Operating Manual AHZC 66150
Operating Manual AHZC 66150
Operating Manual AHZC 66150
Granulex® 3 Series
Hammer mill
AHZC
AHZC-23401-1-2302-en-US
1 General ............................................................................... 9
1.1 Availability of the instructions.................................................................................... 9
1.2 Scope of validity....................................................................................................... 9
1.3 Applicable documents ............................................................................................. 9
1.4 Contact.................................................................................................................... 10
1.4.1 Feedback regarding these instructions..................................................................... 10
1.5 Personnel qualification ............................................................................................. 10
1.5.1 Operating personnel ................................................................................................ 10
1.5.2 Service engineers..................................................................................................... 10
1.6 Conventions of depiction.......................................................................................... 10
1.6.1 Action sequence ...................................................................................................... 10
1.7 Abbreviations ........................................................................................................... 11
1.8 Technical terms ....................................................................................................... 11
2 Safety.................................................................................. 12
2.1 Superstructure of the warning messages ................................................................. 12
2.2 Explanation of the warning instructions .................................................................... 12
2.3 Intended use............................................................................................................ 13
2.4 Part of the operating instructions.............................................................................. 13
2.5 Technical state......................................................................................................... 13
2.6 ATEX marking .......................................................................................................... 13
2.7 Personnel qualification ............................................................................................. 13
2.8 Protective measure to prevent unexpected starting.................................................. 14
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 3
3.3.1 Housing dimensions................................................................................................. 16
3.3.2 Dimensions, throughput control ............................................................................... 16
3.3.3 Dimensions, display ................................................................................................. 16
3.4 Weight, throughput control ...................................................................................... 16
3.5 Interfaces ................................................................................................................. 16
3.6 Miscellaneous .......................................................................................................... 16
3.7 Design versions........................................................................................................ 17
4 Description ......................................................................... 18
4.1 Operating principle................................................................................................... 18
4.1.1 Throughput control .................................................................................................. 20
4.1.2 Vertical hammer mill ................................................................................................. 21
4.1.2.1 Start......................................................................................................................... 21
4.1.2.2 Stop......................................................................................................................... 22
4.1.2.3 Reduce the overrun time.......................................................................................... 22
4.1.3 Feeding.................................................................................................................... 22
4.1.3.1 Dosing release ......................................................................................................... 22
4.1.3.2 Starting .................................................................................................................... 23
4.1.3.3 Stop......................................................................................................................... 23
4.1.4 Heavy particle flap.................................................................................................... 23
4.1.5 Outlet cone .............................................................................................................. 23
4.1.6 Discharge conveyor ................................................................................................. 23
4.1.7 Gravity flow diverter (option) ..................................................................................... 24
4.1.8 Temperature monitoring (option) .............................................................................. 24
4.1.9 Vibration monitoring (option)..................................................................................... 24
4.1.10 Magnetic door and back-up probe........................................................................... 24
4.1.11 Profibus interface ..................................................................................................... 24
4.1.12 Profinet interface (option) ......................................................................................... 25
4.1.13 EtherNet/IP interface (option) ................................................................................... 25
4.2 Operating and display elements ............................................................................... 25
4.2.1 Display operating elements ...................................................................................... 25
4.3 Time charts.............................................................................................................. 27
4.3.1 Standard sequence.................................................................................................. 27
4.3.2 Clearance time......................................................................................................... 27
4.3.3 Timeout ................................................................................................................... 27
5 Installation .......................................................................... 29
5.1 General arrangement drawing .................................................................................. 29
Bühler Group
AHZC-23401-1-2302-en-US
4 | Operating manual
5.1.1 Vertical hammer mill control ..................................................................................... 29
5.1.2 Throughput control .................................................................................................. 29
5.2 Main circuit board EBD 1311 ................................................................................... 30
5.2.1 Jumpers EBD 1311 ................................................................................................. 30
5.2.2 Connecting the power supply .................................................................................. 31
5.2.3 Profibus-DP or RS-485 SIO_2.................................................................................. 31
5.2.4 CAN interface .......................................................................................................... 32
5.2.5 24 V inputs .............................................................................................................. 33
5.2.6 24 V outputs ............................................................................................................ 36
5.2.6.1 Outputs 24 V on input plugs .................................................................................... 37
5.2.7 Analog inputs 0 … 5 V or 0/4 … 20 mA ................................................................... 39
5.2.8 0/4 ... 20 mA analog outputs ................................................................................... 40
5.3 Decentralized IO modules ........................................................................................ 42
5.3.1 Digital IO module EBD 1318..................................................................................... 42
5.3.2 Jumpers EBD 1318 ................................................................................................. 42
5.3.3 Digital IO expansion module 1.................................................................................. 42
5.3.4 Digital IO expansion module 2.................................................................................. 44
5.3.5 Digital IO expansion module 5.................................................................................. 45
5.3.6 Digital IO expansion module 6.................................................................................. 47
5.3.7 Analog IO module EBD 1317 ................................................................................... 48
5.3.8 Analog I/O expansion module EBD 1317 ................................................................. 49
5.3.9 Analog I/O expansion module 1 ............................................................................... 50
5.3.10 Analog I/O expansion module 2 ............................................................................... 51
5.4 Display module EBD 1316 ....................................................................................... 52
5.4.1 Circuit board EBD 1316 ........................................................................................... 52
5.4.2 Description of electric terminals X50......................................................................... 52
5.4.3 Description of electric terminals X52......................................................................... 53
5.4.4 Digital inputs of the display circuit board .................................................................. 53
5.4.5 Jumpers EBD 1316 ................................................................................................. 53
5.4.6 Wiring of vertical hammer mill control DFCQ V ......................................................... 54
5.4.7 Wiring of throughput control DFCQ H (main circuit board only)................................. 55
5.4.8 Wiring of throughput control (with CAN modules) ..................................................... 57
6 Operation ............................................................................ 59
6.1 Operate keys and lamps .......................................................................................... 59
6.2 Set parameters and parameter groups..................................................................... 60
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 5
7 Configuration...................................................................... 61
7.1 Setting the application.............................................................................................. 61
7.2 Device-specific settings............................................................................................ 61
7.3 Using the input wizard.............................................................................................. 62
7.4 Activate Profibus ...................................................................................................... 62
7.5 Activating Profinet .................................................................................................... 62
7.6 Activating Ethernet ................................................................................................... 62
7.7 Optimizing controller settings ................................................................................... 63
7.7.1 Descriptions of controller characteristics .................................................................. 63
7.7.2 Ziegler Nichols optimization...................................................................................... 63
7.7.3 Determining control parameters for controlled system with balancing....................... 63
7.7.3.1 Recording the step response ................................................................................... 63
7.7.3.2 Determining critical reinforcement ............................................................................ 65
7.7.4 Determining control parameters for controlled system without balancing.................. 66
7.7.5 Empirical optimization .............................................................................................. 66
7.8 Temperature monitoring........................................................................................... 67
7.8.1 Configure existing temperatures............................................................................... 67
7.8.2 Set scaling data ....................................................................................................... 67
7.8.3 Check settings of CAN module EBD 1317 ............................................................... 68
7.8.4 Calibrate and check temperatures ........................................................................... 68
7.9 Setting frequency converter of the feed roller ........................................................... 68
7.9.1 Schneider ATV 320 .................................................................................................. 69
7.9.2 Schneider ATV 312/31............................................................................................. 72
7.10 Controlling the main motor with frequency converter................................................ 73
7.10.1 Configuring the frequency converter Schneider ATV 930 (example).......................... 75
7.10.2 Configuring the frequency converter DANFOSS VLT 5000 ....................................... 76
7.11 Special applications ................................................................................................. 77
7.11.1 Control on the discharge conveyor with fan (pneumatic suction conveying system).. 77
7.11.1.1 Load control by current measurement of the fan motor (control with DOL starting 77
or soft starter) ..........................................................................................................
7.11.1.2 Load control via the motor torque of the fan motor (control with frequency con- 78
verter) ......................................................................................................................
7.11.1.3 Load control by air volume measurement with dynamic pressure sensor (control 79
fan motor with DOL starting, soft starter or frequency converter)..............................
7.11.2 Screw metering (TCON.FEED = SCREW)................................................................. 81
7.12 Resetting parameters to factory settings .................................................................. 81
8 Parameters ......................................................................... 82
8.1 Notes for the parameter details ................................................................................ 82
Bühler Group
AHZC-23401-1-2302-en-US
6 | Operating manual
8.2 Application parameters ............................................................................................ 82
8.2.1 USER (operating parameters) parameter group........................................................ 82
8.2.2 MAN (manual operation) parameter group................................................................ 84
8.2.3 TCON (configuration parameters) parameter group .................................................. 88
8.2.3.1 Setpoint frequencies of the main motors .................................................................. 98
8.2.4 Parameter group SYS (System configuration)........................................................... 99
8.2.5 ADC (analog-digital converter) parameter group.......................................................105
8.2.6 ADCT (Analog/Digital Converter Temperature) parameter group...............................108
8.2.7 1317 (CAN module EBD 1317) parameter group .....................................................109
8.2.8 Parameter group CTRL (Controller configuration) .....................................................110
8.2.9 PBDP (Profibus DP) parameter group ......................................................................113
8.2.10 ENET (Ethernet) parameter group ............................................................................115
8.2.11 TCP (Ethernet TCP/IP) parameter group ..................................................................119
8.2.12 Parameter group SERV (Service information)............................................................121
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 7
11.1.3.1 Error messages of LED display ................................................................................150
11.2 Remote control ........................................................................................................151
11.2.1 Installation version....................................................................................................151
11.2.2 Table or wall version with ATEX................................................................................152
11.2.3 Table or wall version (old) .........................................................................................153
11.2.4 Connect to MDDR main circuit board SIO_0 ............................................................153
11.3 Parameter list...........................................................................................................154
Bühler Group
AHZC-23401-1-2302-en-US
8 | Operating manual
Chapter 1
General
1 General
1.1 Availability of the instructions
These instructions constitute part of the product.
1. Retain the instructions and related applicable documents during the entire lifetime
of the product and keep them at hand for reference.
2. Pass on the instructions and other applicable documents to the each subsequent
owner or operator of the product.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 9
Chapter 1
General
1.4 Contact
1. In case of any questions, please contact the responsible branch of Bühler Group.
See www.buhlergroup.com
2. Keep the instructions ready at hand.
3. Keep the machine number ready at hand.
1. Action step 1
u Subprocess 1
u Subprocess 2
2. Action step 2
Interim result of action step 2
3. Action step 3
Result of entire action step
Bühler Group
AHZC-23401-1-2302-en-US
10 | Operating manual
Chapter 1
General
1.7 Abbreviations
Abbreviation Meaning
Profibus Fieldbus for the automation which is used for the control of
sensors, actuators and for communication between measur-
ing and process devices, actuators and process control sys-
tems.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 11
Chapter 2
Safety
2 Safety
2.1 Superstructure of the warning messages
The warning messages make staff aware of unavoidable hazards present during the
operation of the machine that are inherent to its design. Observe the measures men-
tioned to avoid these hazards.
General structure of a warning message:
(1) (2) (3) (4)
SIGNAL WORD
(6) (5)
(1) Danger symbol (2) Indicates the type and source of the
danger.
(3) Signal word (4) Signal color
(5) Lists the measures to avoid the (6) Indicates the consequences of ig-
danger. noring the danger.
DANGER
WARNING
CAUTION
Bühler Group
AHZC-23401-1-2302-en-US
12 | Operating manual
Chapter 2
Safety
NOTICE
u Only charge qualified personnel with tasks described in this operating manual.
u Ensure that personnel comply with the locally valid laws and regulations for safe
and hazard-conscious work.
u Define and communicate the work responsibilities. Provide the keys and pass-
words to assigned personnel only.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 13
Chapter 2
Safety
Bühler Group
AHZC-23401-1-2302-en-US
14 | Operating manual
Chapter 3
Technical data
3 Technical data
3.1 Environmental conditions
Designation Value Unit
Frequency 43 … 67 Hz
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 15
Chapter 3
Technical data
3.3 Dimensions
Height 2000 mm
Width 1600 mm
Depth 500 mm
Height 300 mm
Width 380 mm
Depth 155 mm
Height 300 mm
Width 210 mm
Depth 80 mm
Weight, approx. 10 kg
3.5 Interfaces
– Profibus DP: Profibus slave, 9-pin D-sub socket
– USB: USB device interface for service
– CAN: CAN interface for expansion modules
– RJ-45 socket: Profinet, EtherNet/IP, Ethernet TCP/IP (optional)
3.6 Miscellaneous
– Flash EPROM for program and data logger
– Battery-powered RAM for parameters: Data protection for at least 20 years
– Noise emission (emission): EN 50081-1 class B complied with
– Noise immunity (immunity): EN 50082-2 industrial sector complied with
Bühler Group
AHZC-23401-1-2302-en-US
16 | Operating manual
Chapter 3
Technical data
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 17
Chapter 4
Description
4 Description
4.1 Operating principle
The control system is used for the following applications:
– DFCQ -V: Process control for vertical hammer mills of the DFZK or AHZK ma-
chine codes and their product types. The roller feeder DFAV and AHAV and
transportation.
– DFCQ -H: Throughput control for horizontal hammer mills (FCM = Flow Control
Mode). In this process, the output of the hammer mill is regulated by controlling
the roller feeder.
The control system regulates and monitors the grinding process of vertical and hori-
zontal hammer mills.
Depending on the application, the control system performs the following functions:
Bühler Group
AHZC-23401-1-2302-en-US
18 | Operating manual
Chapter 4
Description
(1)
(15) (2)
(14) (3)
(13)
(12)
(4)
(5)
(11) (6)
(7)
(10)
(8)
(9)
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 19
Chapter 4
Description
(16) (1)
(2)
(15) (3)
(14)
(13)
(12)
(4)
(5)
(6)
(11)
(7)
(10)
(8)
(9)
Bühler Group
AHZC-23401-1-2302-en-US
20 | Operating manual
Chapter 4
Description
(1)
(2)
(1) DFCQ -H, compact device (2) DFCQ -H, built-in version
4.1.2.1 Start
The vertical hammer mill is controlled by two 24 V signals. Depending on the operat-
ing hours, the corresponding direction of rotation of the main motor is determined at
the start. This adjustment enables the hammers and sieves to wear evenly.
With two hammer mills, the second main motor first starts after the delay ”TCON.T6“
See page 98. A current transformer measures the present motor output. The ”Motor
is turning“ signal thereby occurs. If there is no current, an error message is displayed
and the mill stops.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 21
Chapter 4
Description
When the time ”TCON.T6“ has elapsed, the air-circulating fan starts on the roller
feeder. ”TCON.T6“ See page 98. The motor contactor of the fan sends an acknowl-
edgement signal to the control system ”DFCQ V“ as confirmation that the fan is run-
ning. If there is no signal, an error message is output and the dosing unit does not
start.
4.1.2.2 Stop
Do not operate the hammer mill for more than 15 minutes without any product since
the air circulation can cause overheating. The hammer mill is stopped by deactivation
of the 24 V start command. The air-circulating fan switches off first, followed by the
main motor. With two hammer mills (DFZK 2), both main motors switch off at short in-
tervals.
If the hammer mill runs without any product (no load), the hammer mill switches off
automatically after the time ”TCON.T3“ has elapsed. ”TCON.T3“ See page 97.
The following conditions are fulfilled that after an automatic stop, the hammer mill
restarts:
– The dosing release is pending.
– The level probe of the intermediate container reports presence of product.
If the hammer mill is stopped during the dosing process, the clearance time
”TCON.T1“ expires first. ”TCON.T1“ See page 97. This ensures that no product is
left behind in the grinding chamber and the hammer mill can restart automatically. If
product is left behind in the grinding chamber, the main motor cannot start. The
product must be removed manually.
4.1.3 Feeding
Bühler Group
AHZC-23401-1-2302-en-US
22 | Operating manual
Chapter 4
Description
4.1.3.2 Starting
Thus, the dosing starts when the following conditions are met:
– The dosing release is pending.
– The level probe of the intermediate container reports presence of product.
– The blockage probe in the roller feeder is not covered.
The main motor is regulated by a setpoint, this is given in percent. The setpoint corre-
sponds to 100 % of the rated power of the main motor.
The control system regulates the optimum utilization of the main motor by means of
the segment slide gate gap and the speed of the feed roller. If two hammer mills
(DFZK 2) are present, the two segment slide gate settings are corrected until the
power consumption of both hammer mills is distributed evenly.
4.1.3.3 Stop
The following conditions must be met for dosing to stop:
– The dosing release is no longer present.
– The level probe of the intermediate container is not covered.
– The product discharge is no longer ensured.
The control system remains in this state until all conditions have been met for a
restart.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 23
Chapter 4
Description
Bühler Group
AHZC-23401-1-2302-en-US
24 | Operating manual
Chapter 4
Description
The circuit board Profinet - Ethernet fieldbus EBD 1326 (EKP-85388-810) is required.
The circuit board EtherNet/IP - Ethernet fieldbus EBD 1325 (EKP-85387-810) is re-
quired.
H1 H2 H3 H4 H5 H6
lb
kg
S1 S2 S3 S4 S5 S6 S7 S8
H1 Remote control
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 25
Chapter 4
Description
H3 Not used
H4 Manual mode
Flashing = manual operating mode active
H5 Not used
H6 Capacity range
Flashing = overload; Lit = actual/target deviation ≤ 10 %
H7 Weight unit lb
H8 Weight unit kg
Bühler Group
AHZC-23401-1-2302-en-US
26 | Operating manual
Chapter 4
Description
T6
DO 0.17 Main motor start 2
T6
DO 0.13 Fan
Dosing start
DO 0.13 Fan
Dosing start
4.3.3 Timeout
The hammer mill stops in the following cases after the timeout” TCON.T3“:
– When no product is in the inlet
– When no release is present
This protects the cone from overheating. When there is product in the inlet again, the
hammer mill starts independently.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 27
Chapter 4
Description
DO 0.13 Fan
Dosing start
Bühler Group
AHZC-23401-1-2302-en-US
28 | Operating manual
Chapter 5
Installation
5 Installation
5.1 General arrangement drawing
(3)
(4)
(1) Main circuit board EBD 1311 (2) Frequency converter of the feed
roller
(3) Display circuit board EBD 1316 (4) Power section depending on design
version (a star-delta start here)
(3)
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 29
Chapter 5
Installation
(1)
(2)
(3)
(4)
Bühler Group
AHZC-23401-1-2302-en-US
30 | Operating manual
Chapter 5
Installation
1
2
3
Fig. 5.4 ID electric terminal X1
Terminal Function
1 +24 V
2 0V
3 PE
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 31
Chapter 5
Installation
5
9
4
8
3
7
2
6
1
X Signal Description
3
4
Terminal Function
1 +24 V
2 0V
3 CAN H
4 CAN L
X Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
32 | Operating manual
Chapter 5
Installation
X Signal Description
5.2.5 24 V inputs
1
2
3
4
5
6
7
8
Fig. 5.7 ID electric terminal X3, X10, X11, X12 and ID electric terminal X20, X21, X22
3 DI_0.17 DI_0.21 −
7 DI_0.19 DI_0.23 −
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 33
Chapter 5
Installation
DI X3 Signal Description
0.1 X3:3 Activate brake 24 V = when switching off the motors, the
signal is checked. If it is active, the motors
are stopped with reverse current brake.
0.5 X10:3 Release for main 24 V = Main motor of hammer mill 1 will be
motor 1 started.
0.8 X11:2 Segment slide 24 V pulse signal = counting pulse for mea-
gate pulse 1 suring position of the segment gate.
0.10 X11:6 For screw meter- 24 V = Level probe in the upper surge hop-
ing per is covered (operating state).
Low level in upper 0 V = level probe in the upper surge hopper
surge hopper is uncovered (alarm condition).
0.11 X11:7 Alarm for fre- 0 V = the frequency converter of the feed
quency converter roller is reporting an alarm.
Bühler Group
AHZC-23401-1-2302-en-US
34 | Operating manual
Chapter 5
Installation
0.17 X20:3 Release for main 24 V = Main motor of hammer mill 2 will be
motor 2 started.
0.20 X21:2 Segment slide 24 V pulse signal = counting pulse for mea-
gate pulse 2 suring position of the segment gate.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 35
Chapter 5
Installation
5.2.6 24 V outputs
1
2
3
4
5
6
DO X2 Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
36 | Operating manual
Chapter 5
Installation
1
2
3
4
5
6
7
8
Fig. 5.9 ID electric terminal X3, X10, X11, X12 and ID electric terminal X20, X21, X22
2 − − − −
3 − − − DO_0.13
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 37
Chapter 5
Installation
6 − − − −
7 − − − DO_0.15
2 − − −
3 − − DO_0.25
6 − − −
7 − − DO_0.27
Bühler Group
AHZC-23401-1-2302-en-US
38 | Operating manual
Chapter 5
Installation
1
2
3
4
5
6
7
1 + AI_0.0 + AI_0.4
2 + AI_0.1 + AI_0.5
3 + AI_0.2 + AI_0.6
4 + AI_0.3 + AI_0.7
5 +5 V +5 V
6 GND GND
7 GND GND
0.1 X14:2 Motor current for Motor power input of discharge conveyor of
discharge 1 hammer mill 1
20 mA = ADC. CON1.2
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 39
Chapter 5
Installation
0.5 X24:2 Motor current for Motor power input of discharge conveyor of
discharge 2 hammer mill 2
20 mA = ADC. CON2.2
1
2
3
4
5
Fig. 5.11 ID electric terminal X4
Terminal Function
1 + AO_0.0
2 GND
3 + AO_0.1
4 GND
5 GND
The function of the analog outputs depends on the configuration of the control sys-
tem.
Bühler Group
AHZC-23401-1-2302-en-US
40 | Operating manual
Chapter 5
Installation
AO X4 Signal Description
TCON.MILL = 1 TCON.MILL = 2
(DFZK 1) (DFZK 2)
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 41
Chapter 5
Installation
1 1 1
H100 H104 H108
2 2 2
CAN
H101 H105 H109
3 3 3
1
4 4 4
2
5 5 5
3
H102 H106 H110 H150
6 6 6 4
H103 H107 H111
7 7 7 X100
8 8 8 ON ON
OFF OFF
X101 X102 X103 1 2
X99
Out 0… 3
Out 4… 7 EBD1318 3 4
Out 8…11
X112 S100
X99 OFF = bus termination deactivated. All modules except the last
module on the bus.
ON = bus termination activated. Last module on the bus.
Bühler Group
AHZC-23401-1-2302-en-US
42 | Operating manual
Chapter 5
Installation
Dx X Signal Description
1.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.
1.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.
1.9 X103:3 Move cone to the 24 V = move linear cylinder to the right
right of the cone.
1.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 43
Chapter 5
Installation
Dx X Signal Description
1.11 X103:7 Move cone lamp Lamp of the move cone button.
When the main motor is at a standstill
and the lamp is lit, the cone can be
opened.
When a sieve change has been re-
quested, the lamp flashes slowly.
Lamp flashes rapidly when the cone is
locked.
Dx X Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
44 | Operating manual
Chapter 5
Installation
Dx X Signal Description
2.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.
2.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.
2.9 X103:3 Move cone to the 24 V = move linear cylinder to the right
right of the cone.
2.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.
2.11 X103:7 Move cone lamp Lamp of the move cone button.
When the lamp is lit, the main motor is
stationary. Cone can be opened.
If the lamp flashes slowly, a sieve
change has been requested.
If lamp flashes rapidly when the cone is
locked.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 45
Chapter 5
Installation
Dx X Signal Description
5.1 X101:3 Fill level of roller 24 V = level probe of the roller feeder is
feeder uncovered (operating state).
0 V = level probe is covered (alarm sta-
tus).
5.8 X103:2 Heavy particle flap 24 V pulse signal = counting pulse for
pulse measuring position of the heavy particle
flap.
Bühler Group
AHZC-23401-1-2302-en-US
46 | Operating manual
Chapter 5
Installation
Dx X Signal Description
Dx X Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 47
Chapter 5
Installation
Dx X Signal Description
6.8 X103:2 Gravity flow di- 24 V pulse signal = counting pulse for
verter pulse signal measuring position of the gravity flow
diverter.
6.10 X103:6 Gravity flow di- 24 V = Move gravity flow diverter in the
verter of hammer direction of hammer mill 2.
mill 2
6.11 X103:7 Gravity flow di- 24 V = Move gravity flow diverter in the
verter of hammer direction of hammer mill 1.
mill 1
Bühler Group
AHZC-23401-1-2302-en-US
48 | Operating manual
Chapter 5
Installation
Jumpers Description
X99 OFF:
– Bus termination deactivated. All modules except the last
module on the bus.
ON:
– Bus termination activated. Last module on the bus.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 49
Chapter 5
Installation
3
4
4 0V 0V 0V 0V
X Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
50 | Operating manual
Chapter 5
Installation
X Signal Description
Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded cables.
Connect shield to electric terminal 4.
3
4
4 0V 0V 0V 0V
X Signal Description
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 51
Chapter 5
Installation
X Signal Description
Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded cables.
Connect shield to electric terminal 4.
X52
X54
X53
3
4
Bühler Group
AHZC-23401-1-2302-en-US
52 | Operating manual
Chapter 5
Installation
2 0 V_Line 0V
7
8
0 0 0 0 0 0
Display 0 Display 1
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 53
Chapter 5
Installation
Abbreviation Description
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
B Start signal of the main motors. This signal is not required while
starting via fieldbus (SYS.EIN).
D Analog setpoint specified for the mill power 0/4 … 20 mA. Is read
only when SYS.REM = REMA.
Bühler Group
AHZC-23401-1-2302-en-US
54 | Operating manual
Chapter 5
Installation
Abbreviation Description
F Alarm output
Function can be inverted via parameter SYS.AINV.
LINAK 1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
LINAK 2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
DFZK-2
(1) RD RD RD RD
(2) BK BK OR OR
(3) BU BU BK BK
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 55
Chapter 5
Installation
(4) BN BN BN BN
(5) VT VT VT VT
(6) YE YE GN GN
(7) GN GN YE YE
Abbrevia- Description
tion
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
C Analog setpoint specified for the hammer mill power 0/4 … 20 mA. Is
only read in, if SYS.REM = REMA.
F Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.
I Alarm output.
Function can be inverted via parameter SYS.AINV.
Bühler Group
AHZC-23401-1-2302-en-US
56 | Operating manual
Chapter 5
Installation
LINAK 1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
LINAK 2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
DFZK-2
(1) RD RD RD RD
(2) BK BK OR OR
(3) BU BU BK BK
(4) BN BN BN BN
(5) VT VT VT VT
(6) YE YE GN GN
(7) GN GN YE YE
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 57
Chapter 5
Installation
Abbrevia- Description
tion
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
C Analog setpoint specified for the hammer mill power 0/4 … 20 mA. Is
only read in, if SYS.REM = REMA.
H Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.
K Alarm output.
Function can be inverted via parameter SYS.AINV.
Bühler Group
AHZC-23401-1-2302-en-US
58 | Operating manual
Chapter 6
Operation
6 Operation
6.1 Operate keys and lamps
(1) (2)
(3)
(4)
(4)
Open cone
Prerequisites:
ü All locks facilitate the opening.
u Open the cone. Press and hold the key (1) until the cone opens.
Lamp does not light up: Cone is locked.
Lamp lights up: Cone is unlocked and can be opened.
Lamp is flashing: Plant control system sends a sieve change request.
When the key is pressed and the lamp is flashing quickly, the cone cannot be
opened because the locks prevent opening at the moment.
Machine stop
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 59
Chapter 6
Operation
USER
S5
S5
+ > 1s
S6
S5 S5 S5 S5 S5
… … … … … …
The control is operated via the USER parameter group and the subordinate parame-
ter groups such as MAIN, SYS, ADC, etc.
By default, the control's display changes to the first parameter of the "USER" param-
eter group after 600 s without user input.
1. Invoke subordinate parameter group. Press <Arrow> and <Data input> key for
1 s.
2. Change to the next subordinate parameter group. Press <Arrow> key.
3. Select parameters.
u Use the <Plus> key to go to the next parameter.
u Use the <Minus> key to go to the previous parameter.
4. Edit parameters. Press the <Data input> key for 1 s until the cursor or parameter
flashes. Then select the decimal place with the <Arrow> key.
5. Increase the parameter value. Press the <Plus> key.
6. Reduce parameter value. Press the <Minus> key.
7. Save the parameter value. Press the <Data input> key.
8. Invoke USER parameter group. Press <Arrow> key for 1 s.
Indexed parameters (e.g. ”USER.SET.x“: ”x“ is the index. ) ”USER.SET.x“ See
page 83.
1. Increase the index. Press and keep the <Function> held down and press the
<Plus> key.
2. Reduce the index. Press and keep the <Function> held down and press the <Mi-
nus> key.
Bühler Group
AHZC-23401-1-2302-en-US
60 | Operating manual
Chapter 7
Configuration
7 Configuration
7.1 Setting the application
Select the desired application with the ”SYS.TYP“ parameter. ”SYS.TYP“ See
page 99.
Prerequisites:
ü The application is not in operation.
Important
As a rule, the application of the control has already been set Ex Works.
u Execute the subsequent procedure only if the application has been reset or
has not been set.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 61
Chapter 7
Configuration
Important
This procedure is used to change important settings that have normally already
been set in the factory.
u Execute this procedure only if the most important parameters were not con-
figured Ex Works or if the control is to be reset.
1. If the Profibus is used, then set the parameter ”SYS.REM“ to REMP. ”SYS.REM“
See page 100.
2. Deactivate the 24 V inputs ”release of main motor“ and ”release of dosing“ in this
case (”SYS.EIN“ = OFF). ”SYS.EIN“ See page 100.
u If Profinet is used, then set the parameter ”SYS.REM“ to REME and ”SYS.ENET“
to P-NET. ”SYS.REM“ See page 100. ”SYS.ENET“ See page 105.
Bühler Group
AHZC-23401-1-2302-en-US
62 | Operating manual
Chapter 7
Configuration
The integrated control algorithm is based on the generally valid controller characteris-
tics. Various controllers can be implemented. We recommend not modifying the con-
troller type because not every controller type can be adapted for each controlled sys-
tem.
Use the Ziegler Nichols procedure to optimize the system. The temporal course of the
actual amount is recorded after modifying the control variable. This is known as the
step response. The control parameters are determined on the basis of this response.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 63
Chapter 7
Configuration
2. The course of the measurand is recorded. Wait until a stationary status levels off
in a controlled system with balancing or a constant rise is achieved in systems
without balancing.
3. The tangents are drawn in and the factors calculated depending on the controller
type. The times ”Tu“ and ”Tg“ are ruling for calculating the factors.
Example: Controlled system with balancing
(1) (2) (3) (4)
45
40
35
30
25
(5)
20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Tu Tg
Ks = Tg × As 270[s] × 50
= = 1,07
Tu × y 315[s] × 40
P controller Ks − −
PI controller 0.8 Ks 3 Tu −
Bühler Group
AHZC-23401-1-2302-en-US
64 | Operating manual
Chapter 7
Configuration
140
120
100
80
T
60
40
20
(3)
0
0 5 10 15 20
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 65
Chapter 7
Configuration
200
180
160
140
120
100
80
60
40 (4)
20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Tu Ti
P controller 0.5/Ki − −
Bühler Group
AHZC-23401-1-2302-en-US
66 | Operating manual
Chapter 7
Configuration
u With parameter ”EBD.1317.AI“, set the temperature sensor type for every config-
ured temperature. ”EBD.1317.AI“.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 67
Chapter 7
Configuration
1. Calibrate temperatures.
u With the default setting, the error is < 2 %.
u If the error is greater, check the configuration again.
2. For the PT100 or PT1000 sensors, correct only the offset error with the parame-
ter ”ADCT.OFFSET“. Modify the offset correction in the working area of the ma-
chine.
3. Measure the current value at the input. (0/4 … 20 mA or 0 … 5 V/10 V)
u Display the current value with parameter ”EBD.1317.AIN“.
u Correct deviations using parameter ”EBD.1317.AIADJ“.
If there is no deviation, the temperature is displayed correctly.
u If no measuring instrument is available, align with parameter ”ADCT.OFFSET“
as well.
Starting delay 3 s
Bühler Group
AHZC-23401-1-2302-en-US
68 | Operating manual
Chapter 7
Configuration
Important
u Adjust the other parameters of the frequency converter to the motor.
u Lock the frequency converter with motor contactor.
u Release the frequency converter only when the main motors are switched
on.
FULL (FULL)
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 69
Chapter 7
Configuration
FULL (FULL)
FULL (FULL)
FULL (FULL)
CTL- (COMMAND)
FULL (FULL)
Bühler Group
AHZC-23401-1-2302-en-US
70 | Operating manual
Chapter 7
Configuration
FULL (FULL)
FULL (FULL)
Connection example:
Alarm input DI 0.11 (alarm ”A065 FC“) is active only if ”TCON.FEED“ = FC_SLD.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 71
Chapter 7
Configuration
0 = Alarm
0 - 1 kHz
0 - 100 Hz
PTC
Bühler Group
AHZC-23401-1-2302-en-US
72 | Operating manual
Chapter 7
Configuration
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 73
Chapter 7
Configuration
Product
Grid FU
Hammer mill
Product discharge
Important
u If the motor is overloaded, the frequency converters will reduce the speed.
This will reduce the throughput and the hammer mill can run even fuller.
u Maximum permissible frequency of hammer mill = 60 Hz.
Bühler Group
AHZC-23401-1-2302-en-US
74 | Operating manual
Chapter 7
Configuration
Fig. 7.6 Configuration menu for analog output AQ1 and AQ2
Tab AI/AQ
In order to display the motor current in amperes and the motor torque in % in the up-
per strip of the graphic terminal screen, make the following setting in the 8.4 Cus-
tomization (CUS):
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 75
Chapter 7
Configuration
Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.
Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.
Bühler Group
AHZC-23401-1-2302-en-US
76 | Operating manual
Chapter 7
Configuration
7.11.1 Control on the discharge conveyor with fan (pneumatic suction conveying
system)
The parameter ”TCON.REG_M2“ must be set to ON. ”TCON.REG_M2“ See
page 94.
The motor load characteristics for the discharge conveyor with fan behave in the op-
posite fashion to a discharge conveyor with a mechanical component. The current
transformer value (ADC.CON 1.2) should lie marginally over the nominal current of the
fan motor.
The load for the discharge conveyor with fan is calculated as shown in the graphic
below:
(USER.LOAD.1)[%]
7.11.1.1 Load control by current measurement of the fan motor (control with DOL
starting or soft starter)
1. Read the current of the fan motor in case of a “minimum load” (maximal current)
in parameter ”ADC.I 1.2“. ”ADC.I 1.2“. This takes place in case of a maximum air
volume and without product. Round up this read current value by 5 % and enter
with a negative sign (–) for ”ADC.MOT 1.2“. ”ADC.MOT 1.2“. Example: Enter dis-
play 100 A → ADC.MOT 1.2 = –105 A (105 % of 100 A).
2. Read the current of the fan motor in case of “maximum load” (minimum current)
in parameter ”ADC.I 1.2“. This takes place in case of a minimum air volume and
with a high product throughput at which the hammer mill sieve slowly gets
clogged and the subsequent discharge conveyor is disrupted. In order to simulate
this state, place a board upstream the air inlet at the gravity separator and place
paper bags on the other air inlets. Enter this read current value for ”ADC.I0 1.2“.
3. After starting the fan, check the load on the control unit DFCQ (USER.LOAD.1).
Approx. 0 % should be displayed in case of a maximum air volume and without
product.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 77
Chapter 7
Configuration
7.11.1.2 Load control via the motor torque of the fan motor (control with frequency
converter)
The motor torque should be used for the control instead of the current while using a
frequency converter. An analog output of the frequency converter is used for the out-
put of the motor torque. Thus the current transformer is omitted.
The following example for the configuration of the analog outputs is applicable for
Schneider ATV 930.
Fig. 7.8 Configuration menu for analog output AQ1 and AQ2
Tab AI/AQ
Bühler Group
AHZC-23401-1-2302-en-US
78 | Operating manual
Chapter 7
Configuration
Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.
7.11.1.3 Load control by air volume measurement with dynamic pressure sensor (control
fan motor with DOL starting, soft starter or frequency converter)
A dynamic pressure probe is used for the air volume measurement, which records
the difference between a static and dynamic pressure and is displayed in Pa (Pascal)
[N/m2] by means of a differential pressure transmitter. The square rooted 4 … 20 mA
- output signal is forwarded to the control system. This means that the output signal
in mA is proportional to the root of the dynamic pressure and with that approximately
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 79
Chapter 7
Configuration
then the air velocity is 1.06 × 24.49 = 25.96 m/s. If φ is not known, or for checking
purposes, the air velocity can be measured with an anemometer and calculated with
Bühler Group
AHZC-23401-1-2302-en-US
80 | Operating manual
Chapter 7
Configuration
NOTICE
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 81
Chapter 8
Parameters
8 Parameters
8.1 Notes for the parameter details
The letter after ”Step“ indicates to what extent the corresponding parameter is locked
against modification when the input lock is activated. The following values apply:
Step Description
The input lock is set with the ”SYS.LOCK“ parameter. It is deactivated by default.
”SYS.LOCK“ See page 102.
P-Pos: 0 Unit: %
P-Pos: 1 Unit: %
Bühler Group
AHZC-23401-1-2302-en-US
82 | Operating manual
Chapter 8
Parameters
P-Pos: 2 Unit: A
Display
With a hammer mill:
I1 XXX.X A
With two hammer mills:
XXX.X A XXX.X A
Left : Hammer mill 1 on the right: hammer mill 2
P-Pos: 3 Unit: %
Unit: Hz
Unit: %
Unit: h
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 83
Chapter 8
Parameters
Unit: h
Unit: °C
Unit: %
Unit: Hz
Bühler Group
AHZC-23401-1-2302-en-US
84 | Operating manual
Chapter 8
Parameters
Step: L Unit: Hz
u Set MAN.FSLD to 5 % before starting the feed roller. Otherwise, the slide gate
will touch against the roller.
u Switch between manual and automatic. Press <Function> key.
Step: L Unit: %
Step: L Unit: %
Value Function
ON Fan activated.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 85
Chapter 8
Parameters
Value Function
ON Discharge activated.
Value Function
ON Discharge activated.
Value Function
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
86 | Operating manual
Chapter 8
Parameters
Step: L Unit: %
Value Function
Step: L Unit: %
Value Function
MAN.POSDIF.x Difference in position between linear cylinder on cone, left and right
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 87
Chapter 8
Parameters
MAN.POSDIF.x Difference in position between linear cylinder on cone, left and right
MAN.RUNH_R.x Operating hours for clockwise direction of rotation, main motor mill x
Unit: h
Unit: h
Unit: mm
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
88 | Operating manual
Chapter 8
Parameters
Value Function
Value Function
1 1 hammer mill
2 2 hammer mills
Value Function
BR FC Frequency converter without change of direction when braking. (Standard for fre-
quency converter Altivar 71 or Altivar 930 via CAN)
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 89
Chapter 8
Parameters
Value Function
AIN The motor current is measured via the analog input of the control.
Hammer mill 1: AI 0.0
Hammer mill 2: AI 0.4
REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/Bytes 14 … 15
Value Function
AIN The motor current is measured via the analog input of the control.
Discharge conveyor 1: AI 0.1
Discharge conveyor 2: AI 0.5
REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/Bytes 16 … 17
Value Function
OFF No monitoring.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
90 | Operating manual
Chapter 8
Parameters
Step: L Unit: Hz
Step: L Unit: Hz
Value Function
REG Regulates to a setpoint. The feed gap and the speed of the feed roller are changed.
This will enable the largest dosing range to be covered. An attempt is made to op-
erate the feed roller in the optimal speed range TCON.FMIN and TCON.FMAX. The
speed is monitored every 5 s and if necessary, the feed gap is adjusted to bring the
speed back within the optimal range.
FREQ Regulates to a setpoint. The feed gap remains at TCON.SMAX. It is not modified.
The dosing quantity is only influenced by the feed roller (0 … 100 Hz). This limits the
dosing range but can also be helpful for special applications. Modifications cannot
be reacted to very quickly in this mode, as the influence of the feed roller is less
than the influence of the roller gap adjuster.
SLIDE Regulates to a setpoint. The feed roller speed remains at TCON.FMIN. It is not
modified. The dosing quantity is only influenced by the feed gap
(TCON.SMIN … TCON.SMAX). The smallest change in the feed gap is determined
by the mechanics. This mode is not recommended for products which require in-
tensive grinding.
CONST Overload is regulated. If the actual mill load is less than the set point, no control will
occur. Therefore, the control will not be activated until the mill load has exceeded
the set point. The controller is deactivated again when the load falls below the set
point again and the standard settings have been reached again. The standard val-
ues for the feed roller and the feed gap are predefined with TCON.FMAX and
TCON.SMAX.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 91
Chapter 8
Parameters
Value Function
ON The gravity flow diverter is then converted automatically based on the 24 V release
inputs (DI 0.4 and DI 0.16). In the case of fieldbus connection, the gravity flow di-
verter is changed over via control bits 1.2 and 2.2. The flap changes the position
when one or both hammer mills are released. If no hammer mill is released, the flap
remains in its current position and is adjusted when a modification is made.
Step: L Unit: %
Value Function
0 A limit switch must be available for the middle position. In this case, the pulse out-
put of linear cylinder (DI 6.8) is ignored. The limit switch for the middle position is
connected to DI 6.9.
>0 Value for the middle position of the flap. In this case, the position of the flap is deter-
mined by means of the pulse output of the linear cylinder (DI 6.8).
Value Function
ON Monitoring activated.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
92 | Operating manual
Chapter 8
Parameters
Value Function
ON Monitoring activated.
Value Function
TCON.FC_SLD Linear cylinder connection location for feed gap adjustment at throughput
control
Value Function
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 93
Chapter 8
Parameters
Value Function
1 1 discharge conveyor
2 2 discharge conveyors
Step: L Unit: %
Value Function
0 Monitoring deactivated.
Value Function
ON_0 Level probe is fitted. 0 V = dosing release (e.g. level probe not covered).
ON_1 Level probe is fitted. 24 V = dosing release (e.g. level probe not covered).
Value Function
ON Control is to the motor with the greater utilization. Main motor or discharge.
Bühler Group
AHZC-23401-1-2302-en-US
94 | Operating manual
Chapter 8
Parameters
Value Function
ON Monitoring activated.
Step: L Unit: Hz
The feed slide gate regulates if the value is exceeded. If TCON.FEED = SCREW or
TCON.FEED = FC, TCON.FMAX is the maximum frequency.
Step: L Unit: Hz
The feed slide gate readjusts when the value falls below the set value. If
TCON.FEED = SCREW or TCON.FEED = FC, TCON.FMIN is the minimum
frequency.
Step: L Unit: %
Step: L Unit: %
Step: L Unit: %
The control always starts with this slide gate opening. When this value increases,
the start becomes faster, but also presents the danger of overshooting.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 95
Chapter 8
Parameters
Value Function
0 TCON.SINI deactivated.
TCON.SMIN slide gate opening start value.
Step: L Unit: %
Step: L Unit: °C
Step: L Unit: s
Bühler Group
AHZC-23401-1-2302-en-US
96 | Operating manual
Chapter 8
Parameters
Step: L Unit: s
Step: L Unit: s
Step: L Unit: s
If TCON.DFCQ = FCM, the feeder device starts once the release input has been
activated. If TCON.DFCQ = DFZK, the feeder device starts once the inlet probe DI
5.0 signals that it is covered.
Step: L Unit: s
If TCON.DFCQ = FCM, the feeder unit stops once the release input has been
deactivated. If TCON.DFCQ = DFZK, then the feeder unit stops once the inlet probe
DI 5.0 signals that it is uncovered.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 97
Chapter 8
Parameters
Step: L Unit: s
Value Function
0 Function deactivated.
Opening only with push-button switches on-site.
Step: L Unit: s
Step: L Unit: s
Bühler Group
AHZC-23401-1-2302-en-US
98 | Operating manual
Chapter 8
Parameters
SYS.TYP Application
Value Function
NOAPP No application.
No signal from the outputs (e.g. when first switching on after loss of data).
HYMIXP Conditioning HYMIX Plus (feeder DDHA and conditioner DCHA Plus).
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 99
Chapter 8
Parameters
Value Function
REMS Remote control – Serial: Setpoint specification via the serial interface.
Not supported.
REMP Remote control – Profibus DP: Control exclusively via Profibus. Setpoint specifica-
tion and control signals via Profibus active.
SYS.EIN 24 V input release main motor, release feeding and mill brakes
Value Function
OFF The inputs do not have a function. Signals come via fieldbus.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
100 | Operating manual
Chapter 8
Parameters
Value Function
STOP Standby when stopped and if no key is pressed for 10 minutes. An LED flashes.
ON Standby if no key is pressed for 10 minutes. An LED flashes when stopping. Run-
ning light with one LED each if not stopped.
The data appears by default on the display after 600 s if no button is pressed during
this time period. The standard time for the change (600 s) can be modified in the
SYS.SDT parameter. In addition, SYS.SD is used to define what is displayed in the
USER.ACTUAL parameter.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 101
Chapter 8
Parameters
Step: L Unit: s
Value Function
0 No automatic change.
>0 The display switches to the standard operating parameter if no key is pressed dur-
ing the time that has been set. ”SYS.SD“
The "SYS.LOCK" parameter prevents certain parameters from being entered and
modified. It is always possible to display the parameters.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
102 | Operating manual
Chapter 8
Parameters
Value Function
Value Function
ON Alarms are acknowledged only with the <Clear alarm> (S3) key, via the serial inter-
face, fieldbus or the 24 V input "Delete alarm".
Value Function
ON 0 V upon alarm.
Value Function
Default value: 0
Step: L Unit: mA
u Select additional analog outputs. Press and keep the <Function> held down
and press the <Plus> key.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 103
Chapter 8
Parameters
Default value: 0
Step: L Unit: mA
u Select additional analog inputs. Press and keep the <Function> held down and
press the <Plus> key.
u Note the adjustment at jumpers X62.
Step: L Unit: %
u Select additional analog outputs. Press and keep the <Function> held down
and press the <Plus> key.
Step: L Unit: %
u Select additional analog inputs. Press and keep the <Function> held down and
press the <Plus> key.
The Bühler standard baud rate of 200 and CAN-Open baud rates are supported.
– 200
– 10
– 20
– 50
– 125
– 250
– 500
– 800
– 1000
Bühler Group
AHZC-23401-1-2302-en-US
104 | Operating manual
Chapter 8
Parameters
Value Function
Value Function
Step: L
Step: L Unit: A
Step: L Unit: A
Step: L Unit: A
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 105
Chapter 8
Parameters
Step: L Unit: A
Step: L Unit: A
Step: L Unit: A
Step: L Unit: A
Step: L Unit: A
Bühler Group
AHZC-23401-1-2302-en-US
106 | Operating manual
Chapter 8
Parameters
Step: L Unit: A
u Apply present current as no-load current. Press the <Function> key for 10 s.
Step: L Unit: A
u Apply present current as no-load current. Press the <Function> key for 10 s.
Step: L Unit: A
u Apply present current as no-load current. Press the <Function> key for 10 s.
Step: L Unit: A
u Apply present current as no-load current. Press the <Function> key for 10 s.
Step: L Unit: %
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 107
Chapter 8
Parameters
Unit: °C
Unit: °C
Unit: °C
Unit: °C
Default value: °C
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
108 | Operating manual
Chapter 8
Parameters
u Select analog inputs. Press the <Function> and the <Plus> key.
Jumper X298/X299:
Value Function
80 mV Differential voltage measurement for DMS 0/1 2/3 4/5 6/7 (Signal +/Signal –)
± 80,000 mV [mV]
u If options with analog inputs are available, select the desired input. Press the
<Function> and the <Plus> or <Minus> key.
Unit: %
u Select analog inputs. Press the <Function> and the <Plus> key.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 109
Chapter 8
Parameters
Default value: 0
Unit: mA
u Select analog outputs. Press the <Function> and the <Plus> key.
Value Function
Unit: mA
u Select analog outputs. Press the <Function> and the <Plus> or <Minus> key.
u For tests, press the <Data input> key.
u If ”SERV.SERM“ = ON, set the current.
Unit: %
u Select analog outputs. Press the <Function> and the <Plus> key.
Unit: °C
u Select the module. Press the <Function> and the <Plus> key.
Controller Description
Bühler Group
AHZC-23401-1-2302-en-US
110 | Operating manual
Chapter 8
Parameters
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Step: L
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 111
Chapter 8
Parameters
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Value Function
P P controller
I I controller
PI PI controller
PD PD controller
See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.
Value Function
P P controller
I I controller
PI PI controller
PD PD controller
Step: L Unit: ms
This time has no influence on the controller speed but merely serves as a basis for
the time. A control action is always executed after a controller interval.
Step: L Unit: ms
This time has no influence on the controller speed but merely serves as a basis for
the time. A control action is always executed after a controller interval.
Bühler Group
AHZC-23401-1-2302-en-US
112 | Operating manual
Chapter 8
Parameters
Step: L
Value Function
Step: L Unit: s
The device stops metering if no more communication takes place during the
timeout time.
The monitoring system is active only when ”SYS.REM“ = REMP.
Value Function
Value Function
NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.
EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 113
Chapter 8
Parameters
EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.
Value Function
Use analysis filter to select a data set from the Profibus protocol. Its value is
displayed via PBDP.DAT.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
114 | Operating manual
Chapter 8
Parameters
Unit: BYTE
Value of the data record defined with the filter. The value is updated when the
corresponding data record is accessed. Note "PBDP.DSCNT" access counter to
check.
The counter is increased by 1 each time the dataset defined by the filter is
accessed.
Current address for Profinet communication. The MEAG registers with this address.
meag-123 (ENET.ADR = 123)
Only available with ProfiNet - ”SYS.ENET“ - P-NET.
In addition, the current bus status is shown.
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 115
Chapter 8
Parameters
Value Function
NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.
EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.
EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.
ENET.IP IP Address
Display of the IP address currently set or of the server status. Only available with
EtherNet/IP - "SYS.ENET" - ETH-IP.
Value Function
Display showing the subnet mask currently set. Only available with EtherNet/IP -
"SYS.ENET" - ETH-IP.
Display showing the Standard Gateway currently set. Only available with EtherNet/
IP - "SYS.ENET" - ETH-IP.
Step: L
Bühler Group
AHZC-23401-1-2302-en-US
116 | Operating manual
Chapter 8
Parameters
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Step: L
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Step: L
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 117
Chapter 8
Parameters
Step: L Unit: s
The device triggers an alarm if no communication has taken place within the
specified time.
The monitoring is active only when ”SYS.REM“ = REME.
Value Function
Default value: ON
Bühler Group
AHZC-23401-1-2302-en-US
118 | Operating manual
Chapter 8
Parameters
Value Function
NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.
EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.
EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.
TCP.IP IP Address
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 119
Chapter 8
Parameters
Step: L
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Step: L
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Step: L
u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.
Bühler Group
AHZC-23401-1-2302-en-US
120 | Operating manual
Chapter 8
Parameters
Step: L Unit: s
The device triggers an alarm if no communication has taken place within the
specified time.
Monitoring is only active when ”SYS.REM“ = REMTCP.
Step: L
SERV.DATE Date
SERV.TIME Time
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 121
Chapter 8
Parameters
The last alarm is displayed in the form ERR.0 A006. The next to last alarm is
displayed with ERR.–1 etc.
u Display older inputs. Press and keep the <Function> held down and press the
<Minus> key.
u Display more recent inputs. Press and keep the <Function> held down and
press the <Plus> key.
u Display the details (alarm text, date and time) of the input by turns. Press and
keep the <Function> key held down.
For operation, see the SERV.ERR parameter. All events (incl. alarms) are displayed.
For operation, see the SERV.ERR parameter. Alarms and events are displayed
mixed.
Display on the left: Current CPU utilization in %. Display on the right: Maximum time
in [ms] for a program execution.
Value Function
ON Function activated.
Bühler Group
AHZC-23401-1-2302-en-US
122 | Operating manual
Chapter 8
Parameters
Value Function
ON Function activated.
Inputs are simulated by means of the output signals. Program and control system
are tested without product.
Value Function
ON Function activated.
Value Function
ON Function activated.
Value Function
ON Function activated.
Also applies to options with digital inputs (e.g. 1.0 ... 1.11).
u Select input (0.0 ... 0.x). Press and keep the <Function> held down and press
the <Plus> or <Minus> key.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 123
Chapter 8
Parameters
u Select output (0.0 ... 0.x). Press and keep the <Function> held down and press
the <Plus> or <Minus> key.
u Set or delete outputs. If ”SERV.SERM“ = ON: Press <Data input> key.
Unit: V/mA
u Select input. Press and keep the <Function> held down and press the <Plus>
or <Minus> key.
Unit: mA
Present current.
u Select output. Press and keep the <Function> held down and press the <Plus>
or <Minus> key.
u Set the output current. If ”SERV.SERM“ = ON. Press <Data input> key.
Unit: °C
Bühler Group
AHZC-23401-1-2302-en-US
124 | Operating manual
Chapter 8
Parameters
Serial interface 1 RS-485 to host or other use. If the HOST.SIO parameter is not
activated for the corresponding interface, " --- OFF" is displayed.
The following elements are displayed from left to right:
– Communication counter. Is raised by 1 (0 … 9999) per communication.
– Bus activity. ”*“ means that a signal was received.
– Command. Identification of the data with different telegrams. ”-“ means that a
command with lowercase letters was received.
– Error number:
– 0 = no error
– 1 = timeout or no answer
– 2 = undefined command or undefined identification
– 3 = incorrect checksum
– 4 = incorrect data length
Serial interface 2 RS-485 to host or other use. For description, see "SERV.SIO1".
Display options:
Value Function
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 125
Chapter 8
Parameters
Step: L
Bühler Group
AHZC-23401-1-2302-en-US
126 | Operating manual
Chapter 9
Alarms and messages
Cause Correction
A002 RAM
Cause Correction
A003 RUNTIME
Cause Correction
Runtime error during the program u Switch device off and on.
execution. Software or hardware u If alarm repeats, note SERV.SADR and contact Bühler
problem. Group customer service.
u Initialize data or load new program version.
u If alarm repeats, replace main circuit board.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 127
Chapter 9
Alarms and messages
A004 WATCHDOG
Cause Correction
A005 NO 24 V
Cause Correction
A006 DATALOST
Cause Correction
Data loss in the battery-backed u Check the fit of the battery socket.
RAM. The parameters and various u If new software has been loaded, acknowledge the alarm.
data are reset to the original value.
Can occur during software u Switch off the power to the control unit. Wait for 15 minutes.
downloads. Switch on the control system. If the alarm reoccurs, replace
the battery.
Cause Correction
W013 EXTDISP
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
128 | Operating manual
Chapter 9
Alarms and messages
A014 PROFI-DP
Cause Correction
W017 DISPLAY
Cause Correction
A018 BATTERY
Cause Correction
Cause Correction
Faulty communication with a CAN u Note the error display on the CAN module. Observe the
module. t = A (EBD 1317) description of CAN expansion modules in the appendix.
t = D (EBD 1318/20) u Check the wiring.
t = L (EBD 1319)
u Check address setting on CAN modules.
n = 1 … 31 (module address). If
CAN COM is displayed, then the u Check whether configured CAN modules are present.
entire bus is faulty.
Cause Correction
A CAN module transmits an error. u Note the error display on the CAN module. Continue in
t = A (EBD 1317) accordance with the module description in the appendix..
t = D (EBD 1318/20) u Replace the CAN module.
t = L (EBD 1319)
n = 1 … 31 (module address).
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 129
Chapter 9
Alarms and messages
Cause Correction
A CAN module has an output error. u Note the error display on the CAN module. Continue
t = D (EBD 1318/20) according to the module description in the appendix.
t = L (EBD 1319) n = 1 … 31 (modul u Check the wiring of the digital outputs.
e address).
u Check whether the alarm is cleared when the outputs are
unplugged.
W075 WARNTEMP
Cause Correction
The temperature in the device is too u Check the temperature in the device.
high. The temperature sensor is u Ensure sufficient ventilation.
located on the display circuit board.
A076 HIGHTEMP
Cause Correction
A077 DIGOUT
Cause Correction
One or more outputs deviate from u Remove external voltage or overload sources.
the expected state.
A020 HOPP
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
130 | Operating manual
Chapter 9
Alarms and messages
A021 INC
Cause Correction
No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 5.4. LED flashes during segment gate
movement.
A022 END P
Cause Correction
The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 5.5 or DI 0.9 input must then show 24 V.
A023 CTEMP
Cause Correction
The temperature sensor of the u The hammer mill was operated for too long in idle state.
hammer mill supplies a temperature Wait until temperature is below TCON.TMAX.
that is above the limit value u Configure correct sensor type for 1317.AI1.0.
TCON.TMAX.
u Connect sensor correctly. Check wiring of PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.
A024 VIB_W
Cause Correction
The vibration value of the hammer u Find the mechanical cause for excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_W within the time u The machine can continue to be operated. During the next
TCON.T VIB. stop, find the cause.
A025 MSTOP
Cause Correction
A027 STILL
Cause Correction
The standstill monitoring of the u DI 1.3 must show 24 V when motor is stationary.
hammer mill is reporting movement
from the motor. The error is only
displayed when attempting to open
the cone.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 131
Chapter 9
Alarms and messages
A028 COPEN
Cause Correction
The cone of the hammer mill is not u DI 1.4 must show 24 V when cone is closed.
locked or the Move cone key was
pressed for too long.
A029 MOTOR
Cause Correction
The main motor of the hammer mill u Once the main motors have been started up, a motor
was started and there has been no current must be measured within 10 s. After the main
response. motors have been stopped, no motor current may be
measured after a delay of 5 minutes. Check whether the
motor contactor is disconnecting and whether the actual
value input AI0.0 is wired correctly.
A030 S < 4 mA
Cause Correction
No signal at the setpoint input of the u The AI0.3 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.3 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.
A031 A < 4 mA
Cause Correction
No signal at the actual value input of u The AI0.0 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill signal is used, set SYS.AI.0 to 0 mA.
A033 LIMIT
Cause Correction
The limit value TCON.TRANS was u Check if hammer mill discharge conveyor is clogged or drive
exceeded for over 5 s. The is blocked.
discharge conveyor is overloaded. u Check discharge motor configuration of ADC.MOT 1.2 and
ADC.CON 1.2.
A034 V < 4 mA
Cause Correction
No signal on the vibration sensor of u The AI1.1 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set 1317.AI1.2 to 0 mA. If no vibration sensor
is present, set TCON.VIBR = OFF.
Bühler Group
AHZC-23401-1-2302-en-US
132 | Operating manual
Chapter 9
Alarms and messages
A035 TSTART
Cause Correction
The discharge conveyor of the u When the discharge conveyor is started, a response must
hammer mill has not started. The be issued within 10 s. If there is no response, the DO 0.7
release for the discharge of the output must be connected to the DI 0.14 input via a jumper
hammer mill is active and there has wire.
been no response.
A036 CTIGHT
Cause Correction
The cone of the hammer mill is u Make sure that both cylinders are in the same position.
jammed. The positions of both cone Then reset the difference with the MAN.POSDIF parameter.
linear cylinders differ by more than
30 mm from each other. If the
position difference of both cylinders
is too great, the cone is usually
jammed. It is also possible that the
pulse signal of a cylinder is not being
measured.
A037 CINC
Cause Correction
No position pulses on the cone of u Check the pulse signal wiring of the linear cylinder on the
the hammer mill. cone.
A038 VIB_A
Cause Correction
The vibration value of the hammer u Find the mechanical cause for the excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.
A039 MOT_TEMP
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 133
Chapter 9
Alarms and messages
A120 ATVCOM
Cause Correction
A121 ATV
Cause Correction
The frequency converter of the main u Read the error cause off the frequency converter display.
motor of hammer mill 1 reports an Correct error in accordance with the operating instructions
error of frequency converter.
u Check address settings on the converter: Hammer mill 1 =
address 1; Hammer mill 2 = address 2.
A040 HOPP
Cause Correction
A041 INC
Cause Correction
No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 6.4. LED flashes during segment gate
movement.
A042 END P
Cause Correction
The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 6.5 or DI 0.21 input must then show 24 V.
Bühler Group
AHZC-23401-1-2302-en-US
134 | Operating manual
Chapter 9
Alarms and messages
A043 CTEMP
Cause Correction
The temperature sensor of the u The hammer mill was operated for too long in idle state.
hammer mill supplies a temperature Wait until temperature is below TCON.TMAX.
that is above the limit value u Configure correct sensor type for 1317.AI2.0.
TCON.TMAX.
u Connect sensor correctly. Check wiring of PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.
A044 VIB_W
Cause Correction
The vibration value of the hammer u Find the mechanical cause for excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_W within the time u The machine can continue to be operated. During the next
TCON.T VIB. stop, find the cause.
A045 MSTOP
Cause Correction
A047 STILL
Cause Correction
The standstill monitoring of the u DI 2.3 must show 24 V when motor is stationary.
hammer mill is reporting movement
from the motor. The error is only
displayed when attempting to open
the cone.
A048 COPEN
Cause Correction
The cone of the hammer mill is not u DI 2.4 must show 24 V when cone is closed.
locked or the Move cone key was
pressed for too long.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 135
Chapter 9
Alarms and messages
A049 MOTOR
Cause Correction
The main motor of the hammer mill u Once the main motors have been started up, a motor
was started and there has been no current must be measured within 10 s. After the main
response. motors have been stopped, no motor current may be
measured after a delay of 5 minutes. Check whether the
motor contactor is disconnecting and whether the actual
value input AI0.4 is wired correctly.
A050 S < 4 mA
Cause Correction
No signal at the setpoint input of the u The AI0.7 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.7 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.
A051 A < 4 mA
Cause Correction
No signal at the actual value input of u The AI0.4 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.4 to 0 mA.
A053 LIMIT
Cause Correction
The limit value TCON.TRANS was u Check if hammer mill discharge conveyor is clogged or drive
exceeded for over 5 s. The is blocked.
discharge conveyor is overloaded. u Check discharge motor configuration of ADC.MOT 2.2 and
ADC.CON 2.2.
A054 V < 4 mA
Cause Correction
No signal on the vibration sensor of u The AI2.1 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set 1317.AI1.3 to 0 mA. If no vibration sensor
is present, set TCON.VIBR = OFF.
A055 TSTART
Cause Correction
The discharge conveyor of the u When the discharge conveyor is started, a response must
hammer mill has not started. The be issued within 10 s. If there is no response, the DO 0.11
release for the discharge of the output must be connected to the DI 0.26 input via a jumper
hammer mill is active and there has wire.
been no response.
Bühler Group
AHZC-23401-1-2302-en-US
136 | Operating manual
Chapter 9
Alarms and messages
A056 CTIGHT
Cause Correction
The cone of the hammer mill is u Make sure that both cylinders are in the same position.
jammed. The positions of both cone Then reset the difference with the MAN.POSDIF parameter.
linear cylinders differ by more than
30 mm from each other. If the
position difference of both cylinders
is too great, the cone is usually
jammed. It is also possible that the
pulse signal of a cylinder is not being
measured.
A057 CINC
Cause Correction
No position pulses on the cone of u Check the pulse signal wiring of the linear cylinder on the
the hammer mill. cone.
A058 VIB_A
Cause Correction
The vibration value of the hammer u Find the mechanical cause for the excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.
A059 MOT_TEMP
Cause Correction
A140 ATVCOM
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 137
Chapter 9
Alarms and messages
A141 ATV
Cause Correction
The frequency converter of the main u Read the error cause off the frequency converter display.
motor of hammer mill 2 reports an Eliminate error according to operating instructions of
error. frequency converter.
u Check address setting on converter: hammer mill 1 =
address 1; hammer mill 2 = address 2.
A060 POWER
Cause Correction
A 24 V miniature circuit breaker has u Check whether the miniature circuit breakers of the control
responded. have triggered.
u DI 0.23 must feature 24 V.
A061 UPSON
Cause Correction
A062 ATVCOM
Cause Correction
A063 ATV
Cause Correction
The frequency converter of the main u Read the error cause off the frequency converter display.
motor is reporting an error. Correct error according to operating instructions of
frequency converter.
u Check address settings on converter: Hammer mill 1 =
address 1; Hammer mill 2 = address 2.
Bühler Group
AHZC-23401-1-2302-en-US
138 | Operating manual
Chapter 9
Alarms and messages
A065 FC
Cause Correction
The frequency converter of the feed u Read the error number off the frequency converter.
roller is reporting an error. Determine the cause by using the operating manual of the
frequency converter.
u The alarm is active only when TCON.FEED = FC_SLD.
A066 DOOR
Cause Correction
Magnetic door is not closed. u Check whether the magnetic door is closed properly. DI 5.2
must show 24 V.
A067 FLAP
Cause Correction
Error in the flap control unit. u Check whether the gravity flow diverter adjustment cylinder
is moving.
u Use the LED of DI 6.8 to check whether pulses are arriving
on the I/O module. LED flashes during the flap movement.
A068 PART
Cause Correction
Defect in the heavy particle u Check whether the heavy particle cylinder is at the limit
separation. position. DI 5.9 must show 24 V in the limit position.
A090 FAN
Cause Correction
The fan was started and there has u When the fan is started, a response must be issued within
been no response. 10 s. If there is no response, the DO 0.13 output must be
connected to the DI 0.12 input via a jumper. Output
DO 0.13 = 24 V → Fan is running. Input DI 0.12 = 24 V →
Fan is running.
A091 PLANT
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 139
Chapter 9
Alarms and messages
A092 SAFES
Cause Correction
A021 INC
Cause Correction
No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 5.4. LED flashes during segment gate
movement.
A022 END P
Cause Correction
The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 5.5 or DI 0.9 input must then show 24 V.
A030 S< 4 mA
Cause Correction
No signal at the setpoint input of the u The AI0.3 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.3 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.
A031 A < 4 mA
Cause Correction
No signal at the actual value input of u The AI0.0 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.0 to 0 mA.
A041 INC
Cause Correction
No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 6.4. LED flashes during segment gate
movement.
Bühler Group
AHZC-23401-1-2302-en-US
140 | Operating manual
Chapter 9
Alarms and messages
A042 END P
Cause Correction
The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 6.5 or DI 0.21 input must then show 24 V.
A050 S < 4 mA
Cause Correction
No signal at the setpoint input of the u The AI0.7 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.7 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.
A051 A < 4 mA
Cause Correction
No signal at the actual value input of u The AI0.4 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.4 to 0 mA.
A065 FC
Cause Correction
The frequency converter of the feed u Read the error number off the frequency converter.
roller is reporting an error. Determine the cause by using the operating manual of the
frequency converter.
u The alarm is active only when TCON.FEED = FC_SLD.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 141
Chapter 9
Alarms and messages
Display State
− Standard operation.
The middle segments are displayed There are no messages.
cyclically from top to bottom.
In the following table, the error messages are listed on the seven-segment after the
display. If an ”E“ flashes alternately with another symbol, an error message is pend-
ing. ”E d“ means, for example, that ”E“ und ”d“ are flashing alternately.
Cause Correction
Error in the FLASH EPROM. No u Switch printed circuit board to de-energized state. Clean
application present. No application with compressed air.
started. u Restart. If the error occurs again, replace the printed circuit
board.
Cause Correction
Error in the DRAM memory. No u Switch printed circuit board to de-energized state. Clean
application starts. For example, as a with compressed air.
result of a short-circuit on the PCB u Restart. If the error occurs again, replace the printed circuit
due to copper residue. board.
Bühler Group
AHZC-23401-1-2302-en-US
142 | Operating manual
Chapter 9
Alarms and messages
Cause Correction
Error in battery RAM memory. No u Switch printed circuit board to de-energized state. Clean
application starts. with compressed air.
u Restart. If the error occurs again, replace the printed circuit
board.
EL
Cause Correction
Defective software version installed. u Reinstall software. If the display does not change, request a
Program 1 shows an incorrect new software version.
checksum. u Disconnect the device from the power supply. Program 2 is
used automatically after restart.
E3
Cause Correction
E4
Cause Correction
E5
Cause Correction
Eb
Cause Correction
E6
Cause Correction
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 143
Chapter 9
Alarms and messages
EC
Cause Correction
u See A070 CAN COM, A071 CAN MOD, A072 CAN DOUT
Ed
Cause Correction
Display State
LOCAL STOP The feeding was manually stopped on the display with the
key <S1>.
m STOP Dosing release is available, but the main motor was not
started.
STARTING Main motor has been started. The message is active during
heavy start-up of the drive.
BRAKE The main motor was stopped. The reverse current brake is
active.
RUN EMPTY The main motor was stopped. Idle time ”TCON.T1“ is active.
STANDBY All releases are present, but the main motor was switched off
after timeout ”TCON.T3“.
OVERLOAD The motor current of the main motor has a value > 130 % of
the nominal current.
VIBRATION The vibration level has exceeded the programmed limit. If not
remedied, the machine will stop with the alarm ”A034“ or”
A054“.
Bühler Group
AHZC-23401-1-2302-en-US
144 | Operating manual
Chapter 9
Alarms and messages
Display State
Display State
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 145
Chapter 9
Alarms and messages
Display State
OUT OF RANGE The value that is input is outside the valid range.
Bühler Group
AHZC-23401-1-2302-en-US
146 | Operating manual
Chapter 10
Spare parts lists
We would recommend keeping the following parts in stock for the corresponding de-
sign version:
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 147
Chapter 10
Spare parts lists
The remaining available spare parts are summarized in the following table:
200 mm WEWS-95011-810
500 mm WEWS-95012-810
1,000 mm WEWS-95013-810
1,400 mm WEWS-95014-810
Bühler Group
AHZC-23401-1-2302-en-US
148 | Operating manual
Chapter 11
Appendix
11 Appendix
11.1 CAN expansion modules
11.1.1 Types
EBD 1319 Load Cell (LC), appropriate 1 high-resolution load cell input
for calibration 8 digital I/O 24 V
Each of the 8 I/O can be configured
as input or output.
11.1.2 Connection
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 149
Chapter 11
Appendix
E1
Cause Correction
Software error u Switch the module off and back on again. If the message is
displayed again, replace the module.
E2
Cause Correction
EEPROM data loss u Switch the module off and back on again. If the message is
displayed again, replace the module.
u Check if the correct address is displayed.
E3
Cause Correction
No CAN interface connection u Press the key and check the address.
u Check parameter settings on MEAG.
E4
Cause Correction
AD converter error u Switch the module off and back on again. If the message is
displayed again, replace the module.
Bühler Group
AHZC-23401-1-2302-en-US
150 | Operating manual
Chapter 11
Appendix
E5
Cause Correction
Digital outputs u One or more outputs deviate from the expected state.
(External voltage, short-circuit, overload).
E6
Cause Correction
No external 24 V for EBD 1320 u Check the external 24 V at the X105:1 plug. LED 24 V EXT
lights up when there is voltage.
Eb
Cause Correction
Automatic baud rate search (no u Press the key and check the address. (For setting, see the
connection to CAN interface). address.)
u Check parameter settings on MEAG.
Technical data
Depth 40 mm
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 151
Chapter 11
Appendix
6 boreholes 6 mm in diameter
200
138
300
Technical data
Depth 40 mm
Bühler Group
AHZC-23401-1-2302-en-US
152 | Operating manual
Chapter 11
Appendix
Technical data
Depth 40 mm
MDDR
MDDR MEAG
MEAG
Main Basisprint
circuit board Anzeigeprint
Display circuit board
EBD 1311 EBD 1316
EBD 1311 EBD 1316
SIO_0 X50
X30
1
2 1 +24 V Line 1
1
3 2 0 V Line 2 2
4 3 RXD_TXD + 3 3
X80
SIO_0
1 6 X30 4 RXD_TXD - 4 4
2 5 X51
3 4 SIO_0
X50
If the local display unit is removed from the control and assembled elsewhere, it is to
be connected as a remote control. Address 1 is still used, however, and the value of
the parameter ”SYS.DISP“ will remain on OFF.
With a distance of 5 m or more, use a shielded, 4-core cable.
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 153
Chapter 11
Appendix
USER.ACTUAL %
USER.LOAD.x %
USER.I A
USER.SET.x %
USER.FEED Hz
USER.SLIDE.x %
USER.RUNHR h
USER.RUNHR2 h
USER.ACT.x °C
USER.VIBR.x %
USER.MOT_F.x Hz
MAN.FROLL 0 Hz
MAN.FSLD 0 %
MAN.FSLD2 0 %
MAN.FAN OFF
MAN.TRAN OFF
MAN.TRAN2 OFF
MAN.MOT OFF
MAN.MOT2 OFF
MAN.SFPOS 0 %
MAN.FLPOS 0 %
Bühler Group
AHZC-23401-1-2302-en-US
154 | Operating manual
Chapter 11
Appendix
MAN.CPOS_R.x mm
MAN.CPOS_L.x mm
MAN.POSDIF.x mm
MAN.RUNH_R.x h
MAN.RUNH_L.x h
MAN.SCREEN.x mm
TCON.DFCQ DFZK
TCON.SETV 1
TCON.MILL 1
TCON.MOTOR NORM
TCON.MOTIN AIN
TCON.TRANSIN AIN
TCON.MOTPTC.x ON
TCON.MOTCAN OFF
TCON.MOT_F1.x 50 Hz
TCON.MOT_F2.x 50 Hz
TCON.MODE REG
TCON.FLAP OFF
TCON.FLMID 50 %
TCON.VIBR OFF
TCON.UPS OFF
TCON.TEMP OFF
TCON.FEED FC_SLD
TCON.FC_SLD BASE
TCON.AOUT ACTV
TCON.N TRANS 2
TCON.TRANS 0 %
TCON.TRAPRB OFF
TCON.REG_M2 OFF
TCON.CSYNC ON
TCON.FMAX 70 Hz
TCON.FMIN 30 Hz
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 155
Chapter 11
Appendix
TCON.SMAX 100 %
TCON.SMIN 5 %
TCON.SINI 0 %
TCON.DIFF 10 %
TCON.TMAX 75 °C
TCON.T VIB 10 s
TCON.T1 30 s
TCON.T2.x 5,0 s
TCON.T3 15 Min.
TCON.T4 1,0 s
TCON.T5 1,0 s
TCON.T6 15 s
TCON.T7 0 Min.
TCON.LOGMSTP 60 s
TCON.LOGMRUN 10 s
TCON.ASSIST
SYS.TYP NOAPP
SYS.REM LOC
SYS.EIN OFF
SYS.DISP OFF
SYS.PSAV STOP
SYS.SD
SYS.SDT 600 s
SYS.LOCK OFF
SYS.MSG ALL
SYS.ACLR OFF
SYS.AINV ON
SYS.ASCROL ON
SYS.AO.x 0 mA
SYS.AI.x 0 mA
Bühler Group
AHZC-23401-1-2302-en-US
156 | Operating manual
Chapter 11
Appendix
SYS.AOADJ.x 100,0 %
SYS.AIADJ.x 100,0 %
SYS.CANBR 50 kBaud
SYS.ENET OFF
SYS.TCP OFF
SYS.INIT
ADC.I 1.1 A
ADC.I 1.2 A
ADC.I 2.1 A
ADC.I 2.2 A
ADC.AOMAX 150 %
ADCT.T.n °C
ADCT.OFFSET.n 0,0 °C
ADCT.TMIN.n –40 °C
ADCT.TMAX.n 300,0 °C
ADCT.UNIT °C
1317.AIn.x OFF
1317.AINn.x
1317.AIADJn.x 100,0 %
1317.AOn.x 0 mA
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 157
Chapter 11
Appendix
1317.AOUTn.x mA
1317.AOADJn.x 100,0 %
1317.MODT.n °C
CTRL.TN.0 7,000
CTRL.TN.1 12,000
CTRL.TV.0 1,450
CTRL.TV.1 1,450
CTRL.KR.0 1,000
CTRL.KR.1 0,150
CTRL.REG.0 PID
CTRL.REG.1 PI
CTRL.TIME.0 1000 ms
CTRL.TIME.1 1000 ms
PBDP.ADR 0
PBDP.TOUT 1,0 s
PBDP.WFOR FIX
PBDP.MPDP NORM
PBDP.COMP OFF
PBDP.CTRLB
PBDP.STATB
PBDP.DSDIR RXD
PBDP.DSNR 0
PBDP.DSIDX 0
PBDP.DSBYTE 8
PBDP.DSTYPE 1 BYTE
PBDP.DAT
PBDP.DSCNT
ENET.ADR 0
ENET.MPDP EXTD_L
ENET.IP
ENET.SUBNET
ENET.STDGW
Bühler Group
AHZC-23401-1-2302-en-US
158 | Operating manual
Chapter 11
Appendix
ENET.IPSET.x 0
ENET.SNSET.x 0
ENET.GWSET.x 0
ENET.TOUT 1,0 s
ENET.STATUS
ENET.COM
ENET.NAMEOS ON
TCP.MPDP EXTD_L
TCP.IP
TCP.SUBNET
TCP.STDGW
TCP.IPSET.x 0
TCP.SNSET.x 0
TCP.GWSET.x 0
TCP.TOUT 1,0 s
TCP.COM
SERV.ID
SERV.V_PROG
SERV.V_APPL
SERV.V_BASE
SERV.V_BOOT
SERV.DATE
SERV.TIME
SERV.ERR.x
SERV.EVT.x
SERV.ALLEVT.x
SERV.CPU
SERV.SADR
SERV.PCNT
SERV.ELOG ON
SERV.CLOG OFF
SERV.SIMM OFF
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 159
Chapter 11
Appendix
SERV.SERM OFF
SERV.SIMAZ OFF
SERV.DIN
SERV.DOUT
SERV.DISPIN
SERV.AIN.x V/mA
SERV.AOUT.x mA
SERV.TINT °C
SERV.SIO1
SERV.SIO2
SERV.USB
SERV.P-DP
SERV.PUPDAT
SERV.PDWDAT
SERV.TEST
Bühler Group
AHZC-23401-1-2302-en-US
160 | Operating manual
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 161
Technical Manual AHSJ en 0120 194898
Bühler AG
CH-9240 Uzwil
Switzerland
[email protected]
www.buhlergroup.com
www.buhlergroup.com