IPD96D1 Relay - Software Versions (1.

22)

IPR96D1 - MODBUS MEMORY MAP


MODBUS
Initial Associated Read/
Add (Hex) REG. ADD Size Description Unit Min Step 1 Level 1 Step 2 Level 2 Step 3 Max Format
Value Command Write
(Dec)
0000 300001 1W Product Code --- --- --- --- --- --- --- --- 72 2 R
0001 300002 1W Product Model --- --- --- --- --- --- --- --- 1 2 R
0002 300003 1W Version Number --- --- --- --- --- --- --- --- 1,22 6 R
0003 300004 1W Product Language --- --- --- --- --- --- --- --- 1 2 R
0004 300005 124 W Reserved
0080 400129 1W Command Operation Code --- --- --- --- --- --- --- --- --- 1200 W
0081 400130 1W Command Password --- --- --- --- --- --- --- --- --- 2 W
0082 300131 14 W Reserved
0090 400145 2W Date & Time Preset Data --- --- --- --- --- --- --- --- --- 6408 5 R/W
0092 400147 10 W Reserved
009C 400157 1W Access Code Preset --- 1111 1 --- --- --- --- 9999 --- 10 13 R/W
009D 400158 32 W Reserved ---
00BD 400190 8W BLE Device Name Preset --- --- --- --- --- --- --- --- --- 6410 4 R/W
00C5 400198 59 W Reserved
0100 400257 1W Display Contrast --- 1 1 --- --- --- --- 10 5 2 R/W
0101 400258 1W Display Brightness --- 0 1 --- --- --- --- 10 5 2 R/W
0102 400259 1W System Frequency Hz 0 1 --- --- --- --- 1 0 6401 R/W
0103 400260 1W Ground CT Primary A 5 5 --- --- --- --- 5000 50 2 R/W
0104 400261 1W Command --- 0 1 --- --- --- --- 3 1 7041 R/W
0105 400262 1W Out Of Service Relay --- 0 1 --- --- --- --- 1 0 7012 R/W
0106 400263 1W Reserved
0107 400264 1W Max Switching Current Config --- 0 1 --- --- --- --- 1 1 6407 R/W
0108 400265 1W Max Switching Current A 50 10 --- --- --- --- 5000 400 2 R/W
0109 400266 13 W Reserved
0116 400279 1W Trip Relay Mode --- 0 1 --- --- --- --- 1 0 902 R/W
0117 400280 1W Aux1 Relay Mode --- 0 1 --- --- --- --- 1 0 902 R/W
0118 400281 1W Aux2 Relay Mode --- 0 1 --- --- --- --- 1 0 902 R/W
0119 400282 6W Reserved
011F 400288 1W Trip Relay Pulse Time ms 100 100 --- --- --- --- 2000 200 2 R/W
0120 400289 1W Aux1 Relay Pulse Time ms 100 100 --- --- --- --- 2000 200 2 R/W
0121 400290 1W Aux2 Relay Pulse Time ms 100 100 --- --- --- --- 2000 200 2 R/W
0122 400291 10 W Reserved
012C 400301 1W Digital Input 1 Function --- 0 1 --- --- --- --- 5 2 1230 R/W
012D 400302 1W Digital Input 2 Function --- 0 1 --- --- --- --- 5 1 1230 R/W
012E 400303 13 W Reserved
013B 400316 1W Ground Timed OverCurrent1 Relays --- 0 1 --- --- --- --- 7 0 1216 R/W
013C 400317 1W Ground Timed OverCurrent1 Pickup % 1 1 --- --- --- --- 300 12 2 R/W
013D 400318 1W Ground Timed OverCurrent1 Curve --- 0 1 --- --- --- --- 12 1 6016 R/W
013E 400319 1W Ground Timed OverCurrent1 Curve Multiplier --- 0.1 0.1 --- --- --- --- 20.0 1 4 R/W
013F 400320 1W Ground Timed OverCurrent1 Delay s 0,1 0.01 1 0.1 100 1 600 1 6 R/W
0140 400321 20 W Reserved
0154 400341 1W Ground Timed OverCurrent2 Relays --- 0 1 --- --- --- --- 7 0 1216 R/W
0155 400342 1W Ground Timed OverCurrent2 Pickup % 1 1 --- --- --- --- 300 12 2 R/W
0156 400343 1W Ground Timed OverCurrent2 Curve --- 0 1 --- --- --- --- 12 1 6016 R/W
0157 400344 1W Ground Timed OverCurrent2 Curve Multiplier --- 0.1 0.1 --- --- --- --- 20.0 1 4 R/W
0158 400345 1W Ground Timed OverCurrent2 Delay s 0,1 0.01 1 0.1 100 1 600 1 6 R/W
0159 400346 20 W Reserved
016D 400366 1W Ground Inst. OverCurrent Relays --- 0 1 --- --- --- --- 7 0 1216 R/W
016E 400367 1W Ground Inst. OverCurrent Pickup %CT 1 1 10 10 --- --- 2000 120 2 R/W
016F 400368 1W Ground Inst. OverCurrent Delay ms 0 10 --- --- --- --- 2000 0 2 R/W
0170 400369 20 W Reserved
0184 400389 1W Breaker Failure Relays --- 0 1 --- --- --- --- 7 0 1216 R/W
0185 400390 1W Breaker Failure Delay ms 10 10 --- --- --- --- 2500 1000 2 R/W
0186 400391 5W Reserved
018B 400396 1W Mechanical Operations Relays --- 0 1 --- --- --- --- 7 0 1216 R/W
018C 400397 1W Mechanical Operations Maximum --- 5 5 --- --- --- --- 9995 3000 2 R/W
018D 400398 10 W Reserved
0197 400408 1W System Events Config --- 0 1 --- --- --- --- 1 1 6407 R/W
0198 400409 1W Output Events Config --- 0 1 --- --- --- --- 1 1 6407 R/W
0199 400410 1W Digital Input Events Config --- 0 1 --- --- --- --- 1 1 6407 R/W
019A 400411 1W Gnd Current Protec. Events Config --- 0 1 --- --- --- --- 1 1 6407 R/W
019B 400412 5W Reserved
01A0 400417 1W Slave Address --- 1 1 --- --- --- --- 247 1 2 R/W
01A1 400418 1W Com (RS-485) Baud Rate --- 3 1 --- --- --- --- 7 3 6409 R/W
01A2 400419 1W Com (RS-485) Configuration --- 2 1 --- --- --- --- 7 2 6414 R/W
01A3 300420 10 W Reserved
01AD 300430 8W BLE Device Name --- --- --- --- --- --- --- --- --- 6410 R
01B5 300438 331 W Reserved
0300 300769 2W IPR96D1 Date & Time --- --- --- --- --- --- --- --- --- 6408 R
0302 300771 1W Reserved
0303 300772 1W Output Relays Status --- --- --- --- --- --- --- --- --- 1211 R
0304 300773 1W Digital Input Status --- --- --- --- --- --- --- --- --- 6020 R
0305 300774 2W Pickup Flag --- --- --- --- --- --- --- --- --- 6022 R
0307 300776 2W Status Flag --- --- --- --- --- --- --- --- --- 6023 R
0309 300778 1W Led Status --- --- --- --- --- --- --- --- --- 6040 R
030A 300779 1W Button Status --- --- --- --- --- --- --- --- --- 6619 R
030B 300780 30 W Reserved
0329 300810 2W Ground RMS Current A 0,00 0,01 10 0,1 100 1 1000 --- 6 R
032B 300812 30 W Reserved
0349 300842 1W Last Trip Cause --- --- --- --- --- --- --- --- --- 1215 R
034A 300843 2W Last Trip Date & Time --- --- --- --- --- --- --- --- --- 6408 R
034C 300845 1W Last Trip Decimal Second --- --- --- --- --- --- --- --- 2 R
034D 300846 5W Reserved
0352 300851 2W Last Trip Ground RMS Current A 0,00 0,01 10 0,1 100 1 1000 --- 6 R
0354 300853 10 W Reserved
035E 300863 1W Trip Counter --- --- --- --- --- --- --- --- --- 2 R
035F 300864 1W Ground OC Counter --- --- --- --- --- --- --- --- --- 2 R
0360 300865 1W Opening Counter --- --- --- --- --- --- --- --- --- 2 R
0361 300866 671 W Reserved
0600 301537 1W Last Event Number --- --- --- --- --- --- --- --- --- 2 R
0601 301538 2W Last Event Date and Time --- --- --- --- --- --- --- --- --- 6408 R
0603 301540 1W Selected Event Number --- --- --- --- --- --- --- --- --- 2 R/W
0604 301541 1W Selected Event Type --- --- --- --- --- --- --- --- --- 1215 R
0605 301542 2W Selected Event Date and Time --- --- --- --- --- --- --- --- --- 6408 R
0607 301544 1W Selected Event Decimal Second --- --- --- --- --- --- --- --- --- 2 R
0608 301545 2W Selected Event Ground RMS Current A 0,00 0,01 10 0,1 100 1 1000 --- 6 R
IPR96D1 DATA FORMATS

Format
Type Value Definition
Code
F1 Integer Signed Integer Value
Example: -123 saved as -123

F2 Integer Unsigned Integer Value


Example: 123 saved as 123

F4 Integer Unsigned Integer Value with 1 decimals


Example: 1.0 saved as 10

F5 Integer Signed Integer Value with 2 decimals


Example: -1.00 saved as -100

F6 Integer Unsigned Integer Value with 2 decimals


Example: 1.00 saved as 100

F10 Integer Unsigned Integer Access Code Value Register Format


Example: 1111 saved as 1111 (only digits 1~9 accepted, digit 0 is NOT ALLOWED)
F902 Integer Relay Mode
0 LATCHED
1 PULSED
F1211 16 Bits BitMap Output Relays Status Register
Bit 0 Trip Output Relay { 0 = "De-energized" , 1 = "Energized" }
Bit 1 Aux1 Output Relay { 0 = "De-energized" , 1 = "Energized" }
Bit 2 Aux2 Output Relay { 0 = "De-energized" , 1 = "Energized" }
Bit 3 ~ Bit 15 Not Used
F1216 Integer Output Relays
0 ---
1 T--
2 -1-
3 T1-
4 --2
5 T-2
6 -12
7 T12
F1230 Integer Digital Input Function
0 NONE
1 BREAKER STATUS
2 EXTERNAL RESET
3 ACTIVATE AUX1
4 ACTIVATE AUX2
F6016 Integer Digital Protection Curve Definition Format Configuration Register Format
0 DefiniteTime
1 ANSI Moderate Inverse
2 ANSI Normal Inverse
3 ANSI Very Inverse
4 ANSI Extreme Inverse
5 IAC Moderate Inverse
6 IAC Normal Inverse
7 IAC Very Inverse
8 IAC Extreme Inverse
9 IEC Short Time
10 IEC A Normal Inverse
11 IEC B Very Inverse
12 IEC C Extreme Inverse
F6020 16 Bits BitMap IPR96D1 Digital Input Status
Bit 0 Digital Input 1{ 0 = "Deactivated" , 1 = "Activated" }
Bit 1 Digital Input 2{ 0 = "Deactivated" , 1 = "Activated" }
Bit 2 ~ Bit 15 Not Used
F6022 32 Bits BitMap IPR96D1 Pickup Flag Format
Bit 0 Gnd Instant Overcurrent
Bit 1 Gnd Timed1 Overcurrent
Bit 2 Gnd Timed2 Overcurrent
Bit 3 Breaker Failure
Bit 4 Mechanical Operation
Bit 5 ~ Bit 31 Not Used
F6023 32 Bits BitMap IPR96D1 Status Flag Format
Bit 0 Gnd Instant Overcurrent
Bit 1 Gnd Timed1 Overcurrent
Bit 2 Gnd Timed2 Overcurrent
Bit 3 Breaker Failure
Bit 4 Mechanical Operation
Bit 5 ~ Bit 12 Not Used
Bit 13 Setpoint Discrepancy
Bit 14 Flash Busy
Bit 15 ADC Failure
Bit 16 BLE Failure
Bit 17 RAM Failure
Bit 18 Check Events
Bit 19 Max Switching Current
Bit 20 Out of Service
Bit 21 ~ Bit 31 Not Used
F6040 16 Bits BitMap IPR96D1 Led Status
Bit 0 Status Led { 0 = "Off" , 1 = "On" }
Bit 1 Trip Led { 0 = "Off" , 1 = "On" }
Bit 2 ~ Bit 15 Not Used
F6401 Integer System Frequency
0 50 Hz
1 60 Hz
F6407 Integer Events Enable/Disable
0 Disable
1 Enable
F6408 Integer Unix Timestamp
This count starts at the Unix Epoch on January 1st, 1970 at UTC
F6409 String BaudRate Value
3 9600 Bps
4 19200 Bps
5 38400 Bps
6 57600 Bps
7 115200 Bps
F6410 String String
BLE Name Allowed characters: &()-./0123456789:ABCDEFGHIJKLMNOPQRSTUVWXYZ[\]_abcdefghijklmnopqrstuvwxyz
F6414 Integer RS Port Configuration
2 8N1 (8 bits Data, Parity NONE, 1 bit Stop)
3 8N2 (8 bits Data, Parity NONE, 2 bit Stop)
4 8E1 (8 bits Data, Parity EVEN, 1 bit Stop)
5 8E2 (8 bits Data, Parity EVEN, 2 bit Stop)
6 8O1 (8 bits Data, Parity ODD, 1 bit Stop)
7 8O2 (8 bits Data, Parity ODD, 1 bit Stop)
F6619 16 Bits BitMap Button Status
Bit 0 Down { 0 = "Not Pressed" , 1 = "Pressed" }
Bit 1 Up { 0 = "Not Pressed" , 1 = "Pressed" }
Bit 2 Function { 0 = "Not Pressed" , 1 = "Pressed" }
Bit 3 Enter { 0 = "Not Pressed" , 1 = "Pressed" }
Bit 4 Esc { 0 = "Not Pressed" , 1 = "Pressed" }
Bit 5 ~ Bit 15 Not Used
F7012 Integer IPR96D1 Out of Service Relay
0 NONE
1 AUX2
F7041 Integer Modbus Command
0 LOCAL
1 REMOTE 485
2 REMOTE BLE
3 REMOTE 485 + BLE
IPR96D1 COMMANDS
(F1200)
Command Label Password Preset data
0 No command no
1 Remote Reset Adv
4 Set BLE Name Adv x
5 Set Date and Time user x
9 Clear Events user
10 Operate Aux1 Adv
11 Operate Aux2 Adv
13 Set Access Code user x
29 Clear Maintenance Data Adv
IPR96D1 EVENTS
(F1215)
Category Event Code
NO_CATEGORY Events Clear 1
GND_CURRENT_PROT Gnd Inst Overcurrent 2
GND_CURRENT_PROT Gnd Timed1 Overcurrent 3
GND_CURRENT_PROT Gnd Timed2 Overcurrent 4
SYSTEM Breaker Failure 5
SYSTEM Mechanical Operation 6
DIGITAL_INPUT Digital Input 1 Deactive 7
DIGITAL_INPUT Digital Input 1 Active 8
DIGITAL_INPUT Digital Input 2 Deactive 9
DIGITAL_INPUT Digital Input 2 Active 10
DIGITAL_INPUT --- 11
DIGITAL_INPUT --- 12
DIGITAL_INPUT Breaker Status Opened 13
DIGITAL_INPUT Breaker Status Closed 14
DIGITAL_INPUT Remote Reset 15
DIGITAL_INPUT Remote Trip Set 16
OUTPUT_RELAY Trip De-Energized 17
OUTPUT_RELAY Aux1 De-Energized 18
OUTPUT_RELAY Aux2 De-Energized 19
OUTPUT_RELAY Trip Energized 20
OUTPUT_RELAY Aux1 Energized 21
OUTPUT_RELAY Aux2 Energized 22
OUTPUT_RELAY Trip Remote De-Energized 23
OUTPUT_RELAY Aux1 Remote De-Energized 24
OUTPUT_RELAY Aux2 Remote De-Energized 25
OUTPUT_RELAY Trip Remote Energized 26
OUTPUT_RELAY Aux1 Remote Energized 27
OUTPUT_RELAY Aux2 Remote Energized 28
SYSTEM Default Setpoint 29
SYSTEM Setpoint Stored 30
SYSTEM Setpoint Discrepancy 31
SYSTEM Password Changed 32
SYSTEM Model Changed 33
SYSTEM Test BLE 34
SYSTEM Trip Data Lost 35
SYSTEM Trip Data Restored 36
SYSTEM Calibration Time Data Lost 37
SYSTEM Calibration Data Lost 38
SYSTEM Power Loss 39
SYSTEM Aux Power Restored 40
SYSTEM Maintenance Data Cleared 41
SYSTEM Maintenance Data Lost 42
SYSTEM Maintenance Data Restored 43
SYSTEM Status Lost 44
SYSTEM BLE Failure 45
SYSTEM ADC Failure 46
SYSTEM Flash Busy 47
SYSTEM Out of Service 48
SYSTEM Max Switch Current 49