organizations for their continued support:
BEAMA Ltd
BCA
Certsure, t r a d i n g as NICEIC
City & Guilds
EAL
ECA
Electrical C o n t r a c t o r s ' A s s o c i a t i o n of S c o t l a n d (SELECT)
Electrical Safety First
Health a n d Safety Executive (HSE)
IHEEM
NAPIT
BSI also maintains stocks of international and foreign standards, with many English
translations. Up-to-date information o n BSI Standards can b e obtained from the BSI
website: www.bsigroup.com
Other illustrations, from different sources, are acknowledged within the text.
Cover design a n d illustration were created by Ken Dobson at Studio Stunt Double:
http://studiostuntdouble.com/.
Copies of Health and Safety Executive documents and approved codes o f practice
(ACOP) c a n be obtained from:
HSE Books
Customer Services
PO Box 2 9
Norwich, NR3 1GN
Tel: + 4 4 (0)333 202 5070
Email: [email protected]
Web: http://books.hse.gov.uk
G u i d a n c e N o t e 3: I n s p e c t i o n & Testing 7
© The Institution o f Engineering and Technology
Preface
Note that use of this Guidance Note does alone n o t provide compliance withBS7671.
Its content is intended to explain some of the requirements of BS 7671. Readers
should always consult BS 7671 to satisfy themselves of compliance and must rely
upon their o w n skill and judgement w h e n making use of the guidance provided within
this publication.
The scope generally follows that of BS7671; t h e relevant regulations and appendices
are noted in the margin. Due to the introduction in 2 0 1 6 of CENELEC Harmonized
Document (HD) 6 0 3 6 4 - 6 covering inspection and testing, the clause numbering in
B S 7 6 7 1 aligns with that in the HD. As a result, Chapters 61 to 6 3 are n o t used; the
text o f Part 6 of BS 7 6 7 1 starts at Chapter 6 4 . Apart f r o m the testing of insulation
resistance a n d residual current devices (RCDs), the requirements for inspection and
testing have not significantly changed f r o m BS 7671 :201 8.
Some Guidance Notes also contain material not currently included i n BS 7671, but
which was present in earlier editions of the Wiring Regulations. All o f the Guidance
Notes contain references to other relevant sources of information.
Electrical installations in the United Kingdom that comply w i t h BS 7671 are likely
to satisfy the relevant parts o f statutory regulations such as the Electricity at Work
Regulations 1989 (EAWR). However, this cannot be guaranteed. It is stressed that
it is essential to establish which statutory and other regulations apply and to install
accordingly. For example, a n installation in premises subject t o licensing may have
requirements different f r o m or additional to those of BS 7671, and these will take
precedence.
Other related electrical installations, such as emergency lighting, fire alarms and
information and communication technology (ICT) systems, have their own installation
requirement standards such as BS 5266, BS 5839 and BS 6701 respectively. These
may have installation, inspection, testing and certification requirements over and above
those required i n BS 7671. It is the responsibility of the duty holder to maintain all
their installations appropriately, and the extent of the inspection and testing, and the
standards to which it is conducted, should b e agreed before any work is undertaken.
The inspector is reminded that for a periodic inspection and test of a n existing
installation, their duty is to assess the suitability of the existing installation for continued
use, subject to any agreed limitations and exclusions. They must therefore make
sufficient inspection and tests to enable them to make that assessment. In addition, it
is the duty of the building or site dutyholder to maintain their installation so that it is
safe and to undertake such maintenance as is necessary to achieve this.
Users of this Guidance Note should assure themselves that they have complied with
any relevant legislation, including, where applicable, legislation that post-dates the
publication.
G u i d a n c e N o t e 3: I n s p e c t i o n & Testing 9
© The Institution of Engineering and Technology
NOTES
This Guidance Note is concerned primarily with Part 6 of BS 7671 (Inspection and
testing) along with Appendix 6 (Model forms for certification and reporting).
Neither BS 7671 nor the Guidance Notes are design guides. It is essential to prepare
a full design and specification prior to commencement or alteration of an electrical
installation.
514.9 The design and specification should set out the requirements and provide sufficient
information to enable competent persons to carryout the installation and to commission
it. The specification must include a description of how the system is to operate and
all the design and operational parameters. It must provide for all the commissioning
procedures that will b e required a n d for the provision of adequate information to the
user. This will be by means of a n operational and maintenance (O&M) manual or
schedule, and 'as-built' drawings, if necessary.
(a) the designer (see the Construction (Design and Management) Regulations 2015
(CDM) for information o n designers' duties);
(b) the installer (contractor or if there is m o r e than one, principal contractor and
contractors);
(c) the verifier;
(d) specialist commissioning engineers;
(e) the distributor of electricity (the distribution network operator (DNO));
(f) the installation owner and/or user (and, where applicable for CDM, the client.
Where there is a domestic client, the client's duties are undertaken by the
contractor or, if there is more than o n e contractor, the principal contractor);
(g) the architect (and, where CDM applies, the principal designer);
(h) the fire risk assessor;
(i) specialist manufacturers or suppliers;
( j ) area Building Control bodies;
( k ) any regulatory authority:
(l) any licensing authority;
(m) any specialist insurers; and
(n) the Health a n d Safety Executive (HSE).
"Designers are those, who as part of a business, prepare or modify designs for a
building, product or system relating to construction work.
1 construction; and
2 the maintenance and use of a building once it is built.
Provide information to other members of the project team to help them fulfil their duties."
Health and safety o f all installation a n d inspection a n d testing staff and any other
persons i n the premises is vital and a work plan including risk assessments a n d
method statements must b e agreed with all parties and put in place before any work
is undertaken.
The installation operational manual must include a description of how the system
as installed is to operate, maintenance provisions and all test and commissioning
records. The manual should also include manufacturers’ technical data for all items
of switchgear, luminaires, accessories, etc. and any special instructions that may b e
needed. The Health and Safety at Work etc. Act 1974 Section 6 and the Construction
(Design and Management) Regulations 2015 are concerned with the provision
of information, and guidance o n the preparation of technical manuals is given i n
BS EN IEC/IEEE 82079-1 Preparation of information for use (instructions for use)
of products - Principles and general requirements and BS 4940 series Technical
information o n construction products and services. The size and complexity of the
installation will dictate the nature and extent of the manual.
1.1 Safety
Before any work can begin, a work programme should b e agreed with the client and a
health a n d safety plan, including risk assessments and method statements, agreed and
put in place. It m a y be that work has to be carried out when the premises is operating
and staff are present, and they must not b e exposed to any safety risks. Work areas
should b e fenced off w i t h temporary barriers a n d electrical equipment should not
be left unattended when open. There should be adequate workspace, access and
lighting appropriate to t h e work being carried out, and during electrical testing it is often
necessary to provide temporary task lighting as parts, or all, of the installation m a y
be isolated. Escape routes must be kept open at all times or temporary alternatives
arranged. Where supplies have to b e isolated, it is necessary that this is planned i n
advance with the premises management. Health and safety guidance (HSG) Electricity
a t work: Safe working practices (HSC85) recommends managers establish a system
of rules and procedures wherever electrical work is to b e carried out, or ensure that
contractors brought in to d o electrical work have appropriate rules and procedures.
Initial verification, and some maintenance activities, o f fixed electrical installations fall
within the scope of the Construction (Design and Management) Regulations 2015 (CDM).
For private domestic clients, the contractor, or, if there is m o r e than one, the principal
contractor, undertakes the client's duties.
(a) understanding the equipment to b e used, its rating and the characteristics of
the installation upon which it is proposed to use the equipment.
(b) checking that the instruments to be used conform to the appropriate
British Standard safety specifications. These are BS EN 61010 series Safety
requirements for electrical equipment for measurement, control, and laboratory
use and BS 5458:1977 (IEC 141:1973) Specification for safety requirements for
indicating and recording electrical measuring instruments and their accessories.
BS 5 4 5 8 has n o w been withdrawn, but is the standard to which older
instruments should have been manufactured.
(c) checking any test equipment before use to see that it is complete and not damaged.
(d) checking that test leads, including any probes or clips used, are i n good order,
are clean and have no cracked or broken insulation. Where appropriate, the
guidance given i n GS38 should b e observed for test leads. This recommends
the use of adequately insulated test equipment, probes, connectors, a n d test
leads, suitable for the insulation overvoltage category in which tests are being
conducted (see Table 1.1). Suitable high breaking capacity (HBC) fuses o r other
means of limiting current, should be provided i n test leads o r test equipment.
Such measures help reduce the risks associated w i t h both accidental contact,
a n d arcing under fault conditions.
Note: The equivalent overvoltage category for a test arrangement is the lowest overvoltage
category of any equipment, including test instruments, leads, probes, connectors, and
similar, connected in the test arrangement.
Particular attention should b e paid to the safety aspects associated w i t h any tests
performed with instruments capable o f generating a test voltage greater t h a n 5 0 V AC
o r 120 V DC in dry conditions, or 2 5 V AC or 6 0 V DC i n wet or damp conditions, or
which use the supply voltage for the purposes of testing earth electrode, earth fault
loop impedance and operation of residual current device(s) (RCD). Note the warnings
given in Section 2.6.16 through to Section 2.6.19 of this Guidance Note.
14 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing
© The Institution of Engineering a n d Technology
Electric shock hazards can arise from, for example, capacitive loads, such as when
cables become charged in the process of an insulation resistance test, or voltages o n
t h e earthed metalwork whilst conducting a loop test or RCDtest. The test limits quoted
in these guidelines are intended to minimize the chances of receiving anelectric shock
during tests.
Under some conditions, such as when working at height, particular care needs to be
taken even with touch voltages below 5 0 V A C or 120 V DC. A spark, or contact with
touch current at the limit of perception, m a y cause an inspector or test equipment
operator to be startled and jump or physically jolt away f r o m the contact, resulting in
a fall or other serious incident. It is important to address such hazards when carrying
out risk assessments before work begins.
Inspectors must also have the relevant education a n d experience to enable them to
perceive risks and avoid the dangers that electricity can create, and be fully versed
in the inspection and testing procedures. This can best be shown by the inspector
holding a recognized inspection and testing qualification, along with a current level 3
certificate in the requirements for electrical installations BS 7671.
Furthermore, the inspector must employ suitable test equipment during t h e inspection
and testing process, be familiar with its operation, and have sufficient inspection
experience in interpreting the results with regard to the requirements of BS 7671.
It is worth noting that the person responsible for inspection and testing may b e required to
formally demonstrate competence by means of registration/certif ication under a recognized
scheme or membership of a recognized trade body, or, for example, as a condition of
contract and/or as a requirement of the Local Authority Building Control (LABC).
It is the responsibility of the inspector, for either the initial or periodic inspection and
testing, as appropriate, to:
641.4 (a) prevent danger to any person or livestock and prevent property damage;
641.3 (b) compare the inspection and testing results with the design criteria (where
available), with BS 7 6 7 1 and/or with previous records, as appropriate;
(c) confirm compliance with the current edition of BS 7671, or any non-compliance
(non-conformity with BS 7671) that may give rise to danger;
(d) take a view on related issues that might constitute or give rise to danger of
the installation itself, or its interface with the premises, such as the condition of
connected electrical equipment, the condition of distributor's equipment, or the
condition of building fabric to which electrical equipment is secured, or through
which wiring systems pass (for example, fire stopping); and
(e) take a view and report o n the condition of the installation.
Sometimes the person ordering the work is not the user of the installation. I n such
cases, it is necessary for the user (for example, the employer or householder) t o have
a copy of the certificate (together with the records o f inspections and test results).
It is recommended that those providing documentation to the person ordering the
work also recommend that a copy of the forms b e passed to the user, including any
purchaser o f a domestic property. For rented accommodation, this m a y b e required
by legislation (see Section 1.3.2).
Copies of any certificates o r reports along with their associated schedules should b e
kept in the operational a n d maintenance (O&M) documentation for t h e premises.
The above Acts d o not directly specify periodic inspection a n d testing of a n electrical
installation. Periodic inspection a n d testing is a means of demonstrating compliance
with the Acts. The Scottish Government has published guidance o n meeting the
tolerable standard a n d repairing standard in Scotland, which can b e downloaded
from: https://www.gov.scot/publications/electrical-installations-and-appliances-private-
rented-properties/.
The Electrical Safety Standards i n the Private Rented Sector (England) Regulations
2 0 2 0 apply t o all n e w tenancies i n private rented properties in England f r o m 1 July
2020, a n d all existing tenancies f r o m 1 April 2021. This legislation requires an EICRto
b e prepared at an interval o f n o t m o r e than 5 years (or shorter period if the inspector
considers it necessary). The legislation also requires specific persons, such as tenants,
new tenants before they occupy the premises, or, o n written request, local authority
644.1 .2 While there is no obligation to inspect and test any part of the existing installation that
does not affect and is not affected by the addition o r alteration, any defects with the
existing installation that are observed during the course of the works, that may give
rise to danger, b u t d o n o t affect the safety of the addition or alteration, are required to
be noted in the ’Comments on existing installation’ section of an EIC (single-signature
or multiple-signature) or o n Minor Electrical Installation Works Certificates (MElWCs).
If there is insufficient space to complete this information, a separate document could
b e used and referred to in the certificate.
1.6 Record-keeping
132.13 It is a requirement that the appropriate documentation called for in Regulation 514.9,
514.9 Part 6 and (where applicable) Part 7 o f BS 7671 is provided for every electrical installation.
Chapter 6 5 Records of all checks, inspections and tests, including test results, should be kept
Appx6 - throughout the working life of an electrical installation. This will enable deterioration to
guidanceto recipents b e identified, a n d could also be used as a management tool to ensure that maintenance
checks are being carried o u t and to assess their effectiveness.
The CDM Regulations also require that once the construction work has been completed,
the health and safety file remains available for inspection by any person who might need
it to comply with any relevant legal requirements. It also requires that the file is revised
and updated as often as may b e appropriate to incorporate any relevant new information.
EICs, MElWCs and EICRs (as appropriate) would constitute relevant information in
relation to this requirement.
In both domestic and non-domestic cases, there may also be insurance requirements
that imply or specify records.
18 G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing
© The Institution of Engineering a n d Technology
1.7 Installations requiring specialist knowledge,
training or experience
This Guidance Note mainly covers the general requirements of BS7671. The following
publications provide further guidance o n types of installation, or special location, that
require additional information, experience, and/or training, for initial verification and
periodic inspection, testing and certification:
710 (a) Medical locations: refer to t h e IET Guide to Electrical Installations in Medical
710.64 Locations, IET Guidance Note 7 Special Locations along with relevant English,
Scottish and Welsh Health Technical Memoranda;
( b ) Solar photovoltaic (PV) installations: refer to the IET Code of Practice for
Grid-Connected Solar Photovoltaic Installations;
722 (c) Electric vehicle charging equipment installations: refer to the IET Code of
Practice for Electric Vehicle Charging Equipment Installation;
(d) Electrical energy storage systems: refer to the IET Code of Practice for Electrical
Energy Storage Systems;
(e) Fuel filling stations: refer to the AREA Guidance for Design, Construction,
Modification, Maintenance and Decommissioning of Filling Stations (also known
as the Blue Book), and the IET/APEA publication Electric Vehicle Charging
Installations at Filling Stations;
(f) Other locations with explosive atmospheres: see BS EN 60079;
(g) Temporary power systems within the scope of BS 7909: refer to the IET
Temporary Power Systems: A guide to the application of BS 7671 and BS 7909
for temporary events and the IET Practitioner's Guide to Temporary Power
Systems;
(h) Fire protection and fire stopping: refer to IET Guidance Note 4 Protection
Against Fire;
(i) Emergency lighting systems: refer to the Electrician's Guide to Emergency
Lighting Systems along with BS 5266-1; and
(j) Fire detection and fire alarm systems: refer to the Electrician's Guide to
Fire Detection and Fire Alarm Systems along with BS 5839-1:2017 and
BS 5839-6:20 19+AI:2020.
This list is n o t exhaustive. The above publications are not a substitute for suitable
experience and/or training in those types o f installation.
Initial verification is carried out on a new installation before it is put into service. The
642.2 purpose is to confirm by way of inspection and testing, during construction and on
completion, that the installation complies with the design and construction aspects of
BS 7671, in so far as is reasonably practicable.
Appx 6, Intro (v) It is important to recognize the responsibilities o f the signatories for the design,
construction and verification. While the inspector is responsible for verifying aspects of
b o t h design a n d construction, they cannot, and are not m e a n t to, absolve responsibility
for their work elements from the designer and installer nor fix any problems they may find.
Example
Consider o n e aspect of the design: the inspector should check that the cable sizes, as
specified, have been correctly selected and installed. In order to do this, the design
criteria is required to be obtained, for example, a cable o r circuit schedule, and will
then carryout a visual inspection of the installed cable sizes for comparison. The m o s t
logical position to d o so will be at the distribution board housing the cables' protective
devices. It would b e unreasonable for the inspector to carry out design cable sizing
checks, as this is the responsibility of the designer.
At this point, it would also be unreasonable for the inspector to check that each cable
size at the distribution point is maintained throughout the cable's length (this is the
responsibility of the installer or constructor).
This example illustrates the principle a n d the responsibilities of the designer and
constructor of the installation. The inspector carries out checks, but only to confirm
the work of others.
42.3 The inspector must have adequate information o n the design details to check and
inspect against. BS 7671 provides a format list in Regulation 642.3 of items to be
checked, although this list is not exhaustive. These items are as follows:
(b) the fixed installation is correctly selected and erected, taking into account
manufacturers’ instructions;
(c) the fixed installation is n o t visibly damaged or otherwise defective so as to
impair safety; and
(d) the installation is ready a n d safe to be used.
644.1 Results
The results of inspection and tests are to be recorded as appropriate. The HSE's
publication HSR25 recommends that records of all maintenance, including test results,
b e kept throughout the working life o f an installation (see guidance on the Electricity
at Work Regulations 1989 (EAWR), Regulation 4(2)). This can enable the condition of
equipment and the effectiveness of maintenance t o be monitored.
643.1 R e l e v a n t c r i t e r i a
The relevant criteria are, for the most part, the requirements of the Regulations for
the particular inspection or test. Most criteria are given i n Sections 2 and 3 of this
Guidance Note.
There will b e some instances where the designer has specified requirements that
are particular to the installation concerned. For example, the intended impedances
may be different from those in BS7671. I n this case, the inspector should either ask
for the design criteria or forward the test results to the designer for verification with
the intended design. In the absence of such data, t h e inspector should apply the
requirements set o u t in BS 7671 .
Verification
The responsibility for comparing inspection a n d test results w i t h relevant criteria, as
required by Regulation 641.3, lies with the party responsible for inspecting and testing
t h e installation. This party, which may be the person carrying out the inspection a n d
testing, should sign the ’Inspection and testing’ section of the Electrical Installation
Certificate (EIC) or the ’Declaration’ section of t h e Minor Electrical Installation Works
Certificate (MEIWC). If the person carrying o u t the inspection and testing is also
responsible for the ’Design’ and 'Construction' of the installation, the design and
construction sections of the EIC should be completed by the same person.
2.2 Certificates
Appx 6 Appendix 6 of B S 7671 contains model forms for the initial certification of a new
installation or for a n addition or alteration to a n existing installation, as follows:
Note: The statutory Electricity Supply, Quality a n d Continuity Regulations (ESQCR) require
that these characteristics should be available f r o m the distribution network operator
(DNO) for all sources of supply from the public supply network.
G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing 23
© The Institution of Engineering a n d Technology
Diagrams, charts or tables
514.9.1 T h e Health a n d S a f e t y at Work etc. Act (HSWA) 1974 generally r e q u i r e s relevant
i n f o r m a t i o n to b e available a s a n a i d to s a f e use, inspection, testing a n d maintenance.
T h i s m a y i n c l u d e t h o s e i t e m s l i s t e d i n R e g u l a t i o n 514.9.1, a s f o l l o w s :
The time intervals between the recommended dates of periodic inspections need consideration.
The p e r i o d t o t h e f i r s t p e r i o d i c i n s p e c t i o n a n d t e s t is r e q u i r e d t o b e c o n s i d e r e d a n d
r e c o m m e n d e d by t h e i n s t a l l a t i o n d e s i g n e r a n d o t h e r r e l e v a n t p a r t i e s , a s n o t e d i n
Regulations 301.1, a n d 341.1, as p a r t of the design.
It h a s n e v e r b e e n c l a r i f i e d w h e t h e r t h e p r o p o s e d p e r i o d t o a s u b s e q u e n t p e r i o d i c
inspection s h o u l d b e m e a s u r e d f r o m the t i m e of t h e previous i n s p e c t i o n o r f r o m the
t i m e w h e n a n y i d e n t i f i e d r e p a i r s have b e e n c o m p l e t e d (they m a y never be!). The
i n s p e c t o r m u s t t a k e a v i e w o n t h i s ; it w o u l d p e r h a p s b e b e s t t o s e t it f r o m t h e t i m e
of the p r e v i o u s inspection, e s p e c i a l l y if there a r e significant r e p a i r s identified o r if t h e
i n s t a l l a t i o n i s p o o r l y maintained.
Section 3.7 contains further guidance on the frequency of periodic inspection and testing.
It should b e noted that Regulation 641.1 requires inspection and testing to b e carried out
during the erection stage of the installation. This is to allow the review and inspection
of work that may later b e covered and inaccessible; however, t h e inspector will require
necessary design information from the designer before any such inspections during
construction or installation.
642.3 BS7671 provides a list of items considered as a minimum to be inspected, but t h e list
is not exhaustive. The inspector, where necessary, will inspect and compare the items
against data provided by the designer and installer and identify any non-compliances
or departures. However, it is not for the inspector to decide what installation items are
required o r necessary, or to identify any repairs or modifications. The list is as follows:
a
Sect526 Connection of conductors
Every connection between conductors and equipment/other conductors should
provide durable electrical continuity and adequate mechanical strength.
It is impractical for an inspector t o physically inspect all connections but they should
inspect a representative sample of connection types, especially larger connections,
such as o n switchgear and busbars. When checking connections, t h e correct torque
setting for screw or bolted terminals should b e used. (It is noted that in some cases,
such as high current busbar connections, specialist resistance tests may b e required
that are outside the scope of BS7671.)
(a) Class 1, solid, conductors. These consist of only a single strand of conductor
forming the entire csa.
(b) Class 2, stranded, conductors. These consist of at least 6 strands, although
some applications in Part 7 of BS 7 6 7 1 specify a m i n i m u m of 7 strands are
used for stranding class 2 conductors.
(c) Class 5, finely stranded (flexible) conductors, These are m o r e finely stranded
than Class 2 stranded conductors, and are typically found in appliance cables,
or flexible installation cables.
(d) Class 6, extra-finely stranded (extra-flexible) conductors, being m o r e finely
stranded again.
Some terminals are only suitable for certain conductor stranding classes, as described
in Table 2.1.
Again, it is impractical for a n inspector to physically inspect all identifications, but they
should inspect a representative sample of types, especially o n larger conductors, such
as to switchgear.
AC power circuit
Notes:
(1) Power circuits include lighting circuits.
(2) M identifies either t h e mid-wire of a three-wire D C circuit, o r t h e earthed conductor of a
t w o - w i r e earthed D C circuit.
(3) Only t h e m i d d l e wire of three-wire circuits m a y b e earthed.
(4) A n earthed PELV conductor is blue.
c Routing of cables
522.8 Cables a n d their cable management systems should be designed a n d installed taking into
account the mechanical stresses that users of the installation will make upon the installation.
150 m m
o
3
3
WHMM
Room 2
Room 1
It will be far t o o late at the end of the construction to view and assess a n y of these things,
so it is vital that the inspector continually i n s p e c t s the installation w o r k d u r i n g construction.
Cables routed in buildings must b e fixed such that they cannot c o m e away from
their supports during fires and collapse to block escape routes or entangle firefighters
searching the building in smoke-filled conditions. Such entanglements have led to
fatalities in t h e past, which could have been avoided with s o m e forethought. Not all
escape routes in a building are defined and signed: in open-plan office areas, there
can b e several possible routes away f r o m a desk or meeting r o o m across an o p e n
office area to an escape stair (see BS 9999) and all such routes should b e kept clear
f r o m possible entanglement. An escape route is defined i n the Regulations as a "path
to follow for access t o a safe area in the event of an emergency". T h e requirement for
surface-run wiring systems n o t t o b e subject to premature collapse in the event of a
fire applies to all areas, and not just designated escape routes.
I n larger industrial or commercial installations, cable ladder or tray and other services
may b e suspended together f r o m concrete structural elements by steel wires or
'drop rods' screwed into the concrete. The inspector cannot physically assess the
suitability or the loading of such fixings, but may look at the design data provided to
see that what is installed is as the design.
The inspector m u s t also assess any fire protection repairs and fire-stopping where
Appendix 13 cables have been installed through a fire-rated building structural element or wall. The
electrical installation designer should provide information in relation to fire safety with
regard to cable routes. Regulation 527.2.1 requires that openings remaining after t h e
passage of wiring systems are sealed according to the degree of fire-resistance
prescribed for the respective element of the building construction before penetration.
The seal is required to:
527.2.3 Where wiring system containment (conduit, trunking, and busbar trunking systems)
Appendix 13 passes through a building element that has specific fire resisting properties and has an
internal cross-sectional area greater than 710 m m 2 for example, a round hole of around
3 0 m m diameter, it must b e internally sealed in accordance with Regulation 527.2.3.
(a) l i g h t i n g ;
(b) emergency lighting;
(c) f i r e detection a n d alarm; a n d
(d) o t h e r e s s e n t i a l s a f e t y s y s t e m s f o r high hazard premises.
132.7 d S e l e c t i o n of c o n d u c t o r s
Sect 523 T h e s p e c i f i c a t i o n of c a b l e s u s e d - B S t y p e a n d designation, t e m p e r a t u r e ratings,
selection for environmental conditions, c o n d u c t o r category a n d material, certification
to a n d c o m p l i a n c e with the r e q u i r e d C o n s t r u c t i o n P r o d u c t s Regulations, etc. - must
b e c h e c k e d , b a s e d o n the d a t a s u p p l i e d by t h e designer a n d installer.
Sect 523 The cross-sectional area (csa) of conductors should be assessed against the overcurrent
Sect 524 protective arrangement and the requirements for limitation of voltage drop, based
Sect 525 upon information provided by the installation designer (where available), such as a
cable schedule or schematic diagram.
132.14.1 e
Verification of polarity: single-pole device in a TN or TT system
530.3.2 must be checked that single-pole devices for protection or switching are installed in
line conductors only, and that Edison screw (ES) lampholders are correctly connected.
553.1.3 Table 55.1 of BS 7671 sets out the three different types of plug and socket-outlet
recognized, their ratings and their associated British Standards.
553.2.2 Particular attention should be made to the correct connection of cable couplers so that
pins of connectors (which would be accessible when the couplers are disconnected)
are connected to the load or downstream side of the connection. Couplers for cables
in which current may flow in either directions, such as some circuits in prosumer’s
electrical installations (PEIs), appropriate couplers having live parts protected to at least
IP2X on both parts of the coupler when disconnected should be used.
559.5.1.204 Bayonet lampholders B15 and B22 should comply with BS EN 61184 and have a
559.5.1.205 temperature rating T2, as described in that standard. With the exception of E14 and
E27 lampholders complying with BS EN 60238, ES lampholders used in TN and
TT systems should have the line of the supply connected to their centre contact, and
neutral connected to the outer contact. Lighting circuits incorporating B15, B22, E14,
E27 or E40 lampholders are only to b e used in a lighting circuit rated up to 16 A.
A wiring system such as conduit, trunking or ducting that penetrates a building element
that has a specified fire rating is to be sealed both internally and externally to the
degree of fire resistance of the external element. Fire barrier requirements are detailed
in Regulations 527.2.2 and 527.2.3.
The tables divide up t h e measures into t h o s e that are generally permitted, those that
are for use o n l y where access is restricted to skilled o r instructed persons, a n d t h o s e
t h a t are f o r u s e only where the installation is controlled o r supervised by skilled or
instructed persons. The tables also list the provisions f o r basic protection a n d fault
p r o t e c t i o n t h a t m a k e up t h e protective measures.
411 Automatic disconnection of Basic insulation of live parts Protective earthing, protective
supply (ADS) and/or barriers or enclosures equipotential bonding and
automatic disconnection in
case of a fault
or Class II equipment
Electrical separation for the Basic insulation of live parts Simple separation from other
413
supply of one item of and/or barriers or enclosures circuits and from Earth
current-using equipment
V Table 2 . 4 Protective measures for use only where access is controlled or supervised
by skilled persons
▼ Table 2 . 5 Protective measures for use only where the installation is controlled or
under the supervision of skilled or instructed persons
Basic p r o t e c t i o n by Fault p r o t e c t i o n b y
Earth-free local equipotential Basic insulation of live parts Protective bonding, notices,
418.2
bonding and/or barriers or enclosures etc.
Electrical separation for the Basic insulation of live parts Simple separation from other
supply of more than one item and/or barriers or enclosures circuits and Earth, to non
of current-using equipment earthed protective bonding,
etc.
This p r o t e c t i v e p r o v i s i o n forms p a r t of a n u m b e r of d i f f e r e n t p r o t e c t i v e m e a s u r e s , a s
s h o w n i n t h e previous tables.
T h e p r o v i s i o n f o r f a u l t p r o t e c t i o n is p r o t e c t i v e e a r t h i n g , p r o t e c t i v e b o n d i n g a n d
automatic d i s c o n n e c t i o n of s u p p l y i n c a s e of a fault. Although v e r i f i c a t i o n of EFLI f o r
each circuit provides evidence that d i s c o n n e c t i o n times a c c o r d i n g to Chapter 41 c a n
b e met, it i s a l s o important to inspect o r o t h e r w i s e verify t h e following items.
(a) e a r t h i n g conductor.
(b) circuit protective conductors (cpcs).
(c) p r o t e c t i v e b o n d i n g c o n d u c t o r s .
(d) m a i n b o n d i n g c o n d u c t o r s . R e g u l a t i o n 411.3.1.2 m e t a l l i c p i p e s w i t h i n t h e b u i l d i n g
c o n n e c t e d to non-conductive service p i p e s entering t h e building n e e d n o t b e
connected to the protective equipotential bonding.
(e) s u p p l e m e n t a r y bonding conductors (where required).
(a) TN-C-S;
(b) TN-S; or
(c) TT (earth electrode(s) used as the means of earthing for t h e installation).
The earthing arrangement should b e confirmed by the DNO, and not assumed by
visual inspection.
411.5 (TN) For installations that receive a low voltage (LV) supply f r o m the public distribution
411.5 (TT) network, the designer should also ascertain whether protective multiple earthing
(PME) conditions apply, as this affects the application of certain requirements of
BS 7671, such as t h e sizing of main protective bonding conductors, and earthing for
some of the special locations in Part 7 (for example, use of a PME earthing arrangement
is precluded for some special locations, such as caravan parks and marinas). Guidance
is available from the local DNO and in Energy Networks Association publication G12/4
Requirements for the Application of Protective Multiple Earthing to Low Voltage
Networks. PME conditions will normally apply in public LV supplies:
The EFLImust b e appropriate for the protective device, i.e. RCD or overcurrent device,
and within the values given in the relevant tables in Chapter 41 of BS 7671.
412.1 For double insulation, basic protection is provided by basic insulation, and fault
protection is provided by supplementary insulation.
For reinforced insulation, both basic protection a n d fault protection are provided by
a single application of reinforced insulation between live parts and accessible parts.
34 G u i d a n c e N o t e 3: I n s p e c t i o n & Testing
© The Institution of Engineering and Technology
2
414.1.1 (a) the nominal voltage must not exceed 5 0 V AC or 120 V DC or the lower limits
414.1.2 specified for a special location according to Part 7 of BS 7 6 7 1 (see note to
Regulation 414.1.2);
a
414.3 (b) suitable source, for example, a safety isolating transformer to BS EN 61558-2-6
or BS EN 61558-2-8;
414.1.1 (c ) protective separation f r o m all non-SELVor PELV circuits;
d r
414.1. ;; ( ) f° SELV, basic insulation between the SELV system and Earth; and
e
414.4.4 ( ) SELV exposed-conductive-parts must have n o connection with Earth, exposed-
conductive-parts or protective conductors of other systems.
Obstacles
Where this measure is used, the area must b e accessible only to skilled persons or to
instructed persons under their supervision.
The measure is not to b e used in some installations and locations of increased shock
risk. See Part 7 of BS7671.
417 Placing out of reach also provides basic protection only. The distances referred to in
Regulations 417.3.1 and 417.3.2 should b e increased where long or bulky conducting
objects are likely to b e handled in t h e vicinity, taking account of the dimensions of
those objects.
410.3.5 Bare live parts are only permitted in areas where access is controlled or supervised
by skilled persons. The dimensions of passageways should be checked against the
information given in Appendix 3 of t h e HSE's guidance o n HSR25 (see Section 729).
Sect 729 Section 7 2 9 (Operating and maintenance gangways) covers situations where open
switchgear or busbars are permitted and where access is restricted to skilled or
instructed persons. Inspection for verification in areas covered by Section 7 2 9 requires
careful checking, including the measurement of separation distances, for example,
those associated with 'arm's reach', as per Figure 417 of BS 7671; these must b e
confirmed with the installation isolated. However, it must be noted that the EAWRtake
precedence in all cases and their requirements for accessible live conductors must b e
followed in all cases.
The inspector should confirm the achievement of this and check that within t h e
location there are n o protective conductors (see also the specific test for this m e t h o d
in Section 2.6.12 of this Guidance Note).
418.2.3 Measures m u s t b e taken to ensure that the local protective bonding conductors are not
connected to Earth either directly or unintentionally via the exposed- and extraneous-
conductive-parts to which they are connected.
The inspection, supplemented with tests, should verify that n o item is earthed within
the area and that n o earthed services or conductors enter or traverse the area, including
t h e floor and ceiling. Inspection should confirm whether or n o t this has b e e n achieved.
Electrical separation for the supply to more than o n e item of current-using equipment
418.3 it is intended to supply more than one item of current-using equipment using
Sect 413 electrical separation, it will b e necessary to m e e t the requirements of Regulation 418.3.
This is in addition to meeting the requirements of Section 413, some of which are
referred to earlier in this section of this Guidance Note in relation to the use of electrical
separation for the supply of one item of current-using equipment.
418.3.3 The separated circuit should b e protected f r o m damage and insulation failure.
418. Socket-outlets should have a protective conductor contact, which is connected to the
protective bonding system described above.
All flexible cables should contain a protective conductor for use as a protective bonding
conductor, except where such a cable supplies only items of equipment having double
or reinforced insulation.
418/ The product of t h e nominal voltage (volts) a n d length (metres) of the wiring system
should not exceed 100,000 Vm and the length of the wiring system (metres) should
n o t exceed 5 0 0 m.
415.1.1 It should b e confirmed that an RCD selected to provide additional protection has a
rated residual operating current not exceeding 3 0 m A and complies with the
relevant standards.
415J.2 It should also b e confirmed that appropriate protective measures in accordance with
Sections 411 to 414 are in place, as an RCD m u s t not b e used as the sole means of
protection against electric shock.
Note: In medical locations of Group 1 and Group 2, and in fuel filling stations installed in
accordance with APEAGuidance for Design, Construction, Modification, Maintenance
and Decommissioning of Filling Stations, the voltage is reduced from 50 V to 25 V.
G u i d a n c e N o t e 3 : I n s p e c t i o n & Testing 37
© The Institution of Engineering and Technology
2
where la is the operating current of the protective device in amps (for overcurrent
devices, this is the 5 s operating current, and for RCDs, | n).
5313 RCDs should be selected in accordance with Regulation 531.3. Selection of RCDs
should take into account the residual fault current operating characteristics of loads
with respect to DC components.
Type AC RCDs shall only be used for fixed equipment, where it is known that the
load current contains no DC components. This precludes the use of socket-outlets
incorporating Type AC RCD protection (SRCDs)to BS 7288.
The RCD residual current operating characteristic Type can be identified by the marking
provided by the manufacturer. See Figure 2.34.
Type AC (Note 1)
B S E N 61008
Residual current Type A
circuit-breaker without RCCB
overcurrent protection Type F
BS EN 62423
Type B
Type AC (Note 1)
B S E N 61009
Residual current Type A
circuit-breaker with RCBO
overcurrent protection Type F
B S E N 62423
Type B
Type B (Note 3)
Notes:
1 O n l y t o b e used for fixed equipment, w h e r e it is k n o w n that t h e load current contains
n o DC components.
2 Additional protection only. Cannot b e used to m e e t disconnection times required by
Chapter 41 o f BS 7 6 7 1 for automatic disconnection of supply.
3 For operation b y skilled or instructed persons only.
4 RCCBs, RCBOs, CBRs a n d MRCDs are also available w i t h a time-delay option. These are
k n o w n as S-Type a n d identified with t h e relevant marking, see Figure 2.34.
132.5.1 This, however, does not include the detrimental influence of other systems onto
t h e electrical installation, such as water leaks or splashing, which are covered by the
requirements of Regulation 132.5.1.
All switch utilization categories must b e appropriate for the nature of the load (see
Table 2.7). It would b e part of the design to specify the appropriate t y p e of device.
Utilization category
Frequent operation Infrequent Typical applications
operation
AC-20a AC-20b Connecting and disconnecting under
no-load conditions
This may b e endorsed with a symbol advising of function, for example, for a switch
disconnector providing isolation as illustrated in Figure 2.3.
Table 537.4 Guidance on the suitability or otherwise of protective, isolation and switching devices
t o be employed for one or more of the functions of isolation, emergency switching
and functional switching is given in Table 537.4 of B S 7 6 7 1 a n d in Guidance Note 2.
The inspector should carry o u t an isolation review to check that effective isolation
can b e achieved, b u t it is n o t the inspector's responsibility t o resolve any apparent
shortcomings or problems with the isolation and switching design. The review could
include, where appropriate, locking-off and inspection or testing to verify that the circuit
is dead and n o other source of supply is present. The designer should also identify
where it may b e necessary to isolate the neutral conductor.
Note (5) to Table 537.4 i n B S 7 6 7 1 points out that circuit-breakers and RCDsare n o t
intended for frequent load switching or functional switching unless they are approved
by the device manufacturer for this duty. The note gives further guidance relating to
this a n d the inspector is at liberty to make a comment o n this use if it is inappropriate.
543.3.3.101 BS 7671 does not allow a switching or isolating device to b e placed in the earth
or protective conductor, other than a plug and socket-outlet, except for the special
conditions outlined in Regulations 543.3.3.101.
421.1.7 Arc fault detection devices (AFDDs) are designed to provide protection by monitoring
the change of current f l o w in a final circuit due to a possible cable conductor fault
that could cause an arc and possible fire. BS 7671 requires AFDDs t o b e provided for
single-phase AC circuits supplying socket-outlets with a rated current not exceeding
3 2 A in electrical installations for:
For other installations, BS 7 6 7 1 recommends their use for AC final circuits supplying
socket-outlets not exceeding 3 2 A, but it is for the designer to decide on their use in
other installations, a n d the inspector cannot comment if they are not installed.
Some makes of AFDDs have a manual test button (like an RCD) a n d this should b e
pressed at commissioning and user advised to press at six monthly intervals to prove
operation. Other AFDDs have an automatic test facility which will trip t h e device in t h e
event of a malfunction, this will b e indicated on the device.
Sect 443 The guidance for the application of surge protective devices (SPDs) has been
revised in BS 7671:2018+A2:2022, providing for protection against switching surges
and surges of atmospheric origin (lightning strikes). Except for simple installations
for which t h e requirements of Sections 443 and 5 3 4 of BS 7 6 7 1 can b e followed,
surge protection, and where applicable lightning protection systems, will usually b e
designed and installed, by specialist suppliers i n accordance with the relevant parts of
BS EN 6 2 3 0 5 . In these cases, the inspector can only review what is installed against
the scheme documentation provided by the specialist suppliers, and review their test
and commissioning documentation.
Instruction notices (iii), (iv), (v) and (viii) above need not b e applied for installations
in domestic (household) premises where t h e information is recorded as part of t h e
certification for initial verification, complete with the Guidance for Recipients as detailed
in Appendix 6 of BS7671.
Appendix 11The minimum size requirements for text o n warning signs and instruction notices have
been revised in Amendment 2 : 2 0 2 2 t o BS 7671:2018, and reference is n o w made to
BS EN IEC/IEEE 82079-1 Preparation o f information for use (instructions for use) o f
products. Principles and general requirements. Warning notices and other safety signs
are additionally required to comply with BS ISO 3 8 6 4 series Graphical symbols. Safety
colours and safety signs and BS EN ISO 7010 Graphical symbols. Safety colours and
safety signs. Registered safety signs. These standards permit far more flexibility in text
sizes than t h e requirements of previous versions of BS7671. Guidance and examples
are provided in Appendix 11.
The warning and instruction notices in Section 514 of B S 7 6 7 1 are discussed below.
514.10.1(j) Voltage
► Warning notices are required where a nominal voltage exceeding 2 3 0 V to earth
exists within an item of equipment or enclosure and where the presence of such
a voltage would n o t normally b e expected. An example would b e the use of a
6 9 0 V three-phase AC power transformer used on an American air base located
in the UK. Examples are shown in Figure 2.4.
Note: In m o s t three-phase 2 3 0 / 4 0 0 V systems, t h e voltage t o Earth is 2 3 0 V. It is n o t
normally necessary in those installations to provide a voltage warning label for
t h e purposes of Regulation 514.10.1.
/X WARNING
/ 7 \ 400/690 V
A WARNING
/7\ 400/690 V
514.11.1(jj) Isolation
► Warning notices are required where live parts are not capable of being isolated
by a single device. The location of disconnectors should also b e indicated, except
where there is n o possibility of confusion.
IMPORTANT
_ . .. „ T S June 2022
Date of last inspection ................................
(iv) RCDs
514.12.2 ► T h e w o r d i n g of t h e required instruction n o t i c e is given i n Regulation 514.12.2.
Examples are shown i n Figure 2.6.
(v) AFDDs
► Where AFDDs are installed, those provided with a manual test button (as RCDs)
should b e tested every six months by pressing t h e button. An instruction notice t o
this effect should be provided. The text of the RCD notice in Regulation 514.12.2
can b e used (see examples in Figure 2.6). Some AFDDs are self-testing. AFDDs
may b e provided in a single package also containing overcurrent and/or residual
current protective devices.
The information may b e clearly marked o n SPDs installed at the distribution board
o r consumer unit. Some SPDs are supplied with a suitable label.
A WARNING
/ 7 \ High protective
y
< ■ conductor currents
The following circuits may have high
protective conductor currents:
Diagrams, charts, warning and information and instruction notices should comply
with the standards specified in Regulation 514.9.2.
Non-standard colours
Over time, there have been changes in the colours for identification of conductors
in BS 7671, and, before 1992, previous editions of the Wiring Regulations. In
BS 7671:2001(2004), awarning notice was introduced for installations using conductor
identification colours to different versions of BS7671. Regulation 514.14.1 was deleted
in BS 7671 :2018+A2:2022 and such a w a r n i n g notice will, in future, n o t b e necessary
t o comply with BS 7671 .
There is nothing to prevent the continued use of this type of warning notice.
q Erection methods
Chapter 5 2 contains detailed requirements on selection and erection. Fixings of
switchgear, cables, conduit, fittings, etc. must b e adequate for the environment and a
detailed visual inspection is required during the erection stages, as well as at completion.
Regulation 521.10.202 requires that cables are to b e supported so they will n o t collapse
and come away f r o m their fixings in the event of a fire and impede the escape of
persons f r o m buildings. This can usually b e achieved by installing a metal cable fixing
at reasonable intervals.
General
(a) Equipment complies with a product standard or equivalent (511.1).
(b) Equipment is installed using good workmanship (134.1.1).
(c) Equipment is accessible for operation, inspection and maintenance (513.1).
(d) Equipment is suitable for local atmosphere and ambient temperature (512.2).
For installations i n potentially explosive atmospheres, the requirements of
BS7671 are supplemented by the requirements or recommendations of other British
or Harmonized Standards or by those of the person ordering the work (110.1.3).
(e) Final circuits are separate, including t h e neutral conductors (314.4).
(f) Protective devices are identified to indicate the circuits they protect (514.8.1).
(g) Protective devices are adequate for their intended purpose, including AFDDs
and SPDs, where installed (Ch. 53).
(h) Disconnection times for protection against electric shock are likely to b e met by
installed protective devices (Ch. 41).
(i) All circuits are identified (514.1,514.8,514.9).
0) Main switch is provided (462.1.201).
(k) Supplies to any safety services are correctly installed, for example, fire alarms
to BS 5 8 3 9 and emergency lighting to BS 5 2 6 6 (Ch. 56). This does not
include any inspection of the safety systems, which should b e inspected and
maintained by specialists.
(l) Auxiliary circuits are installed (557).
(m) Means of isolation are labelled (514.1, 537.2.7).
(n) There is provision for disconnecting the neutral (Ch. 4 6 ; 537.2.8).
(o) Main switches t o single-phase installations, intended for use by an ordinary
person, for example, domestic, shops and office premises, are to b e double
pole (462.1.201).
(p) RCDs are provided where required (411.3.3, 411.3.4, 411.4, 411.5, 415.1,
422.3.9, 522.6.201, 522.6.202, 532.1, 701.411.3.3, 702.53, 702.55.1, 702.55.4,
703.411.3.3, 704.410.3.10, 704.411.3.2.1, 705.411.1, 705.422.7, 706.410.3.3,
708.415, 708.553.1.14, 709.531.2, 710.410.3, 710.411.4,710.531.3, 711.410.3.4,
711.411, 712.531.3.5.1, 714.411.3.4, 717.411.6.2, 717.413, 717.415.1, 721.415.1,
722.531.3, 740.410.3, 740.415.1, 753.411.3.2, 753.415.1).
(q) Selectivity between RCDs is considered to avoid danger (314.1,314.2, 531.3).
(r) Main earthing terminal (MET) is provided (542.4.1), is readily accessible and is
identified where separate from switchgear (514.13.1).
(s) There is provision for disconnecting t h e earthing conductor (542.4.2).
(t) Cables used comply with British or Harmonized Standards and with the
Construction Products Regulation (Appendix 4 of BS 7671).
(u) Earth tail pots are installed where required o n mineral-insulated cables (543.2.7).
(v) Non-conductive finishes o n enclosures are removed where necessary to ensure
good electrical connection and, if necessary, made good after connecting (526.1).
(w) There are adequately rated distribution boards. Distribution boards to t h e
relevant parts of BS EN 6 0 4 3 9 or BS EN 61439 may have a rated diversity
factor (RDF) stated by t h e manufacturer for the assembly, or a group of circuits.
For example, if an assembly has an RDF of 0.8, any combination of outgoing
circuits in the assembly can b e loaded to 8 0 7o of their rated current, provided
the total load o n the outgoing circuits does not exceed the rated current of the
assembly (642.2).
(x) Correct fuses or circuit-breakers are installed (Section 531, Section 533).
(y) All connections are secure (134.1).
(z) Protection is provided against voltage disturbances, including overvoltages,
where required (Ch. 44).
Switchgear
(a) Meets requirements of the relevant parts of BS EN 61008, BS EN 61009,
BS EN 60947-2, BS EN 60898, or BS EN 61439, where applicable, or equivalent
(Section 511).
(b) Is securely fixed (134.1.1) and suitably labelled (514.1).
(c) Switchgear assemblies, including consumer units, are complete with, or
additionally housed in, fire protecting enclosures (421.1.201).
(d) Non-conductive finishes o n switchgear are removed at protective conductor
connections and, if necessary, made good after connecting (526.1).
(e) Suitable cable glands and gland plates are used (526.1).
(f) Switchgear is correctly earthed (Ch. 54).
(g) Account has been taken of environmental conditions likely t o b e encountered,
i.e., switchgear is suitable for t h e foreseen environment (512.2).
(h) Switchgear is suitable as a means of isolation as design, where applicable
(Ch. 46, 537.2).
(i) Need for isolation, mechanical maintenance, emergency and functional
switching is m e t where required by design (Ch. 4 6 , 537).
(j) Firefighters’ switch is provided where required and labelled for identification and
operation (537.4).
(k) All connections are secure (526).
(l) Cables are correctly terminated a n d identified (514, 526).
(m) There are n o sharp edges o n cable entries, screw heads, etc., which could
cause damage to cables (134.1.1,522.8.11).
(n) There is adequate access, lighting a n d working space (132.12 and 513.1).
Notes:
1 Reference should a l s o be m a d e to B S 8 3 0 0 series a n d t h e recommendations contained
in t h e r e l e v a n t A p p r o v e d D o c u m e n t M of t h e B u i l d i n g R e g u l a t i o n s 2010 for England a n d
W a l e s a n d the Scottish Building Standards with regard to t h e h e i g h t s a t w h i c h socket-outlets,
switches a n d other controls s h o u l d b e installed, in o r d e r to afford c o m p l i a n c e with B u i l d i n g
R e g u l a t i o n s . See a l s o the I E T publication Electrician's Guide to the Building Regulations.
2 Guidance o n t h e s e l e c t i o n of protective, i s o l a t i o n a n d switching devices in p r o v i d e d in
T a b l e 537.4 o f B S 7 6 7 1 .
Lighting controls
(a) Lightswitches comply with BS 3 6 7 6 or BS EN 60669-1 (511.1).
(b) Lighting controls are selected for external influences (512.2).
(c) Single-pole switches are connected in line conductors only (132.14.1).
(d) Correct colour coding or marking of conductors is used (514.3).
(e) Exposed-conductive-parts, for example, metal switch plate or surface-mounted
metal back box, are connected to t h e relevant cpc (Ch. 54).
(f) The current rating, allowing for any capacitive or inductive effects as given in the
design cable ratings, is adequate (512.1.2).
(g) A device that simultaneously disconnects all line conductors is provided where
a group of luminaires is divided between three line conductors of a circuit with
only one c o m m o n neutral (559.5.5).
(h) Switch is labelled to indicate purpose, where this is not obvious (514.1.1).
(i) There are appropriate controls suitable for the luminaires (559.5.1.206).
( j ) Standard wall accessory/switches are installed beyond zone 2 in a location
containing a bath or shower (701.512.3).
Lighting points
(a) Lights connected via a recognized accessory (559.5.1), batten lampholders or
pendant sets are in compliance with BS EN 6 0 5 9 8 .
(b) Ceiling rose complies with BS 67 (559.5.1).
(c) Luminaire supporting couplers comply with BS 6972 or BS 7001 (559.5.1).
(d) Installation couplers comply with BS EN 61535 (559.5.1).
(e) A recognized connecting device is used for luminaires that d o n o t provide a
device for connection of t h e supply (559.5.4).
(f) Track systems comply with BS EN 60570 (559.3.4 and 715.521.1).
(g) Systems for ELV lighting comply w i t h BS EN 60598-2-23 (715.521.1).
(h) Bare conductors of ELV lighting installations comply with all requirements of
Regulation 715.521.106 (715.521.1).
(i) There is not m o r e than one flex, unless designed for multiple pendants
(559.5.1.202).
( j ) Flex support devices are used and are suitable for the mass suspended (559.5.2).
(k) Switch-lines are identified (514.3.2 and Appendix 7 of BS 7671). For two-core
switch wires, blue conductors are overmarked with b r o w n or L a t terminations;
for three-, four- or five-core cables, all non-brown line conductors of switch
and intermediate strappers are overmarked at terminations w i t h b r o w n or L.
(l) Penetrations in fire-rated ceiling are m a d e good. Suitable fire-rated luminaires
used where t h e luminaire traverses fire rated ceilings (527.2.1). Recessed
downlighters should b e checked for thermal damage.
Socket-outlets
(a) Socket-outlets comply with BS 5 4 6 , BS 1363-2 or BS EN 6 0 3 0 9 - 2 (553.1.3)
and are shuttered for household a n d similar installations (553.1.201).
(b) Where used for electric vehicle charging, socket-outlets complying with
BS 1363-2 are of a type approved by the socket-outlet manufacturer for such
use (722.55.101.0.201.1).
(c) Mounting height above t h e floor or working surface suitable (553.1.6) (Also
complies with Part M of the Building Regulations and the Scottish equivalent,
where relevant - see Note above).
(d) Polarity is correct (643.6).
(e) If in a location containing a bath or shower, socket-outlets are installed at least
3 m horizontally f r o m t h e bath or shower, w i t h t h e exception of a shaver supply
unit or SELV (701.512.3).
(f) Socket-outlets are suitably protected against external influences where installed
near sinks and cookers. It is recommended that socket-outlets should b e
installed at least 3 0 0 m m horizontally from t h e edges of a sink or washbasin
(excluding drainer) and at least 1 0 0 m m horizontally f r o m the edge of a h o b or
freestanding cooker (see IET Guidance Note 1: Selection and Erection).
(g) Socket-outlets are suitably protected against t h e expected external influences
where mounted in a floor (512.2).
(h) Socket-outlets are not used to supply a water heater having uninsulated
elements (543.3.1).
(i) Where metal conduit (including the accessory box) or earthed cable sheath
or similar is used as a protective conductor, there is presence of an earth tail
between t h e accessory box and the socket-outlet terminal (543.2.7).
(j) Additional requirement is provided by a 3 0 m A RCD or a risk assessment is
provided for specific non-domestic socket-outlets (411.3.3).
(k) Socket-outlets with integral universal serial bus (USB) charging provision, or
other electronic devices such as powerline or wireless local area networking
functionality, comply with BS 1363-2:2016 or BS 1363-2:2016+AI:2018.
Conduit systems
General
(a) Conduit systems are securely fixed, box lids in place and are adequately
protected against mechanical damage (522.8).
(b) Draw points are accessible (522.8.6).
(c) The recommended quantity of cables for easy draw is not exceeded during
installation, to avoid causing insulation damage. Adequate boxes are suitably
spaced. This item should b e inspected during the erection stage, as t h e care
and workmanship of the installer can b e verified (522.8.1 and see Appendix E
of t h e IET On-Site Guide’).
(d) Solid elbows and tees are used only as appropriate (522.8.1).
(e) Unused entries are blanked off where necessary (416.2 and 522).
(f) Conduit system components comply with a relevant British Standard, depending
o n performance requirements (511.1).
(g) Conduit systems are provided with drainage holes and gaskets as necessary
(522.3.2).
(h) The radius of bends is such that cables are n o t damaged (522.8.3).
(i) Conduit systems installed in protected escape routes are classed as non-flame
propagating according to BS EN 6 1 3 8 6 (422.2.1).
Rigid m e t a l c o n d u i t
(a) Rigid metal conduit complies with BS EN 61386-21 (521.6).
(b) Rigid metal conduit is connected to the MET (411.4.2, 411.5.1).
(c) Line, neutral and any additional protective conductors are contained in the
same conduit (521.5.1).
(d) Conduit is suitable for wet, damp or corrosive situations (522.3, 522.5).
(e) Conduit is fixed appropriately (522.8 and see Appendix G of Guidance Note 1).
(f) Unpainted ends and scratches, etc. are protected by painting (134.1.1, 522.5).
(g) Ends of conduit are reamed and bushed, where relevant (134.1.1, 522.8).
Rigid n o n - m e t a l l i c c o n d u i t
(a) Rigid non-metallic conduit complies with BS 4607, BS EN 60423 o r the
BS EN 61386 series (521.6).
(b) Ambient and working temperatures are within permitted limits (522.1, 522.2).
(c) Provision is m a d e t o allow for expansion and contraction (522.15.1).
(d) Boxes and fixings are suitable for the mass of luminaire suspended at the
expected temperature (559.5.2).
(e) Conduit is of the 'non-flame propagating' type (521.6).
Flexible m e t a l c o n d u i t
(a) Flexible metal conduit complies with the BS EN 61386 series (521.6).
(b) A separate protective conductor is provided (543.2.3).
(c) Fixed metal conduit is adequately supported and terminated (522.8).
(d) Line, neutral and any additional protective conductors are contained in the
same conduit (521.5.1).
Trunking
General
(a) Trunking complies with B S 4 6 7 8 or BS EN 50085-1 (521.6).
(b) Trunking is securely fixed and adequately protected against mechanical damage
(522.8).
(c) Trunking is selected, erected and routed to avoid ingress of water and solid
objects (522.3).
(d) Proximity to non-electrical services, i.e. sources of heat, smoke, etc. cannot
cause damage (528.3).
(e) Internal fire sealing is provided where necessary (requires inspection during the
erection stage) (527.2.2).
(f) Holes surrounding the trunking are m a d e good (527.2.1).
(g) Band I circuits are partitioned f r o m Band II circuits or insulated for the highest
voltage present (528.1).
(h) Circuits are partitioned f r o m Band I circuits or wired in mineral-insulated
metal-sheathed cables (528.1).
(i) Cables are supported for vertical runs (522.8.5).
( j ) Trunking systems used in protected escape routes are classed as non-flame
propagating according to BS EN 5 0 0 8 5 (422.2.1).
Metal trunking
(a) Line, neutral and any additional protective conductors are contained in the
same trunking (521.5.1).
(b) Metal trunking is protected against d a m p or corrosion (522.3, 522.5).
(c) Metal trunking is earthed (411.4.2,411.5.1).
(d) Joints are mechanically sound and of adequate continuity (543.2.5).
Insulated cables
Non-flexible cables
(a) Non-flexible cables are of the correct t y p e and comply with the relevant
Construction Products Regulation design requirements (521).
(b) The current rating is correct (523 a n d Appendix 4).
(c) Non-flexible cables are protected against mechanical damage and abrasion (522.8).
(d) Non-flexible cables are suitable for high or low ambient temperature, as
necessary (522.1).
(e) Non-sheathed cables are protected by enclosure in conduit, duct or trunking
2
(except for protective conductors of 4 mm and larger) (521.10 a n d 543.1).
(f) Sheathed cables concealed in a wall at a depth of less than 5 0 m m f r o m the
surface and n o t forming part of a SELVor PELV circuit:
(1) are routed in prescribed zones, with additional protection provided by an
RCD having a rated residual operating current, l£ n , not exceeding 3 0 m A ; or
(si) are provided with mechanical protection complying with (522.6.204).
(g) Cables concealed in a partition containing metallic structural parts:
(i) are provided with additional protection by an RCD having a lAn not
exceeding 3 0 m A ;
(ii) are provided with adequate mechanical protection to suit both the
installation of t h e cable and its normal use; or
(Hi) comply with the requirements set out in Regulation 522.6.203 (522.6.202).
(h) Cables exposed to direct sunlight are of a suitable t y p e or are suitably shielded
(522.11).
(i) Non-flexible cables are not run in lift or hoist shaft unless they are part of the
lift installation a n d of the permitted type (528.3.5).
( j ) Cables in protected escape routes should b e of t h e permitted types with regard
to fire and smoke performance (422.2.1).
(k) Cables buried in the ground are correctly selected and installed for use (522.8.10).
(l) Cables installed overhead are correctly selected and installed for such use (522.8.4).
(m) The internal radius of every bend in a wiring system should be such that it is not so
tight that the cable and/or its conductors suffer damage and such that terminations
are not in any way stressed (522.8.3 and Appendix G of Guidance Note 1).
(n) Non-flexible cables are correctly supported and secured where necessary to
prevent premature collapse in t h e event of a fire (521.10.202, 522.8.4, 522.8.5).
(o) Non-flexible cables are n o t exposed to water, etc. unless they are suitable for
such exposure (522.3).
(p) Metal sheaths and armour are earthed (411.3.1.1).
(q) Conductors are identified at terminations (514.3).
(r) Joints and connections are electrically and mechanically sound and adequately
insulated (526.1, 526.2).
(s) All wires are securely contained in terminals, etc. without strain (522.8.5, 526).
(t) Terminals are enclosed (526).
(u) Glands are correctly selected and fitted with shrouds and supplementary earth
tags as necessary (526.1).
(v) Joints and connections are mechanically sound and accessible for inspection,
testing and maintenance purposes, except as permitted otherwise (526.1, 526.3).
Flexible cables
(a) Flexible cables are of the correct type and comply with the relevant design
requirements of t h e Construction Products Regulation (521.9.1).
(b) Current rating is correct (523 and Appendix 4).
(c) Cables are protected where exposed t o mechanical damage (522.6, 522.8).
(d) Cables are suitably sheathed where exposed to contact with water (522.3) or
corrosive substances (522.5).
(e) Cables are protected where used for final connections to fixed apparatus, etc. (526.8).
(f) Cables are selected for resistance to damage by external heat sources (522.2).
(g) There is segregation of Band I and Band II circuits (528; see also BS 6701 and
B S E N 50174 series).
(h) There is segregation of fire alarm and emergency lighting circuits (528; see also
BS 5839, BS 5266).
(i) Cores are correctly identified (514.3).
(j) Connections have durable electrical continuity, adequate mechanical strength
and are made using appropriate means (526.1, 526.2).
(k) Where used as fixed wiring, the relevant requirements are m e t and cables are
secured where necessary to prevent premature collapse in the event of a fire
(521.9.1, 521.10.202).
(l) Final connections to current-using equipment are properly secured and arranged
to prevent strain o n connections (526.6).
(m) Mass is supported by cable so as not to impair safety of the installation (559.5.2).
Protective c o n d u c t o r s
(a) Cables incorporating protective conductors comply with the relevant British or
Harmonized Standard (511.1).
(b) Joints in metal conduit, ducting or trunking comply with Regulations for
preservation of continuity (543.3).
(c) Flexible or pliable conductive conduit is supplemented by a protective conductor
except where only SELV systems are enclosed by the conduit (543.2.3).
(d) Protective conductors have a suitable m i n i m u m csa (543.1).
(e) Protective conductors with a csa of 6 mm 2 o r less are protected by insulation or
equivalent, unless they are part of a multicore cable, o r f o r m part of a conductive
containment system or enclosure used as a protective conductor (543.3.201).
(f) A cpc at the termination of sheathed cables is protected by sleeving (543.3.201).
(g) A bare cpc is protected against mechanical damage a n d corrosion (543.3.1).
(h) Insulation, sleeving and terminations are identified by t h e bi-colour combination
green-and-yellow (514.4.2).
(i) Joints are electrically and mechanically sound (526.1).
( j ) Separate cpcs of not less than 4 m m 2 if not protected against mechanical
damage and is not an integral part of a cable, n o t formed by conduit, ducting or
trunking, nor contained in an enclosure formed by a wiring system (543.1.1).
(k) Main and supplementary protective bonding conductors are of the correct size (544).
(l) Cables are secured where necessary to prevent premature collapse in the event
of a fire (521.10.202)
Enclosures
General
(a) There is a suitable degree of protection (IP Code in BS EN 6 0 5 2 9 ) appropriate
to external influences w h e n installed, taking account of the manufacturer's
instructions (416.2, 512.2, 522, Part 7).
644.3 (a) the EIC is accompanied by a Schedule of Inspections, Circuit Details and Test
Results. These schedules shall b e based o n the models given in Appendix 6 of
BS 7671;
644.3 (b) the Schedule of Test Results shall include test results for the work done;
644.,: (c) the EIC is signed or otherwise authenticated by a skilled person responsible for
each facet of design, construction and inspection and test and competent to
verify that the requirements of B S 7 6 7 1 have been met; and
644.1. (d) any defects or omissions revealed by the inspector are required to b e made
good by the installer, and, as necessary, inspected and tested again, before the
EIC is issued; it is not the responsibility of the person or organization carrying
out t h e inspection and testing to make good defects or omissions.
Where the installation work does not extend to the installation of a n e w circuit, a
MEIWC may b e used instead of the full EIC. This simplifies the documentation for small
works; in addition, the required installation inspection and testing and tests are limited
to the circuit being extended or modified, as detailed in Part 4 of the certificate. See
Section 5 for further details and guidance o n the completion of this certificate.
NOTE: The model the model forms in Appendix6 of BS7671 can be amended to suit the
installation, provided that the minimum information required is included.
643.2
643.2
Continuity of protective conductors, including main
earthing conductor, and main and supplementary
protective bonding conductors
2.6.6
0®
Regulation 643.1 requires
the tests in Regulations
643.2 to 643.6 inclusive
tests to be conducted
643.3 Insulation resistance 2.6.7 (where relevant for the
particular installation) in
the order shown, prior to
2.6.8 the installation being
643.4 Protection by SELV, PELV or electrical separation
2.8.9 energized.
It is strongly recommended
Insulation resistance of non-conducting floors and to address any
643.5 2.6.11
walls (rarely required) unsatisfactory conditions
discovered during a test,
before proceeding with any
643.6 Polarity 2.6.12 subsequent tests.
2.6.18
643.10 Functional testing
2.6.19
Regulation 643.2.1 requires that a continuity check b e carried out o n all protective
conductors. This includes the earthing conductor, the protective conductors of all
circuits, all main protective bonding conductors and, where applicable, all supplementary
bonding conductors.
Regulation 643.2.1 also requires that a continuity check b e carried out o n each
conductor of every ring final circuit, including the line, neutral and protective conductors.
There are two widely used test methods that have evolved for checking protective
conductor continuity. Test method 1 uses the circuit cable shorted o u t and test
method 2 uses a supplementary length of test cable (this method being popularly
known as t h e 'wandering lead' method).
Instrument: use a low-resistance ohmmeter for these tests (see Section 4.3).
The relevant conductors, mentioned above, should b e tested to verify that they are
electrically sound and correctly connected.
Test method 1, detailed in this item, as well as checking the continuity of the protective
conductor, measures (R 1 + R2) which, when added to the external impedance (Z e),
enables the EFLI(Z S) to b e checked against the design (see Sections 2.6.14 and 2.6.15).
(R 1 + R2) is the sum of the resistances of the line conductor, Ri, and the cpc, R2 .
The effect of parallel earth return paths is that the measured value of protective
conductor continuity, R2) tends towards zero. It is often impractical and, in some cases,
impossible to carry out testing with some or all of the parallel paths disconnected and
the inspector must b e aware of this.
Where the installation has all-insulated wiring (see notes o n parallel earth paths and
effects o n test results above) and the cable accessories are not in contact with earth,
then this test measures(Ri + R2), i.e. the resistance of the line conductor, R i plus the
resistance of t h e protective conductor, R2 , for that circuit which, if added to the EFLI
at the distribution board, can b e taken as t h e circuit's EFLI.lt is important to record
t h e value of (R 1 + R2) obtained at the circuit's extremity, namely the furthest circuit
distance f r o m t h e distribution board.
▼ Figure 2.13 Connections for testing continuity of protective conductors: test method 1
OoUT*
Temporary
link
■; ©
ir
*®1
; voiw
Phw
(a) contactors;
(b) motion and day/night controls;
(c) energy control timers;
(d) lighting dimmers;
(e) remote or smart technology switches; and
(f) building management system controllers.
Figure 2.14 shows a n alternative approach to test method 1 , that can b e used to test
protective conductors downstream of a control device which is open-circuit when low
voltage AC power is removed. This test approach simply measures (R n + R2) instead
o f ( R 1 + R2).
▼ Figure 2.14 Alternative approach for testing continuity of protective conductors: test
method 1, for circuit conductors downstream of electronic control devices
Electronic
control device,
for example a
dimmer
Temporary link
•© ■© >©
AUTO|
VO»W
PhiM
2
As a n e x a m p l e , a radial c i r c u i t of length a b o u t 5 5 m w i t h 2.5 mm line a n d 1.5 m m 2
p r o t e c t i v e c o n d u c t o r s s h o u l d h a v e a n ( R 1 + R2) r e s i s t a n c e as f o l l o w s :
Length o f circuit is 5 5 m
2
Resistance p e r metre of the line a n d protective conductors i n a 2.5 mm /1.5 mm2
c a b l e is 19.51 mQ/m (at 20 °C) f r o m Table B l
W h e n v e r i f y i n g a circuit, t h e i n s p e c t o r s h o u l d t a k e i n t o a c c o u n t t h a t a h i g h e r v a l u e
m i g h t b e m e a s u r e d , as t h e r e will b e s o m e resistance at t h e terminations, a n d t h e r e
m a y b e a c o n t a c t r e s i s t a n c e f o r c o n n e c t i o n of p r o b e s a n d clips, t h a t c a n i n c r e a s e with
c o r r o s i o n on o l d e r terminals. Switches, fuses, a n d other t y p e s of protective device,
might a l s o contribute to a higher reading.
O n e l e a d of t h e t e s t i n s t r u m e n t is c o n n e c t e d t o t h e e a r t h t e r m i n a l a t t h e d i s t r i b u t i o n
b o a r d v i a a length of test c a b l e or ' w a n d e r i n g lead'. The other test lead is used to
make contact with the protective conductor at various p o i n t s o n the circuit under test,
f o r example, a t luminaires, switches, f u s e d connection units, etc. a s shown in Figure
2.15. T h e resistance of the wandering l e a d a n d t h e test l e a d s a r e either measured a n d
d e d u c t e d f r o m t h e r e a d i n g s obtained, or a u t o - n u l l e d by the test instrument, which
m o s t m o d e r n i n s t r u m e n t s a r e a b l e t o do.
This test m e a s u r e s the resistance of the cpc, R 2 , w h i c h should b e recorded o n the Schedule
of Test Results (see notes on parallel earth paths and effects o n test readings above).
wander-lead
2
As a n e x a m p l e , a radial circuit of length a b o u t 5 5 m with a 2 . 5 mm copper protective
c o n d u c t o r s h o u l d h a v e a n R2 r e s i s t a n c e a s f o l l o w s :
Length of c i r c u i t i s 5 5 m
2
Resistance of a 2.5 mm conductor is 7.41 m Q / m (at 20 °C) f r o m Table B l
This method can also be used to confirm a bonding connection between extraneous-
conductive-parts where it is not possible to see a bonding connection, for example,
where bonding d a m p s have been ’built in'. The test would b e d o n e by connecting
the leads of the test instrument between any t w o points, such as metallic pipes, and
looking for a suitably l o w reading taking into account the length of the protective
bonding conductor(s). Keep in mind, however, that 15 m of single-core 6.0 m m 2 or
2
2 5 m of single-core 10.0 m m conductor has a resistance of approximately 0.05 Q .
With such low resistances being measured, t h e resolution of the test instrument may
not permit an accurate reading to b e obtained (see Section 4.3) and therefore where
t h e expected resistance is less than 0.1 Q including contact resistances, a value n o t
exceeding 0.1 Q should b e used as a guideline acceptable reading. It should b e noted
that this is not the R2 resistance measured f r o m the MET to the bonding clamp or
adjacent pipework.
(a) inspect t h e enclosure along its length for soundness of construction; and
(b) perform the standard continuity test using the appropriate test m e t h o d
described above.
Instrument’, use a low-resistance ohmmeter for this test (see Section 4.3).
©■©©©©©© ©©©©©
wander-lead
Instrument', use a low-resistance ohmmeter for this test (see Section 4.3).
Step 1
The line, neutral and protective conductors are visually identified at the distribution
board or consumer unit and t h e end-to-end resistance of each is measured separately
(see Figure 2.17).
▼ Figure 2.17 Connections for ring final circuit continuity testing: step 1
|e
i
csa
__ csa cpc _ line
csacpc x r 2
r x
2- — ~
csa
line
r x r = 1
2=T3 2 -6 7 x r 2
If the resistance readings are not as expected, this could mean the following:
(a) readings lower than the expected resistance would suggest that the ring is
incorrectly configured, possibly wired in a 'figure of eight’ connection; this may
be further confirmed by the step 2 test below; or
(b) readings higher t h a n the expected resistance would suggest an issue with
the integrity of one or more conductor terminations.
The 'expected resistance' is that found from the tabulated DC resistance for the
conductor csa per metre, multiplied by the installed length and corrected for ambient
temperature. A small allowance should be made for instrument errors. Table B i gives
values of DC resistance for conductors.
Step 2
The open ends of the line and neutral conductors are then connected together so that
the outgoing line conductor is connected to the returning neutral conductor, and vice
versa (see Figure 2.18).
▼ Figure 2.18 Connections for ring final circuit continuity testing: step 2
neutral
fl
I
connector blocks
The resistance between line and neutral conductors is measured at each socket-outlet.
The readings at each of the socket-outlets connected to the ring should be substantially
the same and the value will be approximately one-quarter of the resistance of the line
plus the neutral loop resistances, i.e. (ri + rn)/4 (see mathematical explanation in
Figure 2.19). Any socket-outlets wired as spurs will indicate a higher resistance value,
due to the resistance of the spur conductors.
Note: Where single-core cables are used, care should be taken to verify that the line and
neutral conductors of opposite ends of the ring circuit are connected together. An
error in this respect will b e apparent from the readings taken at the socket-outlets,
progressively increasing in value as readings are taken towards the midpoint of the
ring, then decreasing again towards the other end of the ring. Where such behaviour
in readings is between particular points part way round the ring, this may indicate an
interconnection within the ring.
Figures 2.19a to e explain t h e expected results for a correctly wired ring circuit.
a Origin
Testpoint Afor
mathmatical explanation
Figure a above is an example of a correctly wired ring, with the open loop resistances
of t h e line and neutral conductors f r o m step 1 , each being 0.6 O . A test point about a
third distance round t h e ring is used to illustrate t h e maths, as explained below.
b Origin
0.2 0
t
Test point A
0.4Q
Figures b and c show the resistances of each leg of the ring as a test is applied at this
point as per step 2 (line-neutral).
c Test
Ni 0.2(1 E° i n t A
T? 0 2(1 /
N z 0.4(1
L 2 0.4(1
□.3Qq
0.2 fl F
Test cross-connections
point A at consumer unit
n2
0.4 fl F
The equivalent circuit diagram and resultant resistance are shown in Figure e .
In summary, the open loop resistances are 0.6 0 for both line and neutral, giving an
C i + rn) value of (0.6 + 0.6), or 1 . 2 0 .
From Figure e above, it can b e seen that a correctly connected ring will give a step 2
reading of a quarter of the (rj + rn) value, or:
£ £
Rste P 2 tes t = 4 . i n t h i s case = 0 . 3 fl
Step 3
The open ends of the line conductor and cpc are then cross-connected (see Figure 2.20).
▼ Figure 2.20 Connections for ring final circuit continuity testing: step 3
connector blocks
The resistance between line and cpc is measured at each socket-outlet. The readings
obtained at each of the socket-outlets wired in the form of a ring will depend o n
whether the cpc is the same csa and material as t h e line conductors:
(a) Where the cpc is the same copper-equivalent csa as the line conductors, the
readings will b e substantially the same and t h e value will b e approximately
one-quarter of the resistance of the line plus cpc loop resistances, i.e.
(r] + rn)/4 (the explanation for this being similar to that for step 2).
(b) Where the cpc has a different csa f r o m the line conductors, for example where
flat twin-and-earth cable is used, the resistance will increase as t h e tests move
around t h e ring f r o m t h e origin of t h e circuit, to a maximum of approximately
C i + r 2 )/4 at the mid-point of the ring, and decrease as the test point moves
back towards the origin of the circuit. The maximum a n d minimum values
expected during the test are shown in Table 2.8 (see IET Electrical Installation
Design Guide for a comprehensive mathematical explanation).
The highest value recorded represents the maximum (R] + R£) of the circuit and is
recorded o n the Schedule of Test Results. The value can b e used to determine the
EFLI (Z s) of the circuit to verify t h e provisions for automatic disconnection of supply
(see Section 2.6.14).
411.3.2.5 The inspector is again reminded to take note of t h e effects of possible parallel return
4193 paths o n these continuity tests, as described in Section 2.6.5 o f this Guidance Note.
In addition, where supplementary protective equipotential bonding is used in
accordance with Regulations 411.3.2.4 and 419.3, this may also affect the readings for
step 3. Examples of circuits which may b e affected in this way include distribution circuits
and final circuits supplying central heating systems, electric showers, or water heaters.
▼ T a b l e 2.8 Variation in reading during tests around t h e ring in Step 3 where line and cpc
have different csa
a General case
Other (£1Z£2 I 2
combinations ri+r z Ri+rJ
x 100 % of highest reading
Notes:
1 UK cable type 6242Y to BS 6 0 0 4 or type 6242B to BS 721 1 :2012+AI:2020.
2 Flat twin and earth cables manufactured between approximately 1969 and 1981.
3 The lowest reading should occur at the origin of the circuit.
4 Ignoring measurement error.
5 The highest reading should occur at the midpoint of the ring, although there may not b e
a socket-outlet or other accessory installed at that point, at which a measurement can
b e made.
6 Ignoring spurs from the ring.
7 See IET Electrical Installation Design Cuide for an explanation of the data provided in
this table.
8 Exceeds maximum length of circuit due to excessive voltage drop.
643.3 BS 7 6 7 1 requires that insulation resistance is measured between all of the live
conductors and between the live conductors and the protective conductor, with the
protective conductor connected t o t h e earthing arrangement. During t h e test between
live conductors and the protective conductor, the live conductors may b e connected
together. Taking cables as an example, historically, it was acceptable to test a cable
between the various cores, and test to earth (which was actually only the cpc, such as
a single-core conductor, o r the armouring or sheath of the cable); sometimes, these
cables were terminated without further testing. This is n o longer acceptable: it is n o w
essential to test to t h e protective conductor (such as armouring) with this connected
- via a fly-lead if necessary - to the installation earthing arrangement. This is shown
in Figure 2.23. It is a good idea to test all cables, including those tested during the
construction stage, using this method.
The purpose of the insulation resistance test is t o verify that the insulation of conductors
is not damaged and that live conductors or protective conductors are not short-circuited.
Notes:
1 Great care should b e taken w h e n removing neutral conductors or neutral links
o n installations: the m o m e n t the neutral is removed, it may become live, if
there is a 'borrowed neutral' o n t h e installation. Insulated tools should b e used
for this task.
2 (b) and (c) are necessary because, as testing occurs between all conductors,
anything connected and in circuit will b e subjected to t h e test voltage.
Table 64 Insulation resistance tests should be carried out using the appropriate DC test voltage
specified in Table 6 4 of BS 7671. The installation will b e d e e m e d to conform with
t h e Regulations in this respect if the main switchboard and each distribution circuit
tested separately, with all its final circuits connected b u t with current-using equipment
disconnected, has an insulation resistance not less than that specified in Table 64,
reproduced here as Table 2.9.
The tests should b e carried out with the main switch off, all fuses in place, switches
and circuit-breakers closed (i.e., in their O N positions), lamps removed, and fluorescent
and other discharge luminaires and other equipment disconnected. Where the removal
of lamps and/or the disconnection of current-using equipment is impracticable, the
local switches controlling such lamps and/or equipment should b e open. An insulation
resistance test of line and neutral (L&N) connected together to Earth (E) will ensure
that all t h e circuit conductors are tested. Where there are special lighting controls,
such as contactor switching, all the circuit wiring, including such switch-lines, must b e
included in the testing.
□
Test w i t h 2-way switches in
all combinations.
Figure 2.21 shows an example of testing a whole consumer unit (i.e., an installation)
in one test (only the L-N test is shown). The tests required are a test between the
live conductors (L-N) and tests between t h e live conductors and earth (L-Eand N-E).
For circuits containing two-way switches or two-way and intermediate switches, the
switches must b e operated one at a time and the circuits subjected to additional
insulation resistance test in these configurations.
For circuits and/or equipment that is vulnerable t o the test voltage, the line and neutral
conductors can b e linked/connected together and a test made between t h e linked
conductors and protective Earth (as in L&N-E). It is essential that the incoming earth
connection is connected to the MET of the installation (and that this is connected to
t h e means of earthing) for these tests.
For circuits and/or equipment vulnerable to the test voltage, the line and neutral
conductors can b e linked/connected together and a test made between t h e linked
conductors and protective Earth (as in L&N - E). It is essential that t h e incoming earth
connection is connected to the MET of the installation (and that this is connected to
the means of earthing) for these tests.
?© =© -©
Notes:
1 T h e test should b e initially carried o u t o n t h e complete installation, b u t could b e carried
out on completion of wiring at 500 V DC, before the installation of accessories, then retested
at 2 5 0 V DC on completion to verify cables have not been damaged during the work.
2 Bonding a n d earthing connections are i n place.
Circuits with equipment that might influence the result of, or be damaged
during, an insulation resistance test
643.3.3 Some electronic equipment may be susceptible to damage by insulation resistance
tests, for example where electronic components that are not intended to withstand
voltages of 5 0 0 V DC.
Other equipment may influence the measurement being made. For example,
equipment may have:
Regulation 643.3.3 of BS7671 requires that circuits with this type of equipment have
an insulation resistance test in two stages:
(i) When the circuit cables are first installed, an insulation resistance test is
carried out between line conductors, and between line conductors a n d the
protective conductor, with t h e protective conductor connected to the
earthing arrangement. Individual sections of a circuit may b e joined via
temporary connectors in place of vulnerable equipment, to test multiple
cable segments together in this way.
(ii) Following connection of equipment that might b e damaged by, o r influence,
the test, a test at 2 5 0 V D C is to b e applied between live conductors and
t h e protective conductor connected to t h e earthina arrangement. The
insulation resistance shall have a value of at least 1 M Q .
Test 1 L I to L2
Test 3 L2 to L3
Test 4 L I + L 2 + L3 (connected
together) to N
Notes:
1 It is essential for test 5 that t h e protective conductor of t h e cable is connected to t h e
installation's earthing arrangement.
2 Tests 4 a n d 5 can b e done individually, for test 4, each of LI, L 2 and L3 first to N a n d
for test 4, each o f L I , L2, L3 a n d N to E.
For experienced inspectors and testers, Table 2.11 shows h o w it is possible to reduce
t h e number of steps for insulation resistance to four. However, should any test yield
a reading lower than that referred to in Table 2.9, it will b e necessary to follow the
sequence stated in Table 2.10 to identify which conductors are affected.
Test 1 L I to L2 L I to L2
▼ Figure 2.23 Insulation testing of a 4-core p o w e r cable prior to termination (showing the
neutral to earth test)
SWA cable
Connection for
test purposes
AUTO M
Voitef
Phase
Connected
to MET
The insulation resistance readings obtained should b e not less than the minimum
values referred to in Table 2.8.
.* > * ♦ « * *> * * ♦ * *
lili
'O
There are situations where the provision of insulation of SELVor PELV circuits for basic
protection is generally not required by BS7671, i.e. forthe following voltages:
Par However, for locations containing a bath or shower, or i n swimming pools, saunas and
some other special locations, basic protection by insulation is required for SELVand
PELV at all voltages.
It is often, therefore, easier to carry out insulation resistance tests o n these circuits as
a matter of course.
Instrument: use an insulation resistance tester for these tests (see Section 4.4).
Live to Earth Between all SELV live parts a n d Earth 250 0.5
Instrument: use an insulation resistance tester for these tests (see Section 4.4).
Regulation 643.3.2 requires that FELV circuits shall meet t h e test requirements for
LV circuits (such as 'mains voltage' circuits). This includes t h e testing of:
41L7.2 (a ) the
exposed-conductive-parts of t h e FELV system are connected to the
protective conductor of the primary circuit of the source, provided that the
primary circuit is subject to protection by ADS in accordance with Regulations
411.3 to 6;
b the
411.7 ( ) source of t h e FELV system is one that meets t h e requirements of
Regulation 411.7.4; and
(c) plugs, socket-outlets, luminaire supporting couplers (LSCs), devices for
connecting luminaires (DCLs) and cable couplers in a FELV system are required
to have a protective conductor contact (connected to the protective conductor)
and not b e dimensionally compatible with those used for any other systems in
use at the same premises.
134.5 A D S f o r protection against electric shock is not r e q u i r e d i n a FELV system, but may b e
r e q u i r e d f o r o t h e r r e a s o n s , s u c h a s p r o t e c t i o n against t h e r m a l e f f e c t s .
(i) two e x p o s e d - c o n d u c t i v e - p a r t s ; o r
(ii) a n exposed-conductive-part a n d a n y extraneous-conductive-part
if t h e s e p a r t s are liable to b e at different potentials t h r o u g h failure of t h e basic
insulation of a live p a r t ;
(b) i n a non-conducting location, t h e r e m u s t b e n o protective conductors; a n d
(c) a n y socket-outlets i n s t a l l e d in the l o c a t i o n m u s t not incorporate a n earthing
contact.
Testmethod
The insulation resistance test may b e m a d e u s i n g a n i n s u l a t i o n resistance tester (see
S e c t i o n 4.4). T h e t e s t is m a d e b e t w e e n t e s t e l e c t r o d e 1 o r t e s t e l e c t r o d e 2 ( s e e
Figures 2 . 2 5 a n d 2.26) a n d the m a i n protective conductor of t h e installation.
Test electrode 1
The test electrode shown in Figure 2.25 comprises a metallic tripod, of which the
parts resting o n the floor f o r m the points of a n equilateral triangle. Each supporting
part is provided with a flexible base, ensuring, w h e n loaded, close contact with the
surface being tested over an area of approximately 9 0 0 m m 2 and having a combined
resistance of less than 5,000 Q between the terminal and the conductive rubber pads.
Before measurements are made, the surface being tested is cleaned with a cleaning
liquid. While measurements of t h e floors and walls are being made, a force of
approximately 7 5 0 N (75 kg in weight) for floors or 2 5 0 N for walls is applied t o the
tripod.
039
021
10
180 15
5 mm — ♦ 23
aluminium plate
Dimensions in millimetres
terminal
contact stud in
conductive rubber
view from below
Test electrode 2
The test electrode shown in Figure 2.26 comprises a square metallic plate with sides
that measure 2 5 0 m m and a square of dampened, water-absorbent paper, o r cloth,
f r o m which surplus water has been removed, with sides that measure approximately
270 mm. The paper or cloth, as applicable, is placed between the metal plate and the
surface being tested. During measurement, a force of approximately 7 5 0 N (75 k g in
weight) for floors or 2 5 0 N for walls is applied to the plate.
750 N
wooden plate
metal plate
L
damp cloth
floor covering
subfloor
PE
Expected results
The floors and walls are considered to b e non-conducting where t h e measured
resistances are at least 5 0 kQ (where the system voltage to Earth does n o t
exceed 500 V).
645.5 A further test is specified in BS 7671 for extraneous-conductive-parts that are within
the location, b u t to which insulation has been applied during construction. I n these
cases, a 'flash' insulation tester is required, which, after t h e standard 5 0 0 V insulation
test, applies a 2 kV AC root mean square (rms) test and measures the leakage current
(which should not exceed 1 mA).
Instrument', use a low-resistance ohmmeter for these tests (see Section 4.3).
A test for polarity is necessary to ensure that all fuses and single-pole control and
protective devices are connected in t h e line conductor. The centre contact of
screw-type lampholders must b e connected to the line conductor (except EI4 and E27
t o BS EN 60238), so this needs to be verified, as does the correct connection of all
non-reversible plugs and socket-outlets. It is important to remove all other lamps o n
t h e circuit, as these may provide a conductive path between line and neutral which
would t h e n permit an incorrectly connected lampholder to indicate continuity.
Note: The continuity test (see Section 2.6.5) and ring final circuit continuity test
(see Section 2.6.6) help to confirm polarity.
F i g u r e 2 . 2 7 P o l a r i t y test o n a l i g h t i n g c i r c u i t
//
I ‘i S
T/
/
[O]
/
Temporary shorting link
/
/ .
I /
Polarity test is carried out at single
pole switching devices, and screw
type lampholders (except E14and E27
t o BSEN60328).
AUTO |
Ideally, the test should be carried out when the ground conditions are least favourable, such
as when the soil i s frozen or very dry. Refer to Annex C of I E C 60364-6 for further guidance.
VoKW
Pha»e
Temporary test
3 m 3m
15 - 2 5 m 15 - 2 5 m
Notes:
1 Connect to terminals Cl and P I of four-terminal tester, or terminal X of a three-terminal tester.
2 Connect to terminal P2 of a four-terminal tester, o r terminal P of a three-terminal tester.
3 Connect to terminal C 2 of a four-terminal tester, or C of a three-terminal tester.
4 Voltage test spike is moved in t h e directions shown.
By c o m p a r i n g t h e t h r e e r e a d i n g s , a p e r c e n t a g e d e v i a t i o n c a n b e d e t e r m i n e d . T h i s i s
calculated by taking the average of the three readings, finding the maximum deviation of
the readings from this average in ohms, and expressing this a s a percentage of the average.
The instrument should b e capable of checking that the resistance of the temporary
spikes used fortesting iswithinthe accuracy limits stated in t h e instrument specification.
This may b e achieved by an indicator provided on the instrument, or t h e instrument
should have a sufficiently high upper range to enable a discrete test to b e performed
o n the spikes.
Where the resistance of the temporary spikes is t o o high, measures to reduce the
resistance will b e necessary, such as driving the spikes deeper into the ground or
watering with brine t o improve t h e contact resistance. Umno c i r c u m s t a n c e s should
the latter technique b e used to temporarily reduce the resistance of t h e
e a r t h electrode under test.
I n s t r u m e n t using o n e test c o i l
AUTO fi |o
vottu
Phase
Temporary test
15 - 2 5 m 15 - 2 5 m
The clamp containing the test coil is placed around the earth electrode under test,
o r around the conductor connected to that electrode. This eliminates the effects of
parallel resistances, so that only the resistance earth electrode under test is measured.
The resulting level of accuracy is similar to that given by the fall of potential method.
The instrument described here relies for its operation o n there effectively being a
number of earth electrodes within t h e installation, and not just the electrode under
test. The electrodes other than the one under test might not b e actual earth electrodes;
they might b e extraneous-conductive-parts buried in the ground o r in concrete buried
in the ground, such as metallic services pipes or buried structural metalwork or, in TN
systems, the means of earthing of the supply if this is connected during t h e test.
The instrument uses two coils placed a small distance apart around the earthing
conductor of t h e installation, as shown i n Figure 2.30, by means of clamps forming
part of t h e instrument. In practice, t h e coils may b e combined into a single clamp. O n e
coil induces a known voltage in a loop circuit containing t h e earth electrode under test,
the general mass of Earth and other connections with earth within the installation. The
second coil measures the test current.
Installation main
earthing terminal
;
@ @ @ ® ® ® '
@® ® ® ® ® ® ®
Constant
voltage
10
\
Induced
current
measurement
,clamp
Electrode under
test (having
resistance to
Earth RE )
The instrument carries out a calculation using the formula below. This produces a
resistance reading intended to represent the resistance of the earth electrode under test.
where:
The accuracy of the test reading ( R rea ding) depends on t h e existence of multiple parallel
paths for t h e returning test current to t h e instrument, such that t h e effective parallel
resistance of these paths is low enough to b e neglected.
For example, if there were four other 'earth electrodes', effectively connected i n parallel,
each having a resistance of, say, 4 0 Q, their combined resistance would b e 10 Q . If the
resistance of the earth electrode under test was 100 Q, the total resistance, Rrea ding.
measured by t h e test instrument would be 100 Q +10 Q=110 Q . Consequently, the
measured value ( Rrea ding) would b e 1 1 o 7o of the actual value (RE), an error of 10 °/o.
However, if there was only one earth electrode other than the o n e under test, the error
in the measurement could b e significantly greater, as t h e effective path would t h e n b e
through t w o electrodes effectively connected in series. Using the same values as in
the previous example, this would m e a n that the resistance, Rrea din g , measured by the
test instrument would be 100 Q + 4 0 Q =140 Q . Consequently, Rrea ding would then
b e 140 7 o o f the actual value (R E), an error of + 4 0 7o.
For T T s y s t e m s , i n t h e a b s e n c e o f t h e d e s i g n e r ' s s p e c i f i c a t i o n , B S 7 6 7 1 m a x i m u m
values where R C D s a r e used for automatic disconnection of supply are addressed i n
Regulation 411.5.3.
where:
▼ Table 2.1 5 Maximum values of EFLI (Z s) for non-delayed RCDs to BS EN 61 008-1 and
BS EN 61009-1 for U o of 2 3 0 V
The table indicates that the use of a suitably rated RCD will theoretically allow m u c h
higher values of R A, and therefore of Z s, than could b e expected by using the circuit
overcurrent devices for fault protection.
Note: It is advised, however, in Note 2 of Table 41.5, that earth electrode resistance values
above 2 0 0 Q may not b e stable, as soil conditions change due to factors such as soil
drying and freezing.
643. Where RCDs are required for additional protection, this is verified by testing the
operation of RCDs (see Section 2.6.18).
There are two methods used for verifying total EFLIfor a circuit:
The latter is preferred w h e n determining Z s for final circuits and distribution circuits.
Note: An EFLItester may not produce an accurate reading in installations with grid-connected
or island-mode (grid-forming) inverters (see Section 2.6.24).
Zs = Ze + (Ri + R2)
where:
For consumer units or distribution boards not at the origin, confusion can arise over the
term 'external EFLI'(Z e) and some prefer to write or note t h e EFLI at the distribution
board as Zdb- As this value is not external to the installation, the formula is modified to:
Instrument manufacturers can supply l o o p testers that are less liable to trip RCDs by
either limiting t h e test current (to less than 15 mA) or by DC biasing (this technique
saturates the core of the RCD prior to applying the test).
M e a s u r e m e n t o f external EFLI (Z e)
The externa
542 4 2 l EFLI, Z e , is measured using an EFLItester at the origin of the installation.
The impedance measurement is made between t h e line conductor of the supply and
the means of earthing with t h e main switch open or with all t h e circuits
isolated. The means of earthing must b e disconnected f r o m t h e installation MET for
t h e duration of t h e test, to remove parallel paths. Care should b e taken to avoid any
shock hazard to the testing personnel and other persons on the site, both whilst
establishing contact and whilst performing t h e test. It is strongly recommended to
check for diverted neutral currents where there is a TN-C or TN-C-S earthing
arrangement, or where PME conditions apply (see Appendix E).
| pate I I
[oonia i&h i<wh|
■O
0101
gBfflBBfla
Test between i n c o m i n g l i n e
conductor a n d t h e m e a n s o f
earthing, which s h o u l d be
disconnected from t h e rest
100 A of t h e installation, a n d f r o m
extraneous-conductive-
parts, s o t h e r e a r e n o
parallel p a t h s .
As previously mentioned, the measured Ze can be used to add to circuit (Rj + R2) values.
The inspector must have knowledge of the design in this respect as, for example, if t h e
switchgear at the origin of a n installation is suitably rated for prospective fault current,
a n d switchgear of similar short-circuit rating is used downstream of that point, then
n o further checks will b e necessary. This is because the magnitude of the prospective
fault current decreases with increasing distance downstream of the origin, assuming
there is not another source of supply, such as a generator, connected to t h e installation
at a point other than the main supply terminals of the installation. Any fault current
contribution f r o m a generator must b e included if the generator can operate in parallel
with the supply. If a generator or other source can supply the installation in place of
t h e normal supply, then generally fault currents will b e significantly lower and t h e
protection may take longer to clear a fault, making it possible that t h e l 2 t contribution
could cause thermal damage t o some cables or equipment.
Instrument: use the prospective fault current range of a suitable EFLItester for this test
(see Section 4.5, final paragraph).
With some instruments, the voltage between line conductors cannot b e measured
directly. Where this is t h e case, it can b e assumed that for three-phase supplies,
the maximum balanced prospective short-circuit level will be, as a rule of thumb,
approximately twice the single-phase value. This figure errs o n the side of safety.
Where a n instrument is rated for the higher voltage, a more accurate prospective fault
current measurement, for a three-phase installation, can b e obtained by measuring the
line-to-line fault current and dividing the measured result by 0.87.
Prospective earth fault current may b e obtained with the same instrument. Again, care
must b e taken to ensure that t h e instrument is set correctly and connected as per the
manufacturer's instructions for use.
Note: A prospective fault current tester may not produce an accurate reading in installations
with grid-connected or island-mode (grid-forming) inverters (see Section 2.6.24).
Whichever is the greater of the prospective short-circuit current and the prospective
earth fault current obtained should be recorded o n the EIC,EICRand the Schedule of
Test Results, as appropriate.
Note on the accuracy of EFLIand prospective fault current testers (see also
Sections 2.6.24 and 4.5)
EFLI testers become less accurate at low value impedance readings, such as w h e n
measuring close to a transformer or other low impedance source. It should b e
noted that the standard instrument used for determining prospective fault current is
effectively an EFLI instrument.
While earth fault loop testers should have a resolution of at least 0.01 Q, this should
not b e confused with accuracy.
A displayed test result of less than about 0.1 Q, or about 1.0 Q,when o n the lower
current range (such as 15 mA), could b e prone to significant errors. Such errors can
significantly affect the calculation o f prospective fault current.
Should more accurate measurements b e needed o n large installations with very low
impedance supplies, specialist high-current four-wire EFLI testers are available.
Note: An EFLI and prospective fault current tester may not produce a n accurate reading
in installations with grid-connected or island-mode (grid -forming) inverters
(Section 2.6.24).
S2A 2
S4A 4
8 0 kA a t 400 V
3.0 (3-0)
6 (6-0)
10 (7-5)
15 (7.5)
20 (10.0)
25 (12.5)
The difference between the two short-circuit ratings described above is the condition
of the circuit-breaker after manufacturer's testing.
I c n is the maximum fault current that the device can interrupt safely, although its
characteristics may have been altered and i t may n o longer b e usable.
Ics is the maximum fault current that the device can interrupt safely without
loss of performance.
The l c n value (for example, 6,000) is marked o n the device in a rectangle. For
t h e majority of applications, t h e prospective fault current at t h e terminals of t h e
circuit-breaker should not exceed this value.
Fault currents up to 16 kA
Except in London and some other major city centres, the maximum fault current for
2 3 0 V single-phase supplies up to 1 0 0 A is unlikely to exceed 16 kA. Appendix 14 of
BS7671 advises that it is often not necessary to measure o r calculate the prospective
fault current at the origin of individual dwellings or similar premises i n which the
distributor has declared the prospective fault current to b e 16 kA:
The term 'distribution board for operation by ordinary persons' used in BS EN 61439-3
applies to a wider range of products than a domestic consumer unit. The 16 kA
conditional rating applies only to consumer units as defined in B S 7 6 7 1 as follows:
536.4.201 The short-circuit capacity of OCPDs individually having a short-circuit capacity rated less
than 16 kA, but incorporated within consumer units, may b e taken to b e 16 kA where:
(a) the installation has a supply provided in accordance with the ESQCR, with a
nominal voltage of up to 2 5 0 V A C ;
(b) the service cutout is a fuse rated 100 A or less complying with either BS 1361
(Type II) o r BS 88-3;
(c) t h e consumer unit complies with either:
(i) BS EN 61439-3 (including t h e 16 kA conditional short-circuit test described
in Annex ZB of t h e standard), incorporating only components and protective
devices specified by t h e manufacturer; or
(ii) (for initial verification of additions a n d alterations to existing installations
with older consumer units) either:
• BS 5486-13:1979 with label 'CM16';
• BS 5486-13:1989; or
• BS EN 60439-3 (including the 16 kA conditional short-circuit test
described in Annex ZA of the standard), incorporating only components
and protective devices specified by the manufacturer (see Regulations
432.1 and 530.3.4 of BS 7671:2008).
643.9 Regulation 643.9 requires verification that the phase sequence is maintained for
multiphase circuits within an installation. In practice, this will b e achieved by checking
polarity a n d connections throughout the installation. While the regulation requires phase
sequence to b e maintained throughout the installation, this should not b e confused
with phase rotation. Phase rotation is a description of which way a correctly-wired
three-phase induction motor will run. If t h e timing of t h e sine waves o n LI, L 2 and L3
are such that LI precedes L2, which precedes L3, then t h e motor will run clockwise.
If t h e timing of t h e sine waves is changed by swapping any two wires, as shown in
Figure 2.32, then the motor will run anticlockwise. To ensure correct operation of
three-phase loads, for example three-phase laundry equipment, it is recommended to
test phase rotation at t h e point closest to the load, before the load is energized.
Original 1-2-3
phase rotation (wires 1 and 2 swapped) End result
phase rotation = 2-1-3
2
3 ----------------------------------------------------- 3
3 2
2 2
Optionally, a n d o c c a s i o n a l l y , t h e i n s p e c t o r may w i s h to c h e c k p h a s e s e q u e n c e b y u s i n g
a p h a s e rotation tester, of e i t h e r :
I n s t r u m e n t s c o n t a i n i n g b o t h of t h e a b o v e f o r m s o f i n d i c a t i o n a r e a l s o a v a i l a b l e .
In the c a s e of a rotating d i s c type instrument, the d i s c will rotate either clockwise o r anticlockwise.
With the indicator l a m p type, either the L1/L2/L3 (formerly R/Y/B) lamp or the
L1/L3/L2 (formerly R/B/Y) l a m p will be illuminated.
▼ Figure 2.33 Examples of phase sequence indication from phase rotation instruments
Alphanumeric
For example multifunction
tester, phase sequence
meter
Graphical symbols
For example multifunction
tester, phase sequence
meter
Illuminated L E D
For example approved
two-pole voltage tester
643.7.1 (a) where they are relied o n for disconnection for compliance with Chapter 41 of
BS7671; and
643.8 (b) where they are installed as additional protection, as specified in Chapter 41 of
BS 7671.
Where RCDs are installed with circuit-breakers and the circuit has the characteristics to
satisfy Chapter 41 of BS 7671 without the RCD,then testing of the RCDisnot essential
unless it is specified for additional protection.
Operation of R C D s
411.4.5 Before using a test instrument, the RCDtest button should b e pressed. This provides
4H.5.3 basic information that the RCD is functioning, and will help avoid danger that may
occur during test if the RCD did not respond.
BS EN 61557-6 requires the test current for a tripping test to b e applied at the
zero-crossing point of the AC wave. Therefore, for each of the tests, readings should b e
taken with the test waveform starting on both positive and negative half-cycles usually
identified '0°' and '180°’ o n test instruments, and the longer operating t i m e recorded
for t h e l x l An Type AC test.
Prior to these R C D tests, it i s essential, for safety reasons, that the EFLI i s
tested to check the r e q u i r e m e n t s h a v e been met.
a Recommended tests
b Examples of optional RCD tests for fault-finding and similar purposes (see notes 5 and 6)
Notes:
1 Where applicable, Instruments without an 'RCD Type' setting can only b e used to carry
out Type AC tests.
2 Harmonized standards for the purposes of Table 2.17a are considered to be
BS EN 61008, BS EN 61009, BS EN 60947-2 and BS 7288:2016. (BS 7288:2016 is the
UK implementation of HD 6 2 6 4 0 Residual current devices with or without overcurrent
protection for socket-outlets for household and similar uses').
3 RCDs to BS 4293 and editions of BS 7 2 8 8 earlier than BS 7288:2016 should b e tested
as Type AC only. Tests for other Types are not applicable for RCDs to these standards.
4 This test is required by Regulation 643.7 of BS 7671 (where the RCD is used for
automatic disconnection of supply) or Regulation 643.8 of BS 7671 (where the RCD
is used for additional protection). RCD to BS 4293 or BS 7288:1990 should meet the
operating times of the appropriate product standard, where these are shorter than those
specified in BS 7671 :201 8+A2:2022, because a longer operating time than that in the
relevant product standard may indicate that the RCD is n o longer operating correctly.
The longest tripping time for each of the two tests (0° and 180°) is recorded in
column 2 8 of the Schedule of Test Results (see example in Figure 5.6).
5 Optional tests are intended for fault-finding and similar purposes only. The performance
requirements of the optional tests are to be met by product manufacturers and are not
BS 7671 requirements. Not all test instruments can perform all of the tests listed here
(see note 1).
6 Since RCDs are only rated for a finite number of operations, carrying out frequent
optional tests can shorten the product's life. For example, in carrying out all of the
above tests, including optional tests, for a 30 mA Type B RCD, would require the RCD to
trip 12 times.
7 For RCDs to harmonized standards (see note 2), with residual operating current l An 30 mA,
the manufacturer may select a current for the Type AC 40 m s tripping test of 2 5 0 mA
instead of 5 x l An . Where this is declared by t h e manufacturer, failing to trip within 4 0 m s
at 5 x l An . does not necessarily mean the RCD is faulty. For this reason, and to prevent
shortening the usable life of RCDs (see note 5), BS 7671:2018+A2:2022 does not
require testing of RCDs at 5 x l An .
symbol reference
RCD Type isymbol
in IEC 60417
T y p e A C to B S EN 61008,
B S EN 61009, B S EN 60947-2 or 6148
B S 7288:2016
T y p e A to B S E N 61008,
B S E N 61009, B S E N 60947-2 or 6149
B S 7288:2016
6149+6160
T y p e F to BS E N 62423 OR
or B S E N 60947-2
6399
——— 6149+6160+6297
T y p e B to B S EN 62423 or B S 6398
EN 60947-2
OR
6150
S t y p e (time d e l a y ) in addition
6395
to one of the a b o v e markings
Note: RCDs to BS 4293, and BS 7288:1 990, have no marking for residual current operating
characteristic. They would be considered equivalent to Type AC RCDs if assessing their
continued use with respect to additions to an existing installation downstream of the
device. The designer should also consider that there have been other improvements
in product standards for RCDs in relation to device characteristics, isolation,
short-circuit rating, reliability, and electromagnetic compatibility.
RCD test method 1: residual current test applied between line and
protective conductor
RCDtest method 1 is preferred where RCDs are used for fault protection, as it provides
further validation that the RCD is operating within a specific t i m e for a simulated fault
to t h e relevant protective conductor.
The test is m a d e o n the load side of the RCD between t h e line conductor of t h e
protected circuit and the associated cpc. The load should b e disconnected during
the test to avoid spurious results. These tests can result in a potentially dangerous
voltage o n exposed-conductive-parts and extraneous-conductive-parts when t h e EFLI
approaches t h e maximum acceptable limits. Precautions m u s t therefore b e taken to
prevent contact of persons o r livestock with such parts.
It may not b e possible to use this test method conclusively in s o m e situations, for
example where:
(a) there is an upstream RCD for which there is n o selectivity, such as a test on an
RCD in a caravan supplied f r o m a caravan site or repair workshop socket-outlet,
where B S 7 6 7 1 requires that the socket-outlet and caravan both have additional
protection by an RCD rated 3 0 m A or less. In these cases, either RCD may trip
first, and it is n o t guaranteed that t h e disconnection t i m e measurement will b e
that of t h e RCD under test.
(b) protective conductor currents f r o m equipment that cannot b e disconnected
f r o m the circuit under test, or f r o m other parts of the installation that are
energized, affect the conditions of the applied test so that the disconnection
time measurement is affected.
(c) an RCD in an IT system is being tested, and there is n o current return path via
a cpc.
The test is m a d e between a live conductor o n the supply side (upstream) of t h e RCD
and another live conductor o n the load side (downstream) of the RCD, for example:
Note: The instrument, test leads, and probes, must be rated for the line-to-line voltage of
the three-phase system at appropriate overvoltage category (see Section 1.1).
Examples of testing an RCCBand RCBOare shown in Figures 2.35 and 2.36 respectively.
These examples are included to illustrate the principles only. The person carrying out
the test should take all practicable steps to avoid the risk of contact with live parts,
such as the example shown in Figure 2.37. The test should only b e performed with
covers removed, in equipment where all line conductor terminals meet IP2X/IPXXB.
Before attempting this test method, check with the test equipment manufacturer's
instructions that the method is supported by the instrument. Some test instruments
require only two test leads to be connected during the test, but some require three
test leads.
b. 3-lead test
Other circuits
©©©©©©©
switched off
where possible
Supply
©I© ©I©
©’ E3
l&n 30mA
instrument is suitable for the
upstream/downstream test.
TEST
I Other circuits
switched off where
Supply possible
1
oet
b. 3-lead test
I \l 1 II Other circuits
switched off where
Supply possible
1
EERIE \ \
©
Y-splitter
caravan \ -pitch
inlet outlet
caravan
connecting
pgSBs lead
downstream line
Upstream
connection from
neutral
socket-outlet in wander-lead connection
caravan, via
from trailing
shrouded test BS EN 60309-2
socket-outlet,
Plug plug to BS 1363-
via shrouded y
2 trailing socket
test plug /
outlet converter
2Q3ms
30mA
Y-splitter
caravan pitch
inlet outlet
caravan
connecting
|?BBB|B|B! lead
downstream line
Upstream
connection from
neutral —
socket-outlet i n wander-lead connection
caravan, via
from trailing
shrouded test BS EN 60309-2
socket-outlet,
plug plug to BS 1363-
via shrouded
2 trailing socket
test plug /
outlet converter
30.3 ms
30mA
The maximum disconnection t i m e for a residual test current of | An for the AC test is
recorded in the Schedule of Test Results.
Operation of the integral test device does not provide a means of checking:
514.12.2 The RCDtest button will only operate the RCD if it is energized. B S 7 6 7 1 recommends
that the test button is pressed at least every 6 months.
The settings o n all adjustable relays and controls, etc. should b e checked to see that
they align with the designer’s proposed requirements. RCD test buttons should b e
operated t o see that the RCD trips.
AFDDs have b e e n introduced in t h e 18th Edition of the IET Wiring Regulations (532.6).
There are two general types: those with a test button and those with an automatic test
facility. Functional testing can only b e carried out by pressing the test button; there is
n o means of functionally testing the t y p e without a test button.
Where it may b e necessary to verify that voltage drop does not exceed t h e limits stated
Sect 525 In the relevant product standards of installed equipment, B S 7 6 7 1 provides guidance
to d o so. Where no such limits are stated, voltage drop should be such that it does not
impair t h e proper a n d safe functioning of installed equipment.
Voltage drop problems are quite rare, but the inspector should b e aware that long runs
of circuit conductors and/or high currents can sometimes cause voltage drop problems.
Table 4Ab Appendix 4 of BS 7 6 7 1 gives maximum values of voltage drop for lighting and for
other uses, depending u p o n whether an installation is supplied directly from a public
LV distribution network o r f r o m a private LV supply. The voltage drop for general
purposes in Appendix 4 exceed the requirements of s o m e product standards. For
example, BSEN 61851-1:2011 for electric vehicle charging equipment requires charging
points t o operate within a utilization voltage range of Uo ± 10 7o, which therefore
requires a maximum voltage drop of 4 7o in a consumer's installation supplied in
accordance with t h e ESQCR.
It should b e remembered that voltage drop may exceed t h e values stated in Appendix 4
in situations such as motor starting periods and where equipment has a high inrush
current, where such events remain within the limits specified in the relevant product
standard or reasonable recommendation by a manufacturer.
Sect 442 The protection referred to in this section of the Guidance Note is the subject of
Section 4 4 2 of BS7671. F o r m o r e information, see Guidance Note 1.
442.2.2 Regulations 442.2.1 and 442.2.2 give t h e requirements concerning the magnitude
and duration of temporary overvoltages occurring due to a fault in t h e HV system
(typically, 11 kV) supplying t h e substation f r o m which t h e LV installation is supplied.
442.2.1 Where the LV installation is supplied from a privately owned substation, the design
442.2.2 responsibility for complying with Regulations 442.2.1 and 442.2.2 rests with the
designer(s) of t h e substation and the associated LV distribution network up to the
incoming terminals of the LV installation. The inspector will need to b e in possession
of sufficient information provided by this party (or parties) about the intended means
of compliance, to enable him or her to verify, so far as is reasonably practicable, that these
means have been properly put into effect. Matters to b e checked by the inspector include:
(a) that the HV and LV earthing arrangements of the substation have b e e n correctly
installed and that their resistances to Earth meet the designer's requirements;
(b) that t h e HV earthing and LV arrangements are interconnected or, where appropriate,
separated, according to t h e designer's requirements;
(c) that any global earthing system or additional connections with Earth in the
LV network that are relied o n for safety are in existence and properly installed,
and that the resistance of connections with Earth meets the designer's
requirements; and
(d) that t h e rated currents and settings of protective devices are as intended by
the designer.
442.3 Regulations 442.3, 442.4 and 442.5 require consideration to b e given to t h e stress
voltages that would occur in an installation in t h e event of loss of the neutral conductor
In a TN or TT system, a n earth fault in an IT system with distributed neutral, or a
short-circuit between a line conductor and a neutral conductor.
In practice, there is usually little that an installation designer and constructor can
d o to meet the requirements of these regulations beyond selecting and installing
equipment with appropriate insulation voltage ratings, such as 600/1,000 V cables for
an installation of nominal voltage of 2 3 0 / 4 0 0 V. The inspector should check that this
has been done.
Table 4 4 : Irrespective of whether the electrical designer has chosen to specify SPDs, t h e
inspector should check that all electrical equipment of the installation has been so
selected and installed that, according to its product standards, it provides at least the
applicable value of rated impulse voltage referred to in Table 443.2 of BS 7671. The
values of rated impulse withstand voltage in that table are given according to the
Category (I, II, III or IV) into which the equipment falls and to t h e nominal voltage of
the installation. Table 4 4 3 . 2 of BS 7671 gives examples of equipment falling into each
of the categories.
Where protection against overvoltages by the use of SPDs has been specified by the
Section 534 designer, the inspector should check that these have been selected and installed in
accordance with t h e designer's requirements or otherwise in accordance with
Section 5 3 4 of BS7671.
The inspector needs t o verify that SPDs have n o t become expired or defective by
ensuring that indicator lights are correctly illuminated or that the coloured flag or flags
o n the devices indicate that they are serviceable. Remote status indicating facilities
such as connection to an audible alarm may also have been provided and this should
also b e checked for correct operation.
S e c t i o n 4 4 4 s p e c i f i e s a d d i t i o n a l m i t i g a t i n g m e t h o d s f o r E M C a p p l i e d t o t h e design and
installation of cables and equipment. Many of these mitigating methods concern the routing
of cables and their distance from other cables, a s well as providing equipotential bonding.
(a) c h e c k i n g t h e E M C d e s i g n h a s b e e n f o l l o w e d w i t h r e s p e c t to c a b l e routing,
s e p a r a t i o n distances, use of suitable containment a n d enclosures, etc.;
(b) inspection of cable sheath and screen terminations and, if considered
n e c e s s a r y , c o n t i n u i t y c h e c k i n g of t h e s e items; and
(c) c a r r y i n g o u t c o n t i n u i t y c h e c k s o f a n y a d d i t i o n a l m i t i g a t i n g b o n d i n g n e t w o r k
p r o v i d e d (for e x a m p l e , a l o c a l m e s h network).
While there are n o specific requirements in BS 7671 for either installers or inspectors
to carry out electric field or magnetic field strength measurements, designs for certain
installations may require such measurements to b e made, based o n assessments
carried out at t h e design stage.
This section outlines particular considerations for initial testing with this t y p e of
installation. Further information, including guidance on initial verification, can be found
in the IET Code of Practice for Electrical Energy Storage Systems and the IET Code of
Practice for Grid-Connected Solar Photovoltaic Systems.
Note: In PEIs, the term power conversion equipment (PCE) is used to describe both
inverters and AC-DC converters, as a single device, such as a combined inverter
charger for a battery storage system, may perform both functions.
M u l t i p l e s u p p l i e s a n d safe i s o l a t i o n
PEIsusually have m o r e than one source of supply. Isolation of the electrical installation
for safe working o n certain parts of the installation will involve m o r e than one point
of isolation.
(a) The earthing arrangement may change, for example f r o m TN-C-S to TN-S, or
f r o m TT to TN-S. A consumer's earth electrode may b e required.
(b) The prospective fault current is likely to b e far less, and the effective EFLI
greater, than in connected modes of operation. In smaller installations, there
may be insufficient fault current to operate overcurrent protective devices, a n d
RCDs or protection built into electronic converters must b e used for protection
against electric shock. Manufacturer’s instructions should b e consulted to check
whether external protective devices are required.
Notes:
1 Local storage units can supply current-using equipment or be charged by local power
supplies and/or the public distribution network.
2 Local storage units can supply current-using equipment and/or the public distribution
network or be charged by local power supplies.
3 An island mode can be either the result of an automatic process or the result of a
deliberate action.
When a prospective fault current or EFLI measurement is taken in a PEI in island mode,
especially using a 'no trip' or 'low current' setting usually used to avoid tripping RCDs,
the prospective fault current reading may b e much higher than t h e actual value, and
the EFLI lower.
The IET Code of Practice for Electrical Energy Storage Systems advises:
(a) external earth fault loop impedance and prospective fault current measurements
are carried out at the origin, with all PCE isolated.
(b) earth fault loop impedance and prospective fault current measurements for
the remainder of the installation are not taken unless all the inverters in the
system are isolated. In order to provide verification for automatic disconnection
of supply, t h e following tests can b e used:
(i) for connected mode: the verification of earth fault loop impedance
(Zdb and Z$) is based o n the external earth fault loop impedance, Ze, plus
measured (R1+R2) values. Prospective fault current should b e the measured
prospective fault current plus the sum of t h e current limit of all connected
m o d e inverters.
(ii) for island mode: if applicable, verification of earth fault loop impedance
(Zdb and Zs) is determined using measured (R1+R2) values, plus the
manufacturer's information regarding the value of Z e to b e assumed for the
EESSor the relevant PCE within it. Prospective fault current should b e t h e
sum of the current limit of all connected-mode inverters.
Note: The prospective fault current measurement at the origin is not necessary if it can be
determined by other means (see Section 2.6.16).
The periodic inspection and testing is carried out, so far as is reasonably practicable, for:
(a) the safety of persons and livestock against the effects of electric shock and bums;
(b) protection against damage to property by fire and heat arising f r o m a n
installation defect;
(c) confirmation that t h e installation is not damaged or deteriorated so as to impair
safety; and
(d) the identification of installation defects and departures f r o m the requirements
of B S 7 6 7 1 that may give rise to danger.
(a) legislation requires that electrical installations are maintained in a safe condition,
and this lends itself to periodic inspection and testing (see also Tables3.1 and 3.2);
(b) licensing authorities, public bodies, insurance companies, mortgage lenders and
others may require periodic inspection and testing of electrical installations, as
is, for example, the case for HMOs (see Tables 3.1 a n d 3.2); and
Reference to legislation and other documents is made below. It is vital that these
requirements are ascertained before undertaking periodic inspection a n d testing.
HSR25, which provides guidance o n these regulations, advises that this regulation
is concerned with t h e need for maintenance to ensure the safety of the system,
rather than with the activity of carrying out t h e maintenance in a safe manner, which
is required by Regulation 4(3). The obligation to maintain a system arises if danger
would otherwise result. There is n o specific requirement to carry out a maintenance
activity as such; what is required is that the system is kept in a safe condition. The
frequency and nature of the maintenance must be such as to prevent danger so far
as is reasonably practicable.
There have been many debates as to what 'reasonably practicable' means. In the
event of an accident, i t would b e for a court to decide the issues. In essence, however,
the reduction of risk to as low as is reasonably practicable means weighing that risk
against the sacrifice needed t o further reduce it. The decision should b e weighted in
favour of health and safety, because the presumption is that t h e duty holder should
implement t h e risk reduction measure. To avoid having to make this sacrifice, the duty
holder must b e able to show that it would b e grossly disproportionate to the benefits
of risk reduction that would b e achieved. Thus the process is not one of balancing t h e
costs and benefits of measures, b u t rather, of adopting measures except where they
are ruled o u t because they involve grossly disproportionate sacrifices.
Ultimately, under t h e EAWRit is the duty holder who is responsible for t h e safety of an
electrical installation at work. This leads to the question as to w h o the duty holder is.
In Section 4 of the Health a n d Safety at Work etc. Act 1974 (HSWA), reference is m a d e
to a person "who has, t o any extent, control of premises". This may b e an identified
person with that specific responsibility within an organization, such as a landlord, or
perhaps a manager or supervisor.
A p p e n d i x E d e s c r i b e s a s a f e t y check p r o c e d u r e to i d e n t i f y d i v e r t e d n e u t r a l currents.
3.4 Design
341.1 W h e n c a r r y i n g o u t the design of a n installation, a n d p a r t i c u l a r l y when s p e c i f y i n g the
e q u i p m e n t , the designer s h o u l d t a k e into account the quality of t h e m a i n t e n a n c e t o
b e r e a s o n a b l y expected, i n c l u d i n g t h e f r e q u e n c y of routine checks and t h e p e r i o d
between subsequent inspections (supplemented, a s n e c e s s a r y , by testing).
Commercial and industrial installations come under the EAWR. For these installations,
formal arrangements are required for maintenance and interim routine checks (as well
as for periodic inspections); there should also b e the facility to receive wear-and-tear
reports f r o m users of the premises.
The frequency and t y p e of these routine checks will depend entirely u p o n the nature
of the premises and should b e set by the electrical dutyholder. Routine checks should
include t h e items listed in Table 3.1. Table 3.2 ( i n Section 3.7) provides guidance o n
the frequency for initial interval between inspections, which m a y need to b e increased
as an installation ages.
Activity Check
Defects reports All reported defects have b e e n rectified
(a) breakages
(b) wear/deterioration
(c) signs of overheating
(d) missing parts (covers, screws)
(e) loose fixings
Confirm:
(a) switchgear accessible (not obstructed)
(b) doors of enclosures secure
(c) adequate labelling in place
Operation Operate:
(a) switchgear (where reasonable)
(b) e q u i p m e n t - switch o n and off
(c) including RCDs (using test button)
Note that routine checks need not b e carried out by an electrically skilled person,
but should b e undertaken by somebody who is able to safely use t h e installation and
recognize defects.
There is a general ongoing requirement to manage health and safety at work, and
electrical safety is just one area of this. To ensure that regular routine checks are m a d e
o n the electrical installation, it may b e advantageous in larger premises to combine
these with other regular checks, such as emergency lighting a n d fire alarm inspections,
general fire safety inspections, emergency exit route inspections, and so on, o n security
patrols. A system to record obvious defects should b e implemented and a simple f o r m
is all that is needed.
514.9 Enquiries should b e m a d e to t h e person responsible for the electrical installation with
regard to t h e provision of diagrams, design criteria, type of electricity supply (and any
alternative supply) and earthing arrangements.
Where there are n o records, in all but t h e simplest domestic installation, a n inspector
may first need to spend t i m e tracing installation systems and circuits and producing
basic drawings and schedules, before starting any inspection and testing work.
652.1 In advising the person ordering t h e work about t h e t i m e interval for t h e period for t h e
next recommended periodic inspection and test, t h e inspector is required to take into
consideration t h e individual characteristics of t h e type of installation and equipment, its
condition, use and operation, any damage and deterioration, any known maintenance
and t h e external influences to which it is subjected. The results and recommendations
of any previous periodic inspection reports should also b e considered.
The suggested initial frequencies for inspection and testing given in Table 3.2 are
recommendations and not legal requirements. The period between subsequent
inspections may b e reduced, o r occasionally increased. It is the responsibility of the
person responsible for the electrical installation to determine when the next periodic
inspection is undertaken. In making this decision, they should take appropriate advice
f r o m specialists, where necessary, t o assessthe conditions affecting t h e installation that
might lead to defects, potential damage and/or deterioration that would affect safety.
Such advice m a y include routine checks, manufacturers' o r engineers' advice and
guidance, and periodic inspection and testing reports, with this information assisting
the person responsible for t h e electrical installation in determining t h e maintenance
plan for t h e installation. Over time, and with practical maintenance experience, it may
b e possible to extend periodic inspection and testing intervals if t h e results of routine
checks, inspections or tests show that few faults are found and that t h e installation
is not subject to excessive deterioration. However, if faults are common, it may b e
necessary t o reduce intervals or take other action to improve maintenance and reduce
risk. Routine checks and periodic inspection and testing by an inspector are only a
part of the requirement for maintenance; t h e person responsible for the electrical
installation has a continuing ongoing responsibility for the safety of an installation.
Note: Persons responsible for electrical installations are reminded of the requirements of
Regulation 4(2) of the EAWR. Undertaking routine inspection and testing of their
installationswill assist in meeting this duty.
The inspector, being a skilled person, should apply sound engineering judgement
and experience w h e n deciding u p o n t h e intervals between inspecting and testing
an installation based u p o n t h e criteria in Regulation 6 5 2 of BS 7671. It must also b e
noted that in the event of an accident or dangerous occurrence, t h e inspector may b e
required to justify their decision.
651.1 The formal periodic inspection and testing should b e carried out in accordance with
Regulation 642, supplemented by tests as detailed in Regulation 643. This requires
an inspection comprising a detailed examination of the installation, carried o u t without
dismantling, or with partial dismantling as required, together with the appropriate tests
of Regulation 643 as required to comply with Regulation 651.2.
652.2 Where there is an effective management system in place for inspection and preventative
maintenance of the installation (for example, where there are competent permanent
on-site maintenance staff), periodic inspection and testing can b e replaced by an
adequate regime of continuous monitoring and maintenance of the installation and its
constituent equipment. However, appropriate records must b e maintained o n site to
show that a n inspection and preventative maintenance plan is in place and is being
adhered to.
Notes:
1 Particular care m u s t b e taken t o comply w i t h t h e Electricity Safety, Quality a n d
Continuity Regulations (ESQCR) (as amended).
2 Regulation 4 of t h e E A W R a n d HSR25.
3 See BS 5266-1 : 2 0 1 6 Emergency lighting. Code o f practice for the emergency lighting of
premises a n d t h e IET Electrician's Guide to Emergency Lighting.
4 Other intervals are r e c o m m e n d e d f o r t e s t i n g operation of batteries and generators.
5 See BS 5839-1 : 2017 Fire detection and fire alarm systems for buildings. Code o f practice
for design, installation, commissioning and maintenance of systems in non-domestic
premises and the IET Electrician's Guide to Fire Detection and Fire Alarm Systems.
6 Local Authority conditions of licence. There is specific legislation listed i n BS 7 6 7 1
relating to cinemas a n d theatres.
7 It is r e c o m m e n d e d that a caravan is inspected a n d tested every three years, w i t h this
period reduced t o every year if it is used frequently (see Regulation 721.514.1 and Fig 721
(Instructions for electricity supply)).
Any landlord (of an H M O or other occupancy) may b e considered to have duties under
the EAWRdue to their responsibilities under Section 3 of t h e HSWA 1974 (relating, for
example, to the c o m m o n areas of a set of flats). In Scotland, the private rented sector
has legal requirements to maintain the electrical installation. Landlords are required by
law to ensure that the electrical installation in a rented property is safe w h e n tenants
m o v e in and is maintained in a safe condition throughout its duration and that an H M O
has a periodic inspection carried o u t o n the property every five years.
Although there are various approaches to carrying out inspection and testing, one
suggested method is to first obtain an overview of the installation, ideally f r o m
diagrams a n d charts, as well as from a simple 'walk-round' survey prior to starting the
full inspection. This will enable the inspector to b e able to plan the inspection and to
identify items that require isolation, etc. M o s t importantly, this initial survey will enable
the inspector to set sample sizes, (see Section 3.8.3).
651.1 Where diagrams, charts or tables are not available, a degree of exploratory work may
b e necessary so that inspection and testing can be carried out safely and effectively;
this may include a survey to identify switchgear, controlgear and the circuits they control.
Indeed, for m o r e involved installations without design information, such as, diagrams
or charts, t h e client should b e advised that such diagrams require producing in order
to plan and conduct the inspection and testing. Alternatively, where the inspector
considers that it is safe to proceed, the inspection can commence, but may b e limited to
visual inspection. The production of diagrams and charts can be called for on the EICR.
During t h e inspection, opportunity should b e taken to identify dangers that might arise
during t h e testing. Any location and equipment for which safety precautions may b e
necessary should b e noted and the appropriate steps taken.
A thorough inspection should b e made of all electrical equipment that is not concealed,
and should include the accessible internal condition of a sample of the equipment.
The external condition should b e noted and, if damage is identified or if the degree of
protection has been impaired, this should b e recorded o n t h e Schedule of Inspections
appended to the Report. The inspection should include a check o n t h e condition of
electrical equipment and material, taking into account any available manufacturer's
information, with regard to the following:
(a) safety;
(b) age;
(c) damage and defects;
(d) corrosion and external influence®;
T h e a s s e s s m e n t o f c o n d i t i o n s h o u l d t a k e a c c o u n t o f k n o w n changes i n conditions
influencing a n d a f f e c t i n g e l e c t r i c a l safety, f o r example, plumbing o r s t r u c t u r a l changes.
643.3.2 A c a r e f u l c h e c k s h o u l d b e m a d e of t h e t y p e of e q u i p m e n t o n site s o t h a t t h e n e c e s s a r y
p r e c a u t i o n s c a n b e taken, w h e r e c o n d i t i o n s r e q u i r e , t o d i s c o n n e c t o r s h o r t - o u t
electronic a n d other equipment t h a t might b e damaged by testing. Special c a r e must
b e taken w h e r e control a n d protective devices contain electronic c o m p o n e n t s .
(a) t h e approximate age and probable condition of the electrical installation in the
area being inspected;
(b) any electrical installation work carried out since the last inspection and test;
(c) any differences in the installation in the area (part of it may have been
refurbished or taken from another area);
(d) the type a n d usage of the installation o r part thereof in that area (part of it may
have b e e n used for another purpose previously);
(e) the ambient environmental conditions in t h e area and any differences in t h e
ambient environmental conditions over the area;
(f) the apparent effectiveness of ongoing maintenance, if any;
(g) the period of t i m e elapsed since previous inspection/testing;
(h) the size of the installation and any differences i n the ambient environmental
conditions over the area;
(i) consultation with the installation owner; and
(j) the quality of records such as EICs, MElWCs, previous periodic inspection
reports, maintenance records, site plans/drawings and data sheets relating to
installed equipment.
It should b e noted that the initial sample size is based only o n a visual pre-inspection
and consultation of records. Further, what may at first appear to b e good, for example,
the quality of maintenance, may turn o u t to b e poor during the detailed inspection
and testing.
In determining the sample size, it should b e noted that the minimum population size
to get meaningful results is 1 0 0 according to statistical sampling theory. That means
that inspection and testing as a whole, should cover at least 100 points on electrical
equipment. The term electrical equipment is defined in BS 7671 as follows:
For very small installations such as those in some domestic premises, this principle is
likely to m e a n that most electrical equipment forming part of the fixed installation is
inspected a n d tested as appropriate. For example, a small domestic installation may
only have four circuits each with less than ten accessories connected; t h e total number
of items of electrical equipment, including the consumer unit and circuit wiring, is likely
to b e well under 100, and, because it is practicable, all items are likely to b e included
in the inspection and test. There should certainly b e n o sample of circuits made in
such premises.
periodic
verification
required
conduct pre
inspection survey
and establish sample
size
carry out
inspection and
testing on
samples selected
increase sample
intermediate/poor/ size or discuss
good results indeterminate results with client
status of results whether more
in-depth
investigation is
necessary
no sample size to be
increased?
yes
final report
Where the inspection or testing of a sample yields poor or unacceptable results, this
would suggest that similar problems might exist elsewhere in uninspected or untested
items. The inspector will t h e n need either to increase the sampling or refer back to
the client; it may b e that the inspector recommends that 100 °/otesting is carried o u t
in that area.
If relatively small sample sizes are chosen, it is important that these are representative
of the complete installation. Similarly, if a repeat periodic inspection is undertaken
using a sampling system, then a different sample, again representative of the complete
installation, must be chosen. Therefore, previous periodic inspection and test records
should be consulted prior to commencement of a sample inspection and test.
Suggested sample sizes for visual inspections are provided in Table 3.3; suggested
sample sizes for testing are discussed in Section 3.10.1 of this Guidance Note and in
Table 3.4.
Main switchgear internal Ideally 100 % but not less Signs of overheating, ageing,
sections and cable than 2 0 % (note 2) check tightness of terminals
terminations
Final circuit distribution Ideally 100 % but not less Signs of overheating, ageing,
boards than 25 % (note 4) check tightness of terminals
Notes:
1 Where t h e inspection o f a sample yields p o o r or unacceptable results, this w o u l d
suggest that similar problems m a y exist elsewhere i n t h e uninspected items. T h e
inspector will n e e d either t o increase t h e sampling or refer back t o t h e client; it m a y b e
that t h e inspector r e c o m m e n d s that 1 0 0 % inspection is carried o u t i n that area.
2 1 0 0 % where practicable.
3 Generally, it is less appropriate to apply small sample sizing to the inspection of
socket-outlets compared w i t h samples for lighting, as i t is m o r e likely that user
e q u i p m e n t will b e hand-held presenting a greater risk for potential electric shock.
4 D o not 'sample samples', resulting in a very l o w overall sampled installation. Samples
m u s t b e representative. If i t is decided t o sample, for example, sub-main cables at
10 7o,then further sampling should not b e applied to t h e final circuit distribution boards
o n these circuits.
5 One easy way t o remember sampling is to reflect o n the fact that where just 1 0 % of final
circuits have b e e n inspected, this actually means that 9 0 % have not b e e n inspected.
OTHER METHODS O F PROTECTION (where any of the methods listed below are
employed details should b e provided o n separate pages)
• Non-conducting location (418.1)
• Earth-free local equipotential bonding (418.2)
• Electrical separation (Section 413; 418.3)
• Double insulation (Section 412)
• Reinforced insulation (Section 412)
DISTRIBUTION EQUIPMENT
• Adequacy of working space/accessibility to equipment (132.12; 513.1)
• Security of fixing (134.1.1)
• Condition of insulation of live parts (416.1)
• Adequacy/security of barriers (416.2)
• Condition of enclosure(s) in terms of fire rating etc (; 421 .1.6; 421.1.201 ; 526.5)
• Enclosure not damaged/deteriorated so as to impair safety (651.2)
• Presence and effectiveness of obstacles (417.2)
• Components are suitable according to manufacturers' assembly instructions or
literature (536.4.203)
• Presence of main switches), linked where required (462.1; 462.1.201; 462.2)
• Operation o f main switches) (functional check) (643.10)
• Manual operation of circuit-breakers, RCDs and AFDDsto prove functionality (643.10)
• Confirmation that integral test button/switch causes RCD(s) to trip when
operated (functional check) (643.10)
• RCD(s) provided for fault protection, where specified (411.4.204; 411.5.2; 531.2)
• RCD(s) provided for additional protection, where specified (411.3.3; 415.1)
• Confirmation overvoltage protection (SPDs) provided where specified
(534.4.1.1)
• Presence of RCD six-monthly test notice where required (514.12.2)
• Presence of diagrams, charts or schedules at or near equipment, where
required (514.9.1)
• Presence of alternative supply warning notice, where required (514.15)
Labels for multiple supplies should b e provided at:
1 The origin
2 The meter position, if remote f r o m origin
3 The distribution board to which the alternative/additional sources are
connected
4 All points of isolation of ALL sources of supply
• Presence of next inspection recommendation label (514.12.1)
• Presence of other required labelling (Section 514)
• Selection of protective device(s) and base(s); correct t y p e and rating (411.3.2;
411.4,.5, .6; Sections 432, 433, 434)
• Single-pole protective devices in line conductors only (132.14.1, 530.3.2; 643.6)
• Protection against mechanical damage where cables enter equipment
(522.8.1; 522.8.5; 522.8.11)
• Protection against electromagnetic effects where cables enter ferromagnetic
enclosures (521.5.1)
Confirmation that ALL conductor connections, including connections to busbars, are
correctly located in terminals and are tight and secure (526.1)
The use of individual components in a distribution board or consumer unit
assembly complying with their respective product standard(s) does not indicate
their compatibility when installed with other components in an LV switchgear and
controlgear assembly.
651.1 The periodic testing is supplementary to the inspection of the installation: see Section 3.8.1.
The same range and level of testing as for initial testing is not necessarily required, or
indeed possible, installations that have been previously tested and for which there are
comprehensive records of test results may not need the same degree of testing as
installations for which n o such records exist.
651.5 Periodic testing may cause danger if t h e correct procedures are not applied. Persons
carrying out periodic testing must b e competent in the use of t h e instruments
employed and have adequate knowledge and experience of the t y p e of installation
(see Section 3.8.1).
The inspector will n e e d t o set a sample size for testing. Notes o n the principle of this
are included in Section 3.8.3, which should b e studied together with the guidance o n
suggested tests in Table 3.4.
651.2 The tests considered appropriate by t h e person carrying out the inspection should
b e carried out in accordance with t h e recommendations in Table 3.4 a n d considering
Section 3.8.1 to 3.8.3 of this Guidance Note.
See Section 2.6 of this Guidance Note for test methods, noting that alternative methods
m a y b e used, provided they give reliable results.
Functional tests
Notes:
1 The person carrying out t h e testing should decide which of the above tests are appropriate
by using their experience and knowledge of t h e installation being inspected and tested and
by consulting any available records (see Section 3.8.3 of this Guidance Note).
2 Where sampling is applied, t h e percentage u s e d is at t h e discretion of t h e inspector
(see Section 3.8.3 of this Guidance Note). A percentage of less t h a n 1 0 7o, or sampling
i n installations w i t h a sample population of less than 1 0 0 items of electrical equipment,
is inadvisable.
3 T h e tests n e e d n o t b e carried o u t i n t h e order s h o w n i n t h e table.
4 T h e EFLI test m a y b e used to confirm t h e continuity o f protective conductors at
socket-outlets and, w h e r e it is safe to d o so, at accessible exposed-conductive-parts of
current-using e q u i p m e n t a n d accessories.
5 Generally, accessibility m a y b e considered t o b e within 3 m f r o m t h e floor or f r o m
w h e r e a person can stand.
6 Where t h e circuit includes SPDs or other electronic devices that require a connection
to earth for functional purposes, these devices will require disconnecting t o avoid
influencing t h e test result and t o prevent t h e m being damaged.
7 Where an installation is fully loaded and the conductors are at their normal operating
temperatures, measured loop impedance values can b e directly compared with the
maximum values of EFLI set out in the tables in Chapter 41 of the Regulations. Loop
impedance data for unloaded conductors at 20 °C can b e found in t h e lET's On-Site Guide.
W h e r e it i s not p r a c t i c a b l e t o i s o l a t e a n e l e c t r i c a l i n s t a l l a t i o n f r o m t h e s u p p l y a t t h e
t i m e of t h e i n s p e c t i o n a n d t e s t i n g w o r k s , t h e p r o t e c t i v e e a r t h i n g o r b o n d i n g c o n d u c t o r s
s h o u l d not b e d i s c o n n e c t e d as, u n d e r f a u l t c o n d i t i o n s , t h e e x p o s e d - c o n d u c t i v e - p a r t s
a n d e x t r a n e o u s - c o n d u c t i v e - p a r t s c o u l d b e r a i s e d to a d a n g e r o u s v o l t a g e relative to
Earth potential. In addition, the measurement of EFLI at various parts of the installation is, for
practical reasons, carried out with the protective earthing a n d bonding conductors connected.
Motor circuits
L o o p i m p e d a n c e tests o n m o t o r circuits c a n o n l y b e c a r r i e d o u t o n t h e s u p p l y s i d e of
isolated m o t o r controlgear. A continuity t e s t b e t w e e n t h e circuit protective c o n d u c t o r
(cpc) a n d the m o t o r i s t h e n n e c e s s a r y .
b Insulation resistance
I n s u l a t i o n r e s i s t a n c e tests s h o u l d b e m a d e o n electrically isolated circuits w i t h a n y
e l e c t r o n i c e q u i p m e n t t h a t might b e d a m a g e d by a p p l i c a t i o n of t h e test voltage
disconnected, o r o n l y a m e a s u r e m e n t t o protective earth m a d e , w i t h t h e live conductors
c o n n e c t e d together. It i s a d v i s e d to d i s c o n n e c t f u n c t i o n a l e a r t h c o n n e c t i o n s to
r e s i d u a l c u r r e n t d e v i c e s (RCDs) a n d r e s i d u a l c u r r e n t circuit-breakers (with overcurrent
protection) (RCBOs) w h e n c a r r y i n g o u t i n s u l a t i o n r e s i s t a n c e tests, as it m a y o t h e r w i s e
i n f l u e n c e t h e results.
Test Recommendations
Continuity of Where there are records of previous tests, this test may not b e
ring final circuit necessary unless there m a y have been changes m a d e to the ring final
conductors circuit
Functional tests
Notes:
1 The person carrying out the testing should decide which of the above tests are appropriate
by using their experience and knowledge of t h e installation being inspected and tested and
by consulting any available records (see Section 3.8.3 of this Guidance Note).
2 Where sampling is applied, t h e percentage used is at t h e discretion of t h e inspector
(see Section 3.8.3 of this Guidance Note). A percentage of less than 10 7o, or sampling
in installations w i t h a sample population of less than 1 0 0 items of electrical equipment,
is inadvisable.
3 The tests n e e d n o t b e carried o u t i n t h e order s h o w n i n t h e table.
4 The EFLI test m a y b e used t o c o n f i r m t h e continuity of protective conductors at
socket-outlets and, where i t is safe t o d o so, at accessible exposed-conductive-parts o f
current-using e q u i p m e n t a n d accessories.
5 Generally, accessibility m a y b e considered to b e within 3 m f r o m t h e floor o r f r o m
w h e r e a person can stand.
6 Where t h e circuit includes SPDs o r other electronic devices that require a connection
to earth for functional purposes, these devices will require disconnecting t o avoid
influencing t h e test result a n d to prevent t h e m b e i n g damaged.
7 Where an installation is fully loaded and t h e conductors are at their normal operating
temperatures, measured loop impedance values can b e directly compared with t h e
maximum values of EFLI set out in t h e tables in Chapter 41 of the Regulations. Loop
impedance data for unloaded conductors at 20 °C can b e found in the lET's On-Site Guide.
Motor circuits
Loop impedance tests o n motor circuits can only b e carried o u t o n the supply side of
isolated motor controlgear. A continuity test between t h e circuit protective conductor
(cpc) and the motor is t h e n necessary.
b Insulation resistance
Insulation resistance tests should b e m a d e o n electrically isolated circuits with any
electronic equipment that might b e damaged by application of the test voltage
disconnected, or only a measurementto protective earth made, with t h e live conductors
connected together. It is advised to disconnect functional earth connections to
residual current devices (RCDs) and residual current circuit-breakers (with overcurrent
protection) (RCBOs) w h e n carrying out insulation resistance tests, as it may otherwise
influence t h e results.
643.3 For most installations, t h e most practical test is an insulation resistance test between
live conductors (connected together) and earth; i n practice, t i m e does not usually
allow for a line to neutral test. Where equipment is installed that may be susceptible
to damage by a 5 0 0 V DC test voltage, such as electronic control and monitoring
devices, Regulation 643.3 states that t h e test should b e conducted with a test voltage
of 2 5 0 V DC.
The results of insulation testing should b e compared with previous results, where
possible. Table 2.8 of this Guidance Note (Table 6 4 of BS7671) requires a minimum
insulation resistance of 1 M Q , but strictly speaking, this value applies only to initial
verification. It can, however, be used as a guide for periodic testing. Such low insulation
resistancereadingsmay indicate that there isa problem with an item of electrical equipment,
and where possible past records should be reviewed to identify historical readings to
determine if there has been a sudden, or gradual, decrease, from previous tests.
Where equipment is disconnected for these tests and the equipment has exposed-
conductive-parts required by t h e Regulations to b e connected to protective conductors,
the insulation resistance between t h e exposed-conductive-parts and all live parts of the
equipment should b e measured separately and ought to comply with the requirements
of the appropriate British Standard for t h e equipment.
There is a range of possible outcomes when carrying out insulation testing. Tests are
typically made between all live conductors connected together and Earth at a test
voltage of 5 0 0 V DC.
The inspector will need to measure the values of insulation resistance for a given
distribution board and then take a view based o n their engineering judgement as to
whether the results obtained are acceptable. It should b e noted that distribution boards
with large numbers of final circuits will generally give a lower insulation resistance value
than distribution boards with fewer final circuits.
c Polarity
It should b e established whether there have been any additions or alterations to the
installation since its last inspection. If no additions or alterations have been made, the
polarity test may n o t b e necessary.
If there is doubt about the integrity of the automatic mechanism for circuit-breakers of
t h e sealed type, designed n o t to b e maintained, it will normally b e m o r e practicable to
replace the device than to make further tests. Such doubt may arisefrom visual inspection,
if the device appears to have suffered damage or undue deterioration, or where there is
evidence that the device may have failed t o operate satisfactorily in service.
Circuit-breakers with the facility for injection testing may b e so tested and, if appropriate,
their relay settings confirmed.
It should b e verified by inspection that easy access to such devices is maintained and
that effective operation is not impaired by any material placed near the device. Access
and operation areas may b e required to b e marked to ensure they are kept clear.
For isolating devices in which the position of the contacts o r other means of isolation is
externally visible, visual inspection of operation is sufficient and n o testing is required.
Where it is a requirement that the device interrupts all t h e supply conductors, the
use of a proprietary test lamp, or two-pole voltage detector connected between each
line and t h e neutral on the load side of the switching device, is essential to confirm
isolation. Reliance should not b e placed o n a simple observation that the equipment
controlled has ceased to operate.
Where switching devices are provided with detachable or lockable handles in accordance
with the Regulations, a check should b e made to verify that the handles or keys are n o t
interchangeable with any others available within the premises.
Where switching devices are provided for isolation or for mechanical maintenance
switching, the integrity of the means provided to prevent any equipment from being
unintentionally or inadvertently energized or reactivated m u s t b e verified.
f Operation of RCDs
643.7 Fault protection
Where an RCD is provided for fault protection, t h e operating time should generally b e
n o greater than those stated in Table 41.1 (Regulation 411.4.5) for final circuits and 5 s
for distribution circuits, unless supplementary bonding has been applied in accordance
with Regulation 419.3.
Additional protection
643.8 Where an RCD with a rated residual operating current n o t exceeding 3 0 m A is used t o
provide additional protection in t h e event of failure of basic protection and/or failure of
t h e provision for fault protection or carelessness by users, t h e effectiveness is d e e m e d
to have b e e n verified where an RCD meeting t h e requirements of Regulation 415.1.1
disconnects within 3 0 0 ms w h e n tested at a current equal to or higher than its rated
residual operating current (lAn).
and
Schedule of Circuit Details and Schedule of Test Results (one or more)
On completion of periodic inspection and testing, the EICR and its accompanying
schedules must b e given to the client or person who ordered the inspection.
In all cases, t h e inspection should b e carried o u t against the current edition of BS7671 .
It is likely that there will b e items that d o not comply with that edition, but this does
n o t necessarily m e a n that t h e installation is unsafe. If the inspector considers that an
item, although not warranting code C l or C2, requires improvement, it should b e given
code C3 o n the EICR. If the item does not require improvement, it may b e recorded
as an observation but it does not warrant a classification code.
The series of standards to which electrical test equipment for verification of measures
for protection against electric shock is BS EN 61557 Electrical safety in low voltage
distribution systems up to 1000 1/ a.c. and 1500 1/ d.c. Equipment for testing,
measuring or monitoring of protective measures. This standard includes performance
requirements and requires compliance with BS EN 61010.
In Section 1.1 of this Guidance Note, reference was made to the use of test leads
conforming to HSEGS38. The HSE always advise only to carry out live tests that are
actually useful and informative, so as to minimize danger; the inspector should always
consider whether any particular live test is necessary before undertaking it. The safety
measures and procedures set o u t in GS38 should b e observed for all instruments,
leads, probes and accessories. Some test instrument manufacturers advise that
their instruments are used in conjunction with fused test leads a n d probes. Other
manufacturers advise the use of non-fused leads and probes where t h e instrument
has in-built electrical protection, but it should b e noted that such electrical protection
does not extend to the probes and leads.
Where unsure, a risk assessment should b e carried out to establish if fused test leads
should b e used.
It should not b e assumed that the accuracy of the reading taken in normal field use
will b e as good as the basic accuracy. The ’operating accuracy’ is always worse than
the basic accuracy, and additional errors derive from three sources:
Instruments should also b e subjected t o regular checks before use so that errors
caused by deterioration of leads, probes, connectors, etc. d o n o t result in inaccurate
readings being recorded when, for example, Schedules of Test Results are compiled.
The instrument used for low-resistance tests may b e either a specialized low-resistance
ohmmeter or t h e continuity range of an insulation and continuity tester. The test current
may b e DC or AC. It is recommended that it b e derived f r o m a source with no-load
voltage between 4 V and 24 V and a short-circuit current of not less than 200 m A .
The measuring range should cover the span 0.2 Q to 2 Q , with a resolution of at least
0.01 Q for digital instruments.
Whilst contact resistance cannot b e eliminated with two-terminal testers, and can
introduce errors, the effects of lead resistance can b e eliminated by measuring this
prior to a test and subtracting t h e resistance f r o m t h e final value, or by using t h e test
instrument's 'nulling' feature built in to most m o d e r n instruments. Interference from
an external AC source (interference pick-up) cannot b e eliminated, although it may
b e indicated by vibration of the pointer of an analogue instrument or by an unstable
digital readout. Thermocouple effects can b e eliminated by reversing the test probes
and averaging the resistance readings taken in each direction.
Table 64 (a) 2 5 0 V DC for SELVand PELV circuits with equipment such as SPDs that may
influence test results or b e damaged - but the insulation resistance is to b e at
least 1 M Q (643.3.2);
(b) 5 0 0 V DC for all circuits rated u p to and including 5 0 0 V, except SELVand PELV
circuits; and
(c) 1,000 V DC for circuits rated above 5 0 0 V and u p to 1,000 V.
Instruments conforming to BSEN 61557-2 will fulfil all the above instrument requirements.
When an insulation resistance test is applied to a test subject, the measurement may
b e influenced by different circuit characteristics, for example:
These factors can b e reduced or eliminated by extending the test time for which
the test voltage is applied, and can be seen as a steady insulation reading on the
instrument, after a n initial rapid increase in value.
Test currents higher than 15 A risk tripping some low current miniature circuit-breakers (MCBs).
Safety
To m i n i m i z e e l e c t r i c s h o c k h a z a r d f r o m t h e p o t e n t i a l o f t h e p r o t e c t i v e c o n d u c t o r
d u r i n g L-E i m p e d a n c e tests, t h e test d u r a t i o n s h o u l d b e w i t h i n safe l i m i t s . For
two-wire high current tests, the instrument should cut off the test current after 40 ms
or a time determined by the s a f e t y limits derived f r o m the information contained within
B S I E C 60479-1 Effects of current on human beings and livestock. General aspects,
i f t h e voltage rise o f t h e p r o t e c t i v e c o n d u c t o r e x c e e d s 5 0 V d u r i n g the t e s t . O n s o m e
installations, t h i s t h r e s h o l d m a y b e 2 5 V , e s p e c i a l l y w h e r e l i v e s t o c k a r e p r e s e n t .
For low current (non-trip) tests, the instrument must monitor the e a r t h voltage and
disconnect the test if the e a r t h voltage is exceeded.
Sources o f error
T h e l o w e r t h e l o a d c u r r e n t e m p l o y e d i n t h e test, t h e m o r e v a r i a t i o n a n d e r r o r i s likely
i n t h e result, as t h e voltage drop i s p r o p o r t i o n a l l y lower. D i s t o r t i o n o r n o i s e o n the
supply will a l s o c o m p r o m i s e accuracy a n d repeatability, a s the instrument c a n n o t easily
differentiate between a voltage drop created by the applied l o a d o r a voltage change
i n d u c e d by n o i s e o r h a r m o n i c s , etc. For this r e a s o n , the test with t h e higher load
currents should always b e u s e d w h e r e possible.
RCD u p l i f t
RCD uplift can b e avoided by choosing an instrument that declares immunity to this
effect. Alternatively, if uplift is suspected, measuring o n the source and load sides
of the RCD will identify any additional impedance within the RCD. This can then be
deleted f r o m the measurement.
This phenomenon is not encountered with high test currents, but these tests will trip
the RCD during the test, preventing their use.
Transformer impedances can also affect results, as the impedance close to source can
b e very reactive, rather than resistive. This is only a real issue when measuring close
to the source transformer, but the instrument resolution and accuracy becomes very
significant in this location.
Test l e a d errors
As with t h e low resistance ohmmeter section earlier, t h e test lead resistance can b e
’nulled' or may already b e accounted for in the instrument. If not, the lead resistance
should b e measured and deducted f r o m future measurement values.
Fused leads can add significantly to lead resistance. A 5 0 0 mA fuse can add as much
as 1.8 Q in a test lead pair. If fused leads are used for loop impedance testing, they
will need to b e fused with higher rating fuses, typically 7 A or 10 A fuses, t o prevent
the test current rupturing the fuse.
The resolution of a n instrument is the smallest increment that the instrument can
detect and display. This is usually measured in terms of the multiples of the least
significant (right-most) digit of t h e instrument display. Instrument resolution can
compromise measurement accuracy, especially at the lower loop impedances found
near t h e source transformer. When measuring loop impedances below 0.1 Q, caution
should b e exercised in the interpretation of the results, as the instrument accuracy
significantly affects measurement values close to t h e lowest end of the range.
These instruments may also offer additional facilities for deriving prospective fault
current. The basic measuring principle is the same as for EFLI testers. The current
is calculated by dividing the loop impedance value into the nominal mains voltage.
Instrument accuracy is determined by the same factors as for EFLI testers. In this case,
instrument accuracy decreases as scale reading increases, because the loop value is
divided into the mains voltage. It is important to note these aspects and to consult the
manufacturer's documentation.
(a) test method E l , using a dedicated earth electrode tester (fall of potential,
three- or four-terminal type);
(b) test m e t h o d E2, using a dedicated earth electrode tester (stakeless o r
clamp-type); and
(c) test m e t h o d E3, using an EFLItester.
Test method E2 is more accurate if there are a number of earth electrodes. The
method the stakeless or probe tester cannot b e used to measure the resistance of a
single earth electrode unless there is at least one other earth electrode connected,
which may b e formed from extraneous-conductive-parts or, in TN systems, the means
of earthing of the supply.
RCDs are tested by applying a test load to t h e RCD, inducing a calibrated test current
to flow in t h e L-E circuit. This creates a n imbalance in t h e L-N currents in t h e RCD and
the device trips. The t i m e it takes to trip is then displayed.
The test instrument should b e capable of applying the full range of test current to an
in-service accuracy as given in BS EN 61557-6. This in-service reading accuracy will
include the effects of voltage variations around the nominal voltage of the tester.
As with loop impedance testing, the Earth voltage is monitored and prevented f r o m
exceeding the touch voltage limit, either 5 0 V or 2 5 V, depending o n t h e requirements
of t h e location.
I n s t r u m e n t s c o n f o r m i n g t o B S E N 6 1 5 5 7 - 6 w i l l f u l f i l the a b o v e r e q u i r e m e n t s .
However, asthe size and complexity of an installation increases, isolation f r o m the supply
becomes increasingly difficult. This is particularly true where continuity of supply has
health implications, as may b e the case in hospitals and similar premises, or financial
implications, as would b e the case in banks, share-dealing and commodities markets,
and t h e like. Nevertheless, i t remains necessary to confirm the continuing suitability
of such installations for use. Therefore, they must still b e subjected to planned and
preventative maintenance or regular periodic assessment of their condition.
Some defects, however, cannot b e discovered by visual inspection alone. For example,
incorrectly tightened connections can result in a high resistance joint, which can t h e n
cause a high temperature to occur locally to t h e connection. If left uncorrected over
time, further deterioration of t h e connection may well occur, leading to a continuing
increase in temperature, which may subsequently present a risk of fire. This fire
risk will b e significantly increased in installations where a build-up of dust or other
flammable materials can occur in close proximity to the source of heat. It should
also b e remembered that increased heat at terminations can result in accelerated
deterioration of the insulation locally. Heating effects symptomatic of a fault or other
problem within an electrical installation can also occur as a result of cyclical-load
operations, use of conductors of inadequate current-carrying capacity, incorrect load
balancing and more mechanically related issues, such as incorrect alignment of motor
drive couplings and overtightened belt-drives.
The amount of radiated energy detected can b e presented in a readily usable form,
typically being shown as differences in colour that vary with the temperature being
detected. Figure 4.1 shows a colour/temperature correlation indicator such as those
that may accompany images. Such scales will aid the person ordering t h e inspection
or responsible for maintenance activities in their interpretation of t h e thermal images.
m-|J
MOO'
1200'
icoo-
The section also contains some notes on completion of the forms, although helpful
information on this will also b e gained by reading earlier sections of this Guidance Note.
(b) Form 2: Schedule of Inspections for domestic and similar premises with u p to
100 A supply, or a more extensive schedule where necessary (see below).
(c) Form 3: generic Schedule of Test Results.
642.3 Form 2 is not suitable for the inspection of installations rated at more than 100 A
or that are more complex. For such installations, t h e inspector will probably need to
formulate their own inspection schedules. These should b e based o n the requirements
of Regulation 642.3 and t h e list of examples of items requiring inspection during initial
verification, given i n Appendix 6 of BS 7671.
The MEIWC (Form 4) is included here, taken from Appendix 6 of BS7671. Notes o n
completion and guidance for recipients are provided with the form.
For periodic inspections, the Schedule of Inspections for initial verification (Form 2)
should not b e used. The dedicated model suggested in BS7671 (Form 6) may b e used
for inspections of domestic installations a n d installations up to 1 0 0 A. For larger and
m o r e complex installations, t h e inspector will need to formulate bespoke inspection
schedules. These should be based on the requirements of Regulation 642.3 and t h e
list of examples of items requiring inspection for an EICRwhich are applicable, given
in Appendix 6 of BS7671.
INSTALLATION ADDRESS , , .x , _ _ , x _ , „ . _
Un/t 3 , The Quadrant, Sovnetown Business
.......................................Park, .Sawetawn..SL1.QZZ.......................................................................
Details of permitted exceptions (Regulation 41 1.3.3). Where applicable, a suitable risk assessment(s) must be attached to this Certificate.
The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.
For the DESIGN of the installation: **(Where there is mutual responsibility for the design)
Signature: ...... ............ Date: 7/C?7/ >22Name (IN BLOCK LETTERS): ...... P. ............................ Designer No 1
Signature: .................................. Date: ............... Name (IN BLOCK LETTERS): .................................................. Designer No 2**
FOR CONSTRUCTION
I, being the person responsible for the construction of the electrical installation (as indicated by my signature below), particulars of
which are described above, having exercised reasonable skill and care when carrying out the construction hereby CERTIFY that the
construction work for which I have been responsible is to the best of my knowledge and belief in accordance with BS 7671:2018,
amended to P. -.(date) except for the departures, if any, detailed as follows:
Signature: .......... Date: .P.7/. 2 Name (IN BLOCK LETTERS): .......P.kLNNETH..................... Constructor
FOR INSPECTION & TESTING
I, being the person responsible for the inspection & testing of the electrical installation (as indicated by my signature below), particulars
of which are described above, having exercised reasonable skill and care when carrying out the inspection & testing hereby CERTIFY
that the work for which I have been responsible is to the best of my knowledge and belief in accordance with BS 7671:2018,
amended to2Z?.2r£.(date) except for the departures, if any, detailed as follows:
Certificate No.:
PARTICULARS OF SIGNATORIES TO THE ELECTRICAL INSTALLATION CERTIFICATE
Designer (No 1) Name; P JpnfcS Company:
Schedule of Inspections
Item Description Outcome Item Description Outcome
1
No. Z / N/A No. Z/n/A
8.0 Circuits (Distribution and Final)
1.0 Condition of consumer's intake equipment
' z z
(Visual inspection only) 1 9.0 Isolation and switching
2.0 Parallel or switched alternative
sources of supply
N/A 10.0 Current-us equipment
(permanently connected)
z
3.0 Protect! measure:
Automatic Disconnection of Supply (ADS)
Z 11.0 Identification and notices z
4.0 Bas protection z 12.0 Location(s) containing a bath or shower N/A
5.0 ___ Protective measures other than ADS __________ z 13.0 Other special installations or locations N/A
6.0 Addition protection z 14.0 Prosumer's low voltage electrical
N/A
7.0 Distributi equipment z installation(s)
COMMENTS ON EXISTING INSTALLATION (in the case of an addition or alteration see Regulation 644.1 .2):
...None................................................................................................................................................................
SCHEDULES
This Certificate is valid only when. .Schedules of Circuit Details and Test Results are attached.
(Enter quantities of schedules attached).
T h i s s a f e t y C e r t i f i c a t e h a s b e e n i s s u e d t o c o n f i r m t h a t t h e e l e c t r i c a l installation w o r k t o
which it relates h a s been designed, constructed, inspected and tested in a c c o r d a n c e
with BS 7671.
Y o u s h o u l d h a v e r e c e i v e d a n 'original' C e r t i f i c a t e a n d t h e p e r s o n t h a t i s s u e d t h e
Certificate should have r e t a i n e d a duplicate. If you were the person ordering the work,
but not the o w n e r of the installation, you should p a s s this Certificate, o r a f u l l copy of
it i n c l u d i n g the s c h e d u l e s , immediately to t h e owner.
This Certificate is only valid if the Schedule of Inspections has been completed to
confirm that all relevant inspections have been carried out and where accompanied
by Schedule(s) of Circuit Details a n d Test Results.
Where the installation includes a residual current device (RCD) it should b e tested
six-monthly by pressing the button marked T or 'Test'. The device should switch off
the supply and should then be switched on to restore the supply. If the device does
not switch off the supply when the button is pressed, seek expert advice. For safety
reasons it is important that this instruction is followed.
Where the installation includes an arc fault detection device (AFDD) having a manual
test facility it should b e tested six-monthly by pressing the test button. Where a n AFDD
has both a test button and automatic test function, manufacturer's instructions shall
b e followed with respect to test button operation. Where the installation includes a
surge protection device (SPD)the status indicator should b e checked to confirm it is in
operational condition i n accordance with manufacturer's information. If t h e indication
shows that t h e device is not operational, seek expert advice. For safety reasons it is
important that this instruction is followed.
DB reference: Consumer Location: Under stairs cupboard Supplied from: Supply meter
Unit
Distribution circuit OCPD: BS (EN): 1361 _________ Type: H Rating/Setting: 80 A
t
SPD Details: Type(s)*: T1 T2 gf T3 D N/AD
CIRCUIT DETAILS
Conductor details Overcurrent protective device RCD
Type of wiring
______
Live (mm2)
Rating (A)
Rating (A)
Circuit description
cpc (mm 2)
(N3) sa
(Viu) "’i
BS (EN)
(D
Type
ID
o>
cn
w
IS
?
00
2 14
-
1 Ring - downstairs socket- outlets A 102.# IO 2X2.5 1.5 61001 B 32 6 1.37 61001 A 30 32
2 Ring - upstairs socket- outlets A 102# 8 2X2.5 1.5 61001 B 32 6 1.37 61001 A 39 32
3 Ring - kitchen socket- outlets A 102# 8 2x2.5 1.5 61001 B 32 6 1.37 61001 A 39 32
4 Cooker - kitchen A A 1 2x6.0 2.5 61001 B 32 6 1.37 61001 A 39 32
5* Lights - upstairs A 1O1# 7 2X1.0 1.0 61001 B 6 6 7.28 61001 A 50 6
© The Institution of Engineering and Technology
8 SPARE - - - - - - - - - - - - -
Thermoplastic insulated/ Thermoplastic cables in Thermoplastic cables in Thermoplastic cables in Other - please state
Thermoplastic cables i n
Thermoplastic SWA cables Thermosetting SWA cables Mineral insulated cables
s h e a t h e d cables metallic conduit non-metallic conduit metallic trunking non-metaliic trunking
* SPDType. Where a combined T1 + T2 orT2 + T3 device is installed, indicate by ticking both Type boxes.
t Where a T3 SPD is installed to protect sensitive equipment, enter details in Remarks’, column 31 , of the Schedule of Test Results. (See Section 534 of BS 7671;2018+A2:2022.)
155
1 The circuit number as marked o n the distribution board or consumer unit. The
normal convention for single-phase distribution boards and consumer units,
circuit 1 is closest to t h e main isolator of the assembly. For single-phase circuits
in three-phase installations, it is preferred to use the designation L I , L2, L3.
For example, for single-phase circuits in the fifth compartment, the designation
would b e 5L1, 5L2 and 5L3.
2 Brief description of t h e circuit.
3 The type of wiring is identified by a code, following the convention at t h e
b o t t o m of t h e form.
4 The reference method is identified according to Table 4 A 2 in Appendix 4 of
BS 7671.
5 The number of points served is the total number of accessories or other
connection points for current-using or generating equipment. A double or triple
socket-outlet to BS 1363-2 is usually considered to b e a single point.
6 Number and size of live conductors. Where the conductors are not copper,
this should also b e identified using the chemical symbol in this column. For
example:
• 2x1.5 indicates two copper live conductors with cross-sectional area 1.5 m m 2 ;
• 4 x 1 6 Al indicates four aluminium live conductors with cross-sectional area
1 6 m m 2.
7 Number and size of cpc. Where the conductors are not copper, this should also
b e identified using the chemical symbol in this column.
8 Number of the standard for the overcurrent protective device, for example:
• ’ 6 0 8 9 8 ' for an MCB to BS EN 60898;
• ' 3 0 3 6 ' for a re-wireable fuse BS 3 0 3 6 .
9 Type of overcurrent protective device, where applicable. For example, B, C or D
for MCBs and RCBOsto BS EN 6 0 8 9 8 or BS EN 61009.
10 Rated operating current l n of the overcurrent protective device.
11 Rated breaking capacity o f t h e overcurrent protective device.
12 Maximum permitted earth fault loop impedance Z s of the circuit for automatic
disconnection of supply. These figures are usually obtained f r o m Tables 41.1 to
41.6 in BS 7671 (see Appendix A). Where table 41.5 of BS 7671 applies for
TT systems served by a public supply, an earth fault loop impedance exceeding
2 2 5 Q is unlikely to b e acceptable, as this implies the earth electrode resistance
is unlikely to b e stable as indicated in the Note to Table 41.5 of BS 7671.
13 Number of the standard for the RCD protecting the circuit (if any), for example
'610009' for an RCBO to BS EN 61009.
14 Type of t h e RCD protecting t h e circuit (if any), either 'AC','A’,'F' or 'B'.
15 Residual current rating of the RCD protecting the circuit (if any).
16 Maximum operating current of t h e RCD protecting the circuit (if any).
Distribution board details Details of test instruments used (serial and/or asset numbers)
Disconnection
r n (neutral)
r, (line) (0)
Polarity#
Q.
0)
CJ1
CO
O>
00
=4
u?
ro
M
LD
w
5
20 22 24 31
o
to
1 0.62 0.62 1.02 0.41 N/A 500 >999 >999 0.71 28 N/A
2 0.62 0.62 1.02 0.41 N/A 500 >999 >999 J 0.71 36 </ N/A
3 0.22 0.22 0.37 0.15 N/A 500 >999 >999 0.44 25 J N/A
4 N/A N/A N/A 0.16 N/A 500 >999 >999 0.46 34 N/A
5 N/A N/A N/A 2.56 N/A 250 N/A >999 J 2.85 29 N/A Circuit S insulation 2.50 V (L+N)-E due to LEO drivers
©
6 N/A N/A N/A 8.20 N/A 500 >999 >999 Y 2.86 33 J N/A High Zs on U/S lighting (circuit 6) found to be due to loose
7 N/A N/A N/A 1.57 N/A 500 >999 >999 J 1.90 31 N/A terminals at the point of connection of additional lighting
g g 8 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A circuitry. With the additional circuitry disconnected } a
§ 8 satisfactory Zs of 2.86 O. was obtained. Conductors remain
damaged and cabling requires replacement.
™ CD
<§•
-I f o
I
<8 Signature: G Date: 1S/O7/ 2.022
CIRCUIT DETAILS
Conductor details Overcurrent protective device RCD
Type of wiring
Live (mm2)
cpc (mm 2)
Rating (A)
Circuit description
(ns) sa
BS (EN)
Type
Type
1
I
U1
QC
00
co
o»
£
co
15 ~~ 16
o
2
* SPD T)pe. Where a combined T1 + T2 or T2 + T3 device is installed, indicate by ticking both Type boxes.
•f Where a T3 SPD is installed to protect sensitive equipment, enter details in ‘Remarks', column 31, of the Schedule of Test Results. (See Section 534 of BS 7671:201 8+A2:2022. )
t See Table 4A2 of Appendix 4 of BS 7671 ;2018+A2:2022.
§ Where the maximum permitted earth fault loop impedance value stated in column 12 is taken from a source other than the tabulated values given in Chapter 41 of BS 7671:201 8+A2:2022, state the source of the data in the appropriate cell for the circuit in the ‘Remarks’, column 31, of the Schedule of Test Results.
Form 3 Generic Schedule of Test Results for part of a three-phase installation
D B reference: .....QBX ............. Z db ____O»3O ______ __________ Q I f ____ 0,8 __ ... _____ kA M ultifu notion: ................. ....... . .Ser 1022305 ..................... ....... .........
Continuity: ................ N/A
Confirmed: Correct polarity |Vf P h a s e sequence [Vf Insulation resistance: N/A
E a r t h fault l o o p impedance: N/A
SPD: Operational status confirmed |Vf N/A
RCD: ..... _ N/A
Earth electrode resistance: ..... ..... N/A
Live - Live ( M Q )
Test voltage (V)
Circuit n u m b e r
vulnerable to d a m a g e w h e n testing
rn (neutral)
r, (line) (0)
of
+ CD
of O
<D
U1
W
NJ
NJ
21 22 26 31
2
o
1 0.00 0.00 0.00 0.00 N/A 250 >999 J 0.30 N/A N/A N/A Insulation 250 V (Ll+L2 L3-t-N)-E: SPDs in circuit *
2L1 0.65 0.65 X.8X 0.61 N/A 500 >999 / 0.91 52 N/A
2.L2. N/A N/A N/A 1.35 N/A 250 N/A >999 Y 1.65 22 N/A Insulation 250 V (L.+N)-E: dawn to dusk sensors
2.L3 N/A N/A N/A 0.54 N/A 500 >999 >999 / O.S4 23 J N/A
3 L 1 N/A N/A N/A 1.02 N/A 250 N/A >999 </ 1.32 N/A N/A N/A Insulation 250 V (L N)-E: PIRs in circuit *
© 3L2 0.67 0.67 1.20 0.62 N/A 500 >999 >999 J 0.92 25 J N/A
3L3 N/A N/A N/A 0.51 N/A 250 N/A >999 / 0.21 N/A N/A N/A Insulation 250 V (L+N)-E: PIRs in circuit
s Institution of Engineering and Technology
Guidance Note 3: Inspection & Testing
3 LX N/A N/A N/A 0.52 N/A 500 >999 >999 0 . 2 2 N/A N/A N/A
3L2 0.51 0.51 1.39 0.42 N/A 500 >999 >999 J 0.72 21 N/A
3L3 N/A N/A N/A 1.15 N/A 500 >999 >999 1.36 N/A N/A N/A
5 N/A N/A N/A 0.42 N/A 500 >999 >999 0.20 34 J N/A
6
NOTES
The following notes relate to the column number in the f o r m (Form 3).
1 . Details of the Client . .&£.&. ............................................. Date minor works completed “3“# 202-2.
2. Installation location/address . 2 kP.YP,. Little. 2A. Y. .............................................................
3. Description of the minor works .lighting points t o .office/b ................................
4. Details of any departures from BS 7671 :2018 as amended to 2022 (date) for the circuit altered or extended
(Regulation 120.3, 133.1.3 and 133.5).
Details of permitted exceptions (Regulation 411.3.3). Where applicable, a suitable risk assessment(s)
must be attached to this Certificate. . , ,m
Risk assessment attached |_|
None.
5. Comments on (including any defects observed in) the existing installation (Regulation 644.1.2):
No protection against overvoltage. Distributor's equipment issue - cut-out ruseholder corner cracked.
Customer- advised ■to ■contact -supplier ..............................................................................................................................
PART 2: Presence and adequacy of installation earthing and bonding arrangements (Regulation 132.16)
2. Earth fault loop impedance at distribution board (Zdb) supplying the final circuit ........ Q
PART 4: Test results for the altered or extended circuit (where relevant and practicable)
Protective conductor continuity: (R R 2)......................................... Q or R 2 .................. <24 ............... Q
Continuity of ring final circuit conductors: L/l ___bt/A. ........... Q N/N ..... .......... Q cpc/cpc ...... bf/A ........ Q
Insulation resistance: Test voltage3Z?<?.V Live - Live Z.9.9.9MQ Live - Earth .>9.9.9... MQ
Polarity satisfactory: 0 Maximum measured earth fault loop impedance: Zs Q
RCD disconnection time at rated residual operating current (l An) .../2-?-4.ms Satisfactory test button operation:
AFDD satisfactory test button operation: NOTE: Not all AFDDs have a test button
SPD functionality confirmed: Q NOTE: Not all SPDs have visible functionality indication
PART 5: Declaration
I certify that the work covered by this certificate does not impair the safety of the existing installation and the work has
been designed, constructed, inspected and tested in accordance with BS 7671:2018 amended to .4<?42..... (date)
and that to the best of my knowledge and belief, at the time of my inspection, complied with BS 7671 except
as detailed in Part 1 above.
Scope
1,2,3 The minor works must be so described that the work that is the subject of
the certification can be readily identified.
4 See Regulations 120.3 and 133.5. No departures are to be expected, except
in the most unusual circumstances. See also Regulation 644.1.
5 Note any defects observed in the existing installation that are not related to
the work being carried out.
Under the "Comments on existing installation ..." heading, only deficiencies that do
not impair the safety of any alteration or addition covered by the Certificate may be
referred to. An example would b e existing main bonding conductors identified by
the colour green only (rather than green-and-yellow) or which have a csa less than
that required by Chapter 54, but which are nevertheless considered adequate by the
designer of the alteration or addition.
Any deficiency liable to impair the safety of the alteration or addition must be corrected
before the alteration or addition is carried out (see Regulation 132.16). It would be
unacceptable simply to refer to the deficiency on the Certificate.
The existing earthing and bonding must be inspected and tested to confirm that it is
adequate for the new works. Any extension to earthing and bonding must be installed
for the works, if required.
Generally, for domestic installations, this is simple: record details of the circuit protective
device and circuit conductors.
The relevant provisions of Part 6 (Inspection and testing) of BS7671 must be applied
in full to all minor works. For example, where a socket-outlet is added to an existing
circuit, it is necessary to:
Part 5 Declaration
When filling out a n d signing a form o n behalf of a company or other business entity,
individuals m u s t state for w h o m they are acting.
This Certificate has been issued to confirm that t h e electrical installation work to which
it relates has been designed, constructed, inspected and tested in accordance with
BS 7671.
You should have received an 'original' Certificate and t h e person that issued the
Certificate should have retained a duplicate. If you were the person ordering the work,
but n o t t h e owner of t h e installation, you should pass this Certificate, or a copy of
it, to the owner. A separate Certificate should have been received for each existing
circuit o n which minor works have been carried out. This Certificate is not appropriate
if you requested the person that issued the Certificate to undertake m o r e extensive
installation work, for which you should have received an EIC.
The Certificate should b e retained in a safe place and b e shown to any person
inspecting or undertaking further work o n the electrical installation in the future. If
you later vacate the property, this Certificate will demonstrate to the n e w owner that
the minor electrical installation work carried out complied with the requirements of
BS7671 at the time t h e Certificate was issued.
For safety reasons, the electrical installation will need to b e inspected at appropriate
intervals by a skilled person or persons, competent in such work.
Where the installation includes a residual current device (RCD) it should b e tested
six-monthly by pressing t h e button marked T or 'Test'. The device should switch off
t h e supply and should then b e switched o n to restore t h e supply. If the device does
not switch off t h e supply w h e n the button is pressed, seek expert advice. For safety
reasons it is important that this instruction is followed.
Where t h e installation includes an arc fault detection device (AFDD) having a manual
test facility it should b e tested six-monthly by pressing the test button. Where a n AFDD
has both a test button and automatic test function, manufacturer's instructions shall b e
followed with respect to test button operation.
Where the installation includes a surge protection device (SPD) the status indicator
should b e checked to confirm it is in operational condition in accordance with
manufacturer's information. If the indication shows that t h e device is n o t operational,
seek expert advice. For safety reasons it is important that this instruction is followed.
Date(s) on which inspection and testing was carried out ....... l.tL August ,2022 ..................................
SECTION C. DETAILS OF THE INSTALLATION WHICH IS THE SUBJECT OF THIS REPORT
Occupier
Address
Description of premises
Residential Ef Commercial Industrial Other (include brief description)
Estimated age of wiring system years
Evidence of additions I alterations? Yes ST No Not apparent If yes, estimate age £ .........years
Installation records available? (Regulation 651.1) Yes □ No |Vf Date of last inspection ....................................... (date) __________
SECTION D. EXTENT AND LIMITATIONS O F INSPECTION AND TESTING
Extent of the electrical installation covered by this report ..Visual .inspeetion..o.f..suprilier!s..ter.nninal..eauipi(nent i ..inspection.
. a n d .test of c p uwier unit
Agreed limitations including the reasons (see Regulation 653.2)
Bu tiding. fabric ,not ,to b e , distu rbed
Agreed with: .....Client ....................... ................. ....... .......... ...................................................... ............................................................ ..........
Operational limitations including the reasons (see page no ) ...None
The inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS 7671:2018
as amended to ...............................
It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or
underground, have not been inspected unless specifically agreed between the client and inspector prior to the inspection. An inspection should be
made within an accessible roof space housing other electrical equipment.
SECTION G. DECLARATION
l/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures
below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and
testing, hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate
assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report.
Inspected and tested by: Report authorised for issue by:
Name (Capitals) ....... fdECEE..TH.QM ................. Name (Capitals) PFF THOMPSON ...........................
Signature Signature
For/on behalf of . . . . T . a n d C , Electrical Forton behalf of T.and.C Electrical. ..................................
Position Prwrfe.r .................................................................. Position Proprietor ................................................................
Address U/hrte/eaf Close, Ne pwn .EA.4 SXX
Address Whiteleaf Close,
Date 14 August iozi
Date
SECTION H. SCHEDULE(S)
.....i Inspection Schedule(s) and Schedule(s) of Circuit Details and Test Results are attached.
The attached schedule(s) are part of this document and this report is valid only when they are attached to it.
Report N o . : ...1342.
Main protective bonding conductors Material .......... csa ........ «?. .......... mm* Connection / continuity verified 0
To water installation pipes 0 To gas installation pipes 0 | To oil installation pipes To structural steel
To lightning protection Toother Specify .................................................................................................................................................
Main switch / Switch -fuse / Circuit-breaker I RCD
Location ........................................................ Current rating ........ 1Q.Q.................. A If RCD main switch
Under-stairs cupboard Fuse / device rating or setting .N/A .A RCD Type .......... ...............................................
BS(EN) ...... 4 7 - 3 ........................... Voltage rating ZZQ .................. V Rated residual operating current (Jap) ...... .C/ZA...... m A
Rated time delay ........ NZA ..................................... ms
No of poles ...... £ ..........................................
Measured operating time ..... ............................. ms
SECTION K. OBSERVATIONS
Referring to the attached inspection schedule(s) and schedule(s) of circuit details and test results, and subject to the limitations specified at the
Extent and limitations of inspection and testing section
No remedial action is required The following observations are made EF (see below):
OBSERVATION(S) Include schedule reference, as appropriate CLASSIFICATION
CODE
1-. . .tP.,lighting, circuit at Junction box.. Arcing ,and, burnt .insulation evident ......................................... Cl
t/‘
Loose connections as above, causing unreliable earthing of circuit and risk of fire.
2. No additional protection bg RCD, or earthed mechanical protection, for cables concealed in walls ....UM
One of the following codes, as appropriate, has been allocated to each of the observations made above to indicate to the person(s) responsible for
the installation the degree of urgency for remedial action.
C1 - Danger present. Risk of injury. Immediate remedial action required
02 - Potentially dangerous - urgent remedial action required
C3 - Improvement recommended
Fl - Further investigation required without delay
1 This Report should only b e used for reporting o n the condition of an existing
electrical installation, and n o t for the replacement of a consumer u n i t /
distribution board. An installation which was designed to an earlier edition of
BS 7671 or the IEE Wiring Regulations and which does not fully comply with
the current edition is not necessarily unsafe for continued use, or requires
upgrading. Only damage, deterioration, defects, dangerous conditions and non-
compliance with the requirements of BS 7 6 7 1 or t h e IEE Wiring Regulations,
which may give rise t o danger, should b e recorded.
2 The Report, normally comprising at least five pages, should include schedules
of both the inspection a n d t h e test results. Additional pages may be necessary
for other than a simple installation a n d for the "Guidance for recipients". The
number of each page should b e indicated, together with the total number of
pages involved.
3 The reason for producing this Report, such as change of occupancy or landlord's
periodic maintenance, should b e identified in Section B.
4 Those elements of the installation that are covered by the Report and those
that are not should b e identified in Section D (Extent and limitations). These
aspects should have b e e n agreed with the person ordering the report and
other interested parties before the inspection and testing commenced. Any
operational limitations, such as inability t o gain access t o parts of the installation
or an item of equipment, should also b e recorded in Section D.
5 The maximum prospective value of fault current (l p f) recorded should b e the
greater of either the prospective value of short-circuit current or the prospective
value of earth fault current.
6 Where a n installation has an alternative source of supply a further schedule of
supply characteristics and earthing arrangements based u p o n Section I of this
Report should b e provided.
7 A summary of the condition of the installation in terms of safety should
b e clearly stated in Section E. Observations, if any, should b e categorized in
Section K using the coding C l to C3 as appropriate. Any observation given
a code C l or C 2 classification should result in the overall condition of t h e
installation being reported as unsatisfactory.
8 Wherever practicable, i t e m s classified as 'Danger p r e s e n t ' ( C l ) should b e
m a d e s a f e o n discovery. Where this is not possible the owner or user should
b e given written notification as a matter of urgency.
9 Where an observation requires further investigation (Fl) because the inspection
has revealed an apparent deficiency which could not, owing to the extent or
limitations of the inspection, b e fully identified and further investigation may
reveal a code C l o r C2 item, this should b e recorded within Section K, given
the code Fl and marked as unsatisfactory in Section E.
10 If the space available for observations in Section K is insufficient, additional
pages should b e provided as necessary.
11 The date by which the next Electrical Installation Condition Report is
recommended should b e given i n Section F. The interval between inspections
should take into account t h e requirements of Regulation 652.1 and the overall
condition of the installation.
12 Any deficiencies with intake equipment should be reported to the person
ordering the work.
ELECTRICAL INSTALLATION C O N D I T I O N R E P O R T
Certificate/Report
£342
Number ....................
CONDITION REPORT INSPECTION SCHEDULE FOR
RESIDENTIAL AND SIMILAR PREMISES WITH UP TO 100 A SUPPLY
Note: This form is suitable for many types of smaller installation, not exclusively residential.
The persons responsible for the periodic inspection of the installation should include the relevant items in relation to the electrical
installation, the inspection schedule can be reduced or expanded depending on the requirements for the installation.
Person ordering word / Duty holder notified (Delete as appropriate) -Yf N/A (Delete a s appropriate)
3.2 Presence a n d condition of earth electrode connection where applicable (542.1.2.3) N/A
3.3 Provision of earthing/bonding l a b e l s at all appropriate locations (514.13.1) J
3.4 Confirmation of earthing conductor size (542.3; 543.1.1) J
3.5 Accessibility a n d condition of earthing conductor at M E T (543.3.2) J
3.6 Confirmation of m a i n protective b o n d i n g conductor sizes (544.1)
4.4 Condition of enclosure(s) in terms of fire rating etc (421.1 .201, 526.5)
4.11 Presence of alternative supply warning notice at or near consumer unit/distribution board (514.15) N/A
4.12 Presence of other required labelling (please specify) (Section 514) N/A
4.13 Compatibility of protective d e v i c e a n d base and other components; correct type and rating. (No
signs of u n a c c e p t a b l e thermal d a m a g e , arcing o r o v e r h e a t i n g ) (536.4.203)
4.15 Protection against mechanical damage where cables enter consumer unit/distribution board (132.14.1;
y
522.8.1; 522.8.5; 522.8.11; 530.3.2)
4.16 Protection against electromagnetic effects where cables enter consumer unit/distribution board/enclosures (521 .5.1)
4.17 RCD(s) provided for fault protection - includes RCBOs (41 1 .4.9; 41 1 .5.2; 5 3 1 .2) N/A
4.18 RCD(s) provided for a d d i t i o n a l protection - i n c l u d e s RCBOs (411 ,3.3; 415.1)
Certificate/Report
1342
Number ....................
Acceptable Unacceptable State Improvement State Further
OUTCOMES Fl Not verified N/V Limitation LIM Not applicable N/A
condition condition C 1 or C 2 recommended C3 investigation
OUTCOME
(Use codes above. Provide additional
ITEM
DESCRIPTION comment where appropriate.
NO C1, C2, C3 and Fl coded items to be recorded
in Section K of the Condition Report)
5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation (Section 523) y'
5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1)
5.7 Adequacy of protective devices: type and rated current for fault protection (41 1 .3)
5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (Section 522)
5.10 Concealed cables installed i n prescribed z o n e s (see Section D. Extent and limitations) (522.6.202)
5.11 C a b l e s concealed under floors, above ceilings o r in walls/partitions, adequately protected against
damage (see Section D. Extent and limitations) (522.6.204)
5.12 Provision of additional protection by R C D n o t exceeding 30 mA:
■ for all socket-outlets of rating 32 A or less, unless an exception is permitted (411.3.3) y'
■ for supply to m o b i l e e q u i p m e n t not exceeding 32 A rating for u s e outdoors ( 4 11 .3.3)
■ for cables concealed in walls at a depth of less than 5 0 m m (522.6.202; 522.6.203) LIM
■ for cables concealed in walls/partitions containing metal parts regardless of depth (522.6.203) N/A
5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527)
5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (Section 526)
5.21 Single-pole switching o r protective devices in line conductors only (132.14.1; 530.3.2)
6.4 Presence of supplementary bonding conductors, unless not required by B S 7671:2008 (701.415.2) y
6.5 Low voltage (e.g. 2 3 0 volt) socket-outlets sited at least 2 . 5 m from z o n e 1 (701.512.3) y
6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701 .512.2)
6.8 Suitability of current-using equipment for particular position within the location (701 .55)
Al Tables
643.7.3 The tables in this appendix provide maximum permissible measured EFLI (Z s) for
411.4.201 compliance with BS 7671, which must not b e exceeded when the tests are carried
411.4.202 out at an ambient temperature of 10 °C. Table A7 provides correction factors for other
411.4.203 ambient temperatures.
411.3.2.2 1 where the circuit concerned is a final circuit not exceeding 32 A for circuits
supplying only fixed equipment, or 6 3 A for circuits with one o r m o r e
socket-outlets, and the maximum disconnection t i m e for compliance with
Regulation 411.3.2.2 is 0.4 s for TN systems; and
411.3.2.3 2 where the circuit concerned is a final circuit exceeding 32 A for circuits
supplying only fixed equipment, or 63 A for circuits with one or m o r e
socket-outlets, or a distribution circuit and the disconnection time for
compliance with Regulation 411.3.2.3 is 5 s for TN systems.
543.1.3 In each table, the EFLI given correspond to t h e appropriate disconnection time f r o m
a comparison of the time/current characteristics of t h e device concerned and t h e
adiabatic equation given in Regulation 543.1.3.
The tabulated values apply only where the nominal voltage to Earth (U o) is 2 3 0 V.
(i) 0.4 s disconnection (final circuits n o t exceeding 32 A for circuits supplying only
fixed equipment, or 63 A for circuits with one or more socket-outlets, in
TN systems)
Protective Fuse rating
conductor (mm 2)
5A 15 A 20 A 30 A
(ii) 5 s disconnection (final circuits exceeding 32 A for circuits supplying only fixed
equipment, or 63 A for circuits with one or more socket-outlets, and
distribution circuits in TN systems)
Note: NP means that the combination of the protective conductor and the fuse is Not
Permitted.
▼ Table A2 BS 88-2 fuses. Maximum measured EFLI (in Q) at ambient temperature where
the OCPD is a fuse to BS 88-2 or BS 8 8 - 6
(i) 0.4 s disconnection (final circuits not exceeding 32 A for circuits supplying only
fixed equipment, or 63 A for circuits with one or more socket-outlets, in
TN systems)
Note: NP means that the combination of the protectivei conductor and the fuse is Not
Permitted.
(i) 0.4 s disconnection (final circuits not exceeding 32 A for circuits supplying only
fixed equipment, or 63 A for circuits with one or more socket-outlets, in
TN systems)
Protective Fuse rating
conductor (mm 2)
5A 16 A 20 A 32 A
1.0 7.94 1.84 1.54 0.6
(ii) 5 s disconnection (final circuits exceeding 32 A for circuits supplying only fixed
equipment, or 63 A for circuits with o n e or more socket-outlets, a n d distribution
circuits in TN systems)
Note: NP means that the combination of the protective conductor and the fuse is Not
Permitted.
(i) 0.4 s disconnection (final circuits n o t exceeding 32 A for circuits supplying only
fixed equipment, or 63 A for circuits with one or more socket-outlets, in
TN systems)
Protective Fuse rating
conductor (mm 2)
5A 15 A 20 A 30 A
1.0 7.95 2.50 1.29 0.77
(ii) 5 s disconnection (final circuits exceeding 32 A for circuits supplying only fixed
equipment, or 63 A for circuits with one or more socket-outlets, and distribution
circuits in TN systems)
Notes:
1 NP means that the combination of the protective conductor and the fuse is Not Permitted.
2 While BS 88-3 has replaced BS 1361, and BS 1361 has been withdrawn, it can
be seen from Table A3 that the maximum measured EFLI for BS 88-3 fuses
cannot be applied to circuits protected by BS 1361 fuses, even of the same
nominal rating. For example, the maximum permitted EFLI for 20 A fuses to
BS 88-3 is far higher than that permitted for a circuit protected by a 20 A fuse to BS 1361.
▼ T a b l e A 5 Circuit-breakers. M a x i m u m m e a s u r e d EFLI ( i n O) at a m b i e n t t e m p e r a t u r e
w h e r e t h e o v e r c u r r e n t d e v i c e is a circuit-breaker to B S 3 8 7 1 o r B S E N 6 0 8 9 8
or RCBOto BS EN 6 1 0 0 9
2 8.4 5.0 4.2 2.5 1.67 1.58 1.25 1.0 0.83 0.79 0.63 0.56 0.5 0.4 0.25
B 11.65 7.0 5.82 3.5 2.33 2.15 1.75 1.4 1.17 1.1 0.87 0.78 0.7 0.55 0.35
3&C 5.82 3.49 2.91 1.75 1.16 1.10 0.87 0.7 0.58 0.54 0.44 0.38 0.35 0.28 0.18
D 5 sec 2.91 1.75 1.09 0.87 0.7 0.55 0.44 0.35 0.28 0.17
Regulation 434.5.2 of BS 7671 :2018 requires that the protective conductor csa meets
t h e requirements of BS EN 60898-1-2 or BS EN 61009-1, or t h e m i n i m u m quoted by
t h e manufacturer. The sizes given in Table A6 are for energy-limiting Class 3, Types B
and C devices only.
For other d e v i c e types and ratings, or higher fault levels, consult m a n u f a c t u r e r ' s data.
S e e Regulation 4 3 4 . 5 . 2 a n d t h e I E T Electrical Installation Design Guide.
Notes:
1 The correction factor is given by: {1 + 0.004 (ambient temp - 20)}/{l + 0.004
(10 - 20)} where 0 . 0 0 4 is t h e simplified resistance coefficient per °C at 20 °C given b y
BS EN 6 0 2 2 8 for b o t h copper a n d aluminium conductors. (Alternatively, t h e correction
factor is given by (ambient temp + 230)/(10 + 230)).
2 The factors are different f r o m those of Table B.2 because Table A7 corrects f r o m 1 0 °C
a n d Table B.2 f r o m 2 0 °C.
A 2 Appendix 3 of B S 7671
Anox 3 Appendix 3 of BS 7671 takes into account t h e increase of the conductor resistance with
increase of temperature due to load current, which may b e used to verify compliance
with t h e requirements of Regulation 41 1.4 for TN systems.
The requirements of Regulation 411 .4.4 are considered met when the measured value
of fault loop impedance satisfies the following equation:
U X min
Zs(nn)=0.8x °j
where:
Zs (m) is the measured impedance of the earth fault current loop up to the most
distant point of the relevant circuit from the origin of the installation (£2)
Uq is the nominal ACrms line voltage to Earth (V)
la is the current in amps (A) causing operation of the protective device
within t h e time stated in Table 41.1 of BS 7671 or within 5 s according to
the conditions stated in Regulation 411.3.2.3.
Cmin isthe minimum voltagefactorto take account of voltagevariationsdepending
o n time and place, change of transformer taps and other considerations.
0.8 is a temperature adjustment factorfor ambient temperature (see Table A7).
Note: For an LV supply given in accordance with t h e ESQCR, C m in 's given t h e value 0.95.
A circuit is wired in flat t w i n and cpc 70 °C thermoplastic (PVC) cable and protected
by a 6 A Type B circuit-breaker to BS EN 60898. When tested at a n ambient
temperature below 20 °C, determine the maximum acceptable measured value of
Z s for the circuit.
Solution:
Ztest ( m a x ) “ Zs
Ztest (max) = 1 , 2 0 X
Ztest (max) = 6 . 0 7 Q
A more accurate value can b e obtained if t h e external EFLI,Ze , is known. I n this case,
the following formula may b e used:
test - Z e + |z (z s Z e)
Ztest (max) = 6 . 1 3 Q
Where the test ambient temperature is likely to b e other than 2 0 °C, a further
correction can b e m a d e to convert t h e value to correspond with the expected ambient
temperature, using the following formula:
Ztest (max) = 2 e + Z e)
Ztest(max)= 0 . 3 5 + (7.28-0.35)
Aest (max) = 5 . 7 8 Q
where:
Note: Cm in is the minimum voltage factor, the meaning of which is explained in Section A2
of this appendix.
In the previous example, taking t h e (Ri + R2) reading for t h e circuit as 0.2 Q :
Z s for t h e circuit at 70 °C
= Ze +F(R 1 + R 2)test
= 0.35+1.20x0.2
= 0.59 Q
The temperature-corrected Z s figure of 0.59 Q is acceptable, as it is less than t h e
maximum value of 7.28 Q given in Table 41.3 of BS 7671.
Ztest = Ze + ( R i + Rz)test
= 0.32+0.2
= 0.55Q
x
Ztest(max) = 1,20 7.28=6.07£2
434.5.2 To check compliance with Regulation 434.5.2 and/or Regulation 543.1.3, i.e. to evaluate
543.1.3 the equation
I2!
S2 = 1,2
Un
0
x
Fault current, I =
where:
Zs = Ze + Ri + R2
where:
Ri is the resistance of the line conductor from the origin of the circuit
to the point of utilization
r2 is the resistance of the protective conductor from the origin of the
circuit to the point of utilization.
Similarly, in order to design circuits for compliance with the limiting values of EFLIgiven
in Tables 41.2 to 41.4 of BS7671, it is necessary to establish the relevant impedances
of the circuit conductors w h e n the line conductor is at t h e appropriate maximum
permitted operating temperature, as given in Table 52.1 of BS7671, and the cpc is at
t h e appropriate 'assumed initial temperature', as given in Tables 54.2 to 54.5.
1* 1 36.20
1.5 — 12.10
1.5* 1 30.20
2.5 — 7.41
2.5 1 25.51
4 — 4.61
4* 1.5 16.71
4 2.5 12.02
4 4 9.22
6 — 3.08
6* 2.5 10.49
6 4 7.69
6 6 6.16
10 — 1.83
10* 4 6.44
10 6 4.91
10 10 3.66
16 — 1.15 1.91
16* 6 4.23 —
16 10 2.98 —
25 — 0.727 1.20
25 10 2.557 —
25 16 1.877 3.11
25 25 1.454 2.40
35 — 0.524 0.87
35 16 1.674 2.78
Note: * identifies copper line/protective conductor combination that complies with Tables
4 and 5 of BS 6004:201 2+A1:2020 for thermoplastic insulated and sheathed cables,
single-core and cpc (UK code 6241Y), twin and cpc (UK code 6242Y) or three-core
and cpc (UK code 6243Y) and similar cable constructions for thermosetting cables
according to Table 5 of BS 7211:2012+AI:2020 (UK codes 6241B, 6242B, 6243B).
1
The correction factor is given by: {1 + 0.004 (ambient temp - 2 0 °C)} where 0.004 is
the simplified resistance coefficient per °C at 20 °C given by BS EN 60228 for copper
and aluminium conductors.
mft/mxL
1000
L= Rxiooo
m&/m
For verification purposes, the designer will need to give t h e values o f the line a n d
cpc resistances a t the ambient temperature expected d u r i n g t h e tests. This m a y b e
different f r o m t h e reference t e m p e r a t u r e of 2 0 ° C u s e d for Table B l . T h e correction
factors in Table B2 m a y b e applied to the Table Bl values to take account of the
a m b i e n t t e m p e r a t u r e (for test p u r p o s e s only).
Table 41.4 conductors and/or cpcs in order to determine compliance with the EFLIof Tables 41.2,
41.3 o r 41.4 of B S 7 6 7 1 .
No,es:
Table 54.2
1 See Table 54.2 of BS 7671. These factors apply when the protective conductor is not
incorporated or bunched with cables, or for separate bare protective conductors in
contact with cable covering but not bunched with cables.
2
Table 54 See Table 54.3 of BS 7671. These factors apply when the protective conductor is a core
in a cable or is bunched with cables.
3 The factors are given by F = 1 + 0.004 {conductor operating temperature - 2 0 °C}
where 0.004 is the simplified resistance coefficient per °C at 20 °C given in BSEN 60228
for copper and aluminium conductors.
4 If cable loading is such that the maximum operating temperature is 70 °C, thermoplastic
(70 °C) factors are appropriate.
Where safe access is available to enclose the live conductors in a current clamp,
but not t h e protective conductor, a suitably rated earth leakage current clamp meter
(sometimes called a tong tester) can b e used to provide an indication of t h e state of
insulation in a circuit downstream of the test point, by measuring 'earth leakage'. An
example is shown i n Figure C l .
▼ Figure Cl Example of the measurement of earth leakage with a current clamp meter
RRTE I
00D4 ISHHhWH
0101
-a-+ssx
Note: The earth leakage current clamp for this test goes around the live conductors only.
Note: Diverted neutral currents may originate from another installation, and so may be
present even if the installation is isolated.
If an open-ciruit PEN conductor or diverted neutral currents are suspected after carrying
out the safety checks, the DNO should b e informed immediately using the emergency
number 105.
Notes:
1 If there is an open-circuit PEN conductor, the line to neutral voltage may rise to 400 V
nominal.
2 One way of measuring earth leakage is to use a leakage current clamp ammeter.
Leakage current clamp meters are similar to those used for measuring load current, but
are more sensitive and therefore more accurate at measuring currents below 5 mA.
▼ Table D I Example of checks for diverted neutral currents or broken PEN conductor in a
dwelling
2. Switch off power to the The test for proving that t h e The installation does
installation, lock-off or installation is dead shows it not appear to b e dead
otherwise secure t h e point(s) is dead. as expected.
of isolation, a n d prove the
installation is dead using an
approved 2-pole contact
voltage tester.
3. Check for current flowing i n The current has dropped to Current continues to
the m a i n earthing conductor zero, or to an extremely small flow i n t h e
a n d m a i n protective bonding level. earthing conductor
conductors of t h e installation and/or main bonding
using a current clamp meter. conductors. Current
measured in t h e
customer
bonding conductors
orpipework can b e
influenced by adding
load to the
customers installation,
using a simple
technique such as
boiling a kettle or
switching a heater on.
i n TN-C-S systems,
Ze < 0 . 3 5 Q
i n TN-S systems,
Z e < 0.80 Q
A
Access 2.5.2 item o
testing 5.4
B
Barriers
Degrees of protection
Emergency lighting
Fire alarms
Switchgear
C
Cables
Certificate, Electrical Installation 1.3.1; 1.4; 1.6; 2.1; 2.2; 2.6.2; 2.6.16;
3.4; 3.8.2; 3.8.3; Section 5
Condition Report, Electrical Installation 1.3.1; 1.3.2; 1.6; 2.6.16; 3.1; 3.8;
3.11:3.12; Section 5
Conductors
resistance Appx B
Continuity
main bonding 2.5.1; Section 5 ; Table 3.4
’all-insulated' installations -
ring final circuit conductors, test method 2.6.4; 2.6.6; Fig 2.2; Fig 2.3
D
Defects 3.7; 3.11; Section 5
E
Earth electrode resistance 2.6.4; 2.6.13; Table 3.4; Fig 2.28;
Fig 2.29; Fig 2.30
PEIs
testers 4.5
verification 2.6.15
Electrical Installation Certificate (EIC) 1.3.1; 1.4; 1.6; 2.1 ; 2.2; 2.6.2;
2.6.16; 3.4; 3.8; Section 5
Electrical separation
source of supply
inspection 2.6.9
F
Fault protection 2.5.2 item h
Forms Section 5
G
General requirements Section 1
H
Health a n d S a f e t y a t W o r k etc. Act
1974 Introduction; 2.3; 3.4
H o u s i n g ( S c o t l a n d ) Act 2 0 1 4 1.3.2
I
I d e n t i f i c a t i o n by c o l o u r 2.5.2 item b
Initial i n s p e c t i o n
schedule Section 5
Initial t e s t i n g 2.6
results, r e c o r d i n g of 2.6.1
f r e q u e n c y of s u b s e q u e n t i n s p e c t i o n 2.4; Table 3 . 2
p u r p o s e of 2.1
scope 2.4
Inverters 2.6.24
J,K, L
L a b e l l i n g and marking 2.5.2 items m, p; 3.9.1
M
Medical locations 1.7; 2.5.2 item h; 2.6; 3.7; Table 3 . 2
M i n o r Electrical I n s t a l l a t i o n W o r k s
C e r t i f i c a t e (MEIWC) 2.2; 5 . 2 ; 5 . 4
N
Non-conducting location 2.6.11
O
Ohmmeters
low-resistance 2.6.5; 2 . 6 . 6 ; 4 . 3
O v e r v o l t a g e s of a t m o s p h e r i c origin o r
d u e to switching 2.6.22
P
PELV 2.5.2 item h; Table 2.9; 2.6.4; 2.6.8;
Table 2.12; Table 2.13; 2.6.10; 3.9.1; 4.4
Periodic inspection
i n s p e c t i o n checklist 3.9.1
p u r p o s e of 3.1
Periodic i n s p e c t i o n a n d testing
forms Section 5
f r e q u e n c y of 3.7;Table 3 . 2
p u r p o s e of 3.1; 3.8.1
Phase s e q u e n c e 2 . 6 . 4 ; 2.6.17
instruments 4.8
verification of 2.6.17
P o w e r c o n v e r s i o n e q u i p m e n t (PCE) 2.6.24
Prosumers e l e c t r i c a l installations
(PEIs) 2.6.24
P r o t e c t i o n by
barriers p r o v i d e d d u r i n g e r e c t i o n 2.6.4
Q,R
Record k e e p i n g 1.6; 2.5.1
Reference tests
test m e t h o d s 1 a n d 2 2.6.5
continuity of r i n g f i n a l circuit
conductors 2.6.6; Fig 2.2; Fig 2.19; Fig 2.20; Table 3.4
insulation
resistance o f f l o o r s a n d w a l l s 2.6.11
s e q u e n c e of 2.6.4
Residual c u r r e n t d e v i c e s (RCDs)
testers 4.7
R e s i s t a n c e of c o n d u c t o r s Appx B
Rule of thumb
Specification Introduction
X,Y, Z
No entries