EE18701 Unit-I Protection Schemes
EE18701 Unit-I Protection Schemes
PROTECTION AND
SWITCHGEAR
OBJECTIVES
• Realize the causes of abnormal operating conditions
of the power system.
• Understand the operating characteristics and
functions of electromagnetic, static and numerical
relays.
• Comprehend the schemes of apparatus protection.
• Design and selection of circuit breakers
SYLLABUS
SYLLABUS
OUTCOMES
• Interpret the faults in power system and essential qualities of
protection.
• Understand the operation of various electromagnetic relays.
• Analyze the protection schemes for power system apparatus.
• Synthesize various relays using static comparators and
microcontroller.
• Analyze the circuit breaker arcing phenomenon and
understand the functioning of various types of circuit breakers
TEXT AND REFERENCE BOOKS
UNIT I
PROTECTION SCHEMES
Principles and need for protective schemes – nature and
causes of faults – types of faults – fault current
calculation using symmetrical components – Methods of
Neutral grounding – Zones of protection and essential
qualities of protection – Protection schemes for
distributed generation – Micro grid protection - IEEE
standards for power system protection.
INTRODUCTION
• Switching device: opening/closing and protective device: over-
current protection
• What is “Switchgear”?
• For all types of faults the sequence network equations will be the
same but the 3 equations describing the boundary conditions will
be different for different types of faults
• Sequence Networks of Transmission lines
• Sequence Networks of Loads
• Sequence Networks of Transformers
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Single Line to Ground Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
A 25 MVA, 13.2 KV alternator with solidly grounded neutral has a
sub-transient reactance of 0.25 p.u. The negative and zero
sequence reactances are 0.35 and 0.1 p.u. respectively. A
SLG/LL/LLG fault occurs at the terminals of an unloaded
alternator; determine the fault current and line-to-line voltages.
Neglect resistance.
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Let the line-to-neutral voltage at the fault point before the
fault be 1.0 + j0.0 p.u.
• For a line to-ground fault the fault impedance is
j0.25 + j0.35 + j0.1 = j0.7
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
-
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
• Now actual line-to-line voltages (magnitude: polar form)
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Line to Line Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Problem continued for Line-to-line fault:
• Solution: Since the zero sequence network is absent,
assuming (1 + j0.0) prefault per unit voltage,
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Double Line to Ground Fault
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Problem continued for Double Line-to-ground fault:
• Solution: Assuming (1 + j0.0) prefault per unit voltage,
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Three Phase Fault (Symmetrical Fault)
FAULT CURRENT CALCULATION USING
SYMMETRICAL COMPONENTS
Conclusion:
1. Positive sequence currents are present in ALL types of faults
2. Negative sequence currents are present in ALL
Unsymmetrical faults
3. Zero sequence currents are present when the neutral of the
system is grounded and the fault also involves ground, the
magnitude of neutral current is 3Ia0
POWER SYSTEM GROUNDING OR
EARTHING
• The process of connecting the metallic frame (non-current carrying
part) of electrical equipment or some electrical part of the system
(neutral point) to earth (soil) is called “Grounding” or “Earthing”
• Connection to earth may be through a conductor or some other
circuit elements (resistor, CB) depending upon the situation.
Advantages :
1. Protection to power systems
2. Ensures the safety of the persons handling the equipment
Grounding or earthing may be classified as
(i) Equipment grounding
(ii) System (Neutral) grounding
UNGROUNDED NEUTRAL SYSTEM
• It can be seen that 3 phase faults have a more effect on the system
and they must be cleared faster than the SLG fault
• Relays should not be made extremely fast (<10 msec), because
when there is any lightning surge on the line, surge diverters must
have sufficient time to discharge the lightning to ground, otherwise
the relay will operate unnecessarily for transient conditions
ESSENTIAL QUALITIES OF PROTECTION
6. Discrimination: A relay should be able to distinguish
between a fault and an overload.
• In case of transformers inrush of magnetizing current (5 to 7
times full load current) may be comparable to fault current.
The relay should not operate for inrush currents.
• In interconnected systems, there will be power swings, which
should also be ignored by the relay.
• The discrimination may either be an inherent characteristic of
relay or may be achieved by connecting auxiliary devices
(minimum voltage relay).
• It may be noted that the word ‘discrimination’ is sometimes
used to include ‘selectivity’
PROTECTION SCHEMES
• Protective scheme comprises set of ‘protective
systems’ and the protection schemes are named
according to the protected equipment. For example,
– Generator protection (scheme)
– Transformer protection (scheme)
– Motor protection (scheme)
– Bus bar protection (scheme)
• The term ‘protective system’ or simply ‘protection’ is
also named according to the principle of operation
or abnormal condition
PROTECTION SCHEMES
• Names based on abnormal condition:
– Over-current protection
– Earth-fault protection
– Reverse-power protection
– Under-voltage protection
– Under-frequency protection
• Names based on principle of operation:
– Differential protection
– Distance protection
– Power line carrier protection
PROTECTION SCHEMES
• A protective scheme includes one or more relays of the same
or different types. The following are the most common
schemes.
1. Over current protection: An O/C relay may operate when
the current increases above a certain magnitude. It is used
for protection of distribution lines, motors, equipments, etc.
2. Distance protection: A distance relay measures the distance
between the relay location and point of fault in terms of
impedance, reactance, etc. and operates if the point of fault
lies within the protected section of the line.
– It is used for the protection of transmission or sub-transmission lines;
usually 33 KV, 66 KV and 132 KV lines. The important types are:
– Impedance, Reactance and Mho type relays
PROTECTION SCHEMES
3. Carrier-current protection: Relay operates depending on the
information available in generated carrier signal (50-500 kHz).
• A transmitter and receiver are installed at each end of a
transmission line to be protected. Information regarding the
direction of fault current is transmitted from one end of the line
section to the other.
• Depending on the information, relays placed at each end trip if the
fault lies within their protected section. Relays do not trip in case
of external faults.
• Relays are of distance type and their tripping operation is
controlled by ‘carrier signal’.
• Used for protection of EHV and UHV lines (132 KV and above)
PROTECTION SCHEMES
4. Differential protection: Relay operates by comparing the current
entering and leaving a machine.
• Used for protection of generators, transformers, motors of very
large size, bus zones, etc.
• CTs are placed on both sides of each winding of a machine. The
outputs of their secondaries are applied to the relay coils
(compares current entering and leaving the machine winding )
• Under normal conditions or during external fault, the current
entering the winding is equal to the current leaving the winding.
• In case of an internal fault on the winding, these are not equal.
This difference in the current actuates the relay
Protection Schemes for Distributed
Generation
• Due to the increasing demand of energy and the need for Renewable
energy sources, Distributed Generation (DG) has come into play.
• The International Energy Agency (IEA) and the IEEE classify any source
which is connected to the distribution level and which delivers power
to the load as DG.
• DG should not be confused with renewable energy because the DG
may include renewable technologies, non-renewable technologies,
or a combination of both.
• However, the introduction of DG poses some serious problems for the
electrical power network.
• The power network has been inherently radial. Introduction of DG
makes it bidirectional as power can flow from DG as well as the main
utility grid.
Protection Schemes for Distributed
Generation
• This poses various problems regarding system voltage profile,
power quality, security, power flow control, energy
management and frequency control, system protection and
lower fault current contribution from inverter interfaced DGs.
• Recent research study has highlighted the negative effects of
DG units on short circuit currents and overcurrent (OC)
protection systems in distribution networks.
• Change in the direction of fault current flow, increase or
decrease of fault current magnitude, and the blindness of
protection are some of the possible impacts of DG unit
integration.
Protection Schemes for Distributed
Generation
Effect of DG units on fault current
• Integration of DG units should be taken into account in the
fault current calculation as these conditions certainly impact
the fault current level.
• The contribution of a DG unit to a fault current is related to
the type of DG unit [synchronous generators, induction
generators and inverter-based units].
• However, the response of each type to a fault and its
contribution to the fault current varies.
Protection Schemes for Distributed
Generation
Effect of DG units on protection systems
• Any changes in the fault current level at any point within the power
system would affect the operation of Protective Devices.
• The negative impacts that the integration of DG units would have
on Protective Devices can be classified as follows:
– Reverse power flow.
– False tripping.
– Blinding of protection.
– Unwanted islanding.
– Unsynchronised reclosing.
– Loss of main power.
Protection Schemes for Distributed
Generation
Protection systems in distribution networks with DG units
• Many attempts have been made to mitigate the impact of DG units
on the power systems to which they are connected.
• Some solutions consider protection system reformation while a few
of the others take the capacity and the characteristics of DG units
into account.
• The suggested methods can be classified as follows
1. Disconnection of DG units
2. Recalculation and/or resizing of protective devices
3. Directional protection
4. Application of fault current limiter
5. Limiting DG size
Protection Schemes for Distributed
Generation
6. Inverter control methods for inverter-based DG units
7. Adaptive protection [online modification of protective
settings to address changes in the network by means of
external control signals]
8. Multiagent-based method
9. Application of distance protection
10. Application of differential protection
11. Voltage-dependent OC protection
12. Network matrix algorithm
13. Artificial neural network (ANN) and optimization method
14. Other methods
Micro-Grid Protection
• The International Council on Large Electric Systems (CIGRE)
defines micro grid as, Microgrids are electricity distribution
systems containing loads and distributed energy resources, (such
as distributed generators, storage devices, or controllable loads)
that can be operated in a controlled, coordinated way either while
connected to the main power network or while islanded.
• Micro grids are miniature version of conventional large power
grids functioning either autonomously (island-mode) or with
inter connection to the main grid (grid-connected mode).
• A microgrid is a self-sufficient energy system that serves a
discrete geographic footprint
• Primary function of micro grid is to serve power at distribution
level, such as a college campus, hospital complex, business center,
or neighborhood.
Micro-Grid Protection
• Distributed Energy Resources (DERs) connected to the micro grid
enables reliable and efficient operation of micro grid.
• Protection of micro grids assumed importance due to increased
penetration of DERs.
• Most of the distribution systems in earlier days are radial in
nature and protection systems are designed for that.
• These protection systems pose serious challenges when applied
to present day distribution systems which are mesh connected
and fed by the DERs (intermediate current injection-bidirectional)
• Hence the protection of micro grid systems with DERs require
different approach to ensure faults are cleared in less time.
• A typical CIGRE benchmark LV micro grid is shown in Fig. 1
Micro-Grid Protection