Connection Manual
1
Version Date Modification
V1.0.0 Janu 18,2015 First Draft
V1.0.1 MAR 7 2019 Increase Xinje
V1.0.2 MAR 15 2019 Increase Vigor
3
2.15 Yudian............................................................................................................................. 252
AI ........................................................................................................................ 252
2.16 Xinje ............................................................................................................................... 255
2.16.1 XC series ............................................................................................................... 255
2.16.2 XD series............................................................................................................... 259
2.17 Vigor ............................................................................................................................... 263
2.17.1 M/VB/VH Series ...................................................................................................... 263
2.17.2 VS series .................................................................................................................. 267
2.18 LS .................................................................................................................................... 272
2.18.1 LS XBC-cnet ........................................................................................................ 273
2.18.2 LS XEC-Cnet ........................................................................................................ 276
2.18.3 LS XBC-Fnet ........................................................................................................ 280
2.18.4 LS XEC-Fnet......................................................................................................... 283
4
P5070S/ P5070N/ P5070N1/ P5102S/ P5102N/ P5102N1
PIN# COM1
1
2 RX
3 TX
4
5 GND
6
7 RTS
8 CTS
9
RS-422/ Old Model
485
5
New Model
P2K SERIES
6
2. PLC Connection
2.1 FATEK Automation Corp.
FBs/B1/B1z/HB1
2.1.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 1 Must match PLC
port setting
Communication Method FATEK Communication
Protocol
7
2.1.1.3 Connecting to PLC
Under the PLC tab, select the Setting option and choose Port 0. Here, the Baud rate
and other parameters of the serial port can be configured.
Note: For more detailed information please refer to the PLC manual.
8
Connecting PLC to HMI
9
2 RX
3 TX
4
5 GND
6
7 RTS
8 CTS
9
10
FBe
2.1.2.1 Communication Setting
Item Default Setting Remark
Signal Level RS232 / RS485
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 1 Must match PLC
port setting
Communication Method FATEK Communication
Protocol
11
WX 16 DDDD 0 255 Input Discrete
WY 16 DDDD 0 255 Output Relay
WM 16 DDDD 0 2001 Input Relay
WS 16 DDDD 0 999 Step Relay
RT 16 DDDD 0 255 Timer Register
RC 16 DDDD 0 199 Counter Register
DRC 32 DDDD 200 255 Counter Register
R 16 DDDD 0 8071 Data Register
D 16 DDDD 0 4095 Data Register
Under the PLC tab, select the Setting option and choose Port 0. Here, the Baud rate
and other parameters of the serial port can be configured.
12
Note: For more detailed information please refer to the PLC manual.
13
Under Interface Type select Serial
Under Manufacturer select FATEK Automation Corp.
Under Product Series select FATEK FBe
Under Port select the port corresponding to the connection to the PLC
Verify the other parameters are consistent with the settings on the PLC
14
PIN# COM1 (RS232)
1
2 RX
3 TX
4
5 GND
6
7 RTS
8 CTS
9
15
P5070S/ P5070N/ P5070N1/ P5102S/ P5102N/ P5102N1
HMI COM3 PLC RS485 Port
6 DATA+ DATA+
7 DATA- DATA-
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS485 Port
1 DATA+ DATA+
6 DATA- DATA-
16
Wiring Diagrams:P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
FBs/B1/B1z/HB1 (TCP)
2.1.3.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.1.3
Port 500
PLC Station No. 0
Communication Method TCP
17
WM 16 DDDD 0 2001 Input Relay
WS 16 DDDD 0 999 Step Relay
RT 16 DDDD 0 255 Timer Register
RC 16 DDDD 0 199 Counter Register
DRC 32 DDDD 200 255 Counter Register
R 16 DDDD 0 8071 Data Register
D 16 DDDD 0 4095 Data Register
F 16 DDDD 0 8191 File Register
Select the PLC to connect to and right click or press Properties to change the IP.
Note: The default IP address for the PLC has 1 for its third octet. If the IP address of the
computer has a different number at that position, the PLC will not show up in the scan.
Configure network settings on the computer to be able to see the PLC in the local
network.
In the dialog window, the IP address and other parameters of the PLC can be
configured. In the Service Ports tab, the port number of the PLC can be changed.
18
Note: For more detailed information please refer to the PLC manual.
19
Use the IP address and port number assigned on the PLC
FBe (TCP)
2.1.4.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.1.3
Port 500
PLC Station No. 0
Communication Method TCP
Note: The default IP address for the PLC has 1 for its third octet. If the IP address of the
computer has a different number at that position, the PLC will not show up in the scan.
Configure network settings on the computer to be able to see the PLC in the local
network.
In the dialog window, the IP address and other parameters of the PLC can be
configured.
Note: For more detailed information please refer to the PLC manual.
21
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select FATEK Automation Corp
Under Product Series select FATEK FBe (TCP)
Use the IP address assigned on the PLC
Leave the Port at the default value
FBs/B1/B1z/HB1 (UDP)
2.1.5.1 Communication Setting
Item Default Settings Remark
Signal Level Ethernet
Internet Protocol 192.168.1.100
Port 500
PLC Station No. 0
Communication UDP
Method
22
Device Data Bits Address Min. Max. Description
Format
X 1 DDDD 0 255 Input Discrete
Y 1 DDDD 0 255 Output Relay
M 1 DDDD 0 2001 Internal Relay
S 1 DDDD 0 999 Step Relay
T 1 DDDD 0 255 Timer Discrete
C 1 DDDD 0 255 Counter Discrete
WX 16 DDDD 0 255 Input Discrete
WY 16 DDDD 0 255 Output Relay
WM 16 DDDD 0 2001 Input Relay
WS 16 DDDD 0 999 Step Relay
RT 16 DDDD 0 255 Timer Register
RC 16 DDDD 0 199 Counter Register
DRC 32 DDDD 200 255 Counter Register
R 16 DDDD 0 8071 Data Register
D 16 DDDD 0 4095 Data Register
F 16 DDDD 0 8191 File Register
In the dialog window, the IP address and other parameters of the PLC can be
23
configured.
Note: For more detailed information please refer to the PLC manual.
24
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select FATEK Automation Corp
Under Product Series select FATEK FBe (UDP)
Use the IP address assigned on the PLC
Leave the Port at the default value
25
Electrical specifications Asynchronous serial communication half
duplex
Baud rate 2400,4800,9600,19200,38400,57600bps
Data bit 8 bit
Parity bit None even odd
Parameter
parameter Setting value
No.
RS-485 communication 1-32
4.0
address Initial value 1。
0: 2,400bps
1: 4,800bps
RS-485 communication 2: 9,600bps
6.0 3:19,200bps
Baud rate
4:38,400bps
5:57,600bps (Initial value)
26
RS-485 communication 0:1 bit(Initial value)
6.1
STOP bit 1:2 bit
0:none(Initial value)
RS-485communication
6.2 1:EVEN
parity
2:ODD
RS-485 communication 0:no use(Initial value)
8.0
ON/OFF 1:use
RS-485 Communication
0-255
11.0 Minimum response
Initial value 3 [ms]。
time
參數設定方法
Method1:
27
Method2:
Open Sankyo S-TUNE and use the mini USB cable to connect to the computer USB port, it
will automatically connect
28
HMI 設定
29
30
2.2 Mitsubishi
FX2N CPU
2.2.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 4W
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 0
Communication Method Programming Protocol
31
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select Mitsubishi FX2N
Under Port select COM3
32
5
6
7 TX+
8
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS422 Port
5 RX- 4 TX-
4 RX+ 7 TX+
7 TX- 1 RX-
6 TX+ 2 RX+
3 ISO_GND 3 GND
33
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- 4 TX-
4 RX+ 7 TX+
6 TX- 1 RX-
1 TX+ 2 RX+
5 GND 3 GND
FX2N-485BD
2.2.2.1 Communication Setting
34
Item Default Setting Remark
Signal Level RS485
Baud Rate 19200
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 1
TX Control Form1 Without CR,LF
Checksum Yes
Communication Method Computer Link
35
Select Serial USB in the Transfer Setup Communication window.
Select the RS-232C radio button and select the COM Port that the PLC is connected at.
Click Connection Test to verify the connection and then press OK.
36
After confirming the Parameter option is checked, press Execute in the Online Data
Operation window.
Under the Project Sidebar, expand Parameter and select PLC Parameter.
37
Navigate to the PLC System(2) tab and configure it to the settings detailed below.
Note: For more detailed information please refer to the PLC manual.
39
HMI COM3 Pinout
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS422 Port
5 RX- SDB
4 RX+ SDA
7 TX- RDB
6 TX+ RDA
3 ISO_GND SG
40
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- SDB
4 RX+ SDA
6 TX- RDB
1 TX+ RDA
5 GND SG
41
FX3U CPU
2.2.3.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 4W
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 0
Communication Method Programming Protocol
42
CS Counter Discrete 1 0 199
WX Input Discrete 16 0 360
WY Output Relay 16 0 360
WM Internal Relay 16 0 7664
WS Step Relay 16 0 4080
TN Timer Memory 16 0 511
CN Counter Memory 16 0 199
D Data Register 16 0 7999
SD Special Data Register 16 8000 8511
R Extended Register 16 0 32767
DCN Counter Memory 32 200 255
43
2.2.3.4 Wiring Diagrams
PLC RS422 Pinout
P5070S/P5070N/P5070N1/P5102N/P5102N1
44
HMI COM3 PLC RS422 Port
5 RX- 4 TX-
4 RX+ 7 TX+
7 TX- 1 RX-
6 TX+ 2 RX+
3 ISO_GND 3 GND
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- 4 TX-
4 RX+ 7 TX+
6 TX- 1 RX-
1 TX+ 2 RX+
5 GND 3 GND
45
FX3U-485BD
2.2.4.1 Communication Setting
Item Default Setting Remark
Signal Level RS485
Baud Rate 19200
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 1
TX Control Form1 Without CR,LF
Checksum Yes
Communication Method Computer Link
46
WM Internal Relay 16 0 7664
WS Step Relay 16 0 4080
TN Timer Memory 16 0 511
CN Counter Memory 16 0 199
D Data Register 16 0 7999
SD Special Data Register 16 8000 8511
R Extended Register 16 0 32767
DCN Counter Memory 32 200 255
47
Select the RS-232C radio button and select the COM Port that the PLC is connected at.
Click Connection Test to verify the connection and then press OK.
After confirming the Parameter option is checked, press Execute in the Online Data
Operation window.
48
Under the Project Sidebar, expand Parameter and select PLC Parameter.
Navigate to the PLC System(2) tab and configure it to the settings detailed below.
49
Check Operate Communication Setting to enable configuration
Set Protocol to Dedicated Protocol
Set Parity to Even
Set Transmission Speed to 19200
Set H/W Type to RS-485
Check the Sum Check checkbox
Verify the Station Number is consistent with the one set in FvDesigner.
Note: For more detailed information please refer to the PLC manual.
50
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select Mitsubishi FX3U/3G-485BD.
Under Port select COM3
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS422 Port
5 RX- SDB
4 RX+ SDA
7 TX- RDB
6 TX+ RDA
3 ISO_GND SG
52
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- SDB
4 RX+ SDA
6 TX- RDB
1 TX+ RDA
5 GND SG
FX3U Ethernet
2.2.5.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0
Port 5001
PLC Station No. 0
Communication Method MC protocol Binary/ASCII
54
Select the RS-232C radio button and select the COM Port that the PLC is connected at.
Click Connection Test to verify the connection and then press OK.
After confirming the Parameter option is checked, press Execute in the Online Data
Operation window.
55
Under the Project Sidebar, expand Parameter and select PLC Parameter.
56
Click Open Setting and set the entire Open System column to MC Protocol. For the
Host Station Port No., set row 1 to 5001, row 2 to 5002 and so on.
Under the Online menu option, select Write to PLC to save the settings to the PLC.
Press Execute in the Online Data Operation window.
57
Note: For more detailed information please refer to the PLC manual.
58
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select one of the Mitsubishi FX3U-ENET-ADP options. The last
part of the series name (BINARY or ASCII) should be consistent with the Connection
Data Code set in the Ethernet Port for the PLC.
Enter the IP Address that was written into the PLC.
Enter 5001 for the Port.
FX5U-Serial
2.2.6.1 Communication Setting
Item Default Setting Remark
Signal Level RS485
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 0
59
TX Control Form1 Without CR,LF
Checksum Yes
Communication Method MC Protocol 3C
61
In the connection window, select Ethernet Board. Click PLC Module and in the dialog
window, select the Ethernet Port Direct Connection radio button.
62
Click Connection Test to verify the connection and then press OK.
Click Select All in the Online Data Operation window and press Execute. Allow the read
to finish.
63
In the Project sidebar, expand Parameter, FX5UCPU, and Module Parameter and
select 485 Serial Port.
Under Fixed Setting, change Message Pattern to Pattern 1 and verify the station
number is consistent with the one set in FvDesigner.
64
Under the Online menu option, select Write to PLC to save the settings to the PLC.
Click Select All and press Execute in the Online Data Operation window.
Note: For more detailed information please refer to the PLC manual.
66
2
3 ISO_GND
4 RX+
5 RX-
6 TX+
7 TX-
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS422 Port
5 RX- SDB
4 RX+ SDA
7 TX- RDB
6 TX+ RDA
3 ISO_GND SG
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- SDB
4 RX+ SDA
6 TX- RDB
1 TX+ RDA
5 GND SG
67
Wiring Diagrams: P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
FX5U Ethernet
2.2.7.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0
Port 1025
PLC Station No. 0
Communication Method MC protocol 3E Binary/ASCII
68
SB Link Special Relay 1 HHHH 0 7FFF
S Step Relay 1 DDDD 0 4095
TS Timer Contact 1 DDDD 0 1023
TC Timer Coil 1 DDDD 0 1023
SS Retentive Timer 1 DDDD 0 1023
Contact
SC Retentive Timer 1 DDDD 0 1023
Coil
CS Counter Contact 1 DDDD 0 1023
CC Counter Coil 1 DDDD 0 1023
LCS*1 Long Counter 1 DDDD 0 1023
Contact
LCC*1 Long Counter Coil 1 DDDD 0 1023
SM Special Relay 1 DDDD 0 9999
WX*2 Input Relay 16 OOOO 0 1760
WY*2 Output Relay 16 OOOO 0 1760
WM*3 Internal Relay 16 DDDDD 0 32752
B_Word *3 Link Relay 16 HHHH 0 7FF0
F_Word *3 Annunciator 16 DDDDD 0 32752
SB_Word *3 Link Special Relay 16 HHHH 0 7FF0
WS*3 Step Relay 16 DDDD 0 4080
TS_Word *3 Timer Contact 16 DDDD 0 1008
TC_Word *3 Timer Coil 16 DDDD 0 1008
SS_Word *3 Retentive Timer 16 DDDD 0 1008
Contact
SC_Word *3 Retentive Timer 16 DDDD 0 1008
Coil
CS_Word *3 Counter Contact 16 DDDD 0 1008
CC_Word *3 Counter Coil 16 DDDD 0 1008
SM_Word Special Relay 16 DDDD 0 9984
*3
In the connection window, select Ethernet Board. Click PLC Module and in the dialog
window, select the Ethernet Port Direct Connection radio button.
70
71
Click Connection Test to verify the connection and then press OK.
Click Select All in the Online Data Operation window and press Execute. Allow the read
to finish.
72
In the Project sidebar, expand Parameter, FX5UCPU, and Module Parameter and
select Ethernet Port.
The IP Address of the PLC can be obtained here. Switch the Communication Data Code
to the mode needed (Binary or ASCII). Double click “<Detailed Setting>” under
External Device Configuration to get the port information. Verify the Protocol is TCP.
73
If the user needs to change the IP Address, edit the IP address under the Own Node
Settings. Then enter the Detailed Settings and press Close with Reflecting the Setting.
Under the Online menu option, select Write to PLC to save the settings to the PLC.
Click Select All and press Execute in the Online Data Operation window.
Note: For more detailed information please refer to the PLC manual.
74
Connecting PLC to HMI
75
TX Control Procedure Form4 Without CR,LF
76
TC_Word Timer Coil 16 DDDD 0 32752
SS_Word Retentive Timer 16 DDDD 0 32752
Contact
SC_Word Retentive Timer Coil 16 DDDD 0 32752
CS_Word Counter Contact 16 DDDD 0 32752
CC_Word Counter Coil 16 DDDD 0 32752
SM_Word Special Relay 16 DDDD 0 2032
TN Timer Current Value 16 DDDD 0 32752
SN Retentive Timer 16 DDDD 0 32752
Current Value
CN Counter Current 16 DDDD 0 32752
Value
D Data Register 16 DDDDD 0 39935
W Link Register 16 HHHH 0 9bff
SW Link special Register 16 HHH 0 7FFF
SD Special Register 16 DDDD 0 2047
R File Register 16 DDDDD 0 32767
Z Index Register 16 DD 0 19
ZR File Register 16 HHHHH 0 9fff
77
Configure it to the settings detailed below.
Note: For more detailed information please refer to the PLC manual.
80
HMI COM3 pinout
Wiring Diagrams:RS232
81
RS422
HMI COM3 QJ71 RS422/485 Port
4 RX+ SDA
5 RX- SDB
6 TX+ RDA
7 TX- RDB
3 GND SG
Wiring Diagrams:RS422
RS485
HMI COM3 QJ71 RS422/485 Port
SDA
6 TX+
RDA
7 TX- SDB
82
RDB
3 GND SG
83
S Step Relay 1 DDDDD 0 16383
TS Timer Contact 1 DDDDD 0 32767
TC Timer Coil 1 DDDDD 0 32767
SS Retentive Timer 1 DDDDD 0 32767
Contact
SC Retentive Timer Coil 1 DDDDD 0 32767
CS Counter Contact 1 DDDDD 0 32767
CC Counter Coil 1 DDDDD 0 32767
SM Special Relay 1 DDDD 0 2047
DX Direct Input 1 HHHH 0 1fff
DY Direct Output 1 HHHH 0 1fff
WX Input Relay 16 HHHH 0 1ff0
WY Output Relay 16 HHHH 0 1ff0
WM Internal Relay 16 DDDDD 0 61424
WL Latch Relay 16 DDDDD 0 32752
B_Word Link Relay 16 HHHH 0 Eff0
F_Word Annunciator 16 DDDDD 0 32752
WV Edge Relay 16 DDDDD 0 32752
SB_Word Link Special Relay 16 HHHH 0 7ff0
WS Step Relay 16 DDDDD 0 16368
TS_Word Timer Contact 16 DDDDD 0 32752
TC_Word Timer Coil 16 DDDDD 0 32752
SS_Word Retentive Timer 16 DDDDD 0 32752
Contact
SC_Word Retentive Timer Coil 16 DDDDD 0 32752
CS_Word Counter Contact 16 DDDDD 0 32752
CC_Word Counter Coil 16 DDDDD 0 32752
SM_Word Special Relay 16 DDDD 0 2032
TN Timer Current Value 16 DDDDD 0 32767
SN Retentive Timer 16 DDDDD 0 32767
Current Value
CN Counter Current Value 16 DDDDD 0 32767
D Data Register 16 DDDDD 0 39935
W Link Register 16 HHHH 0 9bff
SW Link Special Register 16 HHHH 0 7fff
SD Special Register 16 DDDD 0 2047
84
R File Register 16 DDDDD 0 32767
Z Index Register 16 DD 0 19
ZR File Register 16 HHHHH 0 9ffff
The setting of Q series CPU setting if ‘’Use serial communication’’ is checked, please
use QSeries-Serial Communication (Link Port).
Note: For more detailed information please refer to the PLC manual.
85
Within the Link configuration window in FvDesigner:
Under Interface Type select Direct Link(Serial)
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select one of the Mitsubishi QSeries-Series Communication(CPU
Port).
Verify the parameters match the window above.
86
HMI COM1 Pinout
87
Q/L Series-ENET
2.2.10.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0
Port 4999
PLC Station No. 0
Communication Method MC protocol 3E Binary/ASCII
88
Contact
SC Retentive Timer 1 DDDD 0 32767
Coil
CS Counter Contact 1 DDDD 0 32767
CC Counter Coil 1 DDDD 0 32767
SM Special Relay 1 DDDD 0 2047
DX Direct Input 1 HHHH 0 1fff
DY Direct Output 1 HHHH 0 1fff
WX*1 Input Relay 16 HHHH 0 1ff0
WY*1 Output Relay 16 HHHH 0 1ff0
WM*1 Internal Relay 16 DDDDD 0 61424
WL Link Relay 16 DDDD 32752
B_Word *1 Link Relay 16 HHHH 0 eff0
F_Word *1 Annunciator 16 DDDDD 0 32752
WV Edge relay 16 DDDDD 0 32752
SB_Word Link Special Relay 16 HHH 0 7ff0
*1
Navigate to Built-in Ethernet Port Setting tab, the IP address and other parameters can
be set.
90
Click Open Setting and set the entire Open System column to MC Protocol. For the
Host Station Port No 4999.
Note: For more detailed information please refer to the PLC manual.
91
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select one of the Mitsubishi Q/L Series-ENET(BINARY 或 ASCII).
The last part of the series name (BINARY or ASCII) should be consistent with the
Connection Data Code set in the Ethernet Port for the PLC.
Enter the IP Address that was written into the PLC.
Verify the parameters match the window above.
iQ-R Series-ENET
93
Current Value
CN 16 Counter Current Value DDDDD 0 35487
Z 16 Index Register DD 0 23
16 Long Timer Current DDDDD 0 35487
LTN
Value
16 Long Retentive Timer DDDDD 0 35487
LSTN
Current Value
16 Long Counter Current DDDDD 0 35487
LCN
Value
LZ 16 Long Index Register DD 0 11
Navigate to Built-in Ethernet Port Setting tab, the IP address and other parameters can
be set.
94
Click Open Setting and set the entire Open System column to MC Protocol. For the
Host Station Port No 4999.
Note: For more detailed information please refer to the PLC manual.
95
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Mitsubishi Electric Corporation
Under Product Series select one of the Mitsubishi iQ-R Series-ENET(BINARY 或 ASCII).
The last part of the series name (BINARY or ASCII) should be consistent with the
Connection Data Code set in the Ethernet Port for the PLC.
Enter the IP Address that was written into the PLC.
Verify the parameters match the window above.
2.3 Omron
Omron SYSMAC CP Series
2.3.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
96
Baud Rate 9600
Data Length 7
Stop Bit 2
Parity Even
PLC Station No. 0
Communication Method FINS
97
Navigate to 序列埠 1 tab and configure it to the settings detailed below.
Note: For more detailed information please refer to the PLC manual.
98
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac CP Series (FINS)
Under Port select COM1
99
6
7
8
9 GND
100
Omron SYSMAC CP Series Ethernet
2.3.2.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0 To be configured
Port 9600
PLC Station No. 0
Communication Method FINS/TCP
101
2.3.2.3 Connecting to HMI
Configuring IP Address on PLC
Use CX-Programmer to configure the IP of the PLC.
In the 專案 Task sidebar, expand 設定
Navigate to 內置乙太網路 tab, the IP address and other parameters can be set.
102
Note: For more detailed information please refer to the PLC manual.
HMI 設定
103
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac CP Series (FINS/TCP)
Enter the IP Address that was written into the PLC
Enter 9600 for the Port
Note: For more detailed information please refer to the PLC manual.
105
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac CS/CJ Series (FINS)
Under Port select COM3
106
HMI COM3 Pinout
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS422 Port
5 RX- SDA-
4 RX+ SDB+
7 TX- RDA-
6 TX+ RDB+
3 ISO_GND FG
107
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS422 Port
9 RX- SDA-
4 RX+ SDB+
6 TX- RDA-
1 TX+ RDB+
5 GND FG
108
Omron SYSMAC CS/CJ Series Ethernet
2.3.4.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0 To be configured
Port 9600
PLC Station No. 0
Communication Method FINS/TCP
109
IR Index Register 32 0 15
110
IP address and other parameters can be set.
Note: For more detailed information please refer to the PLC manual.
111
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac CS/CJ Series (FINS/TCP)
Enter the IP Address that was written into the PLC
Enter 9600 for the Port
112
Omron SYSMAC CPM Series
2.3.5.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 9600
Data Length 7
Stop Bit 2
Parity Even
PLC Station No. 0
Communication Method HOSTLINK
113
Navigate to 序列埠 1 tab and configure it to the settings detailed below.
114
Note: For more detailed information please refer to the PLC manual.
117
UINT --- 16 unsigned integer value
WORD --- 16 word value
DINT --- 32 double integer value
DWORD --- 32 double word value
REAL --- 32 float value
UDINT --- 32 unsigned double integer value
BOOL[] BOOL 1*n array of Boolean value
BYTE[] BYTE 8*n array of byte value
SINT[] SINT 8*n array of short integer value
USINT[] USINT 8*n array of unsigned short integer value
INT[] INT 16*n array of integer value
UINT[] UINT 16*n array of unsigned integer value
WORD[] WORD 16*n array of word value
DINT[] DINT 32*n array of Double integer value
DWORD[] DWORD 32*n array of double word value
REAL[] REAL 32*n array of float value
UDINT[] UDINT 32*n array of unsigned double integer value
118
Note: For more detailed information please refer to the PLC manual.
119
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select SYSMAC NJ/NX Series(EtherNet/IP)
Enter the IP Address that was written into the PLC
Enter 44818 for the Port
Omron Ethernet
2.3.7.1 Communication Setting
121
Note: For more detailed information please refer to the PLC manual.
122
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac Omron Ethernet
Enter the IP Address that was written into the PLC
Enter 9600 for the Port
123
%D DM Area 16 0 32767
%E0_ EM Bank 0 16 0 32767
%E1_ EM Bank 1 16 0 32767
%E2_ EM Bank 2 16 0 32767
%E3_ EM Bank 3 16 0 32767
%E4_ EM Bank 4 16 0 32767
%E5_ EM Bank 5 16 0 32767
%E6_ EM Bank 6 16 0 32767
%E7_ EM Bank 7 16 0 32767
%E8_ EM Bank 8 16 0 32767
%E9_ EM Bank 9 16 0 32767
%EA_ EM Bank 10 16 0 32767
%EB_ EM Bank 11 16 0 32767
%EC_ EM Bank 12 16 0 32767
124
125
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac NJ Series (FINS/TCP)
Enter the IP Address that was written into the PLC
Enter 9600 for the Port
126
%D DM Area 16 0 32767
%E0_ EM Bank 0 16 0 32767
%E1_ EM Bank 1 16 0 32767
%E2_ EM Bank 2 16 0 32767
%E3_ EM Bank 3 16 0 32767
%E4_ EM Bank 4 16 0 32767
%E5_ EM Bank 5 16 0 32767
%E6_ EM Bank 6 16 0 32767
%E7_ EM Bank 7 16 0 32767
%E8_ EM Bank 8 16 0 32767
%E9_ EM Bank 9 16 0 32767
%EA_ EM Bank 10 16 0 32767
%EB_ EM Bank 11 16 0 32767
%EC_ EM Bank 12 16 0 32767
127
Note: For more detailed information please refer to the PLC manual.
128
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac NX/NJ Series (FINS/UDP)
Enter the IP Address that was written into the PLC
Enter 9600 for the Port
129
Device Description Data bit Min. Max.
TNB Timer Area 1 0 255
CNB Counter Area 1 0 255
IR IR area 16 0 227
HR HR area 16 0 19
AR AR area 16 0 23
LR LR area 16 0 15
TN Timer area 16 0 255
CN Counter area 16 0 255
DM DM area 16 0 6655
130
After click 傳輸到 PLC to write in PLC.
Note: For more detailed information please refer to the PLC manual.
131
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Omron Corporation
Under Product Series select Sysmac CQM Series (HOSTLINK)
Under Port select COM1
133
2.4 Siemens
Siemens S7-200 SMART
2.4.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 2W
Baud Rate 9600
Data Length 8
Stop Bit 1
Parity Even
PLC Station No. 2
Communication Method PPI
135
Note: For more detailed information please refer to the PLC manual.
137
5 GND
6 DATA-
7
8
9
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 Port PLC RS485 Port
6 DATA+ 3 DATA+
7 DATA- 8 DATA-
5 GND 5 GND
138
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM3 Port PLC RS485 Port
1 DATA+ 3 DATA+
6 DATA- 8 DATA-
5 GND 5 GND
139
Siemens S7-200 SMART Ethernet
2.4.2.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0 To be configured
Port 102
PLC Station No. 0
Communication Method ISO TCP
140
CW Counter 16 0 255
MW Word Memory 16 0 31
SW SCR 16 0 31
VW V Memory 16 0 20479
SMW Special Memory 16 0 1535
AIW Analog Input 16 0 111
AQW Analog Output 16 0 111
141
Under Network interface, select one of the options to scan the local network. The IP
address of the PLC will show up. The MAC address can be verified with the one on the
PLC.
Navigate to the PLC tab and select to upload the PLC program onto the computer.
On the sidebar, right click CPU CR40 and select the first option. A dialog window will
open up.
142
In the dialog window, the IP address can be changed. Press OK to confirm the setting.
143
In the PLC tab, select to download the settings onto the PLC.
Note: For more detailed information please refer to the PLC manual.
144
Siemens S7-1200 Ethernet
2.4.3.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0 To be configured
Port 102
PLC Station No. 0
Communication Method ISO TCP
146
Under the device in the project tree, select Device configuration and click the Ethernet
port on the device image. Under the Ethernet addresses menu option, the IP address
can be configured.
147
Note: For more detailed information please refer to the PLC manual.
148
Siemens S7-200
2.4.4.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 2W
Baud Rate 9600
Data Length 8
Stop Bit 1
Parity Even
PLC Station No. 2
Communication Method PPI
150
Note: For more detailed information please refer to the PLC manual.
151
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Siemens Corporation
Under Product Series select S7-200
Under Port select the port number that corresponds to the RS485 connection on the
HMI.
152
*Looking into male RS485 Cable
PIN# Signal
1
2
3 DATA+
4
5 GND
6
7
8 DATA-
9
153
*Looking into HMI Device
PIN# COM3
(RS-422/RS-485)
1
2
3 ISO_GND
4
5
6 DATA+
7 DATA-
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 Port PLC RS485 Port
6 DATA+ 3 DATA+
7 DATA- 8 DATA-
5 GND 5 GND
154
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM3 Port PLC RS485 Port
1 DATA+ 3 DATA+
6 DATA- 8 DATA-
5 GND 5 GND
155
Siemens LOGO
2.4.5.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0 To be configured
Port 102
PLC Station No. 0
Communication Method ISO TCP
Model 0BA8 0BA7/0BA8
Local TSAP 1000 HEX
Remote TSAP 2100 HEX
156
VD 32 0 1466
157
Note: For more detailed information please refer to the PLC manual.
158
2.5 Hitachi
EHV Series
2.5.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232C
Baud Rate 19200
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 0
Communication Method h protocol
160
9
161
EHV Series ( Ethernet )
2.5.2.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.1.100
Port 3004
PLC Station No. 0
Communication Method h protocol ( Ethernet )
162
WL Link word 16 HHH 0 3FF
TC Timer / Counter 16 DDDD 0 2559
2.6 Schneider
MODBUS RTU
2.6.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 2W
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 0
Communication Method MODBUS RTU(Zero-based)
163
Note: For more detailed information please refer to the PLC manual.
165
6 DATA+
7 DATA-
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 Port PLC RS485 Port
6 DATA+ 1 DATA+
7 DATA- 2 DATA-
5 GND 5 GND
166
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 Port PLC RS485 Port
1 DATA+ 1 DATA+
6 DATA- 2 DATA-
5 GND 5 GND
MODBUS TCP
2.6.2.1 Communication Setting
Item Default Setting Remark
167
Signal Level Ethernet
Internet Protocol 192.168.0.2
Port 502
PLC Station No. 0
Communication Method MODBUS TCP(Zero-based)
Note: For more detailed information please refer to the PLC manual.
168
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Schneider Electric.
Under Product Series select Modbus TCP.
Enter the IP Address that was written into the PLC.
2.7 Allen-Bradley
CompactLogix/ControlLogix/FlexLogix Tag Series
2.7.1.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.0.2
Port 44818
PLC Station No. 0
Communication Method EtherNet/IP
Under the new Ethernet driver, the PLC connected to the local network should be
visible.
Right click the main module of the PLC and select Module Configuration.
Navigate to the Port Configuration tab. Here, the IP address and other parameters can
be set. Press OK to confirm the settings.
171
Note: For more detailed information please refer to the PLC manual.
172
Enter the IP Address that was written into the PLC.
To access variables in the program, tags will have to be imported. Tags are created in
the program RSLogix 5000.
Right click 控制器标签(controller tag) in the controller sidebar and select 导出
(Export) Tag.
Select which tags to export. The register tags can now be imported into the HMI
project.
174
Under the new Ethernet driver, the PLC connected to the local network should be
visible. If the status of the device is OK, open up RSLogix 500.
In RSLogix 500, under the Comms menu option, select Who Active go Online. In the
dialog window that appears, select the PLC device connected through RSLinx.
Press Create New File in the dialog window that appears after pressing OK.
On the left side of the program, double click Channel Configuration to access the PLC’s
Ethernet settings. Under the Channel 1 tab, the IP address can be changed.
175
Note: For more detailed information please refer to the PLC manual.
176
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Allen-Bradley
Under Product Series select SLC (Ethernet/IP)
Enter the IP Address that was written into the PLC.
Keep the Port at the default setting.
SLC Series
2.7.3.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 1
TX Control CRC CRC/BCC
177
Communication Method DF1
178
Note: For more detailed information please refer to the PLC manual.
179
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Allen-Bradley
Under Product Series select SLC.
Verify the parameters match the window above.
180
5 GND
6
7 RTS
8 CTS
9
181
MicroLogix Series (EtherNet/IP)
2.7.4.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.0.1
Port 44818
Communication Method EtherNet/IP
182
File
Under the new Ethernet driver, the PLC connected to the local network should be
visible. If the status of the device is OK, open up RSLogix 500.
In RSLogix 500, under the Comms menu option, select Who Active go Online. In the
dialog window that appears, select the PLC device connected through RSLinx.
183
Press Create New File in the dialog window that appears after pressing OK.
On the left side of the program, double click Channel Configuration to access the PLC’s
Ethernet settings. Under the Channel 1 tab, the IP address can be changed.
184
Note: For more detailed information please refer to the PLC manual.
185
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Allen-Bradley
Under Product Series select Micrologix (Ethernet/IP)
Enter the IP Address that was written into the PLC.
Keep the Port at the default setting.
MicroLogix Series
2.7.5.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 1
TX Control CRC CRC/BCC
186
Communication Method DF1 Protocol
187
Note: For more detailed information please refer to the PLC manual.
188
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Allen-Bradley
Under Product Series select Micrologix
Under Port select COM1
Verify the other parameters are consistent with the ones set on the PLC.
189
4
5 GND
6
7 RTS
8 CTS
9
190
2.8 Taiwan Instrument & Control Co., Ltd.
FY Series
2.8.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS485 2W
Baud Rate 38400
Data Length 8
Stop Bit 1
Parity Odd
PLC Station No. 0
Communication Method MODBUS RTU
192
Seg.6(Pattern 1)
OUT6 Output Limit of 16 D 0 0
Seg.6(Pattern 1)
SV_7 Set Point of 16 D 0 0
Seg.7(Pattern 1)
TM_7 Run Time of 16 D 0 0
Seg.7(Pattern 1)
OUT7 Output Limit of 16 D 0 0
Seg.7(Pattern 1)
SV_8 Set Point of 16 D 0 0
Seg.8(Pattern 1)
TM_8 Run Time of 16 D 0 0
Seg.8(Pattern 1)
OUT8 Output Limit of 16 D 0 0
Seg.8(Pattern 1)
SV_12 Set Point of 16 D 0 0
Seg.1(Pattern 2)
TM_12 Run Time of 16 D 0 0
Seg.1(Pattern 2)
OUT12 Output Limit of 16 D 0 0
Seg.1(Pattern 2)
SV_22 Set Point of 16 D 0 0
Seg.2(Pattern 2)
TM_22 Run Time of 16 D 0 0
Seg.2(Pattern 2)
OUT22 Output Limit of 16 D 0 0
Seg.2(Pattern 2)
SV_32 Set Point of 16 D 0 0
Seg.3(Pattern 2)
TM_32 Run Time of 16 D 0 0
Seg.3(Pattern 2)
OUT32 Output Limit of 16 D 0 0
Seg.3(Pattern 2)
SV_42 Set Point of 16 D 0 0
Seg.4(Pattern 2)
TM_42 Run Time of 16 D 0 0
Seg.4(Pattern 2)
193
OUT42 Output Limit of 16 D 0 0
Seg.4(Pattern 2)
SV_52 Set Point of 16 D 0 0
Seg.5(Pattern 2)
TM_52 Run Time of 16 D 0 0
Seg.5(Pattern 2)
OUT52 Output Limit of 16 D 0 0
Seg.5(Pattern 2)
SV_62 Set Point of 16 D 0 0
Seg.6(Pattern 2)
TM_62 Run Time of 16 D 0 0
Seg.6(Pattern 2)
OUT62 Output Limit of 16 D 0 0
Seg.6(Pattern 2)
SV_72 Set Point of 16 D 0 0
Seg.7(Pattern 2)
TM_72 Run Time of 16 D 0 0
Seg.7(Pattern 2)
OUT72 Output Limit of 16 D 0 0
Seg.7(Pattern 2)
SV_82 Set Point of 16 D 0 0
Seg.8(Pattern 2)
TM_82 Run Time of 16 D 0 0
Seg.8(Pattern 2)
OUT82 Output Limit of 16 D 0 0
Seg.8(Pattern 2)
P1 OUT1 Proportional 16 D 0 0
Band
I1 OUT1 Integral Time 16 D 0 0
D1 OUT1 Derivative 16 D 0 0
Time
DB1 Dead-band Time 16 D 0 0
ATVL Auto Tuning Offset 16 D 0 0
CYT1 OUT1 Cycle Time 16 D 0 0
HYS1 OUT1 Hysteresis 16 D 0 0
P2 OUT2 Proportional 16 D 0 0
Band
194
I2 OUT2 Integral Time 16 D 0 0
D2 OUT2 Derivative 16 D 0 0
Time
CYT2 OUT2 Cycle Time 16 D 0 0
HYS2 OUT2 Hysteresis 16 D 0 0
GAP1 OUT1 Control Gap 16 D 0 0
GAP2 OUT2 Control Gap 16 D 0 0
LCK Function Lock 16 D 0 0
INP1 Input Type Selection 16 D 0 0
ANL1 Linear Input Zero 16 D 0 0
Calibration
ANH1 Linear Input Span 16 D 0 0
Calibration
DP Decimal Point 16 D 0 0
Position
LSPL Lower Set Point Limit 16 D 0 0
USPL Upper Set Point Limit 16 D 0 0
ANL2 Remote Input Zero 16 D 0 0
Calibration
ANH2 Linear Input Span 16 D 0 0
Calibration
ALD1 Alarm mode for AL1 16 D 0 0
ALT1 Alarm time for AL1 16 D 0 0
ALD2 Alarm mode for AL2 16 D 0 0
ALT2 Alarm time for AL2 16 D 0 0
ALD3 Alarm mode for AL3 16 D 0 0
ALT3 Alarm time for AL3 16 D 0 0
HYSA Hysteresis for all 16 D 0 0
Alarms
CLO1 OUT1 Lower 16 D 0 0
Calibration
CHO1 OUT1 Upper 16 D 0 0
Calibration
CLO2 OUT1 Lower 16 D 0 0
Calibration
CHO2 OUT1 Upper 16 D 0 0
Calibration
195
CLO3 TRS Lower 16 D 0 0
Calibration
CHO3 TRS Upper 16 D 0 0
Calibration
RUCY Full run time of 16 D 0 0
motor valve
WAIT Full run time of 16 D 0 0
proportional motor
valve
SETA 16 D 0 0
PSL Protocol Selection 16 D 0 0
BITS Communication Bits 16 D 0 0
IDNO ID Number 16 D 0 0
BAUD Baud rate 16 D 0 0
SVOS SV Compensation 16 D 0 0
PVOS PV Compensation 16 D 0 0
UNIT Unit of PV and SV 16 D 0 0
PVFT PV Filter 16 D 0 0
CASC 16 D 0 0
OUD Heating / Cooling 16 D 0 0
selection
OPAD Control Algorithm 16 D 0 0
HZ Power Frequency 16 D 0 0
SET1 Hide/ Display 16 D 0 0
parameter
SET2 Hide/ Display 16 D 0 0
parameter
SET3 Hide/ Display 16 D 0 0
parameter
SET4 Hide/ Display 16 D 0 0
parameter
SET5 Hide/ Display 16 D 0 0
parameter
SET6 Hide/ Display 16 D 0 0
parameter
SET7 Hide/ Display 16 D 0 0
parameter
196
SET8 Hide/ Display 16 D 0 0
parameter
SET9 Hide/ Display 16 D 0 0
parameter
SET0 Hide/ Display 16 D 0 0
parameter
INP2 Hide/ Display 16 D 0 0
parameter
OUTY Hide/ Display 16 D 0 0
parameter
VER Output mode 16 D 0 0
selection
OUT% Firmware Version 16 D 0 0
OBIT Output percentage 16 D 0 0
CV CT Current Value 16 D 0 0
PV Process Value 16 D 0 0
Note: For more detailed information please refer to the PLC manual.
197
Connecting PLC to HMI
198
*Looking into HMI
PIN# COM2 (RS485)
1 DATA+
2
3
4
5 GND
6 DATA-
7
8
9
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 Port PLC RS485 Port
6 DATA+ 12 DATA+
7 DATA- 11 DATA-
199
3 ISO_GND GND
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 Port PLC RS485 Port
1 DATA+ 12 DATA+
6 DATA- 11 DATA-
5 GND GND
200
2.9 Delta
DVP Series
2.9.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232C
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 0
Communication Method MODBUS ASCII
201
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Delta Electronics, Inc
Under Product Series select DVP Series
Make sure the other parameters are set at the values in the figure.
202
5 GND
6
7 RTS
8 CTS
9
203
AH500 Series
2.9.2.1 Communication Setting
Item Default Setting Remark
Signal Level RS232C
Baud Rate 9600
Data Length 7
Stop Bit 1
Parity Even
PLC Station No. 1
Communication Method MODBUS ASCII
204
Relay
S Stepping Relay 1 DDDD 0 2047
T Timer 1 DDDD 0 2047
TV Timer memory 16 DDDD 0 2047
C Counter 1 DDDD 0 2047
CV Counter memory 16 DDDD 0 2047
HC 32-bit Counter 1 DD 0 63
HCV 32-bit Counter 32 DD 0 63
memory
SR Special data register 16 DDDD 0 2047
E Index register 16 DD 0 31
205
In ISPSoft, under the Tools menu option, select Communication Settings. Select the
name of the connection configured in COMMGR and press OK.
Under the PLC menu option, select Transfer and Upload. If there is a program on the
PLC, it will be uploaded and the system settings can be configured. If there is no
program present on the PLC one will have to be downloaded.
206
If program has to be downloaded onto the PLC, press open and select a program. In
the active folder, there are example programs. The device associated with the example
program may not be the same as the device connected. Under Tools, select PLC Type
and select the device currently used. Once a program is opened, the PLC settings can
be configured.
In the Project sidebar, double click HWCONFIG. Double click the CPU module and
navigate to the COM Port tab in the settings dialog. Adjust communication parameters
and press OK to confirm the settings.
207
Under the PLC menu option, the program and PLC configurations can be downloaded
onto the device.
Note: For more detailed information please refer to the PLC manual.
208
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Delta Electronics, Inc
Under Product Series select Delta AH500 Series
Select the appropriate Port to establish connection with the PLC.
Verify the other parameters are configured correctly.
209
4
5 GND
6
7 RTS
8 CTS
9
210
2.10 Panasonic
FP Series
2.10.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232C
Baud Rate 9600
Data Length 8
Stop Bit 1
Parity Odd
PLC Station No. 1
Communication Method MEWTOCOL
(computer link)
Go to the Tool Port option in the sidebar and select Read PLC to see the current PLC
settings. Change the settings needed to be changed and press OK.
Navigate to the File menu option and select Download to PLC to save the settings to
the PLC.
212
Note: For more detailed information please refer to the PLC manual.
213
2.10.1.4 Wiring Diagrams
PLC RS232 Pinout
FP Series (Ethernet)
2.10.2.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet With AFPX-
COM5
Internet Protocol 192.168.1.100
Port 9094
PLC Station No. 1
Communication Method MEWTOCOL (computer
link)
215
C Counter 1 DDDD 0 3071
WX External input relay 16 DDD 0 511
WY External output relay 16 DDD 0 511
WR Internal relay 16 DDD 0 886
WL Link Relay 16 DDD 0 639
DT Data register 16 DDDDD 0 99999
LD Link data register 16 DDDD 0 8447
SV Timer/Counter set 16 DDDD 0 3071
value area
EV Timer/Counter 16 DDDD 0 3071
elapsed value area
FL File register 16 DDDDD 0 99999
Right click the PLC and press Communication Setting to change the port if necessary.
Note: For more detailed information please refer to the PLC manual.
216
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Panasonic Corporation
Under Product Series select FP Series(Ethernet)
Enter the IP Address that was written into the PLC.
Enter the Port number that was set on the PLC.
2.11 YASKAWA
Extended MEMOBUS
2.11.1.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.1.1
Port 502
PLC Station No. 1
Communication Method Extended MEMOBUS
217
2.11.1.2 Memory Resource Review
Device Description Data Input Min. Max.
bit format
IB Input bits(Read only) 1 HHHHH 0 FFFFF
MB Data bits 1 DDDDDH 0 65534F
IW Input registers(Read 16 HHHH 0 FFFF
only)
MW Data registers 16 DDDDD 0 65534
IL Input registers 32 HHHH 0 FFFF
(DWord / Read only)
ML Data registers 32 DDDDD 0 65533
(Dword)
IF Input registers (Float 32 HHHH 0 FFFF
/ Read only)
MF Data registers(Float) 32 DDDDD 0 65533
218
Double click 218IFA, or chick 218IFA then chick Edit-Setting
Note: For more detailed information please refer to the PLC manual.
220
Device Description Data Input Min. Max.
bit format
SB System bits 1 DDDDH 0 8191F
MB Data bits 1 DDDDDH 0 65534F
IB Input bits 1 HHHHH 0 FFFFF
OB Output bits 1 HHHHH 0 FFFFF
SW System registers 16 DDDD 0 8191
MW Data registers 16 DDDDD 0 65534
IW Input registers 16 HHHH 0 FFFF
OW Output registers 16 HHHH 0 FFFF
ML Data registers(Dword) 32 DDDDD 0 65533
221
the IP address and other parameters can be set.
Note: For more detailed information please refer to the PLC manual.
222
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select YASKAWA Electric Corporation.
Under Product Series select MP Series Extension (Ethernet).
Enter the IP Address that was written into the PLC.
Verify the parameters match the window above.
2.12 Keyence
KV-3000/5000/5500/7500(Ethernet)
2.12.1.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 0.0.0.0
Port 8501
PLC Station No. 0
Communication Method HOST-LINK
223
COMMUNICATION
Under the Monitor/Simulator menu option, select Read from PLC and execute the
operation.
In the Workspace, right click the PLC model name and select Unit Editor.
225
On the right side of the dialog window, the IP address and Port can be changed. When
done, close out of the window and select ‘Yes’ to save the settings.
Under Monitor/Simulator, select Transfer to PLC to download the changes onto the
PLC. Confirm the execution of the operation
226
Note: For more detailed information please refer to the PLC manual.
227
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select Keyence Corporation
Under Product Series select KV-3000/5000/5500/7500(Ethernet)
Set the IP address and Port to the values configured on the PLC.
228
2.12.2.2 Memory Resource Review
Device Description Data Input Min. Max.
bit format
R Relay 1 DDDdd 0 99915
B Link relay 1 HHHH 0 7FFF
MR Internal auxiliary 1 DDDDdd 0 399915
relay
LR Latch relay 1 DDDdd 0 99915
T Timer 1 DDDD 0 3999
C Counter 1 DDDD 0 3999
CTC_sts High-speed counter 1 D 0 7
comparator
(contact)
CR Control relay 1 DDdd 0 7915
VB Work relay 1 HHHH 0 F9FF
DM Data memory 16 DDDDD 0 65534
EM Extended data 16 DDDDD 0 65534
memory
FM File register 16 DDDDD 0 32767
ZF File register 16 DDDDDD 0 524287
W Link register 16 HHHH 0 7FFFF
TM Temporary data 16 DDD 0 511
memory
CM Control memory 16 DDDD 0 5999
VM Work memory 16 DDDDD 0 50999
Z Index register 32 D 1 12
TC Timer (current 32 DDDD 0 3999
value)
TS Timer (set value) 32 DDDD 0 3999
CC Counter (current 32 DDDD 0 3999
value)
CS Counter (set value) 32 DDDD 0 3999
CTH High-speed counter 32 D 0 3
(current value)
CTC High-speed counter 32 D 0 7
comparator (set
229
value)
TRM Digital trimmer 32 D 0 7
Under the Monitor/Simulator menu option, select Read from PLC and execute the
operation.
In the Workspace, right click the PLC model name and select Unit Editor.
230
On the right side of the dialog window, verify the baud rate is 115200bps. Close out of
the window and select ‘Yes’ to save the settings.
Under Monitor/Simulator, select Transfer to PLC to download the changes onto the
PLC. Confirm the execution of the operation
231
Note: Port 2 of the PLC can also be configured following the steps above. The
parameters for Port 2 are under the parameters for Port 1 in the dialog window.
Note: For more detailed information please refer to the PLC manual.
232
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Keyence Corporation
Under Product Series select KV-L21V/3000/5000/5500(host link)
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
233
3 TXD
4
5 GND
6
7
8
9
234
Using Port 2
HMI COM3 Pinout
235
RDA(-) RDB(+)
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS485 Port
5 RX- 3 SDA(-)
4 RX+ 5 SDB(+)
7 TX- 2 RDA(-)
6 TX+ 4 RDA(+)
3 ISO_GND 1 SG
Wiring Diagrams:P5070S/P5070N/P5070N1/P5102N/P5102N1
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS485 Port
9 RX- 3 SDA(-)
4 RX+ 5 SDB(+)
6 TX- 2 RDA(-)
1 TX+ 4 RDA(+)
5 GND 1 SG
236
KV-Nano (host link)
2.12.3.1 Communication Setting
Item Default Setting Remark
Signal Level RS232C OP-26486
Baud Rate 115200
Data Length 8
Stop Bit 1
Parity Even
PLC Station No. 0
Communication Method HOST-LINK
COMMUNICATION
237
T Timer 1 DDDD 0 511
C Counter 1 DDDD 0 255
CTC_sts High-speed counter 1 D 0 7
comparator
(contact)
CR Control relay 1 DDdd 0 8915
VB Work relay 1 HHHH 0 1FFF
DM Data memory 16 DDDDD 0 32767
W Link register 16 HHHH 0 3FFF
TM Temporary data 16 DDD 0 511
memory
CM Control memory 16 DDDD 0 8999
VM Work memory 16 DDDDD 0 9999
Z Index register 32 D 1 12
TC Timer (current 32 DDDD 0 511
value)
TS Timer (set value) 32 DDDD 0 511
CC Counter (current 32 DDDD 0 255
value)
CS Counter (set value) 32 DDDD 0 255
CTH High-speed counter 32 D 0 3
(current value)
CTC High-speed counter 32 D 0 7
comparator (set
value)
238
Choose KV mode (Host Link) and set the Baud rate to 115200.
Download the settings back onto the PLC and reset it.
239
Note: For more detailed information please refer to the PLC manual.
240
2.12.3.4 Wiring Diagrams
Port 1: RS232
HMI PLC
Serial COM1 RS-232 RS232
Interface 9 pin D-SUB Female 6 pin
241
IP 192.168.1.100
Port 801
PLC Station No. 1
Communication Method ADS
Open TwinCAT system manager build Route Table to ensure whether connecting
success, if reopen plc, need to execute these steps.
Note: when connecting success, display’’x’’
242
2. Use CERHOST to connect with plc, enter IP and Password of plc.
243
Click Network and Dial-up Connections, display information of plc, click plc to ensure
the IP.
Note: For more detailed information please refer to the PLC manual.
244
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select FATEK Automation Corp.
Under Product Series select FATEK FBe
Under Port select the port corresponding to the connection to the PLC
Verify the other parameters are consistent with the settings on the PLC
2.14 Koyo
Direct
2.14.1.1 Communication Setting
245
Stop Bit 1
Parity Odd or even, no
PLC Station No. 1 1-90 DirectNET, K
sequence
1-247 Modbus RTU
Communication Method K sequence (slave),
DirectNET
(master/slave),
Modbus
246
2. choose model and build project.
247
connect success, as shown below.
HMI Setting
248
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Koyo Corporation
Under Product Series select Koyo Direct
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
249
PIN# Signal
1 GND
2 Power+ 5V
3 Rx (RS-232C)
4 Tx (RS-232C)
5 Power+ 5V
6 GND
250
2 RX 4 Tx (RS-232C)
3 TX 3 Rx (RS-232C)
5 GND 1 GND
251
2.15 Yudian
AI
2.15.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232/RS485
Baud Rate 9600 or 4800,19200
Data Length 8
Stop Bit 1
Parity NONE
PLC Station No. 0
Communication Method Yudian Communication
Protocol
HMI Setting
252
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Yudian Automation Technoloqy Co, Ltd.
Under Product Series select Yudian AI Series
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
PIN# Signal
21
22 A
23
24 B
HMI COM3 腳位
253
*Looking into HMI Device
PIN# COM3
(RS-422/RS-485)
1
2
3 ISO_GND
4
5
6 DATA+
7 DATA-
P5070S/P5070N/P5070N1/P5102N/P5102N1
HMI COM3 PLC RS485 Port
6 DTAT+ 22 A
7 DATA- 24 B
Wiring Diagrams:P5070S/P5070N/P5070N1/P5102N/P5102N1
P5043S/P5043N/P5070VS/P5102VS/P2K SERIES
HMI COM2 PLC RS485 Port
1 DATA+ 22 A
254
6 DATA- 24 B
2.16 Xinje
2.16.1 XC series
2.16.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity NONE
PLC Station No. 0
Communication Method HOST-LINK
COMMUNICATION
HMI Setting
256
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Xinje
Under Product Series select XinjeXC Series
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
258
2.16.2 XD series
2.16.2.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity NONE
PLC Station No. 0
Communication Method HOST-LINK
COMMUNICATION
260
HMI Setting
261
2.16.2.4 Wiring Diagrams
HMI COM1 Pinout
262
HMI COM1 PLC RS232 Port
2 RX 7 TXD
3 TX 4 RXD
5 GND 2 GND
2.17 Vigor
2.17.1 M/VB/VH Series
263
Devic Data bit Data format Min. Min. Description
e
X 1 OOO 0 777 External input relay
Y 1 OOO 0 777 External output relay
M 1 DDDD 0 7999 Internal relay
S 1 DDD 0 999 Step relay
SM 1 DDDD 9000 9255 Special relay
TC 1 DDD 0 255 Timer coil
CC 1 DDD 0 255 Counter coil
TS 1 DDD 0 255 Timer contact
CS 1 DDD 0 255 Counter contact
D 16 DDDD 0 8999 D data register
SD 16 DDD 9000 9255 Special data resgister
T 16 DDD 0 255 Timer
C 16 DDD 0 199 16 bits counter
CL 16 DDD 200 255 32 bits counter
2.17.1.3 Connecting to HMI
PLC Setting
Open Ladder Master and use the Vigor VBUSB-200 cable to connect to the
computer USB port, it will automatically connect.
HMI Setting
264
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Vigor Corporation
Under Product Series select VS Series
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
265
4
5 GND
6
7
8
9
PIN# Signal
1
2 D-
3 D+
4 GND
266
2.17.2 VS series
2.17.2.1 Communication Setting
Item Default Setting Remark
Signal Level RS232
Baud Rate 19200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 0
Communication Method HOST-LINK
COMMUNICATION
267
DB 1 DDDD.H 0.0 8999.f D data register bits
RB 1 DDDDD.H 0.0 25999.f R data register bits
TC 1 DDD 0 511 Timer coil
CC 1 DDD 0 255 Counter coil
TS 1 DDD 0 511 Timer contact
CS 1 DDD 0 255 Counter contact
D 16 DDDD 0 8999 D data register
SD 16 DDD 9000 9511 Special data resgister
R 16 DDDDD 0 25999 R data resgister
T 16 DDD 0 511 Timer
C 16 DDD 0 199 16 bits counter
WX 16 OOO 0 377 External input relay
WY 16 OOO 0 377 External output relay
WM 16 DDDD 0 8191 Internal relay
WS 16 DDDD 0 4095 Step relay
CL 32 DDD 200 255 32 bits counter
268
HMI Setting
269
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select Vigor Corporation
Under Product Series select VS Series
Under Port select required COM port. Verify the baud rate is the same as the value set
on the PLC.
Signal
D-
D+
270
*Looking into COM3 Port
PIN# COM3
(RS-485)
1 DATA+
2
3
4
5 GND
6 DATA-
7
8
9
P5043S/P5043N/P5070VS/P5102VS/P2K
HMI COM3 PLC RS485 Port
1 DATA+ D+
6 DATA- D-
6 DATA+ DATA+
7 DATA- DATA-
Wiring Diagrams:P5043S/P5043N/P5070VS/P5102VS/P2K
2.18 LS
272
2.18.1 LS XBC-cnet
2.18.1.1 Communication Setting
Item Default Setting Remark
Signal Level RS-232/RS-485
Baud Rate 115200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 0
Communication method Serial
CX 0-2047 0-1023
UX 0-3F.31F 0-A.31F
SX 0-12799 0-12799
L 0-4095 0-2047F
D 0-32767 0-10239
R 0-32767 0-2047
PW 0-2047 0-1023
MW 0-2047 0-1023
KW 0-2559 0-2559
FW 0-2047 0-1023
TW 0-2047 0-1023
W CW 0-2047 0-1023
UW 0-3F.31 0-A.31
SW 0-12799 0-12799
ZW 0-127 0-127
LW 0-4095 0-2047F
DW 0-32767 0-10239
273
RW 0-32767 0-10239
HMI setting
274
XBC-Cnet Pinout
XBC-Cnet RS232Pinout XBC-Cnet RS485 Pinout
RS-232 RS-485
SG DATA+(485+)
TX DATA- (485-)
RX
2.18.2 LS XEC-Cnet
2.18.2.1 Communication Setting
Item Default Setting Remark
Signal Level RS-232/RS-485
Baud Rate 115200
Data Length 8
Stop Bit 1
Parity None
PLC Station No. 0
Communication method Serial
276
2.18.2.2 Memory Resource Review
Bit/
Device Type Range XEC
Word
IX 0.0.0-15.15.63 0.0.0-15.15.63
QX 0.0.0-15.15.63 0.0.0-15.15.63
B
MX 0-262143 0-262143
LX 0-65535 0-65535
NX 0-163839 0-163839
KX 0-131071 0-131071
UX 0.0-11.511 0.0-11.511
RX 0-262143 0-262143
AX 0-524287 0-524287
WX 0-524287 0-524287
FX 0-32767 0-32767
I 0.0.0-15.15.3 0.0.0-15.15.3
QW 0.0.0-15.15.3 0.0.0-15.15.3
MW 0-16383 0-16383
LW 0-4095 0-4095
NW 0-10239 0-10239
W KW 0-8191 0-8191
UW 0.0-11.31 0.0-11.31
RW 0-16383 0-16383
AW 0-32767 0-32767
WW 0-32767 0-32767
FW 0-2047 0-2047
HMI setting
277
Within the Link configuration window in FvDesigner:
Under Interface Type select Serial
Under Manufacturer select LS Corporation
Under Product Series select LS XBC cnet
Under Port select COM1
2.18.2.4Wiring Diagrams
278
XBC-Cnet Pinout
RS-232 RS-485
SG D- (485-)
TX D+(485+)
RX
279
3 TX
4
5 GND
6
7 RTS
8 CTS
9
2.18.3 LS XBC-Fnet
2.18.3.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.0.61
Port 2004
PLC Station No. 1
Communication Method TCP
280
2.18.3.2 Memory Resource Review
類型 資料位元 地址格式 最小 最大 說明
PW 16 DDDD 0 2047 I/O relay
MW 16 DDDD 0 2047 Auxiliary relay
LW 16 DDDDD 0 4095 Link relay
KW 16 DDDD 0 2559 Keep relay
FW 16 DDDD 0 2047 Special relay
CW 16 DDDD 0 2047 Counter
TW 16 DDDD 0 2047 Timer
SW 16 DDD 0 12799 Step controller
DW 16 DDDDD 0 32767 Data register
UW 16 DH.DD 0 3F.31 Analog data register
RW 16 DDDDD 0 32767 File register
ZW 16 DDD 0 127 Index register
PX 1 DDDDH 0 2047F Auxiliary relay
MX 1 DDDDH 0 2047F Auxiliary relay
LX 1 DDDDDH 0 4095 Link relay
KX 1 DDDDH 0 2559F Keep relay
FX 1 DDDDH 0 2047F Special relay
DX 1 DDDDDH 0 32767 Data register
UX 1 DH.DD 0 3F.31F Analog data register
RX 1 DDDDDH 0 32767 File register
SX 1 DDDDD 0 12799 Step controller
TX 1 DDDD 0 2047 Timer
CX 1 DDDD 0 2047 Counter
PLC setting
Open XG5000.exe and use mini-USB to connect the USB port of the computer, it will
connect automatically.
281
HMI setting
282
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select LS Corporation
Under Product Series select LS XBC fnet
Please confirm that the HMI communication setting and the PLC setting are consistent
2.18.4 LS XEC-Fnet
2.18.4.1 Communication Setting
Item Default Setting Remark
Signal Level Ethernet
Internet Protocol 192.168.0.6
Port 2004
PLC Station No. 1
Communication Method TCP
283
2.18.4.2 Memory Resource Review
Bit/
Device Type Range XEC
Word
IX 0.0.0-15.15.63 0.0.0-15.15.63
QX 0.0.0-15.15.63 0.0.0-15.15.63
B
MX 0-262143 0-262143
LX 0-65535 0-65535
NX 0-163839 0-163839
KX 0-131071 0-131071
UX 0.0-11.511 0.0-11.511
RX 0-262143 0-262143
AX 0-524287 0-524287
WX 0-524287 0-524287
FX 0-32767 0-32767
I 0.0.0-15.15.3 0.0.0-15.15.3
QW 0.0.0-15.15.3 0.0.0-15.15.3
MW 0-16383 0-16383
LW 0-4095 0-4095
NW 0-10239 0-10239
W KW 0-8191 0-8191
UW 0.0-11.31 0.0-11.31
RW 0-16383 0-16383
AW 0-32767 0-32767
WW 0-32767 0-32767
FW 0-2047 0-2047
PLC setting
Open XG5000.exe and use mini-USB to connect the USB port of the computer, it will
connect automatically.
284
HMI setting
285
Within the Link configuration window in FvDesigner:
Under Interface Type select Ethernet
Under Manufacturer select LS Corporation
Under Product Series select LS XEC fnet
Please confirm that the HMI communication setting and the PLC setting are consistent
286