Network Plateform Software Reference
Network Plateform Software Reference
Network Platform
Network Platform Software Reference Manual
3BUS209544 rev T 1
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
PROPRIETARY DATA
This document contains proprietary data of ABB Inc.
No disclosure, distribution (electronic or otherwise), reproduction,
or other means of dissemination may be made without written permission.
2 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 3
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
4 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 5
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
TABLE OF CONTENTS
3 LICENSES ................................................................................................. 17
3.1 Starting the License Manager Utility ...................................................... 17
6 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
9 SP SERVICE WORKSTATION.................................................................. 85
9.1 Overview ................................................................................................... 85
9.2 License Policy .......................................................................................... 85
9.3 Using the SP Service Workstation Application ...................................... 86
9.4 SP Service Workstation Settings ............................................................ 90
9.5 Saving and Restoring Scanner Configuration........................................ 92
9.6 Adjusting Date/Time Settings on Scanner using SWS .......................... 93
9.7 Using SP Service Work Station via Serial Link (Smart Platform only).. 95
12 APPENDICES ............................................................................................ 99
Appendix A Firewall Configuration ................................................................ 99
Appendix B ABB Actuator Engineering Tool Troubleshooting.................. 100
Appendix C Guide to Changing the password for user QCSApp............... 101
3BUS209544 rev T 7
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
1 Software Overview
Network Platform (NP) software resides in an embedded PC in the ABB Smart Processing Center
(ASPC). All communications and utilities are performed through the Quality Control System
(QCS) LAN. The NP Service Workstation (NP SWS) is the primary tool for interaction with the
NP. Software for the utilities and diagnostics, known as Platform Engineering Tools, are resident
in the SWS Computer.
Platform
Platform Configuration
NP Update Tool
Configuration Tool
Application
Files
Software Platform Data Dictionary
Debug Tool
QCS LAN
Host System
8 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 9
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
10 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Upon first launch, a banner will display at the top of the Access Window. “Enable
Content” must be selected, see Figure 4-3 Scanner Data Dictionary – Enable Content.
3BUS209544 rev T 11
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Figure 2-1 Platform Engineering Tools EULA and Installation Set-Up Screen
4. To proceed with the installation procedure, tick the check box then click the “Next”
button shown above.
12 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
5. The Platform Engineering Tools installer will now carry out a series of Pre-installation
checks to determine if the install will succeed. On the dialog to follow these checks will
be displayed:
a. A warning regarding compatibility issues with OPC Core Components re-
distributables, as detailed in 2.2.1.3 OPC Core Components.
b. Results of the pre-installation checks and a summary of any issues that may be
encountered. For example the text shown in screenshot below.
The default account User Name is “QCSApp” with default Password as “Qcs-Admin”.
3BUS209544 rev T 13
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
If the PC on which the software is being installed is part of a domain then the Host/Domain Name
field will be populated with the domain name by default.
The Host/Domain Name field will be populated with the local machine name if the PC is not
connected to a domain, or is running the installer as a User that does not have domain Administrator
privileges.
If Platform Engineering Tools are being installed for the first time on a PC with no previous SWS
installation or other ABB product having ever been installed on that PC, then the dedicated user
account should not exist and will be created with the default settings by the installation.
NOTE the password entered must adhere to local password strength/format rules; if this criteria is
not met the required user account will NOT be created and installation of the Tools package will
fail.
If SWS is being installed on a PC that had a previous SWS installation or if another ABB product
is already installed on the PC, or the PC is part of a domain which already includes the user
“QCSApp”, then the Platform Engineering Tools installation will not recreate or modify the
existing account, however a mismatch in the specified password and existing password can cause
some applications to behave incorrectly.
ABB service personnel may need to pay special attention to the information entered on this dialog
if they are installing this software on ABB supplied laptop computers. Failure to enter appropriate
information in this dialog could result in an aborted installation or a non-functional installation.
ABB service personnel may need to change the default password when installing for the first time
on an ABB supplied laptop. The laptop may have in place a security policy which requires that
passwords for user accounts to meet certain complexity or “strong” requirements. If this is the case
the default password must be changed so that it meets the requirements of this policy. If uncertain
regarding the security policy on the laptop, please consult the appropriate ABB IS department.
Once the necessary information has been entered press Next to continue.
14 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 15
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The log files from the failed install can be accessed through the link shown and can also be found
in the folder C:\ABB.PET.Install.Bootstrapper.Logs.
Log file names will include the product name and version being installed and also the install date
and time in YYYYMMDDHHMMSS format. For example, log files
ABB_Platform_Engineering_Tools_x64_2.2.18.0_20210409135101.log
ABB_Platform_Engineering_Tools_x64_2.2.18.0_20210409135101_002_msi.log
were stored when installing Version 2.2.18 on 9th April 2021.
When reporting issues to Supportline, please zip and attach all log files generated during the
failed installation(s).
16 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3 Licenses
The QC OPC Server and the Smart Platform Service Workstation applications are licensed
programs. As a result, the user must add system specific licenses in order for these programs to
function.
IMPORTANT: Please refer to Section 9.2 License Policy of this document for details on how the
Smart Platform Service Workstation licensing is implemented and its implications.
3BUS209544 rev T 17
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 19
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
1. Use the Customers and Locations buttons to input data relating to the setup.
2. Click Job Orders and the following screen will be presented with a new job order
screen.
When configuring the Job Order name be aware that the use of non-standard English letters may
result in the Data dictionary XML file not being deployed correctly. For example the following
letters may not be valid: Å, Ä, Ö, Ü and ß.
3. Select the drop down box beside Job Order shown in Figure 4-1
20 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
4. Fill in the information above, where IP address is the IP address of the scanner on the
port that the SWS will connect to.
IMPORTANT: Make sure to select NP1200, NP700 or ReflectionNP for a Network Platform
Frame and SP1200, SP700 or ReflectionSP for a Smart Platform Frame. If incorrect selection is
made, the Diagnostics tool and Service Workstation Health pages will function incorrectly.
5. Select the “+” sign as shown in figure above to bring up the sensor selections.
3BUS209544 rev T 21
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
22 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 23
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
NOTE: After configuring the data dictionary you should select and then delete the “Dummy
Configuration Component” entry.
You should modify the Port address entry to be the IP address of the Smart Platform on the QCS
LAN. Click on the OK button to add the Smart Platform component.
The above procedure can be repeated to add additional Smart Platforms.
24 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Select the Smart Platform component and press the Add Components button or right click on the
entry and select Add Component from the menu.
The Add Components dialog will display the list of sensors which you can add to the Smart
Platform. You can select an individual sensor and click the OK button to add just that sensor.
You can add multiple sensors at once by holding down the Ctrl key while selecting the individual
sensors. When you have selected all required sensors simply click the OK button and they will all
be added to the configuration.
Configuration changes to the Data Dictionary are not utilized immediately. In order for the changes
to be used you will need to either:
Restart the PC or
Stop and then restart the QC OPC Server service (“AccuRayObjectServer”)
3BUS209544 rev T 25
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 27
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
28 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The Grid
3BUS209544 rev T 29
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Select Monitoring Flag to start collecting data for the desired input. See Figure 5-4 on page 29.
30 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Trending will start when AI has been selected. The trend option enables the user to select up to 5
AI trend channels.
3BUS209544 rev T 31
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
32 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
To return from magnification, click the zoom icon above the vertical scale.
3BUS209544 rev T 33
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The Grid
34 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
NOTE: When “Continuous Monitoring Flag” is enabled the user will not be
able to disable the “Monitoring Flag”
Continuous This field will display a checkbox control. The “checked” state indicates that
Monitoring Flag continuous data monitoring is enabled for the digital input, when
“unchecked” continuous monitoring is disabled.
When a user turns on “Continuous Monitoring Flag”, the “Enable
Monitoring Flag” field will be automatically enabled. However, when a user
turns off “Continuous Monitoring Flag”, the “Enable Monitoring Flag” field
will remain unchanged.
If continuous monitoring is selected, monitoring will continue after the
diagnostics tool has been closed.
NOTE: Use this option only if you require to log monitored data over
extended periods. This option will utilize additional resource on the
embedded CPU and should not be enabled unless required for a specific
troubleshooting issue.
Table 5-2 DI Attributes
3BUS209544 rev T 35
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
36 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 37
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
38 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 39
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
1. Double Click to
trend a DO.
3. Select a DO to trend
40 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Profile
Attributes
2. The profiles display can show up to four measurement profiles. To select the profiles for
display double-click on the profile legend to open the profile selection dialog. See Figure
5-18 above. By default the profiles shown are the first four measurements configured in
the data dictionary.
3. Select a Measurement from the list in the “Select Profile Measurement” box as shown in
Figure 5-19 on page 42 . Selected measurements will persist when tool is restarted.
3BUS209544 rev T 41
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
4. The user may change the profile plot options by right-clicking on the profile chart area to
open the profile context menu. It is possible to offset or center the profiles about the
center of the display.
5. The profile vertical axis may be adjusted by use of the “Profile Display Settings”
function. Double click on the vertical scale, select the desired settings. See Figure 5-20
on page 43
42 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
At the bottom of the Profile Page are the attributes of the individual profiles.
3BUS209544 rev T 43
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
To return from magnification, click on the zoom icon in the lower left hand corner of the data box
scale.
44 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
To log profiles:
1. Select “Options” -> “Profile logging”
2. Set the maximum size of amount of data to log. (Typical data generation is 3MB to
10MB per hour while scanning).
3. Select a parent directory for the log folders that will be automatically generated. Ensure
there is sufficient space on the selected drive.
4. Select measurements, see Displaying Profiles
5. Select “Profile Logging”-> “Enable Profile Logging”. A confirmation pop-up will be
displayed:
6. When sufficient data has been gathered select “Disable Profile Logging”
Profiles will be logged to Comma Separated files (CSV) that can be opened in Excel or imported
into custom tools. Each selected measurement will have its own CSV file.
If opening in Excel the time stamp for each profile can be displayed as time by selecting desired
number format.
3BUS209544 rev T 45
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
If more than 4 measurements are required for logging. Open two instances of “ABB Diagnostics
Tool” before starting logging. Select measurements in both instances and then start logging.
46 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 47
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
48 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The Module Filter Settings window will appear. See Figure 6-4 below. By default the Module
Filter Settings dialog will have all modules selected, click on Deselect All to clear all selections
and select only the module(s) you wish to monitor Select Next.
The user will next be presented with the Debug Level Filter Settings dialog. This dialog provides
the user with the ability to select the level of debug information to be associated with the previously
selected Modules. The user can select multiple debug levels. See Figure 6-5 on page 50 Select
Finish.
3BUS209544 rev T 49
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
A window will now be displayed with the applied filters. As new debug becomes available from
the NP ASPC the window will be updated. With messages that adhere to the filter criteria. See
Figure 6-6 below.
It is possible to select multiple modules and multiple Debug levels in a single debug window.
However, it is always worth tuning the filter for the task at hand to ensure that only relevant
information is displayed.
50 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 51
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
It is possible to have multiple tabs (filters) displayed vertically at the same time. This is achieved
by dragging the desired tab header and dropping it into the display area. To return from a multiple
vertical tabbed view display to a singular tabbed display, drag each tab header back to the leftmost
tab header and drop.
52 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The classic horizontal multiple tabbed view interface style is still available. It is not enabled by
default. Enable the horizontal tabbed views by selecting the Options button. The Debug Tool
Options dialog box is launched. Deselect the “Use tabbed user interface” checkbox. Select the OK
button. The debug tool must be shut down and re-launched to enable the classic viewing mode.
In the multiple document interface mode, debug filters can be sized and set out as preferred.
Auto arrangement of multiple debug filters in this mode is achieved by selecting the Windows
button, which launches the Windows dialog box.
Select all the debug filters in the left pane of the dialog box and then click the Tile Horizontally
button.
3BUS209544 rev T 53
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The debug filters are auto arranged to fit the available viewing area of the debug tool.
54 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 55
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
2. Select the appropriate scanner and click next to advance to the next wizard page.
3. Enter the customer information and click next to advance to the next wizard page.
4. Enter scanner setup information and click next to advance to the next wizard page. A
description of the functions shown in this setup can be found in the NP Installation and
Maintenance Manual.
5. Enter the host IP address. See screen shot for more detail. (The next button will be
disabled on the last page)
56 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
6. The scanner configuration page will now open. To add sensors to the configuration, right
click on “Scanner” in the tree view and select the sensor to add. See Figure 7-3 on page
56. The following steps demonstrate Basis Weight as an example.
7. Enter the basis weight and gap sensor head constants, click next after each panel.
8. Enter the standardize limits and click “Finish”.
9. The Sensor’s configuration will now be shown. Each tab shows specific variables for the
sensor. Figure 7-5 above
10. Each sensor installed on the scanner should be added in a similar fashion to that shown
for Basis Weight in steps 6-8 above. See also 7.6 Add Sensors.
3BUS209544 rev T 57
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Save or Restore
Command Health Pages
NP Software
Restart Command
Configuration
To transfer configuration files from the PC to the scanner, open the Configuration tool.
1. Select “Transfer To Platform…” button from the Ribbon
58 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
2. Enter the IP address of the Scanner to which the configuration files are to be sent, the
User name (“NPUPDATE”) and the password (“NP353dlk”).
3BUS209544 rev T 59
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
1. Enter the scanner IP address, user name and password (“NPUPDATE” and “NP353dlk”)
in the dialog. Click Finish to initiate the transfer. Once complete the transferred
configuration will be displayed.
NOTE: Your PC must be correctly configured to communicate with the scanner via a TCP/IP
network connection.
60 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 61
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
When Expert Mode is enabled, the grids allow modifications to the values. The cells that may be
modified have a white background.
To disable Expert Mode, click the “Expert Mode” Ribbon button again.
7.12 IO Views
The scanner and sensors have tabs for the various IO signals. These list the signals used by that
sensor, the scanner or the position control logic in order to function. Each type of IO signal is
displayed on a separate tab. Figure 7-11 below shows the analog inputs (AI) signals used by the
basis weight sensor.
In addition to the display of IO information by sensor, scanner or position control view, you may
view all IO channels of each type by selecting the “All IO by Channel Type” entry in the list box
on the left side of the user interface.
62 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
7.13 IO Editing
It is possible to change the IO information, including channel assignments, by using Expert Mode.
NOTE: Invalid entries to the IO configuration can introduce incompatibilities, which may in turn
prevent the scanner from operating.
The configuration tool checks that no channels are used for more than one signal. The IO will be
validated before saving the configuration or transferring the configuration to a scanner. You may
also validate the IO configuration manually by using the Validate IO Ribbon button.
Any duplicate channels will be indicated in a dialog and by error indicators on the grid row for the
IO signal.
.
Figure 7-12 Duplicate channel error pop-up
3BUS209544 rev T 63
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
To connect to the NP Scanner press the “Connect to Remote Platform” button on the tool, a pop
up appears asking for the desired scanner information.
3BUS209544 rev T 65
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Enter the IP address of the desired scanner along with the username and password. These are
required so as only qualified persons are permitted to perform updates to the software running on
NP Scanners. The last entered IP Address will persist when the pop up box appears. The tool will
also attempt to auto complete the Username as the name is entered. The password must be entered
in full on each login.
For all scanners the Username is NPUPDATE and the password is NP353dlk.
Once all information has been entered press OK. The Update Tool will attempt to establish contact
with the NP Scanner at the IP Address specified and login using the information provided. The
bottom left hand corner of the Update Tool informs the user of current status.
Once the Update Tool establishes communications with the NP Scanner it will display the
following:
Software Update Name
Software Version
Date software was installed
Release notes for that update.
This information allows for accurate tracking of software installation along with the release notes
and date installed. The Update Tool status is displayed in the bottom left corner.
66 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
From this point the tool can be used to complete a number of tasks such as update the software,
both system and measurement, change IP Address and gather information about the scanner. All
of these functions shall be discussed further in the following sections.
3BUS209544 rev T 67
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
If the software version that is installed on the scanner is higher than the packages in the available
list, then those updates, by default, will not be displayed. This is to prevent accidental installation
of an older update. To display all of the available updates choose View > All Updates. This menu
also allows the version marked Last Known Good, or the factory default as shipped with the
scanner, to be selected for reinstatement; note that these are located on the embedded PC.
The Update Tool is now ready to download and install updates on NP Scanners.
68 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Quick boot up time – circa 40 seconds before head can be jogged or placed into Remote
Locked Off Sheet mode, hardware watchdog being serviced by measurement software
Write-Protection enabled on the system disk
Scanner history updated with the latest update package information included
Before executing an update, it is best practice to cycle power to the NP Scanner. This will flush
the memory overlay of stale data that doesn’t need to be committed to disk.
It is highly recommended to connect machine with update tool directly to SBC without intervening
hubs or switches to avoid potential network issues.
To install an update, choose the update package required from the list of available updates.
Press the “Install Selected Update” button and the tool will ask for confirmation.
3BUS209544 rev T 69
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Pressing yes will confirm that the update is to be installed. The tool will create another tab detailing
the individual steps that it will execute to complete the update.
If you choose yes then all of the action buttons are disabled, this is to prevent any interference with
the installation of the update on the NP Scanner. The action buttons are disabled for all operations
that require some amount of time to complete.
During an update or any other operation on the NP Scanner the Update Tool cannot be closed.
This is to prevent the NP Scanner being left in an unknown state and not being able to operate
correctly.
The Update Tool has a feature that enables the user to save the existing version installed on the NP
Scanner as the “Last Known Good” version. When installing a new update a pop up will appear
asking if you wish to back up the existing version or not.
The “Last Known Good” version allows for a new update to be installed and verified on the NP
Scanner safe in the knowledge that if there are any issues with the new update it is possible to roll
back to the Last Known Good version. The “Last Known Good” version is stored on the NP
Scanner in order to facilitate an efficient restoration.
Figure 8-8 Confirmation dialog box to back up existing installation as “Last Known Good”
It is good practice that only an update that has proven to be reliable should be backed up. Also it
should be an appropriate version for the user to roll back to in case of error during the validation
of the new update.
Choosing No to the pop up will result in the existing Last Known Good remaining as the current
last know good version.
If this is the first time that an update has been installed since leaving the factory there will be no
Last Known Good version present on the scanner. This will be stated in the pop up but only backup
a version that is appropriate.
70 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The tool will execute each of the steps specified. Upon completion a dialog box will be displayed
confirming that the install was successful. Note the bottom left corner detailing the status of the
Update Tool.
3BUS209544 rev T 71
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The Update Tool will then re-connect to the NP Scanner and re-read the history file. This will have
been updated with information from the update package that was just installed.
To close the In Progress report tab press the “Close Progress Report” button once it becomes
active.
At this point the update has been fully applied and the NP Scanner is fully operational.
All of the action buttons (Connect, Restart, Install Update, etc.) that were disabled during the
update are enabled and available for use.
Many new releases of Network Platform Embedded software require updated configuration files
for full visibility and customization of new features. Please check to see if a new version of
Platform Engineering Tools is available and then perform 11.2 Update Network Platform
Configuration Files.
72 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
From the Tools menu select “Change IP Address”. The following dialog box will appear with the
correct setting for the adapters found in the scanner.
3BUS209544 rev T 73
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Never modify the network setting for a Network Platform until you understand the consequences
of these settings. See chapter "Understanding IP Addressing" in "3BUS219121 Network Platform
ASPC Manual" for more information.
If a valid IP Address is entered and the Update Tool is NOT connected on that adapter then the
update will proceed as normal. If, however, the IP Address of the adapter that the Update Tool is
connected upon is modified then the tool will first of all run some checks on the new address to
verify the following:
Is there already a machine on the network that is configured with the same IP Address? If
so then this will result in networking failure and therefore will not allow the update to
continue. A dialog box is displayed and the error information is displayed.
Is the new IP Address reachable by this machine? Once the Update Tool modifies the IP
Address of the connected adapter the tool is no longer capable of communicating with the
Scanner. This will result in the Update Tool not being able to reconnect to the Scanner and
the update operation will time out. The NIC Adapter setting for the client machine should
be modified to include the range of address that is required for the NP Scanner. This is
detailed in 8.5.3.
Should the above checks be satisfied, when the IP Address is modified the Update Tool will be
able to re-connect to the Scanner and therefore it is safe to proceed. The Update Tool will prompt
the user - OK to confirm or Cancel to prevent the IP Address update.
74 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Should the Gateway be modified for the Network adapter in question, this will be confirmed also.
The proper action for this situation is to configure the network adapters on the client machine that
the Platform Update Tool is running on so that the new IP Address is reachable. If the network
adapters installed on the client machine are not able to reach the new address then the Update Tool
will not be able to complete the request. This is detailed in section 8.5.3.
3BUS209544 rev T 75
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
As with the software update the Update Tool will execute all of the steps outlined above in order.
Note again the bottom left cornet with the Update Tool’s status and all of the action buttons are
again disabled.
If an update fails do not immediately power cycle the scanner, instead refer to chapter “ASPC
(original) SBC Software update failure.” in “3BUS219121 Network Platform ASPC Manual”.
76 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The Update Tool will then re-connect to the NP Scanner again on the new IP Address and display
the information about current software installed, version, installation date and release notes for the
install.
If the update of IP addresses fails to complete, please see 8.5.1 Failure to complete setting IP
address.
3BUS209544 rev T 77
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
78 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
4. This will open up the properties window for the NIC adapter. Scroll down to select
“Internet Protocol Version 4 (TCP/IP)” and click the “Properties” button.
5. On the TCP/IP properties window that appears, select the “Advanced” button. Under the
IP Addresses section select the “Add” button.
3BUS209544 rev T 79
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
6. This allows for multiple IP Addresses to be added to an adapter. Enter an IP address that
is in the same range as the requested NP Scanner IP Address. This will allow the Update
Tool to reconnect after the setting has been modified and can complete the operation.
80 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Figure 8-24 Restarting the NP Measurement Application using the tool bar
The application may also be restarted by using the menu item found in the Tools menu.
Current status of the restart operation is displayed in the bottom left corner of the Update Tool.
When the request has completed and the application has been restarted the Update Tool will
provide a dialog box reporting the status.
3BUS209544 rev T 81
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
2. When connected and the installed package information is displayed it is then possible for
the Update Tool to retrieve the log files. Click the “Retrieve Event Logs” button on the
Update Tool.
3. The location to store the log files on the local machine must be specified. This is a
directory located on the NP Client PC and it is in this location that the Update Tool will
save the event log files downloaded from the NP Scanner.
4. The progress of the download operation is described on the status bar of the Update Tool
and also states what files are being downloaded.
5. Notification is given once all of the files have been downloaded. Files are saved in the
specified location. These are binary files that may only be viewed using the event
viewer.
6. To view any of these files open up the event viewer on the client PC. From the Action
Menu choose “Open Saved Log…”
82 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
On power up of the NP Scanner a new log file is created for that session. The naming convention
of the log files consists of the date and time that the scanner was started, therefore the newest file
will be the log file for the latest session of the NP Scanner.
When choosing which file to open, specify the type of the event log to be opened. For the NP
Scanner it will always be of type Application.
Prompt to update log file format
The event viewer may take some time to open the log file depending on its file size. When viewing
the event log the messages that are of interest are any whose source is the “ABB Debug Manager
Service”. The measurement application sends all of its debug messages to this service, which in
turn determines the messages that should and should not be logged. Double-click any single
message to view its details.
Figure 8-29 Viewing the downloaded event log from the NP Scanner
3BUS209544 rev T 83
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
On start-up of the ABB Measurement application (after power is switched on to the scanner or the
Update Tool restarts the application) the session is marked with the message shown below. This
means that the messages following it are all relative to this session of the application running.
For more detail about Event log messages please see “Understanding event log entries” in
"3BUS219121 Network Platform ASPC Manual".
84 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
9 SP Service Workstation
9.1 Overview
SP Service Workstation was previously the principle tool for monitoring the status of SP and NP
scanners. Much of its functionality has now been migrated to NP SWS (See 10 NP Service
Workstation); SP SWS remains within the Platform Engineering Tools package for legacy support
purposes. This section describes some of the main features of the standalone SP Service
Workstation application and how to use them.
It is assumed that the users of the SP Service Workstation application are suitably qualified to
interpret the information provided by this application.
It is beyond the scope of this document to provide detailed information on the actual individual
frame and sensor health pages themselves, their functionality or how they should be used to
perform service related activities.
This message until the software connects to a node from which a license can be obtained.
3BUS209544 rev T 85
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
86 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
To select a Scanner simply click on the appropriate entry. The Frame Health Report will then be
displayed by default for the selected Smart Platform.
3BUS209544 rev T 87
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
You should note that when you are actually connected to the QC OPC server located on the local
machine the associated “Connect to local…” button and menu entry will be disabled. If you
subsequently connect to a QC OPC server on a remote node then these entries will once again
become enabled.
The SP Service Workstation application status display shows the name of the node to which you
are currently connected or attempting to connect to.
Lock SP SWS
Unlock SWS
88 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
The SP Service Workstation application status display area will indicate the current operating
mode using the text “LOCKED” or “UNLOCKED” as appropriate.
However you should note that the status display also indicates that by default the SP Service
Workstation will automatically revert back to locked mode after a period of twenty (20) minutes
has elapsed. See 9.4.2 Change “Auto Lock” Settings for further details.
3BUS209544 rev T 89
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
When you attempt to change the Auto Lock settings you will be prompted to enter the existing SP
Service Workstation password. Following this, the change settings dialog will be displayed.
90 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
3BUS209544 rev T 91
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
92 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
if anything has been inadvertently changed or to check that head constants and other user settings
are reasonable.
4. The Set Network Platform Date Time Dialog facilitates the setting of the date or time.
Enter the desired setting and click OK.
5. A message box will appear asking for user confirmation. Click Yes to set the date/time
3BUS209544 rev T 93
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
6. The date/time setting is then applied. SWS date/time control will update to the new
setting.
94 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
9.7 Using SP Service Work Station via Serial Link (Smart Platform
only)
9.7.1 Introduction
The Smart Platform Service Workstation application is an OPC client based application and as
such it reads and writes data to and from the Quality Control OPC server using the industry
standard OPC interfaces.
Normally the QC OPC server communicates with the Smart Platform(s) using the ABB proprietary
ASI protocol over a TCP/IP LAN (i.e. the QCS LAN).
However in some circumstances (e.g. older Smart Platforms) it is required that the Service
Workstation application is run using a standard serial communications port on the Service
workstation PC.
This feature is not supported by the ABB Platform Engineering Tools installation. For
maintenance of legacy installations please see previous versions of this manual installed on the
machine with the Platform Client suite install.
10 NP Service Workstation
NP Service Workstation (NP SWS) is installed as part of the overall Platform Engineering Tools
installation, ref 2 Introduction. It mirrors and extends the functionality available in SP SWS, in
particular to support NP frame and sensor functionality. It allows a status overview of multiple
frames as per the connected OPC Server and its Data dictionary.
For detailed information regarding the functionality of NP Service Workstation (NP SWS) please
refer to the document “3BUS214945 QCS800xA NP Service Workstation”
3BUS209544 rev T 95
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
NOTE: Re-install or update of PET will overwrite the configured data dictionary database. Ensure
you have record of Scanners, scanner IP addresses, and sensor complements before starting. It’s
recommended to take a screenshot of the configuration.
96 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
Configure, build and deploy data dictionary followed by a restart, see 4 Configure ABB
Scanner Data Dictionary
3BUS209544 rev T 97
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
o Driver updates – these allow the update of drivers for 3rd party hardware installed
in the system. Please check associated, release notes, field alerts or instructions to
verify the content and requirements of these packages.
o OSA temporary license – these licenses are loaded onto the system via an update
package. Updating a new license over an expired license will activate the new
license. Be aware that updating a new license over a non-expired temporary
license, will also activate the new license and the remaining activation time for the
old license will be lost.
Read the release note associated with any update prior to installation. These notes are available on
the bottom of the ‘Available Update Package(s)’ display when the update has been imported and
also in ABB Library or P.A.S.S. (Premium ABB Service Suite), normally having a 3BUS ID
sequentially following the update package ID.
Version numbering on ABB Platform OS update packages relate to their content. It is therefore
not necessary that the latest version number of this type of package is installed.
If more than one update of type ABB Platform OS is installed, only the last package installed is
visible in the ABB Platform Update Tool. Packages of this type already installed will only be
(automatically) over-written if required. For example, on a system with the driver update package
for FO-NIC unit installed, if a temporary OSA license is installed then the OSA license detail will
be visible in the ‘Currently Installed Update Packages’ window and the previously visible detail
on the FO-NIC update will have disappeared. The FO-NIC package is however still installed and
functioning.
98 3BUS209544 rev T
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
12 Appendices
Appendix A Firewall Configuration
The Platform Engineering Tools installation includes a script to configure Windows Firewall as
required. In some instances, this will not complete correctly, for example if domain restrictions
prevent modifications or another security application manages the firewall.
The script implements the following rules for inbound traffic.
Prot
Name Program Port ocol
ABB OPC Alarm %ProgramFiles%\ABB Industrial IT\Quality Control
Client Solutions\Communicate IT\Clients\alarmclient.exe 135 TCP
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB OPC Inspector Solutions\Communicate IT\Clients\opcinspector.exe 135 TCP
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB Platform Solutions\Engineering Tools\ABB Platform Configuration
Configuration Tool Tool\bin\ABB Platform Configuration Tool.exe Any Any
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB Platform Debug Solutions\Engineering Tools\ABB Platform Debug
Tool Tool\bin\ABBDebugViewer.exe 2293 TCP
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB Platform Update Solutions\Engineering Tools\ABB Platform Update
Tool Tool\bin\ABB Platform Update Tool.exe Any Any
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB Scanner Solutions\Engineering Tools\ABB Scanner Diagnostic
Diagnostics Tool Tool\bin\ABB Scanner Diagnostics.exe 135 TCP
ABB Service %ProgramFiles(x86)%\ABB Industrial IT\Quality Control
Workstation Solutions\bin\ABB SmartPlatform Service Work Station.exe 135 TCP
ABB Weight xP %ProgramFiles%\ABB Industrial IT\Quality Control
Profiler Engineering Solutions\Engineering Tools\ABB Actuator Engineering
Tool Tool\bin\ABBActEngTool.exe Any TCP
%ProgramFiles(x86)%\ABB Industrial IT\Quality Control
AccurayObjectServer Solutions\Communicate IT\Server\AccuRayObjectServer.exe 135 TCP
OPCEnum %SystemRoot%\SysWOW64\OpcEnum.exe 135 TCP
%ProgramFiles%\ABB Industrial IT\Quality Control
ABB Online Spectral Solutions\Engineering Tools\ABB Online Spectral Analysis
Analysis Tool Tool\bin\ABB Online Spectral Analysis.exe Any Any
Softing OPC Classic %ProgramFiles%\ABB Industrial IT\Quality Control Any TCP
Demo Client (TCP) Solutions\Communicate IT\Clients\soclient.exe
Softing OPC Classic %ProgramFiles%\ABB Industrial IT\Quality Control Any UDP
Demo Client (UDP) Solutions\Communicate IT\Clients\soclient.exe
ABB TCP 135 (ALL) Any 135 TCP
3BUS209544 rev T 99
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
Reproduction, or other means of dissemination may be made without written permission.
DCOM Configuration
DCOM is used by the Actuator Engineering Tool (and others) to retrieve data from remote systems. It is
dependent on correct configuration of the Platform Engineering Tools host machine. If incorrectly
configured, the Actuator Engineering Tool will not be able to connect or retrieve data.
Background
User QCSApp is created when installing ABB Platform Engineering Tools. This is the default
account used for running the Tools and also for communications to external systems.
It is often desirable to change the password for user QCSApp without running a Platform
Engineering Tools install. This procedure provides instructions for changing the account password
and reconfiguring DCOM communication.
3. Select the “Change a password” option, which will present the following screen
DCOM must now be re-configured to use the same password as just modified. In most cases, re-
configuring DCOM requires a script to be run using administrator privileges on the PC.
1. Left-click the Windows icon and type CMD (1). When prompted, click “Run as
administrator” (2)
3. Copy the following command into the command prompt window (Right click in the
window to paste)
cd “C:\Program Files (x86)\ABB Industrial IT\Quality
Control Solutions\bin”
Then press enter and proceed with the Re-configuring DCOM steps below.
For this step the Domain or Machine name, under which the user QCSApp is configured, will be
required.
1. In the same command prompt window as above type the following
SWS_DCOMCONFIG.VBS
Then press enter.
2. When prompted by the dialog, click “Yes”
4. When prompted, enter the QCS user account name (e.g. QCSApp) and click “OK”
6. The information entered is confirmed on the next dialog. Click “Yes” to proceed or click
“No” to abort the process.