Operating Manual AHZC 66150

Download as pdf or txt
Download as pdf or txt
You are on page 1of 162

Operating manual

Granulex® 3 Series
Hammer mill
AHZC

AHZC-23401-1-2302-en-US

Innovations for a better world.


Table of contents

1 General ............................................................................... 9
1.1 Availability of the instructions.................................................................................... 9
1.2 Scope of validity....................................................................................................... 9
1.3 Applicable documents ............................................................................................. 9
1.4 Contact.................................................................................................................... 10
1.4.1 Feedback regarding these instructions..................................................................... 10
1.5 Personnel qualification ............................................................................................. 10
1.5.1 Operating personnel ................................................................................................ 10
1.5.2 Service engineers..................................................................................................... 10
1.6 Conventions of depiction.......................................................................................... 10
1.6.1 Action sequence ...................................................................................................... 10
1.7 Abbreviations ........................................................................................................... 11
1.8 Technical terms ....................................................................................................... 11

2 Safety.................................................................................. 12
2.1 Superstructure of the warning messages ................................................................. 12
2.2 Explanation of the warning instructions .................................................................... 12
2.3 Intended use............................................................................................................ 13
2.4 Part of the operating instructions.............................................................................. 13
2.5 Technical state......................................................................................................... 13
2.6 ATEX marking .......................................................................................................... 13
2.7 Personnel qualification ............................................................................................. 13
2.8 Protective measure to prevent unexpected starting.................................................. 14

3 Technical data .................................................................... 15


3.1 Environmental conditions ......................................................................................... 15
3.2 Electrical data .......................................................................................................... 15
3.2.1 Power supply, throughput control ............................................................................ 15
3.2.2 24 V inputs (8/14) .................................................................................................... 15
3.2.3 24 V outputs (8/20) .................................................................................................. 15
3.2.4 0/4 … 20 mA analog outputs (2) .............................................................................. 15
3.2.5 0/4 … 20 mA analog inputs (2) ................................................................................ 15
3.3 Dimensions .............................................................................................................. 16

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 3
3.3.1 Housing dimensions................................................................................................. 16
3.3.2 Dimensions, throughput control ............................................................................... 16
3.3.3 Dimensions, display ................................................................................................. 16
3.4 Weight, throughput control ...................................................................................... 16
3.5 Interfaces ................................................................................................................. 16
3.6 Miscellaneous .......................................................................................................... 16
3.7 Design versions........................................................................................................ 17

4 Description ......................................................................... 18
4.1 Operating principle................................................................................................... 18
4.1.1 Throughput control .................................................................................................. 20
4.1.2 Vertical hammer mill ................................................................................................. 21
4.1.2.1 Start......................................................................................................................... 21
4.1.2.2 Stop......................................................................................................................... 22
4.1.2.3 Reduce the overrun time.......................................................................................... 22
4.1.3 Feeding.................................................................................................................... 22
4.1.3.1 Dosing release ......................................................................................................... 22
4.1.3.2 Starting .................................................................................................................... 23
4.1.3.3 Stop......................................................................................................................... 23
4.1.4 Heavy particle flap.................................................................................................... 23
4.1.5 Outlet cone .............................................................................................................. 23
4.1.6 Discharge conveyor ................................................................................................. 23
4.1.7 Gravity flow diverter (option) ..................................................................................... 24
4.1.8 Temperature monitoring (option) .............................................................................. 24
4.1.9 Vibration monitoring (option)..................................................................................... 24
4.1.10 Magnetic door and back-up probe........................................................................... 24
4.1.11 Profibus interface ..................................................................................................... 24
4.1.12 Profinet interface (option) ......................................................................................... 25
4.1.13 EtherNet/IP interface (option) ................................................................................... 25
4.2 Operating and display elements ............................................................................... 25
4.2.1 Display operating elements ...................................................................................... 25
4.3 Time charts.............................................................................................................. 27
4.3.1 Standard sequence.................................................................................................. 27
4.3.2 Clearance time......................................................................................................... 27
4.3.3 Timeout ................................................................................................................... 27

5 Installation .......................................................................... 29
5.1 General arrangement drawing .................................................................................. 29

Bühler Group
AHZC-23401-1-2302-en-US
4 | Operating manual
5.1.1 Vertical hammer mill control ..................................................................................... 29
5.1.2 Throughput control .................................................................................................. 29
5.2 Main circuit board EBD 1311 ................................................................................... 30
5.2.1 Jumpers EBD 1311 ................................................................................................. 30
5.2.2 Connecting the power supply .................................................................................. 31
5.2.3 Profibus-DP or RS-485 SIO_2.................................................................................. 31
5.2.4 CAN interface .......................................................................................................... 32
5.2.5 24 V inputs .............................................................................................................. 33
5.2.6 24 V outputs ............................................................................................................ 36
5.2.6.1 Outputs 24 V on input plugs .................................................................................... 37
5.2.7 Analog inputs 0 … 5 V or 0/4 … 20 mA ................................................................... 39
5.2.8 0/4 ... 20 mA analog outputs ................................................................................... 40
5.3 Decentralized IO modules ........................................................................................ 42
5.3.1 Digital IO module EBD 1318..................................................................................... 42
5.3.2 Jumpers EBD 1318 ................................................................................................. 42
5.3.3 Digital IO expansion module 1.................................................................................. 42
5.3.4 Digital IO expansion module 2.................................................................................. 44
5.3.5 Digital IO expansion module 5.................................................................................. 45
5.3.6 Digital IO expansion module 6.................................................................................. 47
5.3.7 Analog IO module EBD 1317 ................................................................................... 48
5.3.8 Analog I/O expansion module EBD 1317 ................................................................. 49
5.3.9 Analog I/O expansion module 1 ............................................................................... 50
5.3.10 Analog I/O expansion module 2 ............................................................................... 51
5.4 Display module EBD 1316 ....................................................................................... 52
5.4.1 Circuit board EBD 1316 ........................................................................................... 52
5.4.2 Description of electric terminals X50......................................................................... 52
5.4.3 Description of electric terminals X52......................................................................... 53
5.4.4 Digital inputs of the display circuit board .................................................................. 53
5.4.5 Jumpers EBD 1316 ................................................................................................. 53
5.4.6 Wiring of vertical hammer mill control DFCQ V ......................................................... 54
5.4.7 Wiring of throughput control DFCQ H (main circuit board only)................................. 55
5.4.8 Wiring of throughput control (with CAN modules) ..................................................... 57

6 Operation ............................................................................ 59
6.1 Operate keys and lamps .......................................................................................... 59
6.2 Set parameters and parameter groups..................................................................... 60

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 5
7 Configuration...................................................................... 61
7.1 Setting the application.............................................................................................. 61
7.2 Device-specific settings............................................................................................ 61
7.3 Using the input wizard.............................................................................................. 62
7.4 Activate Profibus ...................................................................................................... 62
7.5 Activating Profinet .................................................................................................... 62
7.6 Activating Ethernet ................................................................................................... 62
7.7 Optimizing controller settings ................................................................................... 63
7.7.1 Descriptions of controller characteristics .................................................................. 63
7.7.2 Ziegler Nichols optimization...................................................................................... 63
7.7.3 Determining control parameters for controlled system with balancing....................... 63
7.7.3.1 Recording the step response ................................................................................... 63
7.7.3.2 Determining critical reinforcement ............................................................................ 65
7.7.4 Determining control parameters for controlled system without balancing.................. 66
7.7.5 Empirical optimization .............................................................................................. 66
7.8 Temperature monitoring........................................................................................... 67
7.8.1 Configure existing temperatures............................................................................... 67
7.8.2 Set scaling data ....................................................................................................... 67
7.8.3 Check settings of CAN module EBD 1317 ............................................................... 68
7.8.4 Calibrate and check temperatures ........................................................................... 68
7.9 Setting frequency converter of the feed roller ........................................................... 68
7.9.1 Schneider ATV 320 .................................................................................................. 69
7.9.2 Schneider ATV 312/31............................................................................................. 72
7.10 Controlling the main motor with frequency converter................................................ 73
7.10.1 Configuring the frequency converter Schneider ATV 930 (example).......................... 75
7.10.2 Configuring the frequency converter DANFOSS VLT 5000 ....................................... 76
7.11 Special applications ................................................................................................. 77
7.11.1 Control on the discharge conveyor with fan (pneumatic suction conveying system).. 77
7.11.1.1 Load control by current measurement of the fan motor (control with DOL starting 77
or soft starter) ..........................................................................................................
7.11.1.2 Load control via the motor torque of the fan motor (control with frequency con- 78
verter) ......................................................................................................................
7.11.1.3 Load control by air volume measurement with dynamic pressure sensor (control 79
fan motor with DOL starting, soft starter or frequency converter)..............................
7.11.2 Screw metering (TCON.FEED = SCREW)................................................................. 81
7.12 Resetting parameters to factory settings .................................................................. 81

8 Parameters ......................................................................... 82
8.1 Notes for the parameter details ................................................................................ 82

Bühler Group
AHZC-23401-1-2302-en-US
6 | Operating manual
8.2 Application parameters ............................................................................................ 82
8.2.1 USER (operating parameters) parameter group........................................................ 82
8.2.2 MAN (manual operation) parameter group................................................................ 84
8.2.3 TCON (configuration parameters) parameter group .................................................. 88
8.2.3.1 Setpoint frequencies of the main motors .................................................................. 98
8.2.4 Parameter group SYS (System configuration)........................................................... 99
8.2.5 ADC (analog-digital converter) parameter group.......................................................105
8.2.6 ADCT (Analog/Digital Converter Temperature) parameter group...............................108
8.2.7 1317 (CAN module EBD 1317) parameter group .....................................................109
8.2.8 Parameter group CTRL (Controller configuration) .....................................................110
8.2.9 PBDP (Profibus DP) parameter group ......................................................................113
8.2.10 ENET (Ethernet) parameter group ............................................................................115
8.2.11 TCP (Ethernet TCP/IP) parameter group ..................................................................119
8.2.12 Parameter group SERV (Service information)............................................................121

9 Alarms and messages........................................................ 127


9.1 Basic alarms ............................................................................................................127
9.2 Application alarms....................................................................................................130
9.2.1 Application alarms DFCQ-V......................................................................................130
9.2.1.1 Hammer mill 1..........................................................................................................130
9.2.1.2 Hammer mill 2..........................................................................................................134
9.2.1.3 Hammer mill 1 and 2................................................................................................138
9.2.2 Application alarms DFCQ-H .....................................................................................140
9.3 Canceling *No Comm An* display alarm...................................................................141
9.4 Display status of the seven-segment display ............................................................141
9.5 Status messages .....................................................................................................144
9.6 Short messages.......................................................................................................145

10 Spare parts lists ................................................................. 147


10.1 Spare parts management.........................................................................................147
10.2 Basic version, throughput control.............................................................................147
10.3 Spare parts lists .......................................................................................................147

11 Appendix ............................................................................ 149


11.1 CAN expansion modules..........................................................................................149
11.1.1 Types.......................................................................................................................149
11.1.2 Connection ..............................................................................................................149
11.1.3 LED display..............................................................................................................150

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 7
11.1.3.1 Error messages of LED display ................................................................................150
11.2 Remote control ........................................................................................................151
11.2.1 Installation version....................................................................................................151
11.2.2 Table or wall version with ATEX................................................................................152
11.2.3 Table or wall version (old) .........................................................................................153
11.2.4 Connect to MDDR main circuit board SIO_0 ............................................................153
11.3 Parameter list...........................................................................................................154

Bühler Group
AHZC-23401-1-2302-en-US
8 | Operating manual
Chapter 1
General

1 General
1.1 Availability of the instructions
These instructions constitute part of the product.

1. Retain the instructions and related applicable documents during the entire lifetime
of the product and keep them at hand for reference.
2. Pass on the instructions and other applicable documents to the each subsequent
owner or operator of the product.

1.2 Scope of validity


The operating manual is valid for the following machines:

Designation Product type

Hammer mill AHZC, single 06120

Hammer mill AHZC, single 0640

Hammer mill AHZC, single 0655

Hammer mill AHZC, single 0660

Hammer mill AHZC, single 0690

Hammer mill AHZC, single 1265

Hammer mill Granulex® 3 Series 66100


AHZC, single

Hammer mill AHZC, single 66125

Hammer mill Granulex® 3 Series 66150


AHZC, single

1.3 Applicable documents


The following documents are part of these instructions:
The documents for fieldbus and serial interface are written for the programmers. The
descriptions are therefore available only on request and only in German or English.

Operating instructions, hammer AHZC-20496


mill AHZC

Operating Instructions, Hammer Mill AHZC-21445


Granulex® 3 Series AHZC

Operating instructions, hammer mill AHZC-23165


AHZC

Operating manual, MEAG DEVICE uni- MEAG-DEVICE-66698-x-14


versal control unit (x = Documentation version)

Service instructions, description of the MEAG-66435


serial interface RS-485 DUMP-DIFF-
BAG-DCOS-PEARL MEAG

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 9
Chapter 1
General

Service instructions, universal control MEAG-21070


unit MEAG

1.4 Contact

1. In case of any questions, please contact the responsible branch of Bühler Group.
See www.buhlergroup.com
2. Keep the instructions ready at hand.
3. Keep the machine number ready at hand.

1.4.1 Feedback regarding these instructions


Send requests and suggestions regarding these instructions to
[email protected].

1.5 Personnel qualification

1.5.1 Operating personnel


Individuals operating the machine must be technically trained on the machine or have
undergone training on the machine at Bühler Group.

1.5.2 Service engineers


Individuals who are responsible for the administration of the control system must be
technically trained on the machine or have completed a training course on the ma-
chine at Bühler Group.

1.6 Conventions of depiction

1.6.1 Action sequence


Action steps to be carried out are presented in the form of numbered lists. The se-
quence of action steps must be followed.

1. Action step 1
u Subprocess 1
u Subprocess 2
2. Action step 2
’ Interim result of action step 2
3. Action step 3
’ Result of entire action step

Bühler Group
AHZC-23401-1-2302-en-US
10 | Operating manual
Chapter 1
General

1.7 Abbreviations
Abbreviation Meaning

PLC Programmable logic controller

HMI Human-machine interface (human-machine-inter-


face)

Digital I/O Digital input/output

1.8 Technical terms


Technical term Meaning

Profinet Open standard for Industrial Ethernet for the Automation of


Profibus and Profinet International.

Profibus Fieldbus for the automation which is used for the control of
sensors, actuators and for communication between measur-
ing and process devices, actuators and process control sys-
tems.

EtherNet/IP Application for Industrial Ethernet: Ethernet-based fieldbus


used for real-time applications.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 11
Chapter 2
Safety

2 Safety
2.1 Superstructure of the warning messages
The warning messages make staff aware of unavoidable hazards present during the
operation of the machine that are inherent to its design. Observe the measures men-
tioned to avoid these hazards.
General structure of a warning message:
(1) (2) (3) (4)

SIGNAL WORD

Nature and source of the danger.


Consequences of non-compliance.
Measures for avoiding the danger.

(6) (5)

(1) Danger symbol (2) Indicates the type and source of the
danger.
(3) Signal word (4) Signal color
(5) Lists the measures to avoid the (6) Indicates the consequences of ig-
danger. noring the danger.

2.2 Explanation of the warning instructions

DANGER

This message warns against an imminent danger to the human


life and health.
u Non-compliance with this warning message results in severe or
fatal injuries.

WARNING

This message warns against a possibly dangerous situation with


respect to human life and health.
u Non-compliance with this warning message may result in severe
or fatal injuries.

CAUTION

This message warns against a possibly dangerous situation with


respect to human health.
u Non-compliance with this warning message can result in injuries.

Bühler Group
AHZC-23401-1-2302-en-US
12 | Operating manual
Chapter 2
Safety

NOTICE

This note warns of possible property damage.


u Failure to observe this warning message may result in property damage.

2.3 Intended use


This control exclusively controls the machines specified in the scope.

u Use the device only for its intended use.

2.4 Part of the operating instructions


These instructions are an integral part of the respective operating instructions.
Lack of knowledge of the operating instructions may lead to the risk of malfunctions
or impairments of the product.

u Pay attention to the instructions and respective operating instructions.

2.5 Technical state


If the control system is operated when defective, the safety, function and availability
will be impaired.

u Only operate the control system when in perfect technical condition.


u Only operate the machine when the protection devices in full working order. See
respective operating instructions.
u Comply with the maintenance schedule.
u Use original spare parts only.
u If the operating behavior of the control system changes, check the machine for
faults.
u Rectify any faults immediately.
u Do not convert or alter the control system without authorization.

2.6 ATEX marking


The ATEX designation specifies under which conditions the control system can be
used in or attached to an Ex zone.

u Refer to the nameplate.

2.7 Personnel qualification


Unqualified personnel cannot identify risks and are thus exposed to greater hazards.

u Only charge qualified personnel with tasks described in this operating manual.
u Ensure that personnel comply with the locally valid laws and regulations for safe
and hazard-conscious work.
u Define and communicate the work responsibilities. Provide the keys and pass-
words to assigned personnel only.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 13
Chapter 2
Safety

2.8 Protective measure to prevent unexpected starting


If the machine starts up unexpectedly, persons working on the machine can be seri-
ously injured.

u Set the safety switch to <0> and lock it.


u Remove the key and keep it with you.

Bühler Group
AHZC-23401-1-2302-en-US
14 | Operating manual
Chapter 3
Technical data

3 Technical data
3.1 Environmental conditions
Designation Value Unit

Temperature during operation –10 … +50 °C

Temperature during standstill –10 … +75 °C

Relative humidity, non-condensing 0 … 95 %

3.2 Electrical data

3.2.1 Power supply, throughput control

Designation Value Unit

24 V DC variant according to DIN 19240 24 V DC


(+20 %/‑15 %)

Network variant (+10 %/‑15 %) 100 … 240 V AC

Frequency 43 … 67 Hz

Power input, maximum 40 VA

3.2.2 24 V inputs (8/14)

Designation Value Unit

Current consumption, maximum 15 mA

3.2.3 24 V outputs (8/20)

Designation Value Unit

Load, short-circuit proof, maximum 500 mA

Total load, maximum 2 A

3.2.4 0/4 … 20 mA analog outputs (2)

Designation Value Unit

Load resistance, max. 500 Ω

Resolution 1000 Parts

3.2.5 0/4 … 20 mA analog inputs (2)

Designation Value Unit

Input impedance 230 Ω

Resolution 200 Parts

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 15
Chapter 3
Technical data

3.3 Dimensions

3.3.1 Housing dimensions

Designation Value Unit

Height 2000 mm

Width 1600 mm

Depth 500 mm

Degree of protection IP65 –

3.3.2 Dimensions, throughput control

Designation Value Unit

Height 300 mm

Width 380 mm

Depth 155 mm

Degree of protection IP65 –

3.3.3 Dimensions, display

Designation Value Unit

Height 300 mm

Width 210 mm

Depth 80 mm

3.4 Weight, throughput control


Designation Value Unit

Weight, approx. 10 kg

3.5 Interfaces
– Profibus DP: Profibus slave, 9-pin D-sub socket
– USB: USB device interface for service
– CAN: CAN interface for expansion modules
– RJ-45 socket: Profinet, EtherNet/IP, Ethernet TCP/IP (optional)

3.6 Miscellaneous
– Flash EPROM for program and data logger
– Battery-powered RAM for parameters: Data protection for at least 20 years
– Noise emission (emission): EN 50081-1 class B complied with
– Noise immunity (immunity): EN 50082-2 industrial sector complied with

Bühler Group
AHZC-23401-1-2302-en-US
16 | Operating manual
Chapter 3
Technical data

3.7 Design versions


The following design versions are available:
– DFCQ V: Process control for vertical hammer mills (DFZK or AHZK)
– DFCQ H: Throughput control (FCM) for horizontal hammer mills
With the following mounting options:
– Built-in version, 24 V for assembling the cabinet
– Compact device, 24 V or 100 … 240 V AC

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 17
Chapter 4
Description

4 Description
4.1 Operating principle
The control system is used for the following applications:
– DFCQ -V: Process control for vertical hammer mills of the DFZK or AHZK ma-
chine codes and their product types. The roller feeder DFAV and AHAV and
transportation.
– DFCQ -H: Throughput control for horizontal hammer mills (FCM = Flow Control
Mode). In this process, the output of the hammer mill is regulated by controlling
the roller feeder.

The control system regulates and monitors the grinding process of vertical and hori-
zontal hammer mills.
Depending on the application, the control system performs the following functions:

Function DFCQ -V DFCQ -H

Regulating motor utilization to a desired setpoint. X X

Controlling and checking the feeder DFAV (feed roller and X X


roller gap adjuster).

The following elements to detect and control the roller X −


feeder DFAV:
– Low level, upper surge hopper
– DFAV full level
– Magnetic door
– Heavy particle flap
– Air-circulating fan

Controlling the cone adjustment. X −

Determining the direction of rotation of the motors, de- X −


pending on the operating hours.

Starting, stopping and braking the motors. X −

Switching off the motors after idle times of the mill. X −

Generating alarms to monitor the operating state. X X

Communication with the control system via fieldbus. X X

Measuring and evaluating the grinding chamber tempera- X X


ture (option).

Measuring and evaluating the machine vibrations (op- X X


tion).

Controlling the automatic gravity flow diverter for X −


DFZK product type 2 (option).

See also parameter ”TCON.DFCQ“ See page 89.

Bühler Group
AHZC-23401-1-2302-en-US
18 | Operating manual
Chapter 4
Description

(1)
(15) (2)
(14) (3)
(13)

(12)
(4)

(5)
(11) (6)

(7)
(10)

(8)
(9)

Fig. 4.1 Summary of DFZK -1

(1) Gearmotor (2) Segment slide gate linear actuator


(3) Heavy particle flap linear actuator (4) Magnetic door limit switch
(5) Zero-motion monitor (6) Temperature sensor grinding cham-
ber (optional)
(7) Vibration monitor (optional) (8) Blockage probe
(9) Electric motor discharge (10) Level probe discharge
(11) Cone linear actuators (12) Main motor
(13) Blockage probe (14) Electric motor fan
(15) Level probe, intermediate container

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 19
Chapter 4
Description

(16) (1)
(2)
(15) (3)
(14)
(13)

(12)
(4)

(5)
(6)
(11)
(7)
(10)

(8)
(9)

Fig. 4.2 General arrangement drawing of DFZK-2

(1) Gearmotor (2) Segment gate linear actuator (2x)


(3) Heavy particle flap linear actuator (4) Magnetic door limit switch
(5) Zero-motion monitor (2x) (6) Temperature sensor grinding cham-
ber (2× optional)
(7) Vibration monitor (2x optional) (8) Blockage probe
(9) Electric motor discharge (10) Level probe discharge (2x)
(11) Cone linear actuators (2x) (12) Main motor (2x)
(13) Gravity flow diverter linear actuator (14) Blockage probe
(15) Electric motor fan (16) Level probe, intermediate container

4.1.1 Throughput control


The throughput control (FCM) covers only the basic function of the roller feeders.
The feed roller, feed gap or feed screw conveyor are adjusted by means of the mea-
sured motor current in order to regulate the power of the hammer mill. The grinding
chamber temperature and machine vibrations can be recorded. Motors cannot be
switched on or off.

Bühler Group
AHZC-23401-1-2302-en-US
20 | Operating manual
Chapter 4
Description

(1)

(2)

Fig. 4.3 Summary of throughput control DFCQ H

(1) DFCQ -H, compact device (2) DFCQ -H, built-in version

+C5 ”DFCQ H“ as compact unit

+C3 High-voltage section and customer


control system with DFCQ H as built-in
version

A Controlling the feed roller motor (analog


signal 0/4 … 20 mA for frequency con-
verter)

B Controlling the feed gap linear cylinder


(digital control signals)

C Measuring the motor current (analog


signal 0/4 … 20 mA)

D Release of the throughput control (digi-


tal signal)

4.1.2 Vertical hammer mill

4.1.2.1 Start
The vertical hammer mill is controlled by two 24 V signals. Depending on the operat-
ing hours, the corresponding direction of rotation of the main motor is determined at
the start. This adjustment enables the hammers and sieves to wear evenly.
With two hammer mills, the second main motor first starts after the delay ”TCON.T6“
See page 98. A current transformer measures the present motor output. The ”Motor
is turning“ signal thereby occurs. If there is no current, an error message is displayed
and the mill stops.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 21
Chapter 4
Description

When the time ”TCON.T6“ has elapsed, the air-circulating fan starts on the roller
feeder. ”TCON.T6“ See page 98. The motor contactor of the fan sends an acknowl-
edgement signal to the control system ”DFCQ V“ as confirmation that the fan is run-
ning. If there is no signal, an error message is output and the dosing unit does not
start.

4.1.2.2 Stop
Do not operate the hammer mill for more than 15 minutes without any product since
the air circulation can cause overheating. The hammer mill is stopped by deactivation
of the 24 V start command. The air-circulating fan switches off first, followed by the
main motor. With two hammer mills (DFZK 2), both main motors switch off at short in-
tervals.
If the hammer mill runs without any product (no load), the hammer mill switches off
automatically after the time ”TCON.T3“ has elapsed. ”TCON.T3“ See page 97.
The following conditions are fulfilled that after an automatic stop, the hammer mill
restarts:
– The dosing release is pending.
– The level probe of the intermediate container reports presence of product.

If the hammer mill is stopped during the dosing process, the clearance time
”TCON.T1“ expires first. ”TCON.T1“ See page 97. This ensures that no product is
left behind in the grinding chamber and the hammer mill can restart automatically. If
product is left behind in the grinding chamber, the main motor cannot start. The
product must be removed manually.

4.1.2.3 Reduce the overrun time


The overrun time of hammer mill is 10 … 15 minutes until it comes to a standstill. This
time can be reduced, for example, for sieve change. The motor can be slowed down
with the ”Activate brake“ signal. As a result, the motor is controlled for the time
”TCON.T2.x“ with reversed direction of rotation. ”TCON.T1“ See page 97. The mo-
tor is thereby slowed down and the overrun time minimized to approx. 1 minute.

4.1.3 Feeding

4.1.3.1 Dosing release


When all motors are turning, the control system requires a second 24 V signal for
dosing release. This signal releases the roller feeder.
The following conditions are met for a release:
– Air-circulating fan motor is running.
– Motor of the discharge conveyor is running.
– Level probe of the discharge conveyor is not covered.
– Level probe in the intermediate container is covered.

Bühler Group
AHZC-23401-1-2302-en-US
22 | Operating manual
Chapter 4
Description

4.1.3.2 Starting
Thus, the dosing starts when the following conditions are met:
– The dosing release is pending.
– The level probe of the intermediate container reports presence of product.
– The blockage probe in the roller feeder is not covered.

The main motor is regulated by a setpoint, this is given in percent. The setpoint corre-
sponds to 100 % of the rated power of the main motor.
The control system regulates the optimum utilization of the main motor by means of
the segment slide gate gap and the speed of the feed roller. If two hammer mills
(DFZK 2) are present, the two segment slide gate settings are corrected until the
power consumption of both hammer mills is distributed evenly.

4.1.3.3 Stop
The following conditions must be met for dosing to stop:
– The dosing release is no longer present.
– The level probe of the intermediate container is not covered.
– The product discharge is no longer ensured.

The control system remains in this state until all conditions have been met for a
restart.

4.1.4 Heavy particle flap


When the dosing is not active, the heavy particle flap can be opened. The dosing
cannot be started while opening and closing the heavy particle flap. When opening
the heavy particle flap, the linear cylinder retracts. When closing the heavy particle
flap, the linear cylinder extends. See page 59, Chapter ”Operate keys and lamps“.

4.1.5 Outlet cone


The outlet cone can be opened or closed when the rotor is not moving. The two lin-
ear cylinders do not travel at exactly the same speed for production-related reasons.
Therefore, the position of both cylinders is measured by means of a pulse counter. If
the position difference of both cylinders is too great, the position is adjusted by slow-
ing down the faster cylinder momentarily. See page 59, Chapter ”Operate keys and
lamps“.

4.1.6 Discharge conveyor


When the main motor is running, the ”Start discharge“ signal is displayed. The dis-
charge conveyor must acknowledge that it is running by means of a response. If the
discharge conveyor does not return this message within 10 s, the main motor stops.
If there is no response from the discharge conveyor, the response signal must be
routed to the start signal. After the main motor has stopped, the ”Start discharge“
signal first switches off after an overrun time of 60 s. Additionally, capacity monitoring
of the discharge conveyor can be activated with the parameter ”TCON.TRANS“ See
page 94. ”TCON.TRANS“ See page 94.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 23
Chapter 4
Description

4.1.7 Gravity flow diverter (option)


The gravity flow diverter is used for selecting the hammer mill when two hammer mills
are present. It is activated with the dosing release. When the dosing release is
present for both hammer mills, the middle position is approached. The position is pre-
set with the parameter ”TCON.FLMID“ See page 92. ”TCON.FLMID“ See page 92.
In this position the product is conveyed to both hammer mills. If the dosing release is
only enabled for one hammer mill, the gravity flow diverter automatically changes po-
sition and directs the product only to the active hammer mill.
If the parameter ”TCON.FLAP“ is set to OFF, then the gravity flow diverter is not ad-
justed automatically and remains in the current position. ”TCON.FLAP“ See
page 92.

4.1.8 Temperature monitoring (option)


There is a thermal detector in the grinding chamber. If the measured temperature ex-
ceeds the limit value ”TCON.TMAX“, an alarm is triggered and the hammer mill is
switched off. ”TCON.TMAX“ See page 96. If there are two hammer mills (DFZK 2),
each grinding chamber is monitored by its own sensor.

4.1.9 Vibration monitoring (option)


There is a vibration sensor on the machine stand. This measures the vibrations within
the range of 0 … 64 mm/s. Two vibration limits can be set with the parameters
”TCON.VIB_W“ and ”TCON.VIB_A“ See page 96. ”TCON.VIB_W“ See page 96.
”TCON.VIB_A“ See page 96. If the value ”TCON.VIB_W“ is exceeded for the pro-
grammable time ”TCON.T VIB“, a warning is displayed. ”TCON.VIB_W“ See
page 96. ”TCON.T VIB“ See page 96. The machine only stops when the value
”TCON.VIB_A“ is exceeded for the time ”TCON.T VIB“ See page 96. The present vi-
bration value is displayed on the control system as a percent of the programmed limit,
i.e. 100 % corresponds to ”TCON.VIB_A“ See page 96.

4.1.10 Magnetic door and back-up probe


The following mechanisms are triggered in the roller feeder:
– If the magnetic door is opened, an alarm message appears on the display.
– If the back-up probe is covered, the feeder deactivates.

4.1.11 Profibus interface


The control has a Profibus interface to the process control system.
The following process data, among other things, can be displayed on the process
control system:
– Current motor output
– Current segment gate position
– Current speed of the feed roller
– State of all inputs and outputs
– Current alarm messages

Bühler Group
AHZC-23401-1-2302-en-US
24 | Operating manual
Chapter 4
Description

4.1.12 Profinet interface (option)


The controller has an optional Profinet interface to the control system.
The following process data, among other things, can be displayed on the process
control system:
– Current motor output
– Current segment gate position
– Current speed of the feed roller
– State of all inputs and outputs
– Current alarm messages

The circuit board Profinet - Ethernet fieldbus EBD 1326 (EKP-85388-810) is required.

4.1.13 EtherNet/IP interface (option)


The controller has an optional EtherNet/IP interface to the control system.
The following process data, among other things, can be displayed on the process
control system:
– Current motor output
– Current segment gate position
– Current speed of the feed roller
– State of all inputs and outputs
– Current alarm messages

The circuit board EtherNet/IP - Ethernet fieldbus EBD 1325 (EKP-85387-810) is re-
quired.

4.2 Operating and display elements

4.2.1 Display operating elements

H1 H2 H3 H4 H5 H6

lb
kg

S1 S2 S3 S4 S5 S6 S7 S8

Fig. 4.4 Display operating elements

Element Symbol Function

H1 Remote control

H2 Intermediate container product display


Light = product present

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 25
Chapter 4
Description

Element Symbol Function

H3 Not used

H4 Manual mode
Flashing = manual operating mode active

H5 Not used

H6 Capacity range
Flashing = overload; Lit = actual/target deviation ≤ 10 %

H7 Weight unit lb

H8 Weight unit kg

S1 <Start and stop> button


LED flashes: if stopped manually.
0
S2 <Empty> key
LED lights up: emptying is active.

S3 <Clear alarm>/<Lamp test>/<Cancel> key.


Flashing indicates that alarm is pending.

S4 <Function> key with special function, depending on pa-


rameter.
Special function is available when the LED is lit.

S5 <Arrow> key for changing the parameter group or posi-


tion when editing.

S6 <Data input> key for changing or applying values.

S7 + <Plus> key for selecting the next parameter or increasing


a value.

S8 <Minus> key for selecting the previous parameter or re-


ducing a value.

Bühler Group
AHZC-23401-1-2302-en-US
26 | Operating manual
Chapter 4
Description

4.3 Time charts

4.3.1 Standard sequence

DI 0.5 Release for main motor 1

DI 0.17 Release for main motor 2

DI 0.4 Release for feeder device 1

DI 0.16 Release for feeder device 2

DO 0.5 Main motor start 1

T6
DO 0.17 Main motor start 2
T6
DO 0.13 Fan

Dosing start

Fig. 4.5 Standard sequence

4.3.2 Clearance time


The correct start and stop sequence is always executed in the case of a simultaneous
start and release signal. Dosing starts when the motors are turning. The main motors
first switch off after the clearance time ”TCON.T1“ has elapsed. ”TCON.T1“ See
page 97. All of the product is thereby discharged from the hammer mill.

DI 0.5 Release for main motor 1

DI 0.17 Release for main motor 2

DI 0.4 Release for feeder device 1

DI 0.16 Release for feeder device 2

DO 0.5 Main motor start 1

DO 0.17 Main motor start 2

DO 0.13 Fan

Dosing start

Fig. 4.6 Clearance time

4.3.3 Timeout
The hammer mill stops in the following cases after the timeout” TCON.T3“:
– When no product is in the inlet
– When no release is present

This protects the cone from overheating. When there is product in the inlet again, the
hammer mill starts independently.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 27
Chapter 4
Description

DI 0.5 Release for main motor 1

DI 0.4 Release for feeder device 1

DI 5.0 low level, intermediate container

DO 0.5 Main motor start 1

DO 0.13 Fan

Dosing start

Fig. 4.7 Timeout

Bühler Group
AHZC-23401-1-2302-en-US
28 | Operating manual
Chapter 5
Installation

5 Installation
5.1 General arrangement drawing

5.1.1 Vertical hammer mill control


(1) (2)

(3)

(4)

(1) Main circuit board EBD 1311 (2) Frequency converter of the feed
roller
(3) Display circuit board EBD 1316 (4) Power section depending on design
version (a star-delta start here)

5.1.2 Throughput control


(1) (2)

(3)

Fig. 5.1 DFCQ DFCM cabinet

(1) Power supply (2) Display circuit board EBD 1316


(3) Main circuit board EBD 1311

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 29
Chapter 5
Installation

5.2 Main circuit board EBD 1311

(1)

(2)
(3)

(4)

Fig. 5.2 Main circuit board EBD 1311

(1) Battery (2) Seven-segment display


(3) USB connection (4) Fuse

Item Element Function

(1) Battery Supply of the battery-buffered RAM for saving the


parameter settings

(2) Seven-segment Display of the status messages of the universal con-


display trol unit

(3) USB connection Connection for software updates

(4) Fuse Electronics fuse


Fuse type: 4 A, time-delay

5.2.1 Jumpers EBD 1311

Fig. 5.3 Jumpers EBD 1311

Bühler Group
AHZC-23401-1-2302-en-US
30 | Operating manual
Chapter 5
Installation

X71 left B = Profibus at X40 A = RS-485 SIO_2 at X40

X71 right B = Hardware test OFF A = Hardware test ON (at factory)

X70 left B = Profibus at X40 A = RS-485 SIO_2 at X40

X70 right B = Profibus at X40 A = RS-485 SIO_2 at X40

X60 A = Current input at X14 V = Voltage input


(left AI0, right AI1)

X61 A = Current input at X14 V = Voltage input


(left AI2, right AI3)

X62 A = Current input at X24 V = Voltage input


(left AI4, right AI5)

X63 A = Current input at X24 V = Voltage input


(left AI6, right AI7)

X81 1 ... 6 = Pullup 3 ... 4 = Pulldown, SIO_1


2 ... 5 = Term

X80 1 ... 6 = Pullup 3 ... 4 = Pulldown, SIO_0 Display


2 ... 5 = Term

5.2.2 Connecting the power supply


Design version 24 volt DC - Circuit board EBD 1311

1
2
3
Fig. 5.4 ID electric terminal X1
Terminal Function

1 +24 V

2 0V

3 PE

5.2.3 Profibus-DP or RS-485 SIO_2


Switching with the X70 (left and right) and X71 (left) jumpers between Profibus DP and
RS-485 SIO_2:
– B = Profibus DP
– A = RS-485 SIO_2

Always leave jumpers X71 on the right in position B.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 31
Chapter 5
Installation

5
9
4
8
3
7
2
6
1

Fig. 5.5 Profibus

X Signal Description

X40:3 RS485_B Profibus DP or RS-485 SIO_2, positive signal

X40:4 RTS Profibus DP standard

X40:5 0 V_EX Profibus DP standard

X40:6 +5 V_EX Profibus DP standard

X40:8 RS485_A Profibus DP or RS-485 SIO_2, negative signal

5.2.4 CAN interface

3
4

Fig. 5.6 ID electric terminal X100

Terminal Function

1 +24 V

2 0V

3 CAN H

4 CAN L

X Signal Description

X100:1 +24 V +24 V output voltage.


Supplies CAN module
with voltage.

X100:2 0V 0 V and shield connection

Bühler Group
AHZC-23401-1-2302-en-US
32 | Operating manual
Chapter 5
Installation

X Signal Description

X100:3 CAN H CAN positive signal

X100:4 CAN L CAN negative signal

5.2.5 24 V inputs

1
2
3
4
5
6
7
8

Fig. 5.7 ID electric terminal X3, X10, X11, X12 and ID electric terminal X20, X21, X22

Ter- Function Function Function Function


mi- X3 X10 X11 X12
nal

1 +24 V_IO +24 V_IO +24 V_IO +24 V_IO

2 DI_0.0 DI_0.4 DI_0.8 DI_0.12

3 DI_0.1 DI_0.5 DI_0.9 −

4 GND GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO +24 V_IO

6 DI_0.2 DI_0.6 DI_0.10 DI_0.14

7 DI_0.3 DI_0.7 DI_0.11 −

8 GND GND GND GND

Ter- Function Function Function


minal X20 X21 X22

1 +24 V_IO +24 V_IO +24 V_IO

2 DI_0.16 DI_0.20 DI_0.24

3 DI_0.17 DI_0.21 −

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 DI_0.18 DI_0.22 DI_0.26

7 DI_0.19 DI_0.23 −

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 33
Chapter 5
Installation

Ter- Function Function Function


minal X20 X21 X22

8 GND GND GND

DI X3 Signal Description

0.0 X3:2 Emergency stop 24 V = operating state


for plant 0 V = plant is in emergency stop.

0.1 X3:3 Activate brake 24 V = when switching off the motors, the
signal is checked. If it is active, the motors
are stopped with reverse current brake.

0.2 X3:6 Acknowledge 24 V = Impending, acknowledgeable alarms


alarm are deleted with the positive flank when the
alarm condition is no longer active.

0.3 X3:7 not used −

DI X10 Signal Description

0.4 X10:2 Release of Feeder 24 V = Hammer mill 1 feeder device will be


device 1 started.

0.5 X10:3 Release for main 24 V = Main motor of hammer mill 1 will be
motor 1 started.

0.6 X10:6 Speed 2 24 V = main motor runs with


Main motor 1 TCON.MOT_F2
0 V = main motor runs with TCON.MOT_F1.

0.7 X10:7 Safety switch 24 V = the safety switch is switched on (op-


erating status).

DI X11 Signal Description

0.8 X11:2 Segment slide 24 V pulse signal = counting pulse for mea-
gate pulse 1 suring position of the segment gate.

0.9 X11:3 Segment gate 1 24 V = segment gate is open or closed at


limit switch limit position.

0.10 X11:6 For screw meter- 24 V = Level probe in the upper surge hop-
ing per is covered (operating state).
Low level in upper 0 V = level probe in the upper surge hopper
surge hopper is uncovered (alarm condition).

0.11 X11:7 Alarm for fre- 0 V = the frequency converter of the feed
quency converter roller is reporting an alarm.

Bühler Group
AHZC-23401-1-2302-en-US
34 | Operating manual
Chapter 5
Installation

DI X12 Signal Description

0.12 X12:2 Fan is running 24 V = response that fan is running.

X12:3 See digital outputs.

0.14 X12:6 Discharge 1 run- 24 V = response, hammer mill 1 discharge


ning in progress. If no discharge conveyor is
present, provide a jumper to 24 V at the in-
put.

X12:7 See digital outputs.

DI X20 Signal Description

0.16 X20:2 Release of Feeder 24 V = Hammer mill 2 feeder device will be


device 2 started.

0.17 X20:3 Release for main 24 V = Main motor of hammer mill 2 will be
motor 2 started.

0.18 X20:6 Speed 2 24 V = main motor runs with


Main motor 2 TCON.MOT_F2
0 V = main motor runs with TCON.MOT_F1.

0.19 X20:7 Level probe dis- Function according to configuration


charge TCON.TRAPRB.

DI X21 Signal Description

0.20 X21:2 Segment slide 24 V pulse signal = counting pulse for mea-
gate pulse 2 suring position of the segment gate.

0.21 X21:3 Segment gate 2 24 V = segment gate is open or closed at


limit switch limit position.

0.22 X21:6 Not used −

0.23 X21:7 24 V is OK 24 V = circuit breakers in the control system


are OK.

DI X22 Signal Description

0.24 X22:2 UPS is OK 24 V = Power supply from network.


0 V = Power supply from UPS, the machine
is stopped.

X22:3 See digital outputs

0.26 X22:6 Discharge 2 run- 24 V = response, hammer mill 2 discharge


ning in progress.
If no discharge conveyor is present, provide
a jumper to 24 V at the input.

X22:7 See digital outputs

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 35
Chapter 5
Installation

5.2.6 24 V outputs

1
2
3
4
5
6

Fig. 5.8 ID electric terminal X2, X13, X23

Ter- Function Function Function


minal X2 X13 X23

1 DO_0.0 DO_0.4 DO_0.8

2 DO_0.1 DO_0.5 DO_0.9

3 DO_0.2 DO_0.6 DO_0.10

4 DO_0.3 DO_0.7 DO_0.11

5 GND GND GND

6 GND GND GND

DO X2 Signal Description

0.0 X2:1 Alarm of hammer 0 V = alarm, if SYS.AINV = ON


mill 1

0.1 X2:2 Alarm of hammer 0 V = alarm, if SYS.AINV = ON


mill 2

0.2 X2:3 Setpoint of feed 24 V-pulse signal 0 … 1 kHz


roller Set point for frequency converter.
1 kHz = 100 Hz on the gearmotor
Idle state = motor stopped = 24 V

0.3 X2:4 not used -

DO X13 Signal Description

0.4 X13:1 Motor 1 clockwise 24 V = Main motor of hammer mill 1 is


rotation started with direction of rotation to the right.

Open segment 24 V = segment gate 1 is opened.


gate 1

0.5 X13:2 Motor 1 counter- 24 V = Main motor of hammer mill 1 is


clockwise rotation started with direction of rotation to the left.

Close segment 24 V = segment gate 1 is closed.


gate 1

Bühler Group
AHZC-23401-1-2302-en-US
36 | Operating manual
Chapter 5
Installation

DO X13 Signal Description

0.6 X13:3 Brake motor 1 24 V = Main motor of hammer mill 1 is


braked.

Open segment 24 V = segment gate 2 is opened.


gate 2

0.7 X13:4 Start transporta- 24 V = Hammer mill 1 discharge is started.


tion 1

Close segment 24 V = segment gate 2 is closed.


gate 2

D0 X23 Signal Description

0.8 X23:1 Motor 2 clockwise 24 V = Main motor of hammer mill 2 is


rotation started with direction of rotation to the right.

0.9 X23:2 Motor 2 counter- 24 V = Main motor of hammer mill 2 is


clockwise rotation started with direction of rotation to the left.

0.10 X23:3 Brake motor 2 24 V = Main motor of hammer mill 2 is


braked.

0.11 X23:4 Start transporta- 24 V = Hammer mill 2 discharge is started.


tion 2

5.2.6.1 Outputs 24 V on input plugs

1
2
3
4
5
6
7
8

Fig. 5.9 ID electric terminal X3, X10, X11, X12 and ID electric terminal X20, X21, X22

Ter- Function Function Function Function


mi- X3 X10 X11 X12
nal

1 +24 V_IO +24 V_IO +24 V_IO +24 V_IO

2 − − − −

3 − − − DO_0.13

4 GND GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO +24 V_IO

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 37
Chapter 5
Installation

Ter- Function Function Function Function


mi- X3 X10 X11 X12
nal

6 − − − −

7 − − − DO_0.15

8 GND GND GND GND

Ter- Function Function Function


minal X20 X21 X22

1 +24 V_IO +24 V_IO +24 V_IO

2 − − −

3 − − DO_0.25

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 − − −

7 − − DO_0.27

8 GND GND GND

DO X12 Signal Description

X12:2 See digital inputs.

0.13 X12:3 Start the fan. 24 V = fan is started.

X12:6 See digital inputs.

0.15 X12:7 Hammer mill 1 24 V = Hammer mill 1 is in operation.


started.

DO X22 Signal Description

X22:2 See digital inputs.

0.25 X22:3 Not used. −

X22:6 See digital inputs.

0.27 X22:7 Hammer mill 2 24 V = Hammer mill 2 is in operation.


started.

Bühler Group
AHZC-23401-1-2302-en-US
38 | Operating manual
Chapter 5
Installation

5.2.7 Analog inputs 0 … 5 V or 0/4 … 20 mA

1
2
3
4
5
6
7

Fig. 5.10 ID electric terminal X14, X24

Ter- Function Function


minal X14 X24

1 + AI_0.0 + AI_0.4

2 + AI_0.1 + AI_0.5

3 + AI_0.2 + AI_0.6

4 + AI_0.3 + AI_0.7

5 +5 V +5 V

6 GND GND

7 GND GND

AI X14 Signal Description

0.0 X14:1 Hammer mill 1 Motor current input of hammer mill 1


motor current 20 mA = ADC. CON1.1

0.1 X14:2 Motor current for Motor power input of discharge conveyor of
discharge 1 hammer mill 1
20 mA = ADC. CON1.2

0.2 X14:3 Not used −

0.3 X14:4 Setpoint of ham- Analog setpoint specification of hammer


mer mill 1 mill 1
20 mA = 100 %
Active only if SYS.REM = REMA

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 39
Chapter 5
Installation

AI X24 Signal Description

0.4 X24:1 Hammer mill 2 Motor current input of hammer mill 2


motor current 20 mA = ADC. CON2.1

0.5 X24:2 Motor current for Motor power input of discharge conveyor of
discharge 2 hammer mill 2
20 mA = ADC. CON2.2

0.6 X24:3 Not used −

0.7 X24:4 Setpoint of ham- Analog setpoint specification of hammer


mer mill 2 mill 2
20 mA = 100 %
Active only if SYS.REM = REMA

5.2.8 0/4 ... 20 mA analog outputs

1
2
3
4
5
Fig. 5.11 ID electric terminal X4

Terminal Function

1 + AO_0.0

2 GND

3 + AO_0.1

4 GND

5 GND

The function of the analog outputs depends on the configuration of the control sys-
tem.

Bühler Group
AHZC-23401-1-2302-en-US
40 | Operating manual
Chapter 5
Installation

AO X4 Signal Description

TCON.MILL = 1 TCON.MILL = 2
(DFZK 1) (DFZK 2)

0.0 X4:1 + 0/4 … 20 mA Setpoint of feed roller Dependent on


X4:2 − 20 mA = 100 Hz TCON.AOUT
- ACTV Actual perfor-
mance of the hammer
mill 1
- SETV, Feed roller
setpoint for hammer
mill 1 and 2
− MOTF setpoint or
actual speed of main
motor 1

0.1 X4:3 + 0/4 … 20 mA Actual performance of Dependent on


X4:4 − the hammer mill TCON.AOUT
20 mA = ADC.AOMAX - ACTV Actual perfor-
or mance of the hammer
mill 2
Target speed of main
motor 20 mA = 60 Hz - SETV Feed roller set-
point for hammer mill 2
if (TCON.MOTOR = FC (currently not used)
or BR FC)
- MOTF Setpoint or
and actual speed of main
”TCON.MOTCAN“ = ” motor for hammer
OFF“ mill 2

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 41
Chapter 5
Installation

5.3 Decentralized IO modules


The decentralized I/O modules are built-in directly on the machine. The number of
built-in modules depends on the machine design version.

5.3.1 Digital IO module EBD 1318


The digital I/O module EBD 1318 is used for the input and output of digital signals.
The module has 12 configurable IOs. The operating software defines whether an IO is
operated as input or output.

IO 0...3 IO 4...7 IO 8...11

1 1 1
H100 H104 H108
2 2 2
CAN
H101 H105 H109
3 3 3
1
4 4 4
2
5 5 5
3
H102 H106 H110 H150
6 6 6 4
H103 H107 H111
7 7 7 X100

8 8 8 ON ON
OFF OFF
X101 X102 X103 1 2
X99
Out 0… 3
Out 4… 7 EBD1318 3 4
Out 8…11
X112 S100

Fig. 5.12 ID EBD 1318

5.3.2 Jumpers EBD 1318

X99 OFF = bus termination deactivated. All modules except the last
module on the bus.
ON = bus termination activated. Last module on the bus.

X112 ON = outputs are fed from modules (default setting).

5.3.3 Digital IO expansion module 1


The module must have the address 1.
Installation location: safety storage cabinet of hammer mill 1.
1
2
3
4
5
6
7
8

Fig. 5.13 ID electric terminal X101, X102, X103

Bühler Group
AHZC-23401-1-2302-en-US
42 | Operating manual
Chapter 5
Installation

Ter- Function Function Function


minal X101 X102 X103

1 +24 V_IO +24 V_IO +24 V_IO

2 DI_1.0 DI_1.4 DI_1.8

3 DI_1.1 DI_1.5 DO_1.9

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 DI_1.2 DI_1.6 DO_1.10

7 DI_1.3 DI_1.7 DO_1.11

8 GND GND GND

Dx X Signal Description

1.0 X101:2 Close cone switch 24 V = close cone.

1.1 X101:3 Machine stop but- 24 V = machine controls stopping (no


ton emergency stop).

1.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.

1.3 X101:7 Zero-motion moni- 24 V = main motor is stationary.


tor

1.4 X102:2 Cone closed 24 V = the cone is closed.

1.5 X102:3 Filling level of cone 24 V = level probe is uncovered (operat-


ing state).
0 V = level probe is covered (alarm con-
dition).

1.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.

1.7 X102:7 Heavy particle flap 24 V = manually open heavy particle


button flap.

1.8 X103:2 Open cone switch 24 V = open cone.

1.9 X103:3 Move cone to the 24 V = move linear cylinder to the right
right of the cone.

1.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 43
Chapter 5
Installation

Dx X Signal Description

1.11 X103:7 Move cone lamp Lamp of the move cone button.
When the main motor is at a standstill
and the lamp is lit, the cone can be
opened.
When a sieve change has been re-
quested, the lamp flashes slowly.
Lamp flashes rapidly when the cone is
locked.

5.3.4 Digital IO expansion module 2


The module must have the address 2.
Installation location: safety storage cabinet of hammer mill 2.
1
2
3
4
5
6
7
8

Fig. 5.14 ID electric terminal X101, X102, X103

Ter- Function Function Function


minal X101 X102 X103

1 +24 V_IO +24 V_IO +24 V_IO

2 DI_2.0 DI_2.4 DI_2.8

3 DI_2.1 DI_2.5 DO_2.9

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 DI_2.2 DI_2.6 DO_2.10

7 DI_2.3 DI_2.7 DO_2.11

8 GND GND GND

Dx X Signal Description

2.0 X101:2 Close cone switch 24 V = close cone.

2.1 X101:3 Machine stop but- 24 V = machine controls stopping (no


ton emergency stop).

Bühler Group
AHZC-23401-1-2302-en-US
44 | Operating manual
Chapter 5
Installation

Dx X Signal Description

2.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.

2.3 X101:7 Zero-motion moni- 24 V = main motor is stationary.


tor

2.4 X102:2 Cone closed 24 V = the cone is closed.

2.5 X102:3 Cone full level 24 V = level probe is uncovered (operat-


ing status).
0 V = level probe is covered (alarm sta-
tus).

2.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.

2.7 X102:7 Heavy particle flap 24 V = manually open heavy particle


button flap.

2.8 X103:2 Open cone switch 24 V = open cone.

2.9 X103:3 Move cone to the 24 V = move linear cylinder to the right
right of the cone.

2.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.

2.11 X103:7 Move cone lamp Lamp of the move cone button.
When the lamp is lit, the main motor is
stationary. Cone can be opened.
If the lamp flashes slowly, a sieve
change has been requested.
If lamp flashes rapidly when the cone is
locked.

5.3.5 Digital IO expansion module 5


The module must have the address 5.
Installed in: terminal box DFAV-1/2.
1
2
3
4
5
6
7
8

Fig. 5.15 ID electric terminal X101, X102, X103

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 45
Chapter 5
Installation

Ter- Function Function Function


minal X101 X102 X103

1 +24 V_IO +24 V_IO +24 V_IO

2 DI_5.0 DI_5.4 DI_5.8

3 DI_5.1 DI_5.5 DI_5.9

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 DI_5.2 DO_5.6 DO_5.10

7 DI_5.3 DO_5.7 DO_5.11

8 GND GND GND

Dx X Signal Description

5.0 X101:2 Low level, inter- 24 V = Level probe of the intermediate


mediate container container is covered (operating state).
0 V = level probe of the intermediate
container is uncovered (alarm condi-
tion).

5.1 X101:3 Fill level of roller 24 V = level probe of the roller feeder is
feeder uncovered (operating state).
0 V = level probe is covered (alarm sta-
tus).

5.2 X101:6 Magnetic door 24 V = Magnetic door is closed.

5.3 X101:7 not used −

5.4 X102:2 Segment slide 24 V pulse signal = counting pulse for


gate pulse 1 measuring position of the segment
gate.

5.5 X102:3 Segment gate limit 24 V = segment gate is open or closed


switch 1 at limit position.

5.6 X102:6 Open segment 24 V = segment gate is opened.


gate 1

5.7 X102:7 Close segment 24 V = segment gate is closed.


gate 1

5.8 X103:2 Heavy particle flap 24 V pulse signal = counting pulse for
pulse measuring position of the heavy particle
flap.

5.9 X103:3 Heavy particle flap 24 V = heavy particle flap is open or


limit switch closed at limit position.

5.10 X103:6 Opening the heavy 24 V = heavy particle flap is opened.


particle flap

Bühler Group
AHZC-23401-1-2302-en-US
46 | Operating manual
Chapter 5
Installation

Dx X Signal Description

5.11 X103:7 Close heavy parti- 24 V = heavy particle flap is closed.


cle flap

5.3.6 Digital IO expansion module 6


The module must have the address 6.
Installed in: terminal box DFAV 2.
1
2
3
4
5
6
7
8

Fig. 5.16 ID electric terminal X101, X102, X103

Ter- Function Function Function


minal X101 X102 X103

1 +24 V_IO +24 V_IO +24 V_IO

2 DI_6.0 DI_6.4 DI_6.8

3 DI_6.1 DI_6.5 DI_6.9

4 GND GND GND

5 +24 V_IO +24 V_IO +24 V_IO

6 DI_6.2 DO_6.6 DO_6.10

7 DI_6.3 DO_6.7 DO_6.11

8 GND GND GND

Dx X Signal Description

6.0 X101:2 not used −

6.1 X101:3 not used −

6.2 X101:6 not used −

6.3 X101:7 not used −

6.4 X102:2 Segment slide 24 V pulse signal = counting pulse for


gate pulse 2 measuring position of the segment
gate.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 47
Chapter 5
Installation

Dx X Signal Description

6.5 X102:3 Segment gate limit 24 V = segment gate is open or closed


switch 2 at limit position.

6.6 X102:6 Open segment 24 V = segment gate is opened.


gate 2

6.7 X102:7 Close segment 24 V = segment gate is closed.


gate 2

6.8 X103:2 Gravity flow di- 24 V pulse signal = counting pulse for
verter pulse signal measuring position of the gravity flow
diverter.

6.9 X103:3 Gravity flow di- TCON.FLMID > 0:


verter limit switch 24 V = Gravity flow diverter is at limit
position 1 or hammer mill 2.
TCON.FLMID = 0:
24 V = Gravity flow diverter is at middle
position.

6.10 X103:6 Gravity flow di- 24 V = Move gravity flow diverter in the
verter of hammer direction of hammer mill 2.
mill 2

6.11 X103:7 Gravity flow di- 24 V = Move gravity flow diverter in the
verter of hammer direction of hammer mill 1.
mill 1

5.3.7 Analog IO module EBD 1317


The CAN analog module EBD 1317 is used for the options of temperature monitoring
or vibration monitoring. On the module is a temperature sensor that measures the
current ambient temperature.

Circuit board Module type Description

EBD 1317 Analog I/O 8 analog inputs, 2 analog outputs with


0/4 … 20 mA.
Voltage measurement 0 … 5 V or 0 … 10 V
Force sensor input ± 80 mV (2 channels are
necessary)
Resistance measurement
Connection PT100 or PT1000

Bühler Group
AHZC-23401-1-2302-en-US
48 | Operating manual
Chapter 5
Installation

5.3.8 Analog I/O expansion module EBD 1317

0 X290 EBD 1317


AI0 AI4
X298 1 X291
AI1 AI5
4 X294
AO0 X210 X212
5V 24V 5V 24V
5 X295

AO1 0/1 4/5


2/3 6/7 2 X292
X280 X281
3 X293 X100
X201 AI2 AI6
AI3 AI7 6 X296
X299
7 X297
X211 X213 X99
S200

Fig. 5.17 EBD 1317

Jumpers Description

X99 OFF:
– Bus termination deactivated. All modules except the last
module on the bus.

ON:
– Bus termination activated. Last module on the bus.

X280/X281 Select voltage for resistance measurement 5 V or 24 V.


Position, left = 5 V (default setting).

X290 … X297. Select the input type of the analog input.


R: Resistance/PT100/PT1000
V: Voltage 5 V/10 V/80 mV
A: Current 0 mA/4 mA

u Set jumper according to schematic.

X298/X299 Choice of primary voltage 5 V or 10 V.


Jumper plugged in = 5 V (default setting).

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 49
Chapter 5
Installation

5.3.9 Analog I/O expansion module 1


Installation location: safety storage cabinet of hammer mill 1

3
4

Fig. 5.18 ID electric terminal X210, X211, X212, X213

Ter- Function X210 Function X211 Function X212 Function X213


mi-
nal

1 OUT OUT OUT OUT

2 AI 1.0 AI 1.2 AI 1.4 AI 1.6

3 AI 1.1 AI 1.3 AI 1.5 AI 1.7

4 0V 0V 0V 0V

X Signal Description

X210:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X280 (0/1).

X210:2 AI 1.0 Hammer mill 1 temperature sensor (PT100, PT1000)

X210:3 AI 1.1 PTC, main motor of hammer mill 1

X210:4 0 V shield 0 V and shield connection

X211:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X280 (2/3).

X211:2 AI 1.2 Vibration sensor of hammer mill 1

X211:3 AI 1.3 Not used

X211:4 0 V shield 0 V and shield connection

X212:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X281 (4/5).

X212:2 AI 1.4 Not used

X212:3 AI 1.5 Not used

X212:4 0 V shield 0 V and shield connection

X213:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X281 (6/7).

X213:2 AI 1.6 Not used

Bühler Group
AHZC-23401-1-2302-en-US
50 | Operating manual
Chapter 5
Installation

X Signal Description

X213:3 AI 1.7 Not used

X213:4 0 V shield 0 V and shield connection

Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded cables.
Connect shield to electric terminal 4.

5.3.10 Analog I/O expansion module 2


Installation location: safety storage cabinet of hammer mill 2

3
4

Fig. 5.19 ID electric terminal X210, X211, X212, X213

Ter- Function X210 Function X211 Function X212 Function X213


mi-
nal

1 OUT OUT OUT OUT

2 AI 2.0 AI 2.2 AI 2.4 AI 2.6

3 AI 2.1 AI 2.3 AI 2.5 AI 2.7

4 0V 0V 0V 0V

X Signal Description

X210:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X280 (0/1).

X210:2 AI 2.0 Hammer mill 2 temperature sensor (PT100, PT1000)

X210:3 AI 2.1 PTC, main motor of hammer mill 2

X210:4 0 V shield 0 V and shield connection

X211:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X280 (2/3).

X211:2 AI 2.2 Vibration sensor of hammer mill 2

X211:3 AI 2.3 Not used

X211:4 0 V shield 0 V and shield connection

X212:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X281 (4/5).

X212:2 AI 2.4 Not used

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 51
Chapter 5
Installation

X Signal Description

X212:3 AI 2.5 Not used

X212:4 0 V shield 0 V and shield connection

X213:1 +OUT 5 V or 24 V secondary voltage. Set via jumper X281 (6/7).

X213:2 AI 2.6 Not used

X213:3 AI 2.7 Not used

X213:4 0 V shield 0 V and shield connection

Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded cables.
Connect shield to electric terminal 4.

5.4 Display module EBD 1316

5.4.1 Circuit board EBD 1316

X50 EBD 1316


1 5
2 6
3 7
4 8
BA

X52
X54
X53

Fig. 5.20 Circuit board EBD 1316

5.4.2 Description of electric terminals X50

3
4

Fig. 5.21 ID electric terminal X50

Bühler Group
AHZC-23401-1-2302-en-US
52 | Operating manual
Chapter 5
Installation

Ter- Function Description


minal

1 +24 V_Line + 24 V power supply

2 0 V_Line 0V

3 RXD TXD + RS485 signal +

4 RXD TXD− RS-485 signal −

5.4.3 Description of electric terminals X52

7
8

Fig. 5.22 ID electric terminal X52

Ter- Function Description


minal

5 +24 V_EXT + 24 V external power supply for in-


put 1 ... 3

6 24 V_INPUT1 Not used

7 24 V_INPUT2 Not used

8 24 V_INPUT3 Not used

5.4.4 Digital inputs of the display circuit board


SERV.DISPIN displays the current state of the 24 V inputs.

0 0 0 0 0 0

IN3 IN2 IN1 IN3 IN2 IN1

Display 0 Display 1

5.4.5 Jumpers EBD 1316


X54 B = terminating resistor activated (default setting).

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 53
Chapter 5
Installation

5.4.6 Wiring of vertical hammer mill control DFCQ V


DFCQ-V +C1 DFCQ-V +C2
safety storage cabinet

Fig. 5.23 Wiring of control DFCQ V

Abbreviation Description

A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).

B Start signal of the main motors. This signal is not required while
starting via fieldbus (SYS.EIN).

C Motor current or motor torque


0/4 … 20 mA

D Analog setpoint specified for the mill power 0/4 … 20 mA. Is read
only when SYS.REM = REMA.

Bühler Group
AHZC-23401-1-2302-en-US
54 | Operating manual
Chapter 5
Installation

Abbreviation Description

E Analog actual value output of the hammer mill


0/4 … 20 mA

F Alarm output
Function can be inverted via parameter SYS.AINV.

G Digital output of the hammer mill is in operation.


24 V = Hammer mill is running.

5.4.7 Wiring of throughput control DFCQ H (main circuit board only)

LINAK 1
(1)
(2)
(3)

(4)
(5)
(6)
(7)

LINAK 2
(1)
(2)
(3)

(4)
(5)
(6)
(7)

DFZK-2

Fig. 5.24 Wiring of throughput control DFCQ H

No. LINAK 1 from LINAK 2 from LINAK 1 until LINAK 2 until


06.2016 06.2016 05.2016 05.2016

(1) RD RD RD RD

(2) BK BK OR OR

(3) BU BU BK BK

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 55
Chapter 5
Installation

No. LINAK 1 from LINAK 2 from LINAK 1 until LINAK 2 until


06.2016 06.2016 05.2016 05.2016

(4) BN BN BN BN

(5) VT VT VT VT

(6) YE YE GN GN

(7) GN GN YE YE

Abbrevia- Description
tion

A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).

B Motor current or motor torque from the main motor.


0/4 … 20 mA.

C Analog setpoint specified for the hammer mill power 0/4 … 20 mA. Is
only read in, if SYS.REM = REMA.

D Digital input for frequency converter error.


0 V = feed roller error.

E Linear cylinder (LINAK) for adjusting the feed gap.

F Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.

G Frequency converter setpoint of the feed roller.


0/4 … 20 mA → 0 … 100 Hz.

H Analog actual value output of the hammer mill.


0/4 … 20 mA = 0 … ADC.AOMAX

I Alarm output.
Function can be inverted via parameter SYS.AINV.

J Digital output of the hammer mill is in operation.


24 V = Hammer mill is running.

Bühler Group
AHZC-23401-1-2302-en-US
56 | Operating manual
Chapter 5
Installation

5.4.8 Wiring of throughput control (with CAN modules)

LINAK 1
(1)
(2)
(3)

(4)
(5)
(6)
(7)

LINAK 2
(1)
(2)
(3)

(4)
(5)
(6)
(7)

DFZK-2

Fig. 5.25 Wiring of throughput control (with CAN modules)

No. LINAK 1 from LINAK 2 from LINAK 1 until LINAK 2 until


06.2016 06.2016 05.2016 05.2016

(1) RD RD RD RD

(2) BK BK OR OR

(3) BU BU BK BK

(4) BN BN BN BN

(5) VT VT VT VT

(6) YE YE GN GN

(7) GN GN YE YE

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 57
Chapter 5
Installation

Abbrevia- Description
tion

A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).

B Motor current or motor torque from the main motor.


0/4 … 20 mA.

C Analog setpoint specified for the hammer mill power 0/4 … 20 mA. Is
only read in, if SYS.REM = REMA.

D Digital input for frequency converter error.


0 V = feed roller error.

E Linear cylinder (LINAK) for adjusting the feed gap.

F PT-100 temperature probes for monitoring grinding chamber temper-


ature (optional).

G Vibration sensor (optional).


0/4 … 20 mA → 0.0 … 64 mm/s.

H Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.

I Frequency converter setpoint of the feed roller.


0/4 … 20 mA → 0 … 100 Hz.

J Analog actual value output of the hammer mill.


0/4 … 20 mA = 0 … ADC.AOMAX

K Alarm output.
Function can be inverted via parameter SYS.AINV.

L Digital output of hammer mill is in operation.


24 V = Hammer mill is running.

Bühler Group
AHZC-23401-1-2302-en-US
58 | Operating manual
Chapter 6
Operation

6 Operation
6.1 Operate keys and lamps

(1) (2)

(3)

(4)
(4)

Fig. 6.1 Switch cabinet, front side

(1) Open cone (2) Opening the heavy particle flap


(3) Machine stop (4) Close cone (two-hand operation)

Open cone
Prerequisites:
ü All locks facilitate the opening.

u Open the cone. Press and hold the key (1) until the cone opens.
’ Lamp does not light up: Cone is locked.
’ Lamp lights up: Cone is unlocked and can be opened.
’ Lamp is flashing: Plant control system sends a sieve change request.
When the key is pressed and the lamp is flashing quickly, the cone cannot be
opened because the locks prevent opening at the moment.

Opening the heavy particle flap

u Press the (2) key for 2 s.

Machine stop

u Press key (3).


’ Machine stops. (No emergency stop.)

Close cone (two-hand operation)

u Press the keys (4) of the two-hand operation.


’ Cone closes until one of the keys is released or the cone is closed.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 59
Chapter 6
Operation

6.2 Set parameters and parameter groups


Parameters in this document are written as ”Parameter group.Parameter“, e.g.
SYS.TYP is the parameter TYP of the SYS parameter group. The decimal precision of
the displayed weight values depends on the ADC.DIV parameter. Set the weight unit
at the ADC.UNIT parameter.
The following illustration shows the structure of the parameter groups. P1, P2 and P3
represent the individual parameters.

USER

S5

S5

+ > 1s
S6

S5 S5 S5 S5 S5

MAIN SYS ADC HOST PBDP SERV

P1 ... ... ... ... ...


S8

P2 ... ... ... ... ...

P3 ... ... ... ... ...


S7
... ... ... ... ... ...

… … … … … …

The control is operated via the USER parameter group and the subordinate parame-
ter groups such as MAIN, SYS, ADC, etc.
By default, the control's display changes to the first parameter of the "USER" param-
eter group after 600 s without user input.

1. Invoke subordinate parameter group. Press <Arrow> and <Data input> key for
1 s.
2. Change to the next subordinate parameter group. Press <Arrow> key.
3. Select parameters.
u Use the <Plus> key to go to the next parameter.
u Use the <Minus> key to go to the previous parameter.
4. Edit parameters. Press the <Data input> key for 1 s until the cursor or parameter
flashes. Then select the decimal place with the <Arrow> key.
5. Increase the parameter value. Press the <Plus> key.
6. Reduce parameter value. Press the <Minus> key.
7. Save the parameter value. Press the <Data input> key.
8. Invoke USER parameter group. Press <Arrow> key for 1 s.
Indexed parameters (e.g. ”USER.SET.x“: ”x“ is the index. ) ”USER.SET.x“ See
page 83.

1. Increase the index. Press and keep the <Function> held down and press the
<Plus> key.
2. Reduce the index. Press and keep the <Function> held down and press the <Mi-
nus> key.

Bühler Group
AHZC-23401-1-2302-en-US
60 | Operating manual
Chapter 7
Configuration

7 Configuration
7.1 Setting the application
Select the desired application with the ”SYS.TYP“ parameter. ”SYS.TYP“ See
page 99.
Prerequisites:
ü The application is not in operation.

Important
As a rule, the application of the control has already been set Ex Works.
u Execute the subsequent procedure only if the application has been reset or
has not been set.

1. Press <Arrow> and <Data input> key for 1 s.


’ Changes to the subordinate parameter group.
2. Press the <Arrow> key as often as necessary until the SYS parameter group is
selected.
’ The TYP parameter is displayed with the default value NOAPP.
3. Press the <Data input> key for 1 s.
’ The parameter value flashes.
4. Press the <Plus> key or the <Minus> key until the application is displayed.
5. Press the <Arrow> key again.
’ The parameter value lights up. The application is selected.
’ The program restarts automatically.

7.2 Device-specific settings

1. Select the application.


u TCON.DFCQ = DFZK for vertical hammer mill DFCQ V
u TCON.DFCQ = FCM or throughput control DFCQ H
2. Check setting of TCON parameters.
3. Set type of remote control at SYS.REM.
4. Set source of release signals at SYS.EIN.
u For a Bühler plant control system, always set to OFF.
5. Set motor current.
u ADC.MOT.x.1 = Nominal current of main motor
6. Set current transformer value.
u ADC.CON.x.1 = Set value according to the schematic or when using a fre-
quency converter: See page 73, Chapter ”Controlling the main motor with
frequency converter“.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 61
Chapter 7
Configuration

7.3 Using the input wizard


Parameter values are entered using the input wizard.

Important
This procedure is used to change important settings that have normally already
been set in the factory.
u Execute this procedure only if the most important parameters were not con-
figured Ex Works or if the control is to be reset.

1. Select the ”TCON.ASSIST“ parameter. ”TCON.ASSIST“ See page 98.


2. Press <Function> key.
’ The message ASSIST ON lights up briefly. The input wizard is activated.
’ <Function> key flashes.
3. Use <Arrow> key to switch to 1st parameter.
4. Modify the displayed parameter: Press the <Data input> key for 1 s.
’ The parameter value flashes.
5. Press the <Plus> key or the <Minus> key until the desired parameter value is dis-
played.
6. Press the <Data input> key again.
’ The parameter value is set.
7. Use <Arrow> key to switch to the next parameter.
8. Repeat steps 4 to 7 until all parameters have been set.
’ The ASSIST OFF message lights up briefly. The input wizard is deactivated.
’ The <Arrow> key deletes.

7.4 Activate Profibus

1. If the Profibus is used, then set the parameter ”SYS.REM“ to REMP. ”SYS.REM“
See page 100.
2. Deactivate the 24 V inputs ”release of main motor“ and ”release of dosing“ in this
case (”SYS.EIN“ = OFF). ”SYS.EIN“ See page 100.

7.5 Activating Profinet

u If Profinet is used, then set the parameter ”SYS.REM“ to REME and ”SYS.ENET“
to P-NET. ”SYS.REM“ See page 100. ”SYS.ENET“ See page 105.

7.6 Activating Ethernet

u If EtherNet/IP is used, set the parameter ”SYS.REM“ to REME and ”SYS.ENET“


to ETH-IP. ”SYS.REM“ See page 100. ”SYS.ENET“ See page 105.

Bühler Group
AHZC-23401-1-2302-en-US
62 | Operating manual
Chapter 7
Configuration

7.7 Optimizing controller settings

7.7.1 Descriptions of controller characteristics


The parameters of the CTRL parameter group determine the controller characteris-
tics. The devices have basic settings which are sufficient for operation. Optimizations
become necessary if the controller is not working perfectly due to various influences
such as pressure differences, throughput deviations, design value of the machine, air-
flow conduction, etc. Two procedures are available for the optimizations. The proce-
dures differ greatly from one another.

– Optimization according to Ziegler Nichols: If the system to be controlled is not


known, this procedure must be used. Control parameters are adapted according
to the Ziegler Nichols method.
– Empirical optimization: If basic parameters are available, this optimization is ap-
plied. Control parameters are adapted on the basis of observations.

The integrated control algorithm is based on the generally valid controller characteris-
tics. Various controllers can be implemented. We recommend not modifying the con-
troller type because not every controller type can be adapted for each controlled sys-
tem.

7.7.2 Ziegler Nichols optimization


This form of optimization can be used with all systems. The difference is whether it is
a controlled system with or without balancing.
– Controlled system with balancing: If the system assumes a stationary status af-
ter modifying the control variable and after a particular time, then this is a system
with balancing.
Example: A valve for steam is opened to a fixed value (e.g. 50 %). The product is
heated and the temperature rises. After a certain time, a balance is reached. The
product remains at a stable temperature.
– Controlled system without balancing: A controlled system without balancing
behaves differently. A stationary state does not occur.
Example: a water tank is filled with water. If a fixed metering amount is set, the fill-
ing level in the water tank rises until the tank overflows.

Use the Ziegler Nichols procedure to optimize the system. The temporal course of the
actual amount is recorded after modifying the control variable. This is known as the
step response. The control parameters are determined on the basis of this response.

7.7.3 Determining control parameters for controlled system with balancing


Constant operating conditions are needed. Set the machine's surroundings accord-
ing to the process conditions.
Example: pressure reduction valves are set correctly, ventilation and product amounts
correspond to normal operation.

7.7.3.1 Recording the step response


1. Create a step in the control signal. E.g. open a valve for steam from 0 to 50 % or
from 20 to 40 %. Then keep this signal constant.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 63
Chapter 7
Configuration

2. The course of the measurand is recorded. Wait until a stationary status levels off
in a controlled system with balancing or a constant rise is achieved in systems
without balancing.
3. The tangents are drawn in and the factors calculated depending on the controller
type. The times ”Tu“ and ”Tg“ are ruling for calculating the factors.
Example: Controlled system with balancing
(1) (2) (3) (4)

45

40

35

30

25

(5)
20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Tu Tg

Fig. 7.1 Controlled system with balancing

(1) Temperature in °C (2) 0 % => 50 % step response


(3) Turning point (4) Temperature curve
(5) Time in minutes

y = Final temperature = 40.0 °C

As = Step height in this example = 50 %


(Control valve was opened from 0 to
50 %)

Tg = Balancing time in s = 270 s

Tu = Delay time in s = 315 s

Ks = Tg × As 270[s] × 50
= = 1,07
Tu × y 315[s] × 40

Values to set for CTRL.KR CTRL.TN CTRL.TV

P controller Ks − −

PD controller 1.2 Ks − 0.25 …… 0.5 Tu

PI controller 0.8 Ks 3 Tu −

PID controller 1.2 Ks 2 Tu 0.42 Tu

Bühler Group
AHZC-23401-1-2302-en-US
64 | Operating manual
Chapter 7
Configuration

7.7.3.2 Determining critical reinforcement


Operate the feedback loop as a P controller (”CTRL.REG“ = P). Start the device and
increase the reinforcement ”CTRL.KR “ until the actual value starts to oscillate. Mea-
sure the time of oscillation T as soon as the system oscillation is constant. Determine
the control parameters based on this oscillation time. The current ”CTRL.KR “ setting
is referred to as KRcritical.
Constant oscillation at ”CTRL.KR “ = 10,000
(1) (2)

140

120

100

80
T

60

40

20

(3)
0
0 5 10 15 20

Fig. 7.2 Constant oscillation at ”CTRL.KR “

(1) Temperature in °C (2) Temperature curve


(3) Time in minutes
Important: T is determined in s!

Values to set for CTRL.KR CTRL.TN CTRL.TV

P controller 0.5 KR critical − −

PI controller 0.45 KR critical 0.85 Tu −

PID controller 1.2 KR critical 0.5 Tu 0.12 Tu

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 65
Chapter 7
Configuration

7.7.4 Determining control parameters for controlled system without balancing


Example: controlled system without balancing
(1) (2) (3)

200

180

160

140

120

100

80

60

40 (4)
20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Tu Ti

Fig. 7.3 Controlled system without balancing

(1) Temperature in °C (2) 0 % => 50 % step response


(3) Temperature curve (4) Time in minutes

A = Maximum output variable in this exam- = 100 %


ple

As = Step height in this example = 50 %


(Control valve was opened from 0 to
50 %)

Ti = Rise time in s = 750 s

Tu = Delay time in s = 225 s

Ki = A × Tu 100 [%] × 225 [s]


= = 0,6
As × Ti 50 [%] × 750 [s]

Values to set for CTRL.KR CTRL.TN CTRL.TV

P controller 0.5/Ki − −

PD controller 0.5/Ki − 0.5 Tu

PI controller 0.42/Ki 5.8 Tu −

PID controller 0.4/Ki 3.2 Tu 0.8 Tu

7.7.5 Empirical optimization


If the process does not allow, or if the control parameters are known, then optimize
empirically. To do this, note the system variables and adjust if necessary.
The following 2 opposite states can occur:
– The system is oscillating.
– Control corrections are undertaken only very slowly.

Bühler Group
AHZC-23401-1-2302-en-US
66 | Operating manual
Chapter 7
Configuration

The system is oscillating


The controller is working too fast. In this case, decrease the ”CTRL.KR “ parameter. It
is beneficial to reduce this value by half in each case.
If the KR value has been decreased several times, it also makes sense to increase the
”CTRL.TN“ parameter.

”CTRL.KR“ Less than Smaller influence on deviations

”CTRL.TN“ Greater than Smaller influence on deviations

”CTRL.TV“ Active only for PD and PID controller =>


guide value ”CTRL.TN“ /5

Control corrections are undertaken only very slowly


The controller is working too slowly. In this case, increase the ”CTRL.KR -“ parame-
ter.
It makes sense to decrease the ”CTRL.TN“ parameter. Here, the value can be re-
duced in each case by half. Do not adjust the values too much, however. Otherwise
the system will start to oscillate.

”CTRL.KR “ Greater than Larger influence on deviations

”CTRL.TN“ Less than Larger influence on deviations

”CTRL.TV“ Active only for PD and PID controller =>


guide value ”CTRL.TN“ /5

7.8 Temperature monitoring

7.8.1 Configure existing temperatures


Since each channel is set individually, different types of temperature sensors can be
used. ”1317.AI1.x“.

u With parameter ”EBD.1317.AI“, set the temperature sensor type for every config-
ured temperature. ”EBD.1317.AI“.

7.8.2 Set scaling data


With PT100 or PT1000 sensors, no scaling data is necessary. The temperature is al-
ways defined by the resistance value. Parameters ”ADCT.TMIN“ und ”ADCT.TMAX“
have no function. ”ADCT.TMIN“. ”ADCT.TMAX“.

1. If a sensor with current 0 or 4 … 20 mA is used, set the scaling ”ADCT.TMIN“


and ”ADCT.TMAX“ for each channel. Refer to the specifications on the data sheet
of the sensor.
2. If a sensor with voltage output 0 … 5 V or 10 V is used, set the scaling
”ADCT.TMIN“ and ”ADCT.TMAX“ for each channel. Refer to the specifications on
the data sheet of the sensor.
3. If IFM sensors TR2432 are used: set ”ADCT.TMIN“ = -40.0 °C and
”ADCT.TMAX“ = +300.0 °C.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 67
Chapter 7
Configuration

7.8.3 Check settings of CAN module EBD 1317


The settings depend on the sensor type.

1. Check settings of jumpers on the CAN module.


2. Check setting for each channel.

7.8.4 Calibrate and check temperatures

1. Calibrate temperatures.
u With the default setting, the error is < 2 %.
u If the error is greater, check the configuration again.
2. For the PT100 or PT1000 sensors, correct only the offset error with the parame-
ter ”ADCT.OFFSET“. Modify the offset correction in the working area of the ma-
chine.
3. Measure the current value at the input. (0/4 … 20 mA or 0 … 5 V/10 V)
u Display the current value with parameter ”EBD.1317.AIN“.
u Correct deviations using parameter ”EBD.1317.AIADJ“.
’ If there is no deviation, the temperature is displayed correctly.
u If no measuring instrument is available, align with parameter ”ADCT.OFFSET“
as well.

7.9 Setting frequency converter of the feed roller


The frequency converter is controlled via pulse frequency or analog set point speci-
fied.
Set the following values for the frequency converter:

Set point analog 0/4 … 20 mA

Set point of pulse fre- 0 … 1,000 Hz


quency

Minimum motor fre- 0 Hz


quency

Maximum motor fre- 100 Hz


quency

Starting delay 3 s

Quick stop delay 0.1 s

Operating mode Remote operating mode –

Bühler Group
AHZC-23401-1-2302-en-US
68 | Operating manual
Chapter 7
Configuration

Important
u Adjust the other parameters of the frequency converter to the motor.
u Lock the frequency converter with motor contactor.
u Release the frequency converter only when the main motors are switched
on.

7.9.1 Schneider ATV 320


Following parameters are applicable for Schneider ATV 320:

CONF (1.3 CONFIGURATION)

FCS- (FACTORY SETTINGS)

Code Name/Description of the Setpoint


Parameter

FCSI Config. Source InI (Macro-Conf)

FRY- PARAMETER GROUP ALL


LIST Choose ALL and press
key once for confirmation
from ”to“

GFS Goto FACTORY SET- YES and press key for


TINGS 2 seconds.

CONF (1.3 CONFIGURATION)

FULL (FULL)

SIM- (SIMPLY START)

Code Name/Description of the Setpoint


Parameter

BFR Standard mot. freq According to motor


nameplate

NPR Rated motor power According to motor


nameplate

UNS Rated motor volt. According to motor


nameplate

NCR Rated mot. current According to motor


nameplate

FRS Rated motor freq. According to motor


nameplate

NSP Rated motor speed According to motor


nameplate

TFR Max frequency 100.0 Hz

TUN Auto tuning YES and press key for


2 seconds.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 69
Chapter 7
Configuration

CONF (1.3 CONFIGURATION)

FULL (FULL)

SIM- (SIMPLY START)

Code Name/Description of the Setpoint


Parameter

ITH Mot. therm. current According to motor


nameplate

ACC Acceleration 3.0 s

DEC Deceleration 0.1 s

LSP Low speed 0.0 Hz

HSP High speed 100.0 Hz

CONF (1.3 CONFIGURATION)

FULL (FULL)

I_O- (INPUTS/OUTPUTS CFG)

Code Name/Description of the Setpoint


Parameter

TCT 2 wire type PFO (Fwd priority) and


press key for 2 seconds

L5- (LI5 CONFIGURATION)

PFR RP max value 1.00 kHz

CONF (1.3 CONFIGURATION)

FULL (FULL)

CTL- (COMMAND)

Code Name/Description of the Setpoint


Parameter

FR1 Ref. 1 channel PI (RP)

CONF (1.3 CONFIGURATION)

FULL (FULL)

FUN- (APPLICATION FUNCT.)

Code Name/Description of the Setpoint


Parameter

STT- (STOP CONFIGURATION)

STT Type of stop NST (Freewheel)

Bühler Group
AHZC-23401-1-2302-en-US
70 | Operating manual
Chapter 7
Configuration

CONF (1.3 CONFIGURATION)

FULL (FULL)

FUN- (APPLICATION FUNCT.)

Code Name/Description of the Setpoint


Parameter

ADC- (AUTO DC INJECTION)

ADC Auto DC injection No

PSS- (PRESET SPEEDS)

JPF Skip frequency 1.0 Hz

JF2 Skip frequency 2 3.0 Hz

CONF (1.3 CONFIGURATION)

FULL (FULL)

FLT- (FAULT MANAGEMENT)

Code Name/Description of the Setpoint


Parameter

PTC- (PTC MANAGEMENT)

PTCL LI6=PTC sample AS (Always)

ATR- (AUTOMATIC RESTART)

ATR Automatic restart YES and press key for


2 seconds.

TAR Max. restart time CT (Unlimited)

Connection example:
Alarm input DI 0.11 (alarm ”A065 FC“) is active only if ”TCON.FEED“ = FC_SLD.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 71
Chapter 7
Configuration

0 = Alarm

0 - 1 kHz

0 - 100 Hz

PTC

Fig. 7.4 Connection example

7.9.2 Schneider ATV 312/31


The following table applies to a Schneider ATV 312/31 (Bühler special design
UXE-36072-080).
The parameters are already configured Ex Works. With this design version, it is not
possible to modify settings with the Telemecanique software ”Power Suite“.

MENU Parameters Description Set Value

SET DEC Deceleration ramp 0.1 S


time

SET HSP High speed 100.0 HZ

SET ITH Motor thermal protec- 1.3 A


tion - max. thermal
current

SET JPF Skip frequency 1.0 HZ

SET JF2 2nd skip frequency 3.0 HZ

SET SP2 2nd preset speed 50 HZ

DRC BFR Standard motor fre- 50 HZ


quency

DRC UNS Nominal motor voltage According to motor


given on the rating nameplate
plate

DRC FRS Nominal motor fre- According to motor


quency given on the nameplate
rating plate

Bühler Group
AHZC-23401-1-2302-en-US
72 | Operating manual
Chapter 7
Configuration

MENU Parameters Description Set Value

DRC NCR Nominal motor current According to motor


given on the rating nameplate
plate

DRC NSP Nominal motor speed According to motor


given on the rating nameplate
plate

DRC COS Motor Cos Phi given According to motor


on the rating plate nameplate

DRC UFT Selection of the type of CONSTANT TORQUE


voltage/frequency ratio

DRC TFR Maximum output fre- 100.0 Hz


quency

CTL FR1 Configuration refer- PULSE INPUT (PUL)


ence 1

CTL FR2 Configuration refer- ANALOG INPUT AI3


ence 2

FUN STC Normal stop mode FREEWHEEL STOP

FUN ADC Standstill DC injection NO DC INJECTION

FLT ATR Automatic restart YES

FLT TAR Max. duration of UNLIMITED


restart process

FLT LET Configuration of exter- STATE 0


nal fault

FLT DRN Derated operation in YES


the event of an under
voltage

IO TCT Start mode PFO

7.10 Controlling the main motor with frequency converter


When using a frequency converter, the hammer mill utilization can be transferred to
DFCQ by the frequency converter. For this purpose, the frequency converter must
have 0 … 20 mA or 4 … 20 mA output for the motor torque. This schematic can also
be used for a double hammer mill.
The actual value output of the frequency converter must show the following charac-
teristics:
– 20 mA = 150 % motor torque (depending on the size of the frequency converter).
This is needed so that the control system can also measure and evaluate an over-
load.
– If 20 mA = 100 % motor torque, then capacity control is not possible because an
overload cannot be detected.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 73
Chapter 7
Configuration

Product

DFZQ Product supply

Grid FU
Hammer mill

Motor of hammer mill

Product discharge

Fig. 7.5 Schematic of frequency converter DFCQ

Important
u If the motor is overloaded, the frequency converters will reduce the speed.
This will reduce the throughput and the hammer mill can run even fuller.
u Maximum permissible frequency of hammer mill = 60 Hz.

1. Connect the device.


u Hammer mill 1: X14.1 (AI 0.0) − 0/4 … 20 mA signal of FC (+); X14:6 − GND
(−)
u Hammer mill 2: X24:1 (AI 0.4) - 0/4 ... 20 mA signal of the FC (+); X24:6 -
GND (-)
2. Set the parameters in the device.
u Set the parameter ”SYS.AI“ of the corresponding analog input to 0 … 20 mA
or 4 … 20 mA.
3. Setting machine parameters.
u The power consumption of the motor depends on its speed. Do not use the
current as the actual value but the motor torque instead.

Bühler Group
AHZC-23401-1-2302-en-US
74 | Operating manual
Chapter 7
Configuration

7.10.1 Configuring the frequency converter Schneider ATV 930 (example)

Fig. 7.6 Configuration menu for analog output AQ1 and AQ2

Example: motor torque at analog output AQ1


The analog output AQ1 (4 to 20 mA) should display the current motor torque in the
range of 0 to 150 % of the rated torque.
AQ1: 4 … 20 mA = 0 … 150 % of the rated torque
Set the following parameters on the frequency converter:

5.14 Input/output (IO)

Tab AI/AQ

AQ1 configuration (AO1)

Code Name/Description of the Setpoint


Parameter

AO1 AQ1 assignment Motor torq.

AO1T AQ1 Type Current

AOL1 AQ1 min output 4.0 mA

AOH1 AQ1 max. output 20.0 mA

ASL1 Scaling AQ1 min. 0.0 %

ASH1 Scaling AQ1 max. 50.0 %

In order to display the motor current in amperes and the motor torque in % in the up-
per strip of the graphic terminal screen, make the following setting in the 8.4 Cus-
tomization (CUS):

Code Name/Description of the Setpoint


Parameter

PBS Param. Bar Select Motor Current


Motor torque

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 75
Chapter 7
Configuration

Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.

1. Set the following parameter in DFCQ:


u ADC.MOT x.1 = Nominal current of motor (for example, 140 A)
u ADC.CON x.1 = “Nominal current of motor (ADC.MOT x.1)” × “maximum mo-
tor torque (150 % according to the example given above)” × 0.01 (for exam-
ple, 140 A × 150 % × 0.01 = 210 A)
u TCON.MOTOR = FC
2. After starting the hammer mill, check the display on the control unit DFCQ
(USER.ACTUAL). The utilization display in % must match the display on the fre-
quency converter (± approx. 3 %).

7.10.2 Configuring the frequency converter DANFOSS VLT 5000


Set the following parameters on the frequency converter:

Parameters Function Adjustment

221 Torque limits for the motor Maximally depending on the


operation size of the motor and fre-
quency converter

319 or 321 Function of current out- 0−MLIM ¦ 4 … 20 mA/


put 42 or function of cur- 0 … 20 mA
rent output 45

Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.

1. Set the following parameter in DFCQ:


u ADC.MOT x.1 = Nominal current of motor (for example, 140 A)
u ADC.CON x.1 = ”Nominal current of the motor (ADC.MOT x.1)“ × ”maximum
motor torque (parameter 221 in frequency converter)“ × 0.01 (for example,
140 A × 150 % × 0.01 = 210 A)
u TCON.MOTOR = FC
2. After starting the hammer mill, check the display on the control unit DFCQ
”USER.ACTUAL“ See page 82. The utilization display in % must match the dis-
play on the frequency converter (± approx. 3 %).

Bühler Group
AHZC-23401-1-2302-en-US
76 | Operating manual
Chapter 7
Configuration

7.11 Special applications

7.11.1 Control on the discharge conveyor with fan (pneumatic suction conveying
system)
The parameter ”TCON.REG_M2“ must be set to ON. ”TCON.REG_M2“ See
page 94.
The motor load characteristics for the discharge conveyor with fan behave in the op-
posite fashion to a discharge conveyor with a mechanical component. The current
transformer value (ADC.CON 1.2) should lie marginally over the nominal current of the
fan motor.
The load for the discharge conveyor with fan is calculated as shown in the graphic
below:

(USER.LOAD.1)[%]

Fig. 7.7 Calculation of load for discharge

7.11.1.1 Load control by current measurement of the fan motor (control with DOL
starting or soft starter)

1. Read the current of the fan motor in case of a “minimum load” (maximal current)
in parameter ”ADC.I 1.2“. ”ADC.I 1.2“. This takes place in case of a maximum air
volume and without product. Round up this read current value by 5 % and enter
with a negative sign (–) for ”ADC.MOT 1.2“. ”ADC.MOT 1.2“. Example: Enter dis-
play 100 A → ADC.MOT 1.2 = –105 A (105 % of 100 A).
2. Read the current of the fan motor in case of “maximum load” (minimum current)
in parameter ”ADC.I 1.2“. This takes place in case of a minimum air volume and
with a high product throughput at which the hammer mill sieve slowly gets
clogged and the subsequent discharge conveyor is disrupted. In order to simulate
this state, place a board upstream the air inlet at the gravity separator and place
paper bags on the other air inlets. Enter this read current value for ”ADC.I0 1.2“.
3. After starting the fan, check the load on the control unit DFCQ (USER.LOAD.1).
Approx. 0 % should be displayed in case of a maximum air volume and without
product.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 77
Chapter 7
Configuration

7.11.1.2 Load control via the motor torque of the fan motor (control with frequency
converter)
The motor torque should be used for the control instead of the current while using a
frequency converter. An analog output of the frequency converter is used for the out-
put of the motor torque. Thus the current transformer is omitted.
The following example for the configuration of the analog outputs is applicable for
Schneider ATV 930.

Fig. 7.8 Configuration menu for analog output AQ1 and AQ2

Example of motor torque at the analog output AQ1


The analog output AQ1 (4 to 20 mA) should display the current motor torque in the
range of 0 to 110 % of the rated torque.
AQ1: 4 … 20 mA = 0 … 150 % of the rated torque.
Set the following parameters on the frequency converter:

5.14 Input/output (IO)

Tab AI/AQ

AQ1 configuration (AO1)

Code Name/Description of the Setpoint


Parameter

AO1 AQ1 assignment Motor torq.

AO1T AQ1 Type Current

AOL1 AQ1 min output 4.0 mA

AOH1 AQ1 max. output 20.0 mA

ASL1 Scaling AQ1 min. 0.0 %

ASH1 Scaling AQ1 max. 36.7 %

Bühler Group
AHZC-23401-1-2302-en-US
78 | Operating manual
Chapter 7
Configuration

Important
The device's earth connection is with a minus connection of the 0/4 … 20 mA -
signal. This can lead to problems with some frequency converters.
u Use an isolating transformer between the frequency converter and the
DFCQ.

1. Set the following parameter in DFCQ:


u ADC.CON 1.2 = “Nominal current of the fan motor according to the motor
nameplate” × “Motor torque at 20 mA (110 % according to the example given
above)” × 0.01
(for example, 120 A × 110 % × 0.01 = 132 A)
The nominal current of the fan motor is included in the calculation so that, in
addition to the load in % the displayed current values in amperes match in re-
ality. Current and the motor torque are proportional.
u Read the motor torque of the fan motor in case of a ”Minimum load“ (maxi-
mum torque) in parameter ”ADC.I 1.2“ (current value is displayed). This takes
place in case of a maximum air volume and without product. Round up this
read air volume by 5 % and enter with a negative sign (–) for ”ADC.MOT 1.2“.
Example: Enter display 100 A → ADC.MOT 1.2 = –105 A (105 % of 100 A).
u Read the motor torque of the fan motor in case of a ”Maximum load“ (mini-
mum torque) in parameter ”ADC.I 1.2“ (current value is displayed). This takes
place in case of a minimum air volume and with a high product throughput at
which the hammer mill sieve slowly gets clogged and the subsequent dis-
charge conveyor is disrupted. In order to simulate this state, place a board
upstream the air inlet at the gravity separator and place paper bags on the
other air inlets. Enter this read motor torque for ”ADC.I0 1.2“.
2. After starting the fan, check the load on the control unit DFCQ (USER.LOAD.1).
Approx. 0 % should be displayed in case of a maximum air volume and without
product.

7.11.1.3 Load control by air volume measurement with dynamic pressure sensor (control
fan motor with DOL starting, soft starter or frequency converter)
A dynamic pressure probe is used for the air volume measurement, which records
the difference between a static and dynamic pressure and is displayed in Pa (Pascal)
[N/m2] by means of a differential pressure transmitter. The square rooted 4 … 20 mA
- output signal is forwarded to the control system. This means that the output signal
in mA is proportional to the root of the dynamic pressure and with that approximately

proportional to the air velocity, i. e. .


φ is a device-specific factor and also considers the air density, which can however
vary depending on the static pressure and temperature. However, the previous pa-
rameters are neglected for this application. φ is calculated according to the specifica-
tions of the manufacturer and is in the area of approx. 1.06 for Debimo measuring
rods.
The sensor shows a differential pressure, i.e. the difference between dynamic pres-
sures in Pa (Pascal) [N/m2]. This means that if a differential pressure of 600 Pa is dis-
played, then this corresponds to a numerical value of 24.49 m/s. Assume φ is 1.06,

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 79
Chapter 7
Configuration

then the air velocity is 1.06 × 24.49 = 25.96 m/s. If φ is not known, or for checking
purposes, the air velocity can be measured with an anemometer and calculated with

the differential pressure .


To be able to calculate the air volume in m3/min, the air velocity is required in m/s and
the pipe cross section in m2.
Air volume [m3/min] = air velocity [m/s] × 60 s/min × pipe cross section [m2]
Note: In case of the air volume measurement, the current values displayed in am-
peres in the DFCQ correspond with the air volume in m3/min.
Set the following parameter in DFCQ:

1. Determine the maximum measurable air volume in m3/min in case of 20 mA out-


put signal of the sensor ”ADC.CON 1.2“.
u Start the fan with a maximum speed.
u For the inlet of the measuring channel, calculate the average air velocity in m/
s, according to the specifications of the probe manufacturer or measure it
with an anemometer (for example, 16 m/s).
u By means of the measured air velocity and pipe cross section (for example,
0.052 m2), the air volume is to be calculated (for example, 16 m/s × 60 s/min
× 0.052 m2 = 50 m3/min).
u Read the dynamic pressure on the sensor display (for example, 180 Pa) and
bring it in relation to the maximum measuring range of the sensor (for exam-
ple, 600 Pa). Take the square root of the result. (for example, 100 % × root
(180 Pa/600 Pa) = 54.77 %). Therefore, the air volume of 50 m3/min corre-
sponds to 54.77% of the maximum measurable air volume.
u Calculate the maximum measurable air volume in case of an output signal of
20 mA (50 m3/min ÷ 54.77 % × 100 % = 91.3 m3/min).
u Enter the value 91.3 for ”ADC.CON 1.2“.
2. Read the air volume of the fan motor in case of a ”Minimum load“ (i.e. maximum
air volume, no product in sieve or in the pneumatic suction conveying system, the
air flows freely) in parameter ”ADC.I 1.2“ (current value is displayed). This takes
place in case of a maximum air volume and without product. Round up this read
air volume by 5 % and enter with a negative sign (–) for ”ADC.MOT 1.2“.
u Example: Enter display 100 A → ”ADC.MOT 1.2“ = –105 A (105 % of 100 A).
3. Read the air volume of the fan motor in case of a ”Maximum load“ (minimum air
volume, i.e. sieve or pneumatic suction conveying system is about to clog) in pa-
rameter ”ADC.I 1.2“ (current value is displayed). This takes place in case of a min-
imum air volume and with a high product throughput at which the hammer mill
sieve slowly gets clogged and the subsequent discharge conveyor is disrupted. In
order to simulate this state, place a board upstream the air inlet at the gravity
separator and place paper bags on the other air inlets. Enter this read air volume
for ”ADC.I0 1.2“.
4. After starting the fan, check the load on the control unit DFCQ ”USER.LOAD.1“.
Approx. 0 % should be displayed in case of a maximum air volume and without
product.

Bühler Group
AHZC-23401-1-2302-en-US
80 | Operating manual
Chapter 7
Configuration

7.11.2 Screw metering (TCON.FEED = SCREW)


The machine can also be operated with a feed screw conveyor.
In this case, the digital IO expansion module 5 is omitted. The main circuit board pro-
vides the control signals.

1. Set the ”TCON.FEED“ parameter to SCREW. ”TCON.FEED“ See page 93.


2. Connect the frequency converter of the feed screw conveyor to the setpoint out-
put of the feed roller.
u Use the analog signal A 0.0 (X4:1 and X4:2) or the digital signal DO 0.2 (X2:3
and X2:6).
3. Connect the alarm feedback of the frequency converter to X11:7 (DI 0.11). If not
present, connect the input with a 24 V jumper.
4. Connect the level probe of the intermediate container to X11:6 (DI 0.10). If not
present, connect the input with a 24 V jumper.

7.12 Resetting parameters to factory settings

NOTICE

All set values are overwritten.


u Re-enter all the parameters that are different from the factory set-
ting.

1. Select the ”SYS.INIT“ parameter. ”SYS.INIT“ See page 105.


2. Press the <function> key for 8 s.
’ The control is reset to factory settings.
’ ”NOAPP“ appears on the display.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 81
Chapter 8
Parameters

8 Parameters
8.1 Notes for the parameter details
The letter after ”Step“ indicates to what extent the corresponding parameter is locked
against modification when the input lock is activated. The following values apply:

Step Description

No information. Parameters can always be adjusted.

L Parameter adjustable if LOCK parameter = OFF.


Locked if LOCK parameter = LOW/MED/HIGH.

M Parameter adjustable if LOCK parameter = OFF/LOW.


Locked if LOCK parameter = MED/HIGH.

H Parameter adjustable if LOCK parameter = OFF/LOW/MED.


Locked if LOCK parameter = HIGH.

The input lock is set with the ”SYS.LOCK“ parameter. It is deactivated by default.
”SYS.LOCK“ See page 102.

8.2 Application parameters


When an ”x“ or an ”n“ comes after the parameter name, this corresponds to the
channel number.

8.2.1 USER (operating parameters) parameter group


Notes on the ”parameter number“:
The value of the ”parameter number“ stands for the parameter that is displayed after
a certain time if no key is pressed during this time. It is set in the ”SYS.SD“ parame-
ter. ”SYS.SD“ See page 102.
If the SD parameter has the value 1, for example, the parameter of the USER param-
eter group whose parameter number has the value 1 is used.
This data is used only in the USER parameter group.

USER.ACTUAL Set point and actual value for hammer mill

P-Pos: 0 Unit: %

Configure set point and actual value display.


See SYS.SD parameter for details.

USER.LOAD.x Main motor load/discharge conveyor of mill 1

P-Pos: 1 Unit: %

Bühler Group
AHZC-23401-1-2302-en-US
82 | Operating manual
Chapter 8
Parameters

USER.LOAD.x Main motor load/discharge conveyor of mill 1

Is only displayed if TCON.REG_M2 = ON.


USER.LOAD.0 shows utilization of the main motor of the hammer mill 1.
– TCON.MOTCAN = OFF:
0 % = ADC.I0 1.1;
100 % = ADC.MOT 1.1.
– TCON.MOTCAN = ON:
current motor torque in % of the rated torque (read out by the frequency con-
verter).
USER.LOAD.1 shows load of the hammer mill 1 discharge.
– 0 % = ADC.I0 1.2;
100 % = ADC.MOT 1.2.

USER.I Current motor current of mill x (1 or 2)

P-Pos: 2 Unit: A

Display
With a hammer mill:
I1 XXX.X A
With two hammer mills:
XXX.X A XXX.X A
Left : Hammer mill 1 on the right: hammer mill 2

USER.SET.x Setpoint load of mill x (1 or 2)

P-Pos: 3 Unit: %

USER.FEED Current frequency of the feed roller

Unit: Hz

USER.SLIDE.x Current position of the feed slide gate x (1 or 2)

Unit: %

USER.RUNHR Operating hours of mill 1

Unit: h

Is displayed only if TCON.DFCQ = DFZK.

u Clear working hours. Press <Function> key for 10 s.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 83
Chapter 8
Parameters

USER.RUNHR2 Operating hours of mill 2

Unit: h

Is only displayed, if TCON.DFCQ = DFZK and TCON.MILL = 2.

u Clear working hours. Press <Function> key for 10 s.

USER.ACT.x Current grinding chamber temperature of mill x (1 or 2)

Unit: °C

Is only displayed if TCON.TEMP = ON.

USER.VIBR.x Current vibration value of mill x (1 or 2)

Unit: %

Is only displayed if TCON.VIBR = ON. 100 % corresponds to TCON.VIB_A.

USER.MOT_F.x Current frequency of main motor for mill x (1 or 2)

Unit: Hz

Is displayed only if TCON.MOTOR= FC or BR FC or TCON.MOTCAN = ON.


TCON.MOTCAN = ON:
Actual speed of the main motor (current motor frequency read out by the frequency
converter).
TCON.MOTCAN = OFF:
Setpoint speed of the main motor TCON.MOT_F1 or TCON.MOT_F2.

8.2.2 MAN (manual operation) parameter group


The device makes possible manual operation of individual machine components. This
is especially helpful during machine commissioning or when troubleshooting. To start
an element manually, it must first be changed from automatic mode (AUT) to manual
(MAN). This decouples the element from automatic sequence control and it can now
be controlled via the corresponding parameter.
The following parameters of the MAN parameter group can be controlled manually:
– MAN.FROLL
– MAN.FSLD
– MAN.FSLD2
– MAN.FAN
– MAN.TRAN
– MAN.TRAN2
– MAN.MOT
– MAN.MOT2

These parameters are displayed as shown in the following example. Example,


”MAN.FROLL“ See page 85.

Bühler Group
AHZC-23401-1-2302-en-US
84 | Operating manual
Chapter 8
Parameters

Automatic: FROLL AUT 0 %


Manual: FROLL MAN 50 %
The H4 LED flashes in manual operation. When changing from automatic to manual,
the current value is applied as the setpoint for manual operation. This prevents a run-
ning motor from stopping when changing, for example. When changing from manual
to automatic, the current setpoint from the control sequence is applied again.

MAN.FROLL Frequency of the feed roller

Value range: 0 … 100 Default value: 0

Step: L Unit: Hz

u Set MAN.FSLD to 5 % before starting the feed roller. Otherwise, the slide gate
will touch against the roller.
u Switch between manual and automatic. Press <Function> key.

MAN.FSLD Opening between slide gate and feed roller

Value range: 0 … 100 Default value: 0

Step: L Unit: %

At 0 % closed, at 100 % fully opened.

u Switch between manual and automatic. Press <Function> key.

MAN.FSLD2 Opening between slide gate 2 and feed roller

Value range: 0 … 100 Default value: 0

Step: L Unit: %

At 0 % closed, at 100 % fully opened. Is only displayed if TCON.MILL = 2.

u Switch between manual and automatic. Press <Function> key.

MAN.FAN Manually control fan

Step: L Default value: OFF

Is displayed only if TCON.DFCQ = DFZK.

u Switch between manual and automatic. Press <Function> key.

Value Function

OFF Fan deactivated.

ON Fan activated.

MAN.TRAN Manually control discharge

Step: L Default value: OFF

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 85
Chapter 8
Parameters

MAN.TRAN Manually control discharge

Is displayed only if TCON.DFCQ = DFZK.

u Switch between manual and automatic. Press <Function> key.

Value Function

OFF Discharge deactivated.

ON Discharge activated.

MAN.TRAN2 Manually control discharge, mill 2

Step: L Default value: OFF

Is only displayed if TCON.MILL = 2 and TCON.DFCQ = DFZK.

u Switch between manual and automatic. Press <Function> key.

Value Function

OFF Discharge deactivated.

ON Discharge activated.

MAN.MOT Manually control main motor

Step: L Default value: OFF

Is displayed only if TCON.DFCQ = DFZK.

u Switch between manual and automatic. Press <Function> key.

Value Function

OFF Motor switched off.

MOTL Motor starts with counterclockwise direction of rotation.

MOTR Motor starts with clockwise direction of rotation.

MAN.MOT2 Manually control main motor, mill 2

Step: L Default value: OFF

Is only displayed if TCON.MILL = 2 and TCON.DFCQ = DFZK.

u Switch between manual and automatic. Press <Function> key.

Value Function

OFF Motor switched off.

MOTL Motor starts with counterclockwise direction of rotation.

MOTR Motor starts with clockwise direction of rotation.

Bühler Group
AHZC-23401-1-2302-en-US
86 | Operating manual
Chapter 8
Parameters

MAN.SFPOS Setpoint position of linear cylinder for flap control

Value range: 0 … 100 Default value: 0

Step: L Unit: %

Is only displayed if TCON.MILL = 2 and TCON.DFCQ = DFZK and TCON.FLAP =


ON.

u Switch between manual and automatic. Press <Function> key.

Value Function

MIL1 Position mill 1.

MID TCON.MID middle position.

MIL2 Position mill 2.

MAN.FLPOS Position of linear cylinder for flap control

Value range: 0 … 100 Default value: 0

Step: L Unit: %

Displayed only if TCON.MILL = 2, TCON.DFCQ = DFZK, TCON.FLAP = ON and


TCON.FLMID > 0. Display parameters: For manual modification of position, see
MAN.SFPOS.

u Define middle position of gravity flow diverter: See parameter ”TCON.FLMID“


See page 92.

Value Function

0% Linear cylinder fully retracted.

100 % Linear cylinder fully extended.

MAN.CPOS_R.x Position of linear cylinder on cone, right

Value range: 0 … 350 Unit: mm

Is displayed only if TCON.DFCQ = DFZK.


Display parameter: It is not possible to modify the position manually.

MAN.CPOS_L.x Position of linear cylinder on cone, left

Value range: 0 … 350,0 Unit: mm

Is displayed only if TCON.DFCQ = DFZK.


Display parameter: It is not possible to modify the position manually.

MAN.POSDIF.x Difference in position between linear cylinder on cone, left and right

Value range: 0 … 100,0 Unit: mm

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 87
Chapter 8
Parameters

MAN.POSDIF.x Difference in position between linear cylinder on cone, left and right

Is displayed only if TCON.DFCQ = DFZK.


When clearing, the value MAN.CPOS_R = MAN.CPOS_L is set.
This makes the difference = 0.
See alarms A036 and A056.

u Delete current value. Press the <Function> key for 10 s.

MAN.RUNH_R.x Operating hours for clockwise direction of rotation, main motor mill x

Unit: h

Is displayed only if TCON.DFCQ = DFZK.


When deleting, the operating hours counter is set to 0. Since the direction of rota-
tion that has the smaller counter reading is selected when starting the machine in
automatic mode, the direction of rotation can be influenced by deleting the counter
reading.

u Delete current value. Press the <Function> key for 10 s.

MAN.RUNH_L.x Operating hours for counterclockwise direction of rotation, main motor


mill x

Unit: h

Is displayed only if TCON.DFCQ = DFZK.


When deleting, the operating hours counter is set to 0. Since the direction of rota-
tion that has the smaller counter reading is selected when starting the machine in
automatic mode, the direction of rotation can be influenced by deleting the counter
reading.

u Delete current value. Press the <Function> key for 10 s.

MAN.SCREEN.x Displaying current screen size

Unit: mm

Is displayed only if TCON.DFCQ = DFZK.


The value is only transmitted via fieldbus. This provides the operator with informa-
tion as to which sieve is to be inserted. There is no check as to whether or not the
inserted sieve matches this value.

8.2.3 TCON (configuration parameters) parameter group

TCON.DFCQ Select type of device

Step: L Default value: DFZK

Value Function

DFZK Control system for hammer mill inclusive throughput control

Bühler Group
AHZC-23401-1-2302-en-US
88 | Operating manual
Chapter 8
Parameters

TCON.DFCQ Select type of device

DFZC Not supported yet (machine assembly)

FCM Throughput control

T_DFZK DFZK functional check (Bühler only)

T_DFAV DFAV functional check (Bühler only)

TCON.SETV Number of setpoints

Step: L Default value: 1

Is only displayed if TCON.MILL = 2.

Value Function

1 Only one setpoint is available for both hammer mills.


If SYS.REM = REMA, only analog input AI0.3 is active.

2 Both hammer mills receive a setpoint.


If SYS.REM = REMA, both analog inputs AI0.3 and AI0.7 are active.

TCON.MILL Number of mills

Step: L Default value: 1

Value Function

1 1 hammer mill

2 2 hammer mills

TCON.MOTOR Selecting motor type

Step: L Default value: NORM

Is displayed only if the parameter TCON.DFCQ = DFZK.

Value Function

NORM Standard induction motor with current transformer.

VAR Not supported yet.

FC Frequency converter with torque signal.

BR FC Frequency converter without change of direction when braking. (Standard for fre-
quency converter Altivar 71 or Altivar 930 via CAN)

BR SS Soft starter without change of direction when braking.

TCON.MOTIN Source of motor current for mill

Step: L Default value: AIN

It is compulsory to set TCON.MOTIN to AIN, if TCON.MOTCAN = ON.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 89
Chapter 8
Parameters

TCON.MOTIN Source of motor current for mill

Value Function

AIN The motor current is measured via the analog input of the control.
Hammer mill 1: AI 0.0
Hammer mill 2: AI 0.4

REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/Bytes 14 … 15

TCON.TRANSIN Source of motor current for discharge conveyor

Step: L Default value: AIN

Value Function

AIN The motor current is measured via the analog input of the control.
Discharge conveyor 1: AI 0.1
Discharge conveyor 2: AI 0.5

REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/Bytes 16 … 17

TCON.MOTPTC.x Temperature monitoring of main motor for mill x

Step: L Default value: ON

Is displayed only if TCON.DFCQ = DFZK.

Value Function

OFF No monitoring.

ON The main motor's PTC is monitored.

TCON.MOTCAN CAN communication with frequency converter

Step: L Default value: OFF

Is displayed only if TCON.DFCQ = DFZK.


Is used if the main motor is controlled by Altivar 71 or Altivar 930 frequency con-
verter.

u Set TCON.MOTIN to AIN if TCON.MOTCAN = ON.


u Set TCON.MOTOR to BR FC if TCON.MOTCAN = ON.

Value Function

OFF Control via digital signals.

ON Control via CAN interface.

Bühler Group
AHZC-23401-1-2302-en-US
90 | Operating manual
Chapter 8
Parameters

TCON.MOT_F1.x Setpoint frequency 1 of main motor x

Value range: 30 … 60 Default value: 50

Step: L Unit: Hz

Is displayed only if TCON.MOTOR= FC or BR FC or TCON.MOTCAN = ON.


Setpoint frequencies TCON.MOT_F1 and TCON.MOT_F2. See page 98, Chapter
”Setpoint frequencies of the main motors“.

TCON.MOT_F2.x Setpoint frequency 2 of main motor x

Value range: 30 … 60 Default value: 50

Step: L Unit: Hz

Is displayed only if TCON.MOTOR= FC or BR FC or TCON.MOTCAN = ON.


Setpoint frequencies TCON.MOT_F1 and TCON.MOT_F2. See page 98, Chapter
”Setpoint frequencies of the main motors“.

TCON.MODE Operating mode of the control

Step: L Default value: REG

Value Function

REG Regulates to a setpoint. The feed gap and the speed of the feed roller are changed.
This will enable the largest dosing range to be covered. An attempt is made to op-
erate the feed roller in the optimal speed range TCON.FMIN and TCON.FMAX. The
speed is monitored every 5 s and if necessary, the feed gap is adjusted to bring the
speed back within the optimal range.

FREQ Regulates to a setpoint. The feed gap remains at TCON.SMAX. It is not modified.
The dosing quantity is only influenced by the feed roller (0 … 100 Hz). This limits the
dosing range but can also be helpful for special applications. Modifications cannot
be reacted to very quickly in this mode, as the influence of the feed roller is less
than the influence of the roller gap adjuster.

SLIDE Regulates to a setpoint. The feed roller speed remains at TCON.FMIN. It is not
modified. The dosing quantity is only influenced by the feed gap
(TCON.SMIN … TCON.SMAX). The smallest change in the feed gap is determined
by the mechanics. This mode is not recommended for products which require in-
tensive grinding.

CONST Overload is regulated. If the actual mill load is less than the set point, no control will
occur. Therefore, the control will not be activated until the mill load has exceeded
the set point. The controller is deactivated again when the load falls below the set
point again and the standard settings have been reached again. The standard val-
ues for the feed roller and the feed gap are predefined with TCON.FMAX and
TCON.SMAX.

TCON.FLAP Automatic gravity flow diverter

Step: L Default value: OFF

Is only displayed if TCON.MILL = 2 and TCON.DFCQ = DFZK.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 91
Chapter 8
Parameters

TCON.FLAP Automatic gravity flow diverter

Value Function

OFF Gravity flow diverter is not adjusted automatically.

ON The gravity flow diverter is then converted automatically based on the 24 V release
inputs (DI 0.4 and DI 0.16). In the case of fieldbus connection, the gravity flow di-
verter is changed over via control bits 1.2 and 2.2. The flap changes the position
when one or both hammer mills are released. If no hammer mill is released, the flap
remains in its current position and is adjusted when a modification is made.

TCON.FLMID Gravity flow diverter middle position

Value range: 0 … 100 Default value: 50

Step: L Unit: %

Is only displayed if TCON.MILL = 2 and TCON.DFCQ = DFZK and TCON.FLAP =


ON.

Value Function

0 A limit switch must be available for the middle position. In this case, the pulse out-
put of linear cylinder (DI 6.8) is ignored. The limit switch for the middle position is
connected to DI 6.9.

>0 Value for the middle position of the flap. In this case, the position of the flap is deter-
mined by means of the pulse output of the linear cylinder (DI 6.8).

TCON.VIBR Monitoring vibrations

Step: L Default value: OFF

Value Function

OFF Monitoring deactivated.

ON Monitoring activated.

TCON.UPS UPS monitoring

Step: L Default value: OFF

Value Function

OFF Without uninterruptible power system (UPS)

ON With uninterruptible power system.

TCON.TEMP Monitoring temperature

Step: L Default value: OFF

An alarm is triggered if the temperature TCON.TMAX is reached.

Bühler Group
AHZC-23401-1-2302-en-US
92 | Operating manual
Chapter 8
Parameters

TCON.TEMP Monitoring temperature

Value Function

OFF Monitoring deactivated.

ON Monitoring activated.

TCON.FEED Select feeder

Step: L Default value: FC_SLD

Value Function

FC_SLD Standard, feed roller with FC and linear cylinder LINAK.

NORD Not supported yet.

SLIDE Feed screw conveyor 0/4 … 20 mA and linear cylinder.

SCREW Feed screw conveyor 0/4 … 20 mA.

CLIPP Not supported yet.

FC Manual slide gate, only feed roller with FC.

TCON.FC_SLD Linear cylinder connection location for feed gap adjustment at throughput
control

Step: L Default value: BASE

Is only displayed if TCON.DFCQ = FCM.

Value Function

BASE Connection on main circuit board EBD 1311.

CAN Connection on the decentralized IOs EBD 1318.

TCON.AOUT Output of analog outputs AO 0.0 and AO 0.1

Step: L Default value: ACTV

Is displayed only if TCON.MILL = 2. AO 0.0 relates to mill 1 and AO 0.1 to mill 2.

Value Function

ACTV Actual power of the mill.


0/4 … 20 mA = 0 … ADC.AOMAX.

SETV Setpoint for feed roller.


0/4 … 20 mA = 0 … 100 Hz.

MOTF TCON.MOTCAN = OFF: Setpoint speed of the main motor TCON.MOT_F1 or


TCON.MOT_F2.
TCON.MOTCAN = ON: Actual speed of the main motor (current motor frequency
read out by the frequency converter).
0/4 … 20 mA = 0 … 60 Hz.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 93
Chapter 8
Parameters

TCON.N TRANS Number of discharge conveyors

Step: L Default value: 2

Displayed only if TCON.MILL = 2. Defines the number of discharge conveyors.

Value Function

1 1 discharge conveyor

2 2 discharge conveyors

TCON.TRANS Monitor discharge capacity

Value range: 0 … 150 Default value: 0

Step: L Unit: %

Is displayed only if TCON.DFCQ = DFZK.


If the value is exceeded for longer than 5 s, an alarm message is displayed.

Value Function

0 Monitoring deactivated.

>0 Monitoring activated.

TCON.TRAPRB Level probe discharge

Step: L Default value: OFF

Is displayed only if the parameter TCON.DFCQ = DFZK.

Value Function

OFF No level probe present in the discharge.

ON_0 Level probe is fitted. 0 V = dosing release (e.g. level probe not covered).

ON_1 Level probe is fitted. 24 V = dosing release (e.g. level probe not covered).

TCON.REG_M2 Control to 2 motors

Step: L Default value: OFF

Value Function

OFF Control is only to the main motor utilization.

ON Control is to the motor with the greater utilization. Main motor or discharge.

TCON.CSYNC Synchronize cone

Step: L Default value: ON

Bühler Group
AHZC-23401-1-2302-en-US
94 | Operating manual
Chapter 8
Parameters

TCON.CSYNC Synchronize cone

Is displayed only if TCON.DFCQ = DFZK.


If activated, the position of the linear cylinders on the right and left is measured.
When moving the cone, deviations are compensated to a maximum of 10 mm.

Value Function

OFF Monitoring deactivated.

ON Monitoring activated.

TCON.FMAX Maximum frequency on frequency converter of feed roller

Value range: 0 … 100 Default value: 70

Step: L Unit: Hz

The feed slide gate regulates if the value is exceeded. If TCON.FEED = SCREW or
TCON.FEED = FC, TCON.FMAX is the maximum frequency.

TCON.FMIN Minimum frequency on frequency converter of feed roller

Value range: 0 … 100 Default value: 30

Step: L Unit: Hz

The feed slide gate readjusts when the value falls below the set value. If
TCON.FEED = SCREW or TCON.FEED = FC, TCON.FMIN is the minimum
frequency.

TCON.SMAX Maximum slide gate opening

Value range: TCON.SMIN … 100 Default value: 100

Step: L Unit: %

TCON.SMIN Minimum slide gate opening

Value range: 5 … TCON.SMAX Default value: 5

Step: L Unit: %

TCON.SINI Slide gate opening start value

Value range: 0 … 100 Default value: 0

Step: L Unit: %

The control always starts with this slide gate opening. When this value increases,
the start becomes faster, but also presents the danger of overshooting.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 95
Chapter 8
Parameters

TCON.SINI Slide gate opening start value

Value Function

0 TCON.SINI deactivated.
TCON.SMIN slide gate opening start value.

>0 Start value of slide gate opening TCON.SINI.


TCON.SINI must be greater than TCON.SMIN.

TCON.DIFF Maximum difference of rated power - actual power

Value range: 5 … 50 Default value: 10

Step: L Unit: %

If the difference is exceeded, the feed gap will be corrected immediately.

TCON.TMAX Maximum Temperature

Value range: 50 … 100 Default value: 75

Step: L Unit: °C

Is only displayed if TCON.TEMP = ON.


If the temperature is exceeded, an alarm message is displayed.

TCON.VIB_W Vibration limit warning

Value range: 1,0 … TCON.VIB_A Default value: 10,0

Step: L Unit: mm/s

Is only displayed if TCON.VIBR = ON.


If the limit value for the time TCON.T VIB is exceeded, a warning is displayed.

TCON.VIB_A Vibration limit alarm

Value range: TCON.VIB_W … 64,0 Default value: 20,0

Step: L Unit: mm/s

Is only displayed if TCON.VIBR = ON.


If the limit value for the time TCON.T VIB is exceeded, an alarm is displayed. The
machine stops.

TCON.T VIB Vibration alarm delay

Value range: 0 … 30 Default value: 10

Step: L Unit: s

Is only displayed if TCON.VIBR = ON.

Bühler Group
AHZC-23401-1-2302-en-US
96 | Operating manual
Chapter 8
Parameters

TCON.T1 Clearance time of mill 1 and 2

Value range: 0,1 … 999,9 Default value: 30

Step: L Unit: s

Is displayed only if TCON.DFCQ = DFZK.


When the feeder device is stopped, the emptying time is started. When the main
motors are stopped, the motors are stopped after the emptying time has elapsed.

TCON.T2.x Braking time of mill x (0 or 1)

Value range: 0,1 … 99,9 Default value: 5,0

Step: L Unit: s

Is displayed only if TCON.DFCQ = DFZK.


The braking is activated for this period of time. The time must be set to make the
rotor brake sharply without restarting in the opposite direction.

TCON.T3 Main motor timeout after operation without product

Value range: 1 … 60 Default value: 15

Step: L Unit: Min.

Is displayed only if TCON.DFCQ = DFZK.


The mill must not be operated without product, as the cone heats up to a high tem-
perature due to atmospheric friction. The mill stops after the timeout elapses. It
restarts automatically when the release is pending and the product is in the inlet.

TCON.T4 Waiting time until the feed process begins

Value range: 0 … 60,0 Default value: 1,0

Step: L Unit: s

If TCON.DFCQ = FCM, the feeder device starts once the release input has been
activated. If TCON.DFCQ = DFZK, the feeder device starts once the inlet probe DI
5.0 signals that it is covered.

TCON.T5 Waiting time until the feeder unit stops

Value range: 0 … 120,0 Default value: 1,0

Step: L Unit: s

If TCON.DFCQ = FCM, the feeder unit stops once the release input has been
deactivated. If TCON.DFCQ = DFZK, then the feeder unit stops once the inlet probe
DI 5.0 signals that it is uncovered.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 97
Chapter 8
Parameters

TCON.T6 Start time for heavy start-up of main motor

Value range: 5 … 120 Default value: 15

Step: L Unit: s

Is displayed only if TCON.DFCQ = DFZK.


If there are two mills, the second mill is not started until after this time has elapsed.

TCON.T7 Open heavy particle flap automatically

Value range: 10 … 9999 Default value: 0

Step: L Unit: Min.

Is displayed only if TCON.DFCQ = DFZK.


If the sum of the dosing time exceeds the time TCON.T7, the heavy particle flap is
automatically opened once after the dosing stops and after the emptying time
TCON.T1 elapses.

Value Function

0 Function deactivated.
Opening only with push-button switches on-site.

>0 Function activated.

TCON.LOGMSTP Recording interval of cyclical logger when mill is stopped

Value range: 1 … 3600 Default value: 60

Step: L Unit: s

TCON.LOGMRUN Recording interval of cyclical logger when mill is started

Value range: 1 … 3600 Default value: 10

Step: L Unit: s

TCON.ASSIST Wizard for commissioning

The most important parameters can be modified in succession here.


See page 62, Chapter ”Using the input wizard“.

8.2.3.1 Setpoint frequencies of the main motors


The digital inputs DI 0.6 (hammer mill 1) and DI 0.18 (hammer mill 2) can be used to
switch between the 2 setpoint frequencies TCON.MOT_F1 and TCON.MOT_F2.

Hammer mill 1 Hammer mill 2

DI 0.6 = 0 V TCON.MOT_F1.1 DI 0.18 = 0 V TCON.MOT_F1.2

DI 0.6 = 24 V TCON.MOT_F2.1 DI 0.18 = 24 V TCON.MOT_F2.2

Bühler Group
AHZC-23401-1-2302-en-US
98 | Operating manual
Chapter 8
Parameters

8.2.4 Parameter group SYS (System configuration)

SYS.TYP Application

Step: L Default value: NOAPP

Defines the type of application.

Value Function

NOAPP No application.
No signal from the outputs (e.g. when first switching on after loss of data).

MDDR_T Four-roller mill MDDR.


Four-roller mill MDDT.

DFCQ Control unit for hammer mill.

DFCI Pellet mill control.

MHSA Huller MHSA.

MDDP_Q Four-roller mill MDDP.


Eight-roller mill MDDQ.

TEMP Temperature monitoring for roller mill.

SORT Filling level control for SORTEX Z+.

MDGA High-compression mill MDGA.

OLFB Flaking mill OLFB.

RCHULL Rubber-roller huller DRHE.

DFKM Countercurrent cooler DFKM.

MALT Grist mill MDBA.

MDFA Flaking mill MDFA.

LEEA Dryer LEEA.

TUBO Tubular push conveyor LBGA.

HYMIXP Conditioning HYMIX Plus (feeder DDHA and conditioner DCHA Plus).

MDDY_Z Four-roller mill MDDY.


Eight-roller mill MDDZ.

OLCC Cracking mill OLCC.

DFZL Cracking mill DFZL.

DOQB Flaking mill DOQB.

MYUA Temperature measurement MYUA.

SYS.REM Local/Remote mode

Step: L Default value: LOC

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 99
Chapter 8
Parameters

SYS.REM Local/Remote mode

Value Function

LOC Local: Operation on the display.

REMS Remote control – Serial: Setpoint specification via the serial interface.
Not supported.

REMA Remote control – Analog (nominal rate 0/4 … 20 mA).

REMP Remote control – Profibus DP: Control exclusively via Profibus. Setpoint specifica-
tion and control signals via Profibus active.

REMTCP Remote control – Network, protocol according to ”SYS.TCP“

REME Remote control – Profinet or EtherNet/IP according to ”SYS.ENET“

SYS.EIN 24 V input release main motor, release feeding and mill brakes

Step: L Default value: OFF

The following inputs are affected:


– DI 0.1
– DI 0.4
– DI 0.5

Additionally with mill 2:


– DI 0.16
– DI 0.17

Value Function

OFF The inputs do not have a function. Signals come via fieldbus.

ON Inputs are functioning. Signals via fieldbus are not observed.

ONLOC Inputs function only in manual mode (SYS.REM = LOC).

ONREM Inputs are only in function in remote mode (SYS.REM ≠ LOC).

SYS.DISP Remote control

Step: L Default value: OFF

Value Function

OFF No remote control.

LOC Local operation (remote control is display only).

REM Remote control operation (local operation is display only).

BOTH Both local and remote control operation.

Bühler Group
AHZC-23401-1-2302-en-US
100 | Operating manual
Chapter 8
Parameters

SYS.PSAV Power saving mode

Step: L Default value: STOP

Value Function

OFF Display is constantly lit.

STOP Standby when stopped and if no key is pressed for 10 minutes. An LED flashes.

ON Standby if no key is pressed for 10 minutes. An LED flashes when stopping. Run-
ning light with one LED each if not stopped.

SYS.SD Standard operating parameters

The data appears by default on the display after 600 s if no button is pressed during
this time period. The standard time for the change (600 s) can be modified in the
SYS.SDT parameter. In addition, SYS.SD is used to define what is displayed in the
USER.ACTUAL parameter.

Value Function

0/1 If TCON.MILL = 1 (1 mill):


– TCON.REG_M2 = OFF:
Display on left: setpoint utilization [%].
Display on right: actual value utilization mill 1 [%].
– TCON.REG_M2 = ON:
Display on the left: setpoint utilization [%].
Display on the right: actual value of utilization mill 1 [%] or discharge mill 1 [T %].
The value of the machine with the higher utilization is displayed and adjusted to this
value.
Actual value of utilization:
TCON.MOTCAN = OFF:
Main motor mill 1: 0 % = ADC.I0 1.1; 100 % = ADC.MOT 1.1.
Discharge mill 1: 0 % = ADC.I0 1.2; 100 % = ADC.MOT 1.2.
TCON.MOTCAN = ON:
Actual motor torque in % of rated torque (read by frequency converter).

0/1 If TCON.MILL = 2 (2 mills):


– Display on the left: actual value of utilization of mill 1 [%].
Display on the right: actual value of utilization of mill 2 [%].
– Actual value of utilization:
TCON.MOTCAN = OFF:
Main motor mill x: 0 % = ADC.I0 x.1; 100 % = ADC.MOT x.1.
TCON.MOTCAN = ON:
Actual motor torque in % of rated torque (read by frequency converter).

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 101
Chapter 8
Parameters

SYS.SD Standard operating parameters

2/3 If TCON.MILL = 1 (1 mill):


– TCON.REG_M2 OFF:
Display on the left: Actual value of utilization of mill 1 [%].
Display on the right: Actual frequency of the feed roller [Hz].
– TCON.REG_M2 = ON:
Left display: Actual value load of mill 1 [%] or discharge conveyor of mill 1 [T%]. The
value of the machine with higher utilization is displayed and adjusted to this value.
Display on the right: Current frequency of the feed roller [Hz].
Actual value of utilization:
TCON.MOTCAN = OFF:
Main motor of mill 1: 0% = ADC.I0 1.1; 100% = ADC.MOT 1.1.
Discharge conveyor of mill 1: 0% = ADC.I0 1.2; 100% = ADC.MOT 1.2.
TCON.MOTCAN = ON:
Actual motor torque in % of rated torque (read by frequency converter).

2/3 If TCON.MILL = 2 (2 mills):


– Left display: Actual value of load of mill 1 or mill 2 [%]. The value of the mill with higher
utilization is displayed and adjusted to this value.
Display on the right: Current frequency of the feed roller [Hz].
Actual value of utilization:
TCON.MOTCAN = OFF:
Main motor of mill x: 0 % = ADC.I0 x.1; 100 % = ADC.MOT x.1.
TCON.MOTCAN = ON:
Actual motor torque in % of rated torque (read by frequency converter).

SYS.SDT Automatic change to the standard operating parameter

Value range: 0 … 9999 Default value: 600

Step: L Unit: s

Value Function

0 No automatic change.

>0 The display switches to the standard operating parameter if no key is pressed dur-
ing the time that has been set. ”SYS.SD“

SYS.LOCK Input lock

Default value: OFF

The "SYS.LOCK" parameter prevents certain parameters from being entered and
modified. It is always possible to display the parameters.

Value Function

OFF No lock. All parameters can be adjusted.

LOW Low lock. Parameters marked as L are locked.

MED Medium lock. Parameters marked as M and L are locked.

HIGH High lock. Parameters marked as H, M and L are locked.

Bühler Group
AHZC-23401-1-2302-en-US
102 | Operating manual
Chapter 8
Parameters

SYS.MSG Display messages

Step: L Default value: ALL

Value Function

OFF Display no messages.

ALL Display all messages.

STPOFF Do not display "stop" messages.

SYS.ACLR Clearing the alarm

Step: L Default value: OFF

Value Function

OFF Alarms are acknowledged automatically.

ON Alarms are acknowledged only with the <Clear alarm> (S3) key, via the serial inter-
face, fieldbus or the 24 V input "Delete alarm".

SYS.AINV Inverting the alarm output

Step: L Default value: ON

Value Function

OFF 24 V upon alarm.

ON 0 V upon alarm.

SYS.ASCROL Alternating alarm display

Step: L Default value: ON

Value Function

OFF No alternating alarm display.


The alarm with the highest priority is displayed.

ON Alternating alarm display for all active alarms and warnings.

SYS.AO.x Analog outputs

Default value: 0

Step: L Unit: mA

Mode of the analog outputs. Switchover 0 / 4 … 20 mA.

u Select additional analog outputs. Press and keep the <Function> held down
and press the <Plus> key.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 103
Chapter 8
Parameters

SYS.AI.x Analog inputs

Default value: 0

Step: L Unit: mA

Mode of the analog inputs. 0/4 … 20 mA or 0 … 5 V switchover.

u Select additional analog inputs. Press and keep the <Function> held down and
press the <Plus> key.
u Note the adjustment at jumpers X62.

SYS.AOADJ.x Calibrate analog outputs

Value range: 90,0 … 110,0 Default value: 100,0

Step: L Unit: %

The current value will be modified in percentage increments.

u Select additional analog outputs. Press and keep the <Function> held down
and press the <Plus> key.

SYS.AIADJ.x Calibrate analog inputs

Value range: 90,0 … 110,0 Default value: 100,0

Step: L Unit: %

The current value will be modified in percentage increments.

u Select additional analog inputs. Press and keep the <Function> held down and
press the <Plus> key.

SYS.CANBR Baud rate of CAN bus

Value range: 10 … 1000 Default value: 50

Step: L Unit: kBaud

The Bühler standard baud rate of 200 and CAN-Open baud rates are supported.
– 200
– 10
– 20
– 50
– 125
– 250
– 500
– 800
– 1000

u If line lengths exceed 200 m, reduce baud rate.

Bühler Group
AHZC-23401-1-2302-en-US
104 | Operating manual
Chapter 8
Parameters

SYS.ENET Ethernet interface ProfiNet or Ethernet/IP

Step: L Default value: OFF

Value Function

OFF Ethernet interface switched off. EBD1325/EBD1326.

P-NET Profinet EBD1326.

ETH-IP Ethernet-IP EBD1325.

SYS.TCP Ethernet interface TCP/IP (EBD1330)

Step: L Default value: OFF

Value Function

OFF Ethernet TCP/IP interface switched off. EBD1330.

ROPTCP Remote operation protocol via TCP. Connection to MEAT operation.

TCP-IP Fieldbus protocol via TCP.

SYS.INIT Basic initialization of all parameters

Step: L

Resets all parameters to factory settings.


See page 81, Chapter ”Resetting parameters to factory settings“.

8.2.5 ADC (analog-digital converter) parameter group

ADC.MOT 1.1 Nominal current, main motor, mill 1

Value range: -500,0 … 999,9 Default value: 100,0

Step: L Unit: A

ADC.MOT 1.2 Nominal current, motor, discharge conveyor, mill 1

Value range: -500,0 … 999,9 Default value: 100,0

Step: L Unit: A

ADC.MOT 2.1 Nominal current, main motor, mill 2

Value range: -500,0 … 999,9 Default value: 100,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 105
Chapter 8
Parameters

ADC.MOT 2.2 Nominal current, motor, discharge conveyor, mill 2

Value range: -500,0 … 999,9 Default value: 100,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

ADC.CON 1.1 Current transformer value, main motor, mill 1

Value range: 1,0 … 3000,0 Default value: 200,0

Step: L Unit: A

ADC.CON 1.2 Current transformer value, motor, discharge conveyor, mill 1

Value range: 1,0 … 3000,0 Default value: 200,0

Step: L Unit: A

ADC.CON 2.1 Current transformer value, main motor, mill 2

Value range: 1,0 … 3000,0 Default value: 200,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

ADC.CON 2.2 Current transformer value, motor, discharge conveyor, mill 2

Value range: 1,0 … 3000,0 Default value: 200,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

ADC.I 1.1 Present current, main motor, mill 1

Value range: 1,0 … 999,0 Unit: A

ADC.I 1.2 Present current, motor, discharge conveyor, mill 1

Value range: 1,0 … 999,0 Unit: A

ADC.I 2.1 Present current, main motor, mill 2

Value range: 1,0 … 999,0 Unit: A

Is only displayed if TCON.MILL = 2.

Bühler Group
AHZC-23401-1-2302-en-US
106 | Operating manual
Chapter 8
Parameters

ADC.I 2.2 Present current, motor, discharge conveyor, mill 2

Value range: 1,0 … 999,0 Unit: A

Is only displayed if TCON.MILL = 2.

ADC.I0 1.1 No-load current, main motor, mill 1

Value range: 0,0 … 999,9 Default value: 1,0

Step: L Unit: A

u Apply present current as no-load current. Press the <Function> key for 10 s.

ADC.I0 1.2 No-load current, motor, discharge conveyor, mill 1

Value range: 0,0 … 999,9 Default value: 1,0

Step: L Unit: A

u Apply present current as no-load current. Press the <Function> key for 10 s.

ADC.I0 2.1 No-load current, main motor, mill 2

Value range: 0,0 … 999,9 Default value: 1,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

u Apply present current as no-load current. Press the <Function> key for 10 s.

ADC.I0 2.2 No-load current, motor, discharge conveyor, mill 2

Value range: 0,0 … 999,9 Default value: 1,0

Step: L Unit: A

Is only displayed if TCON.MILL = 2.

u Apply present current as no-load current. Press the <Function> key for 10 s.

ADC.AOMAX Scaling analog output AO 0.0 and AO 0.1

Value range: 50 … 250 Default value: 150

Step: L Unit: %

20 mA corresponds to a load of the main motor of ADC.AOMAX.

u Set ADC.AOMAX higher than 100 % to display an overload.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 107
Chapter 8
Parameters

8.2.6 ADCT (Analog/Digital Converter Temperature) parameter group


The parameter group is only visible if TCON.TEMP = ON.

ADCT.T.n Current temperature T.n

Unit: °C

Current temperature T.n in 0.1 °C.

ADCT.OFFSET.n Calibrate current temperature T1

Value range: –20,0 … 20,0 Default value: 0,0

Unit: °C

u Align temperature: Press <Function> key.

ADCT.TMIN.n Minimum temperature

Value range: –100,0 … 999,9 Default value: –40

Unit: °C

This is a scaling factor if a temperature probe with 0/4 … 20 mA or 5 V/10 V output


is used.
The setting depends on the parameter 1317.AIn.x
0 or 4 mA = TMIN
0 V = TMIN
PT100 or PT1000 = no function.

ADCT.TMAX.n Maximum Temperature

Value range: –100,0 … 999,9 Default value: 300,0

Unit: °C

This is a scaling factor if a temperature probe with 0/4 … 20 mA or 5 V/10 V output


is used.
The setting depends on the parameter 1317.AIn.x
20 mA = TMAX
5 V / 10 V = TMAX
PT100 or PT1000 = no function.

ADCT.UNIT Unit temperature

Default value: °C

Value Function

°C Temperature unit in °C.

°F Temperature unit in °F.

Bühler Group
AHZC-23401-1-2302-en-US
108 | Operating manual
Chapter 8
Parameters

8.2.7 1317 (CAN module EBD 1317) parameter group


1.x = CAN module EBD 1317 address 1, temperatures 0 … 7
2.x = CAN module EBD 1317 address 2, temperatures 8 … 15

1317.AIn.x n = 1/2 address, x = 0 … 7 input

Default value: OFF

Mode of the analog inputs according to EBD 1317. X290 … X297.

u Select analog inputs. Press the <Function> and the <Plus> key.
Jumper X298/X299:

u The jumper is used in the default setting. If the 1317.AIn.x = 10 V setting is


used, remove the corresponding jumper.

Value Function

OFF Deactivated − [A]

R General resistance measurement 0.0 [R]

PT100 Temperature measurement PT100 0.0 [R]

PT1000 Temperature measurement PT1000 0.0 [R]

5V Voltage measurement 0 … 5,000 V [V]

10 V Voltage measurement 0 … 10,000 V [V]

80 mV Differential voltage measurement for DMS 0/1 2/3 4/5 6/7 (Signal +/Signal –)
± 80,000 mV [mV]

0 mA Current measurement 0 … 20.00 mA [mA]

4 mA Current measurement 4 … 20.00 mA [mA]

1317.AINn.x n = 1/2 address, x = 0 … 7 input

The currently measured value in accordance with AI is displayed.

u If options with analog inputs are available, select the desired input. Press the
<Function> and the <Plus> or <Minus> key.

1317.AIADJn.x n = 1/2 address, x = 0 … 7 input

Value range: 90,0 … 110,0 Default value: 100,0

Unit: %

Calibration of analog inputs. The current value will be modified in percentage


increments.

u Select analog inputs. Press the <Function> and the <Plus> key.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 109
Chapter 8
Parameters

1317.AOn.x n = 1/2 address, x = 0/1 output

Default value: 0

Unit: mA

Mode of the analog outputs. Switchover 0/4 … 20 mA.

u Select analog outputs. Press the <Function> and the <Plus> key.

Value Function

0 Current measurement 0 … 20.00 mA

4 Current measurement 4 … 20.00 mA

1317.AOUTn.x n = 1/2 address, x = 0/1 output

Unit: mA

Analog outputs (present current).

u Select analog outputs. Press the <Function> and the <Plus> or <Minus> key.
u For tests, press the <Data input> key.
u If ”SERV.SERM“ = ON, set the current.

1317.AOADJn.x n = 1/2 address, x = 0/1 output

Value range: 90,0 … 110,0 Default value: 100,0

Unit: %

Calibration of analog outputs. The current value will be modified in percentage


increments.

u Select analog outputs. Press the <Function> and the <Plus> key.

1317.MODT.n Module temperature

Unit: °C

Displays the temperature measured on module n.

u Select the module. Press the <Function> and the <Plus> key.

8.2.8 Parameter group CTRL (Controller configuration)


The control has 2 controllers that can be configured independently of each other. One
controller is used for the feed roller, the other one is used for the segment slide gate.

Controller Description

Controller 0 CTRL.XXX.0 Feed roller

Controller 1 CTRL.XXX.1 Segment gate

Bühler Group
AHZC-23401-1-2302-en-US
110 | Operating manual
Chapter 8
Parameters

CTRL.TN.0 Monitoring time of the controller

Value range: 0 … 9 999,999 Default value: 7,000

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

CTRL.TN.1 Monitoring time of the controller

Value range: 0 … 9 999,999 Default value: 12,000

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

CTRL.TV.0 Rate time of the controller

Value range: 0 … 9 999,999 Default value: 1,450

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

CTRL.TV.1 Rate time of the controller

Value range: 0 … 9 999,999 Default value: 1,450

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

CTRL.KR.0 Proportionality factor of the controller

Value range: 0 … 9 999,999 Default value: 1,000

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

CTRL.KR.1 Proportionality factor of the controller

Value range: 0 … 9 999,999 Default value: 0,150

Step: L

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 111
Chapter 8
Parameters

CTRL.REG.0 Controller type

Step: L Default value: PID

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

Value Function

P P controller

I I controller

PI PI controller

PD PD controller

PID PID controller

CTRL.REG.1 Controller type

Step: L Default value: PI

See chapter "Optimize controller settings". See page 63, Chapter ”Optimizing con-
troller settings“.

Value Function

P P controller

I I controller

PI PI controller

PD PD controller

PID PID controller

CTRL.TIME.0 Controller interval

Value range: 50 … 65 535 Default value: 1000

Step: L Unit: ms

This time has no influence on the controller speed but merely serves as a basis for
the time. A control action is always executed after a controller interval.

CTRL.TIME.1 Controller interval

Value range: 50 … 65 535 Default value: 1000

Step: L Unit: ms

This time has no influence on the controller speed but merely serves as a basis for
the time. A control action is always executed after a controller interval.

Bühler Group
AHZC-23401-1-2302-en-US
112 | Operating manual
Chapter 8
Parameters

8.2.9 PBDP (Profibus DP) parameter group

PBDP.ADR Profibus DP communication address

Value range: 0 … 255 Default value: 0

Step: L

Profibus address and connection status are displayed.

Value Function

NoCom No communication with the host.

ERROR Hardware error.

TIMOUT Timeout was triggered.

PBDP.TOUT Timeout for Profibus-DP

Value range: 0,1 … 99,9 Default value: 1,0

Step: L Unit: s

The device stops metering if no more communication takes place during the
timeout time.
The monitoring system is active only when ”SYS.REM“ = REMP.

PBDP.WFOR Weight format for the Profibus DP protocol

Step: L Default value: FIX

Value Function

FIX Fixed format like old scale control units.


DUMP, DIFF: kg
DIFF Device type MSDE or MSDF: g
BAG: According to the parameter ”ADC.DIV“

DIV According to the ”ADC.DIV“ parameter

PBDP.MPDP Profibus DP operating mode

Step: L Default value: NORM

Value Function

NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.

SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).

SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).

EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 113
Chapter 8
Parameters

PBDP.MPDP Profibus DP operating mode

EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.

PBDP.COMP Compatibility mode MEAF

Step: L Default value: OFF

u Turn on when replacing MEAF with MEAG.

Value Function

OFF Interface is defined according to MEAG interface protocol.

ON Interface is defined according to MEAF interface protocol.

PBDP.CTRLB Control bits display

Display showing first 4 bytes of received data of Profibus NORM protocol as


hexadecimal value.
Example: F010050A
Sequence on display: Byte 3 | Byte 2 | Byte 1 | Byte 0.
Bits 7 … 0.

PBDP.STATB Status bits display

Display showing first 4 bytes of transmitted data of Profibus NORM protocol as


hexadecimal value.
Example: 00340B11
Sequence on display: Byte 3 | Byte 2 | Byte 1 | Byte 0.
Bits 7 … 0.

PBDP.DSDIR Data set direction analysis filter

Default value: RXD

Use analysis filter to select a data set from the Profibus protocol. Its value is
displayed via PBDP.DAT.

Value Function

RXD Received data (PLC > device)

TXD Transmitted data (device > PLC)

PBDP.DSNR Data set number analysis filter

Value range: 0 … 255 Default value: 0

Bühler Group
AHZC-23401-1-2302-en-US
114 | Operating manual
Chapter 8
Parameters

PBDP.DSIDX Data set index analysis filter

Value range: 0 … 255 Default value: 0

PBDP.DSBYTE Data set byte analysis filter

Value range: 8 … 23 Default value: 8

PBDP.DSTYPE Data set type analysis filter

Value range: 1, 2, 4 … Default value: 1

Unit: BYTE

Number of bytes in the value under consideration.

PBDP.DAT Data set value display

Value of the data record defined with the filter. The value is updated when the
corresponding data record is accessed. Note "PBDP.DSCNT" access counter to
check.

PBDP.DSCNT Access counter data set

The counter is increased by 1 each time the dataset defined by the filter is
accessed.

u Reset counter. Press the <Function> key.

8.2.10 ENET (Ethernet) parameter group


If ”SYS.ENET“ = OFF, the parameter group is not visible.

ENET.ADR ProfiNet address

Step: L Default value: 0

Current address for Profinet communication. The MEAG registers with this address.
meag-123 (ENET.ADR = 123)
Only available with ProfiNet - ”SYS.ENET“ - P-NET.
In addition, the current bus status is shown.

Value Function

NoCom No communication available.

ERROR Error on the additional circuit board EBD1325/EBD1326.

WIRED A cable was connected.

RUN The connection was established successfully.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 115
Chapter 8
Parameters

ENET.MPDP Ethernet operating mode

Step: L Default value: EXTD_L

Value Function

NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.

SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).

SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).

EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.

EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.

ENET.IP IP Address

Display of the IP address currently set or of the server status. Only available with
EtherNet/IP - "SYS.ENET" - ETH-IP.

Value Function

192.168.15.29 IP address currently set.

SERVER The server starts up.


START

SERVER No connection to the server.


ERROR

SERVER The server settings are being updated.


CONFIG

ENET.SUBNET Subnet mask

Display showing the subnet mask currently set. Only available with EtherNet/IP -
"SYS.ENET" - ETH-IP.

ENET.STDGW Standard gateway

Display showing the Standard Gateway currently set. Only available with EtherNet/
IP - "SYS.ENET" - ETH-IP.

ENET.IPSET.x Input, new IP address. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

Bühler Group
AHZC-23401-1-2302-en-US
116 | Operating manual
Chapter 8
Parameters

ENET.IPSET.x Input, new IP address. x = 0 … 3

The 4 bytes of the IP address are input as a single value.


Example: 192.168.15.1
”ENET.IPSET.0“ = 192
”ENET.IPSET.1 = 168“
”ENET.IPSET.2“ = 15
”ENET.IPSET.3“ = 1
Only available with Ethernet/IP - SYS.ENET - ETH-IP.

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

ENET.SNSET.x Input, new subnet mask. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

The 4 bytes of the subnet mask are input as a single value.


Example: 255.255.252.0
”ENET.SNSET.0“ = 255
”ENET.SNSET.1“ = 255
”ENET.SNSET.2“ = 52
”ENET.SNSET.3“ = 0
Only available with Ethernet/IP - SYS.ENET - ETH-IP.

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

ENET.GWSET.x Input, new standard gateway. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

The 4 bytes of the Standard Gateway are input as a single value.


Example: 192.168.15.10
”ENET.SNSET.0“ = 192
”ENET.SNSET.1“ = 168
”ENET.SNSET.2“ = 15
”ENET.SNSET.3“ = 10
Only available with Ethernet/IP - SYS.ENET - ETH-IP.

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 117
Chapter 8
Parameters

ENET.TOUT Timeout for Ethernet

Value range: 0,1 … 99,9 Default value: 1,0

Step: L Unit: s

The device triggers an alarm if no communication has taken place within the
specified time.
The monitoring is active only when ”SYS.REM“ = REME.

ENET.STATUS Communication status indicator

Value Function

NoCom No communication available.

ERROR Error on the additional circuit board EBD1325/EBD1326.

WIRED A cable was connected.

RUN The connection was established successfully.

ENET.COM Communication status indicator

Displays the communication status.


Examples:
– 0×C0000140 = RCX_E_NETWORK_FAULT
– 0×C0000141 = RCX_E_CONNECTION_CLOSED
– 0×C0000142 = RCX_E_CONNECTION_TIMEOUT
– 0×C0000143 = RCX_E_LONELY_NETWORK
– 0×C0000144 = RCX_E_DUPLICATE_NODE
– 0×C0000145 = RCX_E_CABLE_DISCONNECT

Number, left (netx communication status):


– 0 = RCX_COMM_STATE_UNKNOWN
– 1 = RCX_COMM_STATE_NOT_CONFIGURED
– 2 = RCX_COMM_STATE_STOP
– 3 = RCX_COMM_STATE_IDLE
– 4 = RCX_COMM_STATE_OPERATE

Number, right (netx number errors):


– 0 = no error
– > 0 = Error code in accordance with netx description ”netx Dual-Port Memory
Interface DPM“.

ENET.NAMEOS NameOfStation in ProfiNet

Default value: ON

Bühler Group
AHZC-23401-1-2302-en-US
118 | Operating manual
Chapter 8
Parameters

ENET.NAMEOS NameOfStation in ProfiNet

Only available with ProfiNet - "SYS.ENET" - P-NET


Free allocation of the device name available. To ensure that the free allocation of
NameOfStation can be used, the relevant stack (EBD1326_ProfiNet_im-
age_V231.bin) must be loaded on the ProfiNet card EBD1326 and the relevant GS-
DML file (GSDML-V2.31-Buehler-AG-0237-BDC_V002-20160729.xml) must be
used.

8.2.11 TCP (Ethernet TCP/IP) parameter group


If ”SYS.TCP“ = OFF, the parameter group is not visible.

TCP.MPDP Ethernet operating mode

Step: L Default value: EXTD_L

Value Function

NORM Normal protocol with 24-byte data for transmitting and receiving. For description,
see operating manual 66499.

SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).

SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).

EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.

EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.

TCP.IP IP Address

Display of the IP address currently set or of the server status.

Value Function

192.168.15.29 IP address currently set.

SERVER The server starts up.


START

SERVER No connection to the server.


ERROR

SERVER The server settings are being updated.


CONFIG

TCP.SUBNET Subnet mask

Display showing the subnet mask currently set.

TCP.STDGW Standard gateway

Display showing the Standard Gateway currently set.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 119
Chapter 8
Parameters

TCP.IPSET.x Input, new IP address. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

The 4 bytes of the IP address are input as a single value.


Example: 192.168.15.1
”TCP.IPSET.0“ = 192
”TCP.IPSET.1“ = 168
”TCP.IPSET.2“ = 15
”TCP.IPSET.3“ = 1

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

TCP.SNSET.x Input, new subnet mask. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

The 4 bytes of the subnet mask are input as a single value.


Example: 255.255.252.0
”TCP.SNSET.0“ = 255
”TCP.SNSET.1“ = 255
”TCP.SNSET.2“ = 252
”TCP.SNSET.3“ = 0

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

TCP.GWSET.x Input, new standard gateway. x = 0 … 3

Value range: 0 … 255 Default value: 0

Step: L

The 4 bytes of the Standard Gateway are input as a single value.


Example: 192.168.15.10
”TCP.SNSET.0“ = 192
”TCP.SNSET.1“ = 168
”TCP.SNSET.2“ = 15
”TCP.SNSET.3“ = 10

u Select next byte. Press the <Function> and the <Plus> key.
u Start the control with a new IP address. Press <Function> key for 10 s.

Bühler Group
AHZC-23401-1-2302-en-US
120 | Operating manual
Chapter 8
Parameters

TCP.TOUT Timeout for Ethernet TCP/IP

Value range: 0,1 … 99,9 Default value: 1,0

Step: L Unit: s

The device triggers an alarm if no communication has taken place within the
specified time.
Monitoring is only active when ”SYS.REM“ = REMTCP.

TCP.COM Communication counter

Step: L

The counter is increased when a valid data packet arrives.

u Clear the counter. Press <Function> key.

8.2.12 Parameter group SERV (Service information)

SERV.ID Displaying the identification text

Displayed identification text transmitted by a host (e.g. B1 SCALE). A maximum of


28 characters is possible.

u Expand text. Press< Function> key.

SERV.V_PROG Program version

Entire program, application and basic system (e.g. V18A).

SERV.V_APPL Application version

Version and name of the application (e.g. V17A).

SERV.V_BASE Basic system version

Version of the basic system (application-independent software, e.g. V15D).

SERV.V_BOOT Bootloader version

SERV.DATE Date

Value range: 01.01.00 … 31.12.99 Step: L

SERV.TIME Time

Value range: 00.00.00 … 23.59.59 Step: L

The clock is switched on by default. A battery test is performed every 24 hours.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 121
Chapter 8
Parameters

SERV.ERR.x List of alarms

The last alarm is displayed in the form ERR.0 A006. The next to last alarm is
displayed with ERR.–1 etc.

u Display older inputs. Press and keep the <Function> held down and press the
<Minus> key.
u Display more recent inputs. Press and keep the <Function> held down and
press the <Plus> key.
u Display the details (alarm text, date and time) of the input by turns. Press and
keep the <Function> key held down.

SERV.EVT.x List of events

For operation, see the SERV.ERR parameter. All events (incl. alarms) are displayed.

SERV.ALLEVT.x List of alarms and events

For operation, see the SERV.ERR parameter. Alarms and events are displayed
mixed.

SERV.CPU CPU utilization

Display on the left: Current CPU utilization in %. Display on the right: Maximum time
in [ms] for a program execution.

u Reset maximum value. Press< Function> key for 1 s.

SERV.SADR System address in the case of a program error

SERV.PCNT Counter for power failures

SERV.ELOG Internal recording of the events

Step: L Default value: ON

u Delete entries. Press <Function> key for more than 5 s.

Value Function

OFF Function deactivated.

ON Function activated.

SERV.CLOG Internal recording of cyclical data

Step: L Default value: OFF

u Delete entries. Press <Function> key for more than 1 s.

Bühler Group
AHZC-23401-1-2302-en-US
122 | Operating manual
Chapter 8
Parameters

SERV.CLOG Internal recording of cyclical data

Value Function

OFF Function deactivated.

ON Function activated.

SERV.SIMM Simulation mode

Step: L Default value: OFF

Inputs are simulated by means of the output signals. Program and control system
are tested without product.

Value Function

OFF Function deactivated.

ON Function activated.

SERV.SERM Service mode

Step: L Default value: OFF

Set digital and analog outputs for test purposes.

Value Function

OFF Function deactivated.

ON Function activated.

TEST Test mode for the print test.

SERV.SIMAZ Simulation mode for training at Bühler AG

Step: L Default value: OFF

u Always deactivate this parameter for customer systems.

Value Function

OFF Function deactivated.

ON Function activated.

SERV.DIN Digital inputs

Also applies to options with digital inputs (e.g. 1.0 ... 1.11).

u Select input (0.0 ... 0.x). Press and keep the <Function> held down and press
the <Plus> or <Minus> key.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 123
Chapter 8
Parameters

SERV.DOUT Digital outputs

Also applies to options with digital outputs (e.g. 1.0 … 1.11).

u Select output (0.0 ... 0.x). Press and keep the <Function> held down and press
the <Plus> or <Minus> key.
u Set or delete outputs. If ”SERV.SERM“ = ON: Press <Data input> key.

SERV.DISPIN Digital inputs of the display circuit board

Displays the current state of the 24 V inputs.


See page 53, Chapter ”Digital inputs of the display circuit board“.

SERV.AIN.x Analog input main circuit board

Unit: V/mA

Current voltage or present current.

u Select input. Press and keep the <Function> held down and press the <Plus>
or <Minus> key.

SERV.AOUT.x Analog outputs

Unit: mA

Present current.

u Select output. Press and keep the <Function> held down and press the <Plus>
or <Minus> key.
u Set the output current. If ”SERV.SERM“ = ON. Press <Data input> key.

SERV.TINT Current temperature on the display circuit board

Unit: °C

Bühler Group
AHZC-23401-1-2302-en-US
124 | Operating manual
Chapter 8
Parameters

SERV.SIO1 Serial interface 1

Serial interface 1 RS-485 to host or other use. If the HOST.SIO parameter is not
activated for the corresponding interface, " --- OFF" is displayed.
The following elements are displayed from left to right:
– Communication counter. Is raised by 1 (0 … 9999) per communication.
– Bus activity. ”*“ means that a signal was received.
– Command. Identification of the data with different telegrams. ”-“ means that a
command with lowercase letters was received.
– Error number:
– 0 = no error
– 1 = timeout or no answer
– 2 = undefined command or undefined identification
– 3 = incorrect checksum
– 4 = incorrect data length

SERV.SIO2 Serial interface 2

Serial interface 2 RS-485 to host or other use. For description, see "SERV.SIO1".

SERV.USB USB status display

If OFF is displayed, no USB cable is connected.


The following elements are displayed:
– Left: Number of data packets received.
– Right: Current utilization of the data transfer in %.
20 KByte/s = 100 %.

SERV.P-DP Profibus DP status indicator

Display options:

Value Function

WPAR Wait for the parameterization via the bus.

WCFG Wait for the configuration via the bus.

DEXC Normal operation. Data exchange without error.

TIMOUT Data exchange too slow. Timeout error.

INIERR Initialization error hardware module general.

LENERR Initialization error hardware module data lengths.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 125
Chapter 8
Parameters

SERV.PUPDAT Power-up date

Date on which the control system was last activated.

u Display the date. Press <Function> key.

SERV.PDWDAT Power-down date

Date on which the control system was last deactivated.

u Display the date. Press <Function> key.

SERV.TEST Test mode for the fabrication test

Step: L

The control unit is stopped.

u Start test. Press the <Function> key for 1 s.

Bühler Group
AHZC-23401-1-2302-en-US
126 | Operating manual
Chapter 9
Alarms and messages

9 Alarms and messages


Alarms and messages have the following syntax: The letter A for alarm or W for warn-
ing followed by a three-digit number.
Example: A073.
If a number follows the alarm or warning, it is a device-specific warning. The number
then indicates the device number.
Example: A073.2
If no further details are provided about the acknowledgement, then acknowledgement
of the alarms is dependent on the ”SYS.ACLR“ parameter.
– ”SYS.ACLR“ = OFF: Automatic acknowledgement if the cause of the alarm has
been remedied or when a change has been made to Step 1.
– ”SYS.ACLR“ = ON: No automatic acknowledgement. Acknowledgement possible
only with <Clear alarm> key or 24 V input ”Delete alarm“.

9.1 Basic alarms


A001 FLASH

Cause Correction

The FLASH is defective. u Switch device off and on.


u If alarm repeats, replace main circuit board.

A002 RAM

Cause Correction

The RAM is defective. u Switch device off and on.


u If alarm repeats, replace main circuit board.

A003 RUNTIME

Cause Correction

Runtime error during the program u Switch device off and on.
execution. Software or hardware u If alarm repeats, note SERV.SADR and contact Bühler
problem. Group customer service.
u Initialize data or load new program version.
u If alarm repeats, replace main circuit board.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 127
Chapter 9
Alarms and messages

A004 WATCHDOG

Cause Correction

Timeout during a program cycle. u Switch device off and on.


Software or hardware problem. u If alarm repeats, note SERV.SADR and contact Bühler
Group customer service.
u Initialize data or load new program version.
u If alarm repeats, replace main circuit board.

A005 NO 24 V

Cause Correction

The voltage is too low (< 18 V). u Measure voltage at X1.


u If voltage is below 18 V, locate the cause. Possibly the
power supply unit is defective or overloaded.
u If the voltage is above 18 V, replace main circuit board.

A006 DATALOST

Cause Correction

Data loss in the battery-backed u Check the fit of the battery socket.
RAM. The parameters and various u If new software has been loaded, acknowledge the alarm.
data are reset to the original value.
Can occur during software u Switch off the power to the control unit. Wait for 15 minutes.
downloads. Switch on the control system. If the alarm reoccurs, replace
the battery.

A012 HOST COM

Cause Correction

Timeout on the network host u Set host in operation.


interface. The network host system u Check functionality or wiring of interface cable.
no longer communicates with the
device. u Check jumpers X31.
u Increase timeout value of HOST.TOUT parameter or set to
0.

W013 EXTDISP

Cause Correction

Serial communication with the u Check the wiring.


remote control is faulty. Possible u Check setting of X80.
only with an optional remote control.
u Check value of SYS.DISP parameter.

Bühler Group
AHZC-23401-1-2302-en-US
128 | Operating manual
Chapter 9
Alarms and messages

A014 PROFI-DP

Cause Correction

Profibus error or communication has u Check the wiring.


been interrupted (timeout). The u Check address setting in value of PBDP.ADR parameter.
device stops. Alarm only when
SYS.REM = REMP. u Check operating mode setting in value of parameter
PBDP.MPDP.
u Increase timeout value of parameter PBDP.TOUT.
u Check master configuration.

W017 DISPLAY

Cause Correction

Communication with the primary u Check setting of X80.


display is faulty. The display itself u Set address on display (see display alarm *No Comm An*).
can no longer display the error.
u Check the wiring.

A018 BATTERY

Cause Correction

The backup battery has insufficient u Check fit of battery socket.


voltage or the clock has stopped. u With device switched on, replace battery, then switch
control unit off and on again.

A070 CAN Ctn

Cause Correction

Faulty communication with a CAN u Note the error display on the CAN module. Observe the
module. t = A (EBD 1317) description of CAN expansion modules in the appendix.
t = D (EBD 1318/20) u Check the wiring.
t = L (EBD 1319)
u Check address setting on CAN modules.
n = 1 … 31 (module address). If
CAN COM is displayed, then the u Check whether configured CAN modules are present.
entire bus is faulty.

A071 CAN Mtn

Cause Correction

A CAN module transmits an error. u Note the error display on the CAN module. Continue in
t = A (EBD 1317) accordance with the module description in the appendix..
t = D (EBD 1318/20) u Replace the CAN module.
t = L (EBD 1319)
n = 1 … 31 (module address).

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 129
Chapter 9
Alarms and messages

A072 CAN Dtn

Cause Correction

A CAN module has an output error. u Note the error display on the CAN module. Continue
t = D (EBD 1318/20) according to the module description in the appendix.
t = L (EBD 1319) n = 1 … 31 (modul u Check the wiring of the digital outputs.
e address).
u Check whether the alarm is cleared when the outputs are
unplugged.

W075 WARNTEMP

Cause Correction

The temperature in the device is too u Check the temperature in the device.
high. The temperature sensor is u Ensure sufficient ventilation.
located on the display circuit board.

A076 HIGHTEMP

Cause Correction

The maximum permissible u Check the temperature in the device.


temperature for the device has been u Ensure sufficient ventilation.
exceeded. The temperature sensor
is located on the display circuit
board.

A077 DIGOUT

Cause Correction

One or more outputs deviate from u Remove external voltage or overload sources.
the expected state.

9.2 Application alarms

9.2.1 Application alarms DFCQ-V

9.2.1.1 Hammer mill 1

A020 HOPP

Cause Correction

The discharge probe of the hammer u Check product discharge conveyor.


mill is reporting product. u The probe supplies 24 V when no product is present. DI 1.5
must therefore show 24 V.

Bühler Group
AHZC-23401-1-2302-en-US
130 | Operating manual
Chapter 9
Alarms and messages

A021 INC

Cause Correction

No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 5.4. LED flashes during segment gate
movement.

A022 END P

Cause Correction

The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 5.5 or DI 0.9 input must then show 24 V.

A023 CTEMP

Cause Correction

The temperature sensor of the u The hammer mill was operated for too long in idle state.
hammer mill supplies a temperature Wait until temperature is below TCON.TMAX.
that is above the limit value u Configure correct sensor type for 1317.AI1.0.
TCON.TMAX.
u Connect sensor correctly. Check wiring of PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.

A024 VIB_W

Cause Correction

The vibration value of the hammer u Find the mechanical cause for excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_W within the time u The machine can continue to be operated. During the next
TCON.T VIB. stop, find the cause.

A025 MSTOP

Cause Correction

The machine stop of hammer mill u —


was triggered.

A027 STILL

Cause Correction

The standstill monitoring of the u DI 1.3 must show 24 V when motor is stationary.
hammer mill is reporting movement
from the motor. The error is only
displayed when attempting to open
the cone.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 131
Chapter 9
Alarms and messages

A028 COPEN

Cause Correction

The cone of the hammer mill is not u DI 1.4 must show 24 V when cone is closed.
locked or the Move cone key was
pressed for too long.

A029 MOTOR

Cause Correction

The main motor of the hammer mill u Once the main motors have been started up, a motor
was started and there has been no current must be measured within 10 s. After the main
response. motors have been stopped, no motor current may be
measured after a delay of 5 minutes. Check whether the
motor contactor is disconnecting and whether the actual
value input AI0.0 is wired correctly.

A030 S < 4 mA

Cause Correction

No signal at the setpoint input of the u The AI0.3 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.3 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.

A031 A < 4 mA

Cause Correction

No signal at the actual value input of u The AI0.0 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill signal is used, set SYS.AI.0 to 0 mA.

A033 LIMIT

Cause Correction

The limit value TCON.TRANS was u Check if hammer mill discharge conveyor is clogged or drive
exceeded for over 5 s. The is blocked.
discharge conveyor is overloaded. u Check discharge motor configuration of ADC.MOT 1.2 and
ADC.CON 1.2.

A034 V < 4 mA

Cause Correction

No signal on the vibration sensor of u The AI1.1 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set 1317.AI1.2 to 0 mA. If no vibration sensor
is present, set TCON.VIBR = OFF.

Bühler Group
AHZC-23401-1-2302-en-US
132 | Operating manual
Chapter 9
Alarms and messages

A035 TSTART

Cause Correction

The discharge conveyor of the u When the discharge conveyor is started, a response must
hammer mill has not started. The be issued within 10 s. If there is no response, the DO 0.7
release for the discharge of the output must be connected to the DI 0.14 input via a jumper
hammer mill is active and there has wire.
been no response.

A036 CTIGHT

Cause Correction

The cone of the hammer mill is u Make sure that both cylinders are in the same position.
jammed. The positions of both cone Then reset the difference with the MAN.POSDIF parameter.
linear cylinders differ by more than
30 mm from each other. If the
position difference of both cylinders
is too great, the cone is usually
jammed. It is also possible that the
pulse signal of a cylinder is not being
measured.

A037 CINC

Cause Correction

No position pulses on the cone of u Check the pulse signal wiring of the linear cylinder on the
the hammer mill. cone.

A038 VIB_A

Cause Correction

The vibration value of the hammer u Find the mechanical cause for the excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.

A039 MOT_TEMP

Cause Correction

The main motor's PTC has u Allow motor to cool down.


switched. u Find and correct cause for overload.
u If motor has no PTC: TCON.MOT_PTC to OFF.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 133
Chapter 9
Alarms and messages

A120 ATVCOM

Cause Correction

The communication with the u Check CAN connection to the converters.


frequency converters of the main u Check address settings on the converter: Hammer mill 1 =
motor from hammer mill 1 is address 1; Hammer mill 2 = address 2.
interrupted.

A121 ATV

Cause Correction

The frequency converter of the main u Read the error cause off the frequency converter display.
motor of hammer mill 1 reports an Correct error in accordance with the operating instructions
error of frequency converter.
u Check address settings on the converter: Hammer mill 1 =
address 1; Hammer mill 2 = address 2.

9.2.1.2 Hammer mill 2

A040 HOPP

Cause Correction

The discharge probe of the hammer u Check product discharge conveyor.


mill is reporting product. u The probe supplies 24 V when no product is present. DI 2.5
must therefore show 24 V.

A041 INC

Cause Correction

No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 6.4. LED flashes during segment gate
movement.

A042 END P

Cause Correction

The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 6.5 or DI 0.21 input must then show 24 V.

Bühler Group
AHZC-23401-1-2302-en-US
134 | Operating manual
Chapter 9
Alarms and messages

A043 CTEMP

Cause Correction

The temperature sensor of the u The hammer mill was operated for too long in idle state.
hammer mill supplies a temperature Wait until temperature is below TCON.TMAX.
that is above the limit value u Configure correct sensor type for 1317.AI2.0.
TCON.TMAX.
u Connect sensor correctly. Check wiring of PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.

A044 VIB_W

Cause Correction

The vibration value of the hammer u Find the mechanical cause for excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_W within the time u The machine can continue to be operated. During the next
TCON.T VIB. stop, find the cause.

A045 MSTOP

Cause Correction

The machine stop of hammer mill u —


was triggered.

A047 STILL

Cause Correction

The standstill monitoring of the u DI 2.3 must show 24 V when motor is stationary.
hammer mill is reporting movement
from the motor. The error is only
displayed when attempting to open
the cone.

A048 COPEN

Cause Correction

The cone of the hammer mill is not u DI 2.4 must show 24 V when cone is closed.
locked or the Move cone key was
pressed for too long.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 135
Chapter 9
Alarms and messages

A049 MOTOR

Cause Correction

The main motor of the hammer mill u Once the main motors have been started up, a motor
was started and there has been no current must be measured within 10 s. After the main
response. motors have been stopped, no motor current may be
measured after a delay of 5 minutes. Check whether the
motor contactor is disconnecting and whether the actual
value input AI0.4 is wired correctly.

A050 S < 4 mA

Cause Correction

No signal at the setpoint input of the u The AI0.7 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.7 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.

A051 A < 4 mA

Cause Correction

No signal at the actual value input of u The AI0.4 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.4 to 0 mA.

A053 LIMIT

Cause Correction

The limit value TCON.TRANS was u Check if hammer mill discharge conveyor is clogged or drive
exceeded for over 5 s. The is blocked.
discharge conveyor is overloaded. u Check discharge motor configuration of ADC.MOT 2.2 and
ADC.CON 2.2.

A054 V < 4 mA

Cause Correction

No signal on the vibration sensor of u The AI2.1 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set 1317.AI1.3 to 0 mA. If no vibration sensor
is present, set TCON.VIBR = OFF.

A055 TSTART

Cause Correction

The discharge conveyor of the u When the discharge conveyor is started, a response must
hammer mill has not started. The be issued within 10 s. If there is no response, the DO 0.11
release for the discharge of the output must be connected to the DI 0.26 input via a jumper
hammer mill is active and there has wire.
been no response.

Bühler Group
AHZC-23401-1-2302-en-US
136 | Operating manual
Chapter 9
Alarms and messages

A056 CTIGHT

Cause Correction

The cone of the hammer mill is u Make sure that both cylinders are in the same position.
jammed. The positions of both cone Then reset the difference with the MAN.POSDIF parameter.
linear cylinders differ by more than
30 mm from each other. If the
position difference of both cylinders
is too great, the cone is usually
jammed. It is also possible that the
pulse signal of a cylinder is not being
measured.

A057 CINC

Cause Correction

No position pulses on the cone of u Check the pulse signal wiring of the linear cylinder on the
the hammer mill. cone.

A058 VIB_A

Cause Correction

The vibration value of the hammer u Find the mechanical cause for the excessive vibrations, e.g.
mill has exceeded the limit value worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.

A059 MOT_TEMP

Cause Correction

The main motor's PTC has u Allow motor to cool down.


switched. u Find and correct cause for overload.
u If motor has no PTC: TCON.MOT_PTC to OFF.

A140 ATVCOM

Cause Correction

The communication with the u Check CAN connection to the converters.


frequency converters of the main u Check address setting on the converter: hammer mill 1 =
motor from hammer mill 2 is address 1; hammer mill 2 = address 2.
interrupted.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 137
Chapter 9
Alarms and messages

A141 ATV

Cause Correction

The frequency converter of the main u Read the error cause off the frequency converter display.
motor of hammer mill 2 reports an Eliminate error according to operating instructions of
error. frequency converter.
u Check address setting on converter: hammer mill 1 =
address 1; hammer mill 2 = address 2.

9.2.1.3 Hammer mill 1 and 2

A060 POWER

Cause Correction

A 24 V miniature circuit breaker has u Check whether the miniature circuit breakers of the control
responded. have triggered.
u DI 0.23 must feature 24 V.

A061 UPSON

Cause Correction

UPS is active. u Restore power supply.


u Deselect UPS. If not present, TCON.UPS = OFF.

A062 ATVCOM

Cause Correction

The communication with the u Check CAN connection to the converters.


frequency converters of the main u Check address settings on the converter: Hammer mill 1 =
motor is interrupted. address 1; Hammer mill 2 = address 2.

A063 ATV

Cause Correction

The frequency converter of the main u Read the error cause off the frequency converter display.
motor is reporting an error. Correct error according to operating instructions of
frequency converter.
u Check address settings on converter: Hammer mill 1 =
address 1; Hammer mill 2 = address 2.

Bühler Group
AHZC-23401-1-2302-en-US
138 | Operating manual
Chapter 9
Alarms and messages

A065 FC

Cause Correction

The frequency converter of the feed u Read the error number off the frequency converter.
roller is reporting an error. Determine the cause by using the operating manual of the
frequency converter.
u The alarm is active only when TCON.FEED = FC_SLD.

A066 DOOR

Cause Correction

Magnetic door is not closed. u Check whether the magnetic door is closed properly. DI 5.2
must show 24 V.

A067 FLAP

Cause Correction

Error in the flap control unit. u Check whether the gravity flow diverter adjustment cylinder
is moving.
u Use the LED of DI 6.8 to check whether pulses are arriving
on the I/O module. LED flashes during the flap movement.

A068 PART

Cause Correction

Defect in the heavy particle u Check whether the heavy particle cylinder is at the limit
separation. position. DI 5.9 must show 24 V in the limit position.

A090 FAN

Cause Correction

The fan was started and there has u When the fan is started, a response must be issued within
been no response. 10 s. If there is no response, the DO 0.13 output must be
connected to the DI 0.12 input via a jumper. Output
DO 0.13 = 24 V → Fan is running. Input DI 0.12 = 24 V →
Fan is running.

A091 PLANT

Cause Correction

The machine stops after an u Input DI 0.0 = 24 V → no alarm.


emergency stop.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 139
Chapter 9
Alarms and messages

A092 SAFES

Cause Correction

The safety switch of the machine u Input DI 0.7 = 24 V → no alarm.


was actuated.

9.2.2 Application alarms DFCQ-H

A021 INC

Cause Correction

No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 5.4. LED flashes during segment gate
movement.

A022 END P

Cause Correction

The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 5.5 or DI 0.9 input must then show 24 V.

A030 S< 4 mA

Cause Correction

No signal at the setpoint input of the u The AI0.3 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.3 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.

A031 A < 4 mA

Cause Correction

No signal at the actual value input of u The AI0.0 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.0 to 0 mA.

A041 INC

Cause Correction

No pulse signals of the segment u Check whether the LINAK cylinder is moving.
gate are measured. u Check the wiring of the LINAK cylinder.
u Check whether pulses arrive on the I/O module by means of
the LED of DI 6.4. LED flashes during segment gate
movement.

Bühler Group
AHZC-23401-1-2302-en-US
140 | Operating manual
Chapter 9
Alarms and messages

A042 END P

Cause Correction

The segment gate does not reach u Check whether the LINAK cylinder is at the limit position.
the limit position open or closed. The DI 6.5 or DI 0.21 input must then show 24 V.

A050 S < 4 mA

Cause Correction

No signal at the setpoint input of the u The AI0.7 input has a current of < 2 mA. If a 0 … 20 mA
hammer mill. signal is used, set SYS.AI.7 to 0 mA. If there is no analog
setpoint, set SYS.REM ≠ REMA.

A051 A < 4 mA

Cause Correction

No signal at the actual value input of u The AI0.4 input has a current of < 2 mA. If a 0 … 20 mA
the hammer mill. signal is used, set SYS.AI.4 to 0 mA.

A065 FC

Cause Correction

The frequency converter of the feed u Read the error number off the frequency converter.
roller is reporting an error. Determine the cause by using the operating manual of the
frequency converter.
u The alarm is active only when TCON.FEED = FC_SLD.

9.3 Canceling *No Comm An* display alarm


If the *No Comm An* error is displayed, then the connection to the main circuit board
is interrupted.
One of the following configured addresses is displayed:
– Address 1 = Local display in the front door
– Address 3 = Remote control

1. Press the <Clear alarm> key 5 times for approx. ½ s each.


2. Press the <Data input> key.
3. Select corresponding address with <Plus> or <Minus> keys.
4. Press the <Data input> key.
5. Press the <Clear alarm> key.

9.4 Display status of the seven-segment display


The seven-segment display H1 on the main circuit board reflects the hardware status.
If the decimal point is flashing, the control system is activated.
The seven-segment display shows the status and error messages. In the following ta-
ble, the status messages are listed on the seven-segment after the display.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 141
Chapter 9
Alarms and messages

Display State

− Standard operation.
The middle segments are displayed There are no messages.
cyclically from top to bottom.

L Software is installed and activated after


If the display is flashing, the download the restart.
has not yet been completed.
u If the device tool is used, press
<Activate software>.
u If the control system is switched to
a de-energized state, the new soft-
ware will also be activated.

U USB connection active.


Device is connected to PC via a USB
cable.

P Profibus is attached and connected.


For more information: ”SERV.P-DP“

C New software is copied.


Program 1 is updated. Program 2 is
copied. Status message is displayed
only during the startup phase.

F Program 1 is defective. Program 2 is


copied.
Status message is displayed only during
the startup phase.

In the following table, the error messages are listed on the seven-segment after the
display. If an ”E“ flashes alternately with another symbol, an error message is pend-
ing. ”E d“ means, for example, that ”E“ und ”d“ are flashing alternately.

Cause Correction

Error in the FLASH EPROM. No u Switch printed circuit board to de-energized state. Clean
application present. No application with compressed air.
started. u Restart. If the error occurs again, replace the printed circuit
board.

Cause Correction

Error in the DRAM memory. No u Switch printed circuit board to de-energized state. Clean
application starts. For example, as a with compressed air.
result of a short-circuit on the PCB u Restart. If the error occurs again, replace the printed circuit
due to copper residue. board.

Bühler Group
AHZC-23401-1-2302-en-US
142 | Operating manual
Chapter 9
Alarms and messages

Cause Correction

Error in battery RAM memory. No u Switch printed circuit board to de-energized state. Clean
application starts. with compressed air.
u Restart. If the error occurs again, replace the printed circuit
board.

EL

Cause Correction

Defective software version installed. u Reinstall software. If the display does not change, request a
Program 1 shows an incorrect new software version.
checksum. u Disconnect the device from the power supply. Program 2 is
used automatically after restart.

E3

Cause Correction

u See A003 RUNTIME

E4

Cause Correction

u See A004 WATCHDOG

E5

Cause Correction

u See A005 NO 24V

Eb

Cause Correction

u See W018 BATTERY

E6

Cause Correction

u See A006 DATALOST

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 143
Chapter 9
Alarms and messages

EC

Cause Correction

u See A070 CAN COM, A071 CAN MOD, A072 CAN DOUT

Ed

Cause Correction

u See W017 DISPLAY

9.5 Status messages


Status messages provide information about the state of the device. The messages al-
ternate with the normal display and only as long as the status persists.
Alarms have higher priority and overwrite status messages.

Display State

LOCAL STOP The feeding was manually stopped on the display with the
key <S1>.

STOP The feeding was stopped because no dosing release is


present.

m STOP Dosing release is available, but the main motor was not
started.

c STOP The feeding was stopped because there is no dosing release


via the fieldbus.

STARTING Main motor has been started. The message is active during
heavy start-up of the drive.

BRAKE The main motor was stopped. The reverse current brake is
active.

RUN EMPTY The main motor was stopped. Idle time ”TCON.T1“ is active.

STANDBY All releases are present, but the main motor was switched off
after timeout ”TCON.T3“.

OPEN The cone of all hammer mills is open.

OPEN1 The cone of hammer mill 1 is open.

OPEN2 The cone of hammer mill 2 is open.

HL INLET The level probe of the inlet is covered.

OVERLOAD The motor current of the main motor has a value > 130 % of
the nominal current.

EMPTY The intermediate container is empty.

VIBRATION The vibration level has exceeded the programmed limit. If not
remedied, the machine will stop with the alarm ”A034“ or”
A054“.

Bühler Group
AHZC-23401-1-2302-en-US
144 | Operating manual
Chapter 9
Alarms and messages

Display State

DISCHARGE Discharge function (or residual discharging) is active (not nor-


mal emptying).

SERVICE The service mode is active, i.e. ” SERV.SERM“ = ”ON“ (out-


puts can be set). ”SERV.SERM“

MANUAL The device is operated manually. No automatic control se-


quence.

SIM ON The simulator mode is activated, i. e. ”SERV.SIMM“ = ”ON“.

HL TRANSPORT The level probe in the discharge conveyor is covered


”TCON.TRAPRB“. ”TCON.TRAPRB“

9.6 Short messages


Short messages are operating aids. They appear a single time when a key is pressed.
Some of the following messages are application-specific, i.e. they do not occur with
every control system.

Display State

OK Input has been detected and applied.


Example: When a recipe has been loaded.

LOCK Parameter modification is locked. ”SYS.LOCK“

REMOTE The control system is in remote operating mode, e.g. via


Profibus. Parameters can be edited only in remote operating
mode, e.g: ”SYS.REM“ = REMP. ”SYS.REM“

PROTECT Recipes are protected against being overwritten. The recipes


cannot be saved.

DATA INIT Initialization is executed. The control system is reset to default


values. ”SYS.INIT“

SET ZERO Null measurement is executed.

SET CAL Calibration is executed.

SET TARE Taring is executed.

WT INIT Weight values are re-initialized.


Example: If ”ADC.DIV“ is adjusted.

WAIT The device processes an order and prompts the operator to


wait.
Do not operate the control while WAIT is displayed.

CLEAR Data is being deleted.

ESC Modification has been aborted.


Example: If the <Cancel> key is pressed during a modifica-
tion.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 145
Chapter 9
Alarms and messages

Display State

OCCUPIED Interface is occupied.


Example: If SIO is set to Host and is to be reset to an external
device.

NO EDIT Modification is not possible.


Example: When attempting to modify display parameters.

NO CAL Modification is possible only if the calibration switch is on


CAL.
Example: When attempting to modify ”SYS.TYP“ if the cali-
bration switch is in the RUN position.

NO LOCAL Modifications are possible only in LOCAL mode.

NO STOP Modifications are not possible unless the device is stopped.

NO SETVAL No setpoint is present.

ASSIST ON The input wizard has been started.

ASSIST OFF The input wizard has been exited.

MANUAL START The process has been started manually.

MANUAL STOP The process has been stopped manually.

OUT OF RANGE The value that is input is outside the valid range.

ERROR The action has failed.

NO MODE The selected function is not available in this operating mode.

ERR MIN 10 mm Manual stroke movements must be greater than 10 mm.

Bühler Group
AHZC-23401-1-2302-en-US
146 | Operating manual
Chapter 10
Spare parts lists

10 Spare parts lists


10.1 Spare parts management
Stocks of spare parts and parts subject to wear are an important requirement for the
permanent operational readiness of the control system.
Bühler spare parts often fulfil special manufacturing and delivery specifications. Bühler
sells spare parts in accordance with state-of-the-art technology.
Only spare parts supplied by Bühler are checked and approved. Spare parts from
other sources might negatively change the prescribed constructional qualities of the
control system and/or impair safety.

10.2 Basic version, throughput control


MEAG with display in the housing Parts no.

115/230 V AC EKP -80192-810

10.3 Spare parts lists


We would recommend keeping the following spare parts in stock in order to guaran-
tee permanent operational readiness of the control:

Designation Parts no.

Main circuit board EBD 1311 EKP -84336-810

Display circuit board EBD 1316 EKP -84337-810

Fuse F1 (main circuit board, 4 A time- UNE -22002-028


delay)

We would recommend keeping the following parts in stock for the corresponding de-
sign version:

Designation Parts no.

Circuit board CAN expansion (analog I/ EKP -85360-810


O)
EBD 1317

Circuit board CAN expansion (digital I/ EKP -85361-810


O)
EBD 1318

Circuit board EtherNet/IP - Ethernet EKP -85387-810


fieldbus
EBD 1325

Circuit board ProfiNet - Ethernet field- EKP -85388-810


bus
EBD 1326

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 147
Chapter 10
Spare parts lists

The remaining available spare parts are summarized in the following table:

Designation Parts no.

Display unit with front plate and housing EKP -80004-810

Profibus plug UXE -36405-817

Display foil (without circuit board) EKP -10019-010

Battery for RAM (snap-on) UNE -74921-029

USB cable 1.8 m for dVice2L UXE -30802-031

Set of cables (strands) numbered for


CAN expansion or display circuit board:

200 mm WEWS-95011-810

500 mm WEWS-95012-810

1,000 mm WEWS-95013-810

1,400 mm WEWS-95014-810

Bühler Group
AHZC-23401-1-2302-en-US
148 | Operating manual
Chapter 11
Appendix

11 Appendix
11.1 CAN expansion modules

11.1.1 Types

Circuit board CAN expansion modules Description

EBD 1317 Analog I/O 8 analog inputs.


Each input can be configured for
various functions.
PT100
PT1000
0/4 … 20 mA
0 … 5/10 V
± 80 mV Difference
2 analog outputs
0/4 … 20 mA

EBD 1318 Digital I/O 12 digital I/O 24 V


Each of the 12 I/O can be config-
ured as input or output.

EBD 1319 Load Cell (LC), appropriate 1 high-resolution load cell input
for calibration 8 digital I/O 24 V
Each of the 8 I/O can be configured
as input or output.

EBD 1320 Digital I/O 8 digital inputs 24 V


Safe Output 8 digital outputs 24 V

11.1.2 Connection

EBD 1311 / EBD1312 EBD 1317/18/19/20 EBD 1317/18/19/20


1 1
ON ON
X100 CAN OFF OFF
24 V 0 V R/T+ R/T- X100 X99 X100 X99
1 2 3 4 1 2 3 4 1 2 3 4

Fig. 11.1 ID CAN expansion module

Connect the module as follows:

u Wire the CAN Interface as BUS.


u On the last module, switch the terminations on (X99 = ON).

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 149
Chapter 11
Appendix

u On all others, switch the terminations off (X99 = OFF).

11.1.3 LED display


Each CAN expansion module contains a one-digit LED display; EBD 1320 has two-
digit display. It reflects the hardware status.
A flashing decimal point indicates that the module is in operation.
A number from 1 ... 9 indicates the address; for EBD 1320 1 ... 31. If several CAN ex-
pansion modules of the same type are present, different addresses must be set in ac-
cordance with the I/O description of the application.
The address is set as follows:

u Keep the key pressed down until the address flashes.


u Continue pressing the key as often as required until the respective address is dis-
played.
u Keep the key pressed down until the address no longer flashes.
If an ”E“ flashes alternately with another symbol, an error message is pending. If, for
example, ”E“ and ”3“ flash alternately, the fault ”E 3“ is pending.

11.1.3.1 Error messages of LED display

E1

Cause Correction

Software error u Switch the module off and back on again. If the message is
displayed again, replace the module.

E2

Cause Correction

EEPROM data loss u Switch the module off and back on again. If the message is
displayed again, replace the module.
u Check if the correct address is displayed.

E3

Cause Correction

No CAN interface connection u Press the key and check the address.
u Check parameter settings on MEAG.

E4

Cause Correction

AD converter error u Switch the module off and back on again. If the message is
displayed again, replace the module.

Bühler Group
AHZC-23401-1-2302-en-US
150 | Operating manual
Chapter 11
Appendix

E5

Cause Correction

Digital outputs u One or more outputs deviate from the expected state.
(External voltage, short-circuit, overload).

E6

Cause Correction

No external 24 V for EBD 1320 u Check the external 24 V at the X105:1 plug. LED 24 V EXT
lights up when there is voltage.

Eb

Cause Correction

Automatic baud rate search (no u Press the key and check the address. (For setting, see the
connection to CAN interface). address.)
u Check parameter settings on MEAG.

11.2 Remote control


A remote control is an additional display and control unit that is installed at another lo-
cation.

11.2.1 Installation version

Fig. 11.2 Display of dimensional drawing

Technical data

Parts no. EKP -80004-810

Degree of protection IP65

Depth 40 mm

Power supply +24 V DC from the device control

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 151
Chapter 11
Appendix

6 boreholes 6 mm in diameter

Cable cross-section max. 2.5 mm2

Front panel section 99 x 206 mm

11.2.2 Table or wall version with ATEX


200

200
138

300

Fig. 11.3 Remote control, dimensional drawing with ATEX

Technical data

Parts no. EKP -11832-001

Degree of protection IP65

approval ATEX Zone 22

Depth 40 mm

Power supply +24 V DC from the device control

4 boreholes 5.5 mm in diameter

Cable cross-section max. 2.5 mm2

Bühler Group
AHZC-23401-1-2302-en-US
152 | Operating manual
Chapter 11
Appendix

11.2.3 Table or wall version (old)

Fig. 11.4 Remote control, dimensional drawing

Technical data

Parts no. EKP -80042-810

Degree of protection IP65

Depth 40 mm

Power supply +24 V DC from the device control

4 boreholes 5.5 mm in diameter

Cable cross-section max. 2.5 mm2

11.2.4 Connect to MDDR main circuit board SIO_0

MDDR
MDDR MEAG
MEAG
Main Basisprint
circuit board Anzeigeprint
Display circuit board
EBD 1311 EBD 1316
EBD 1311 EBD 1316
SIO_0 X50
X30
1

2 1 +24 V Line 1
1

3 2 0 V Line 2 2
4 3 RXD_TXD + 3 3
X80
SIO_0
1 6 X30 4 RXD_TXD - 4 4
2 5 X51
3 4 SIO_0
X50

Fig. 11.5 Connecting to MDDR main circuit board SIO_0

If the local display unit is removed from the control and assembled elsewhere, it is to
be connected as a remote control. Address 1 is still used, however, and the value of
the parameter ”SYS.DISP“ will remain on OFF.
With a distance of 5 m or more, use a shielded, 4-core cable.

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 153
Chapter 11
Appendix

Recommended cable: UXE -30605-301.

1. Set the address on the remote control.


u Press <Clear alarm> key 5 times.
u Press <Arrow> key.
u Select the address 3 with the keys <Plus> or <Minus>.
u Press the <Data input> key.
u Press the <Clear alarm> key.
2. Activate interface.
u Select ”SYS.DISP“ parameter.
u Press the <Data input> key until the parameter value flashes.
u Select the corresponding value. ”SYS.DISP“

11.3 Parameter list


Parameters Default value: Unit: Customer value

USER.ACTUAL %

USER.LOAD.x %

USER.I A

USER.SET.x %

USER.FEED Hz

USER.SLIDE.x %

USER.RUNHR h

USER.RUNHR2 h

USER.ACT.x °C

USER.VIBR.x %

USER.MOT_F.x Hz

MAN.FROLL 0 Hz

MAN.FSLD 0 %

MAN.FSLD2 0 %

MAN.FAN OFF

MAN.TRAN OFF

MAN.TRAN2 OFF

MAN.MOT OFF

MAN.MOT2 OFF

MAN.SFPOS 0 %

MAN.FLPOS 0 %

Bühler Group
AHZC-23401-1-2302-en-US
154 | Operating manual
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

MAN.CPOS_R.x mm

MAN.CPOS_L.x mm

MAN.POSDIF.x mm

MAN.RUNH_R.x h

MAN.RUNH_L.x h

MAN.SCREEN.x mm

TCON.DFCQ DFZK

TCON.SETV 1

TCON.MILL 1

TCON.MOTOR NORM

TCON.MOTIN AIN

TCON.TRANSIN AIN

TCON.MOTPTC.x ON

TCON.MOTCAN OFF

TCON.MOT_F1.x 50 Hz

TCON.MOT_F2.x 50 Hz

TCON.MODE REG

TCON.FLAP OFF

TCON.FLMID 50 %

TCON.VIBR OFF

TCON.UPS OFF

TCON.TEMP OFF

TCON.FEED FC_SLD

TCON.FC_SLD BASE

TCON.AOUT ACTV

TCON.N TRANS 2

TCON.TRANS 0 %

TCON.TRAPRB OFF

TCON.REG_M2 OFF

TCON.CSYNC ON

TCON.FMAX 70 Hz

TCON.FMIN 30 Hz

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 155
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

TCON.SMAX 100 %

TCON.SMIN 5 %

TCON.SINI 0 %

TCON.DIFF 10 %

TCON.TMAX 75 °C

TCON.VIB_W 10,0 mm/s

TCON.VIB_A 20,0 mm/s

TCON.T VIB 10 s

TCON.T1 30 s

TCON.T2.x 5,0 s

TCON.T3 15 Min.

TCON.T4 1,0 s

TCON.T5 1,0 s

TCON.T6 15 s

TCON.T7 0 Min.

TCON.LOGMSTP 60 s

TCON.LOGMRUN 10 s

TCON.ASSIST

SYS.TYP NOAPP

SYS.REM LOC

SYS.EIN OFF

SYS.DISP OFF

SYS.PSAV STOP

SYS.SD

SYS.SDT 600 s

SYS.LOCK OFF

SYS.MSG ALL

SYS.ACLR OFF

SYS.AINV ON

SYS.ASCROL ON

SYS.AO.x 0 mA

SYS.AI.x 0 mA

Bühler Group
AHZC-23401-1-2302-en-US
156 | Operating manual
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

SYS.AOADJ.x 100,0 %

SYS.AIADJ.x 100,0 %

SYS.CANBR 50 kBaud

SYS.ENET OFF

SYS.TCP OFF

SYS.INIT

ADC.MOT 1.1 100,0 A

ADC.MOT 1.2 100,0 A

ADC.MOT 2.1 100,0 A

ADC.MOT 2.2 100,0 A

ADC.CON 1.1 200,0 A

ADC.CON 1.2 200,0 A

ADC.CON 2.1 200,0 A

ADC.CON 2.2 200,0 A

ADC.I 1.1 A

ADC.I 1.2 A

ADC.I 2.1 A

ADC.I 2.2 A

ADC.I0 1.1 1,0 A

ADC.I0 1.2 1,0 A

ADC.I0 2.1 1,0 A

ADC.I0 2.2 1,0 A

ADC.AOMAX 150 %

ADCT.T.n °C

ADCT.OFFSET.n 0,0 °C

ADCT.TMIN.n –40 °C

ADCT.TMAX.n 300,0 °C

ADCT.UNIT °C

1317.AIn.x OFF

1317.AINn.x

1317.AIADJn.x 100,0 %

1317.AOn.x 0 mA

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 157
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

1317.AOUTn.x mA

1317.AOADJn.x 100,0 %

1317.MODT.n °C

CTRL.TN.0 7,000

CTRL.TN.1 12,000

CTRL.TV.0 1,450

CTRL.TV.1 1,450

CTRL.KR.0 1,000

CTRL.KR.1 0,150

CTRL.REG.0 PID

CTRL.REG.1 PI

CTRL.TIME.0 1000 ms

CTRL.TIME.1 1000 ms

PBDP.ADR 0

PBDP.TOUT 1,0 s

PBDP.WFOR FIX

PBDP.MPDP NORM

PBDP.COMP OFF

PBDP.CTRLB

PBDP.STATB

PBDP.DSDIR RXD

PBDP.DSNR 0

PBDP.DSIDX 0

PBDP.DSBYTE 8

PBDP.DSTYPE 1 BYTE

PBDP.DAT

PBDP.DSCNT

ENET.ADR 0

ENET.MPDP EXTD_L

ENET.IP

ENET.SUBNET

ENET.STDGW

Bühler Group
AHZC-23401-1-2302-en-US
158 | Operating manual
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

ENET.IPSET.x 0

ENET.SNSET.x 0

ENET.GWSET.x 0

ENET.TOUT 1,0 s

ENET.STATUS

ENET.COM

ENET.NAMEOS ON

TCP.MPDP EXTD_L

TCP.IP

TCP.SUBNET

TCP.STDGW

TCP.IPSET.x 0

TCP.SNSET.x 0

TCP.GWSET.x 0

TCP.TOUT 1,0 s

TCP.COM

SERV.ID

SERV.V_PROG

SERV.V_APPL

SERV.V_BASE

SERV.V_BOOT

SERV.DATE

SERV.TIME

SERV.ERR.x

SERV.EVT.x

SERV.ALLEVT.x

SERV.CPU

SERV.SADR

SERV.PCNT

SERV.ELOG ON

SERV.CLOG OFF

SERV.SIMM OFF

Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 159
Chapter 11
Appendix

Parameters Default value: Unit: Customer value

SERV.SERM OFF

SERV.SIMAZ OFF

SERV.DIN

SERV.DOUT

SERV.DISPIN

SERV.AIN.x V/mA

SERV.AOUT.x mA

SERV.TINT °C

SERV.SIO1

SERV.SIO2

SERV.USB

SERV.P-DP

SERV.PUPDAT

SERV.PDWDAT

SERV.TEST

Bühler Group
AHZC-23401-1-2302-en-US
160 | Operating manual
Bühler Group
AHZC-23401-1-2302-en-US
Operating manual | 161
Technical Manual AHSJ en 0120 194898

Bühler AG
CH-9240 Uzwil
Switzerland

T +41 (0)71 955 30 40


F +41 (0)71
Bühler Group955 33 05

[email protected]
www.buhlergroup.com
www.buhlergroup.com

You might also like