Vent
Vent
Introduction
Vents and
Venting
interpretation if an engineer is required to alter an side the building, which prevents the circulation of
existing project constructed under a previous code. air between the house sewer and the public sewer.
A fresh air inlet, based upon code requirements, is
1. BRANCH INTERVAL
often provided on the inlet side of the house trap
A branch interval is the distance, measured verti- and opens to the atmosphere at the nearest floor
cally along a stack, within which the horizontal above the house trap. There is no requirement to
drainage branches from one floor or story are have it terminate at the roof. A building (house)
connected to a drain or soil stack. This distance trap is illustrated in Figure 3-3.
is usually one story, but never less than 8 feet
(2.4 m). A branch interval is illustrated in Figure
3-1.
INDIVIDUAL
VENTS TO
FIXTURES
VENT STACK
Figure 3-2 Branch Vent
5. CIRCUIT AND LOOP VENT branch connection shall be taken off at a vertical
A circuit vent is a branch vent that serves at angle or from the top of the horizontal branch.
least two but not more than eight traps. The vent Figure 3-5 illustrates typical loop-vented and cir-
extends from in front of the last fixture on a drain- cuit vented arrangements. A circuit vent is similar
age line serving multiple fixtures and connects to to a loop vent except a circuit vent connects into
a vent stack. Fixtures that may be vented by this the vent stack.
means are water closets (except blowout type), 6. CONTINUOUS VENT
pedestal urinals, shower stalls, or floor drains
connected in a battery. A loop vent is a branch A continuous vent is a vertical vent that is a
vent serving two or more traps and extends from continuation of the drainage pipe to which it is
in front of the last fixture to its connection with connected. A continuous vent is illustrated in
a stack vent. The basic principal of this type of Figure 3-6.
vent is that the flow of drainage does not exceed
a one-half flow condition.
Additionally, lower-floor branches serving more
than three water closets shall be provided with
a relief vent taken off in front of the first fixture
connection. When lavatories or similar fixtures
discharge above such branches, each vertical
branch shall be provided with a continuous vent.
When the circuit, loop, or relief vent connections
are taken off the horizontal branch, the vent
7. END VENTING
End venting is a method of venting a series of floor
drains with a vent connected to the drainage pipe
at the beginning of the run before the first drain.
The entire drain line, from the first floor drain to
the connection with a main drain, shall be pitched
at 1/8 inch per foot (1 percent) and be sized two
pipe sizes larger than called for in the code. The
theory is that the system is oversized allowing
the sewer to flow partially full, thus permitting
air to circulate above the water in the pipe. This
configuration is similar to a combination waste-
and-vent system.
Circuit Vent
8. FIXTURE BATTERY
A fixture battery is any group of two or more simi-
lar, adjacent fixtures discharging into a common,
horizontal waste or soil branch. A fixture battery
is illustrated in Figure 3-7.
9. FIXTURE UNIT.
A fixture unit is a dimensionless measure of the
probable discharge from any fixture into the
drainage system compared to that of a lavatory.
There are different fixture units assigned to
both the water system (WSFU) and the sanitary
drainage system (DFU) that would appear in the
project location code. The actual flow of waste
from the sanitary drainage is obtained from a
Loop Vent conversion table found in Chapter 1, Sanitary
Figure 3-5 Circuit and Loop Vent Drainage Systems.
40 ASPE Plumbing Engineering Design Handbook — Volume 2
10 . INDIVIDUAL VENT
An individual vent connects directly to only one
fixture and extends to either a branch vent or
vent stack. Another name for the individual vent
is a revent. An individual vent is illustrated in Figure 3-9 Typical Offsets
Figure 3-8.
to the vent terminal in the open air as a direct of fixtures may be installed with a drain from a
extension of one stack. back-vented lavatory, kitchen sink, or combina-
tion fixture serving as a wet vent for a bathtub
17. VENT STACK or shower stall and for the water closet, provided
A vent stack is a vertical pipe extending one or that:
more stories in height and terminating above the 1. Not more than one fixture unit is drained
highest point of a structure, allowing circulation into a 1½-in (38-mm) diameter wet vent or
of air into and out of the drainage system. not more than four fixture units drain into a
2‑in (51-mm) diameter wet vent.
18. VENT STACK TERMINAL
2. The horizontal branch connects to the stack
A vent stack terminal is the part of the venting at the same level as the water-closet drain or
system that extends through the roof, thus keep- below the water-closet drain when installed
ing the drainage system open to atmospheric on the top floor.
pressure.
On the lower floors of a multistory building, the
19. WET VENT waste pipe from one or two lavatories may be used
A wet vent is a continuous vent, other than from as a wet vent for one or two bathtubs or showers,
a water closet, which also receives and conveys provided that:
drainage from additional fixtures. The principal 1. The wet vent and its extension to the vent
of design is to use oversized piping to allow for the stack is 2 in (51 mm) in diameter.
flow of water above the flow of the drainage water. 2. Each water closet below the top floor is indi-
Consult the local code for requirements. These vidually back-vented.
fixtures can discharge without being vented. If
allowed by local codes, a single-bathroom group
Chapter 3 — Vents and Venting Systems 43
Bathroom groups consisting of two lavatories and sizing the vent system
two bathtubs or shower stalls back-to-back on a top
floor may be installed on the same horizontal branch
DEVELOPED LENGTH
with a common vent for the lavatories and with no The developed length of an individual or common
back vent for the bathtubs or shower stalls and for vent is calculated from its connection with the fixture
the water closets, provided the wet vent is 2 in (51 trap arm to the connection with the branch vent or
mm) in diameter and the length of the fixture trap vent stack. A branch vent developed length is taken
arm conforms to Table 3-2. A wet vent is illustrated from the furthest connection with a waste branch to
in Figure 3-13. the point being sized. The developed length of a vent
stack is taken from its connection with the soil or
waste stack to the highest point outside the structure.
Table 3-2 Maximum Length of
Trap Arm The developed length must include an allowance for
Diameter of Trap Distance – Trap
fittings, similar to water lines. The developed length
Arm, in. (mm) to Vent, ft (m) is one of the items necessary to size a vent.
1¼ (32) 2½ (0.76)
1½ (38) 3½ (1.1) FIXTURE UNITS
2 (51) 5 (1.5) One of the other items, the Sanitary Fixture Units,
3 (76) 6 (1.8) is associated with the drainage line or stack for the
4 (101) 10 (3.0)
vent being sized. The actual total of sanitary fixture
units is obtained from a conversion table found in
Chapter 1, Sanitary Drainage Systems.
building sewer. The need for a fresh air inlet must tem. Protective devices are available but may be
be confirmed by the local code. susceptible to frost closure or the accumulation
4. Based on the size of the trap, the maximum of snow. Care must also be taken when locat-
length of the trap arm shall be as shown in ing the vent terminals with respect to building
Table 3-2 walls, higher adjacent roofs, parapet walls, etc.,
as these may affect the proper flow of air into and
VENT TERMINALS out of the venting system as well as provide an
Vent pipes passing through the roof must remain undesirable smell if drawn into an HVAC intake.
open under all circumstances. Two conditions that If necessary, electrical heat tracing or insulation
would cause the exposed pipe to become blocked are could maintain a temperature high enough to
prevent ice from forming.
frost closure and snow. Field test has shown that a
4-in (100-mm) size pipe at the roof level is capable The vent extension shall not be located under or
of remaining open under all but the most severe within 10 ft (3 m) of any window, door, or venti-
conditions. lating opening, unless it is 2 ft (0.8 m) above such
Though it may be small by comparison to the over- an opening. If the terminal is through a building
all sanitary drainage piping, the vent stack terminal wall it shall be located a minimum of 10 ft (3 m)
is an important portion of the system. Through the from the property line, and if above grade, a mini-
terminal vent, air at atmospheric pressure enters mum of 10 ft (3 m) above grade and not under an
the drainage system to hold in balance the water overhang.
seal contained in each fixture trap. The balance of
RELIEF VENTS
atmospheric air pressure and gravitational pull on
Soil or waste stacks with no offsets, in buildings hav-
the wastewater mass follows the principles outlined
ing more than 10 branch intervals, shall be provided
in Chapter 1, Sanitary Drainage Systems. Vent stack
with relief vents every tenth branch vent interval
terminals need to be sized in accordance with local
starting with the top floor. Offsets in the waste stacks
codes and /or good engineering practices, which in-
may also be required to have a relief vent if the code
cludes the following:
requires it. Several configurations are possible by
1. Increase the terminal pipe by two sizes at 18 in various codes. In general, the lower end of the relief
(455 mm) below the roofline. This allows for the vent shall be connected to the waste stack below the
interior building space (which is usually warmer) horizontal branch serving the floor required to have
to provide a convective flow of interior building the relief vent. The upper end of the relief vent shall
heat, keeping the vent terminal at the roof from connect to the vent stack no less than 3 ft (1 m) above
freezing closed.
that same floor level. Its size shall be equal to the vent
2. Project the vent terminal in accordance with juris- stack to which it is connected or the drainage stack,
dictional building codes and locate an appropriate whichever is smaller.
distance from air intake louvers, windows, doors, The purpose of differentiating between branch
and other roof openings, 10 ft (3 m) minimum. intervals and the actual number of horizontal soil or
Sewer gases will be forced upward through the waste branch lines entering the stack is to prevent
terminal stack by the weight of the water in the overloading the stack in a short distance. Many
trap, therefore, the vent pressures versus the air codes limit the number of DFUs allowed in a branch
intake volumes need to be considered. interval.
3. Provide minimum 4-in (100-mm) diameter vent
stack terminals. Experience has proven a 4-in CIRCUIT AND LOOP VENTS
(100-mm) terminal allows an adequate volume of These venting schemes are intended to provide a
air to enter the plumbing system, and its effective more economical means of venting than provided by
opening is not as easily constricted by foreign the individual vent. In the Uniform Plumbing Code
matter, ice, snow, or vermin, as the opening of (UPC), it is allowed only for venting of floor-mounted
a smaller diameter pipe would be. (It should be fixtures, such as water closets, showers, and floor
noted most codes require only one 3-in [75-mm] drains, and may not be acceptable in all jurisdictions.
vent to atmosphere be provided for each building The International Plumbing Code (IPC) does not
drain.). Winds of sufficient force can affect the have the same restrictions. Any fixture, as long as the
function of the venting system and in situations connection is on the horizontal, may be vented in this
of high winds and high moisture (such as at Ni-
manner. The circuit-venting principal is allowed for
agara Falls), the vent size should be increased to
the venting of branch waste lines serving floor drains
6 in (150 mm). A strong wind blowing across the
and other floor-mounted fixtures in some codes.
effective opening of the vent stack terminal can
create unbalanced air pressures within the sys- Circuit venting requires a uniformly sized drain-
age line with at least two, but not more than eight,
Chapter 3 — Vents and Venting Systems 45
fixtures connected in a battery arrangement. The The National Standard Plumbing Code, one of the
circuit vent is connected to the horizontal drain line traditional codes, lists the following special require-
between the two most remote fixtures and is con- ments to avoid suds problems:
nected to the vent stack. In addition to the circuit 1. Where required. Where kitchen sinks, laundry
vent, a relief vent is required to be connected to the trays, laundry washing machines, and similar
vent stack. In addition to the circuit vent, a relief fixtures in which sudsy detergents are normally
vent is required to be connected to the horizontal used and discharge at an upper level into a soil
drain line at the end of the battery, or every eight or waste stack. The drainage and vent piping for
fixtures. The size of each shall be one-half the size such lower fixtures shall be arranged so as to
of the horizontal drainage line or the full size of the avoid connection to suds pressure zones in the
vent stack, whichever is smaller. sanitary drainage and vent systems, or provide a
Loop venting is the same as circuit venting except suds relief vent, relieving to a no-pressure zone.
for the connection of the branch vent to the building Relief vents shall be provided at each suds pres-
system. The loop vent “loops” back to the stack vent sure zone where such connections are installed. In
instead of the vent stack. multistory buildings, with more than six branch
intervals of fixtures described above, separate
SUDS VENTING waste and vent stacks for the lower four branch
High-sudsing detergents are used in kitchen sinks, intervals of fixtures shall be required as indicated
dishwashers, and clothes washing machines in resi- in Table 3-3.
dential occupancies and commercial laundries. These 2. Suds pressure zones. Suds pressure zones shall
suds disrupt the venting action and spread through be considered to exist at the following locations in
the lower portions of multistory drainage systems. sanitary drainage and vent systems as indicated
The more turbulence there is, the greater the suds. in Figure 3-15.
In some cases, suds back up through the traps and Zone 1. In a soil or waste stack that serves
even spill out on the floor. They cause an increase in fixtures on two or more floors and receives
the pressure and vacuum levels in the systems. They wastes from fixtures wherein sudsy deter-
affect both single-stack and conventional systems. gents are used, a zone shall be considered to
Solutions to the problem may involve avoiding suds exist in the vertical portion upstream of an
pressure zones, connecting the suds-producing stack offset fitting and the riser to the upper section
downstream of all other stacks, and increasing the of the system, in the horizontal portion down-
size of the horizontal building drain to achieve less stream of this fitting, and in the horizontal
restrictive flow of air and water. Using streamline fit-
tings, such as wyes, tends to reduce suds formation.
Check valves in fixture tailpieces have been used to
fix problem installations.
eventually escape into the atmosphere. It also permits not be exceeded when the fixture drains or horizontal
the addition of air into the system and the emission branches connect to the building drains or stacks.
of air from all parts of the drainage system. Venting When water flows down a stack or when it flows
requirements relate to this addition and emanation along a sloping drain, for most conditions, the cross
of air from the drainage system as a whole. section the pipe is only partially filled with water.
The purpose of traps in any building drainage Since this means it is also partially filled with air, the
system is to prevent sewer gas from entering into moving water tends to drag the air along with the flow.
the building from the building system, including the This flow might be blocked toward the outlet in many
stacks, branches, and building (house) drain. The ways, for example by a hydraulic jump in the building
water seal in the trap prevents the backflow of sewer drain or a submerged outlet to the public sewer. This
gas into the fixture and from there into a room. There creates a considerable positive pneumatic pressure to
are two major ways in which trap seals are reduced. be built up in the building drain. This pressure may
The first is the pneumatic pressure fluctuations in the extend up the stack for some distance, decreasing as
system. The negative part of the fluctuations caused it travels upwards. If this excessive pressure is to be
by the discharge of fixtures in the system (other than permitted from occurring, adequate venting must be
the fixture in question to which the trap is attached) provided near the bottom of the stack, so air may be
may suck water out of the trap. Then the positive part carried away without developing a pressure of more
of the fluctuation can force sewer gas past the reduced than 1-inch water column in the stack to which the
trap seal. This is called “induced siphonage.” The vent is connected. This is why all of the codes call for
second is where the reduction of the trap seal of the relief vents at various locations in the vent stack.
fixture in question is caused by the discharge of the Water flows down a vertical pipe in what is called
fixture itself. This is referred to as “self-siphonage.” sheet flow. This means the water forms a sheet flowing
The reduction of trap seals of fixture traps will be around the perimeter of the pipe with a hollow core.
the basis for deciding the limitations of drain lengths The outer layer of the sheet of falling water down a
and slope; therefore, a discussion of what trap seal stack exerts a frictional drag on the core of air inside
losses or remaining trap seals are to be considered as the sheet of water. If the drain does not flow full in
necessary. The adequate protection of the building any one section, the stream of air dragged down by
interior against the penetration of sewer air by pas- the water is more or less allowed to flow out of the
sage of that air through or past the trap seal depends outlet end of the drain and into the atmosphere. Some
on the depth of the seal that can be maintained under retardation of the air will occur if the hydraulic jump
all conditions and the effects of air fluctuations on may fill the cross section of the drain. This will create
induced siphonage and self-siphonage. The important a backpressure, which will be felt part way up the
thing to remember is what would be the remaining stack. If the drain is completely blocked at some sec-
trap seal if we limited the trap seal losses. It is a code tion, the airflow will be blocked also. In the absence
requirement for each fixture trap to have a water of vents, the air pressure in the drain might get to
seal of not less than 2 inches. This figure of 2 inches be very high.
allows for the fouling of the fixture drain in time.
The remaining trap seal will still protect against the REFERENCES
passage of air back into the building as long as the 1. American Society of Plumbing Engineers (ASPE)
excess pressure in the stack does not exceed twice the Research Foundation. 1978. Reduced-size venting
depth of water in the seal. design, by E. Brownstein. Westlake Village, CA.
The maximum trap seal loss due to pressure
2. Copper Development Association, Inc. Copper
fluctuations considered to be permissible is 1 inch
sovent single-stack plumbing system handbook
of water. When a “P” trap is used this means the
supplement. New York.
negative pressure of 2 inches of water is required to
reduce the trap seal by approximately this amount 3. Manas, Vincent T. 1957. National plumbing code
for a single pressure fluctuation. Experiments have handbook. New York: McGraw-Hill.
found further trap seal losses will occur if the same 4. National Association of Home Builders Research
pressure reduction is applied to the trap without any Foundation. 1971. Performance of reduced-size
refilling occurring in the meantime. On the basis of venting in residential drain, waste and vent sys-
these considerations, it has arbitrarily been decided to tem. Report LR 210-17.
keep the pressure fluctuations in a building drainage 5. National Association of Plumbing-Heating-
system to a maximum of 1 inch of water. It is not nec- Cooling Contractors and American Society of
essary for these fluctuations to be exceeded anywhere Plumbing Engineers. 1973. National standard
in the system. The important thing is that they shall plumbing code.
48 ASPE Plumbing Engineering Design Handbook — Volume 2