Protection of DC Bus Using Solid-State DC Breaker
Protection of DC Bus Using Solid-State DC Breaker
Breaker
A. Jaya Laxmi
Eswaraiah G Professor & Head,
Research Scholar, Department of Electrical & Electronics
Department of Electrical & Electronics Engineering,
Engineering, JNTUH College of Engineering,
JNTUH College of Engineering, Hyderabad. Hyderabad.
[email protected] [email protected]
Abstract: In this contemporary era, DC micro grids are this paper is on SSCB suitable for voltages under 1
become trendy. DC micro grids have numerous KV DC. For instance, Fig. 1 shows the structure of a
advantages as well as disadvantages. One of the main DC micro grid. There are various applications of DC
drawbacks of DC micro grid is short-circuiting protection; power such as in industries, commercial and
it has become a challenging issue because of the high rise residential buildings, and increasing no. of electronic
rate the fault current. Electro-mechanical switches are loads, such as IT equipment, LED lighting and
very slow which cannot control the short circuit faults adjustable speed motor drives. The DC micro grids at
resulting in over dimensioning of the system. Power any voltage level faces many technical challenges,
electronic circuit breakers have the ability to interrupt particularly, short-circuit protection. [4]-[8]The
high magnitude of fault currents. This paper introduces a problem with fault currents is that they do not have a
new concept of Bi-directional Short-Circuit Current
natural zero crossing like in AC systems. Another
problem is that DC cables have low impedances
Blocker based on Solid-State Circuit Breaker (SSCB).
which lead to high rate of current rise when the
The new Solid-State circuit Breaker detects the short-
system is prone to short-circuit faults. The power
circuit faults by using Current Differential Protection
electronic circuit breaker can be operated for a short
strategy. The SSCB can be directly placed in series with
time and versatile operating modes when compared
the DC Bus without disturbing the normal circuit.
to typical Mechanical switch. Power electronic
Finally, the performance of the blocking circuit is devices are the optimal solution to short-circuit faults.
simulated and results are verified. The results clearly The power electronic circuit breakers are divided into
show that, by using SSCB short-circuit fault current is two types based on their working principles. They are
blocked within 4 ms. The SSCB gives better results than Solid-State Circuit Breakers (SSCB) and hybrid
any other protection mechanism developed until now and circuit breakers. When fault occurs, SSCB isolates
has many benefits such as reclosing, bi-directional the short-circuit current with power electronic switch
blocking and energy releasing functions. SSCB can be and during the normal operation, minimizes power
used numerous times and the best solution for short- loss with the help of a mechanical switch. Hybrid
circuit faults. circuit breakers are generally not employed in DC
micro grids because of its complicated design and
Keywords: DC micro-grid, DC bus protection, circuit problem in finding an exact short-circuit current zero-
breaker crossing point.
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.
Figure 1: Block Diagram of a DC micro grid [1]
Insulated-Gate Bipolar Transistors (IGBT’s) coupled
II WORKING PRINCIPLE OF A BI- in reverse series (Q1, Q2), two Silicon Controlled
DIRECTIONAL SHORT-CIRCUIT CURRENT Rectifiers (SCR’s) linked in reverse parallel (T1, T2),
BLOCKER a blocking capacitor C, TRIAC and an energy release
resistor Reo. [9]-[12]Because blocking capacitor C
A Bi-directional Solid-State Circuit Breaker is
can be charged in both directions. The BSCCB can
connected in series with the DC Bus to protect the
detect and block fault currents in both directions. The
DC bus from the short-circuit faults. It has two
structure of BSCCB is given in Figure.2
A detailed analysis and working principle of BSCCB value of the line is Io, and Figure 4a shows the
is explained in five modes. The current flow path current flow path in this mode.
during these five modes is shown in figure 3 and 4.
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.
capacitor; the current flow path in this stage is shown
in Figure 4b.
C. FAULT-CURRENT BLOCKED STAGE (t1 ≤ t
< t2)
Fig.3(c) shows the fault line is broken by BSCCB,
when the capacitor C completely absorbs the fault
current. The current through T1 will be dropped to
below the maintenance current IH during the fault
current blocking phase, T1 is switched off
automatically, and capacitor C is not discharged to
the external circuit due to decrease in the fault
current. The circuit operation in this stage is shown
in Figure 4c.
D. RECLOSING STAGE (t2 ≤ t < t3)
In this stage shows in the Fig.3 (d) circuit breaker
comes to its usual working mode, and its only
function is to turn on Q1 and Q2. The energy Figure 4: Current waveform of BSCCB in various modes.
accumulated in capacitor C is not discharged until
this operation is completed. If the input voltage is III. CONTROL STRATEGY OF PROPOSED
clamped, the capacitor voltage cannot be decreased BSCCB DIFFERENTIAL PROTECTION
to zero and the fault current is not completely STRATEGY
absorbed whenever the fault occurs next time.
Voltage measurements and it takes only current
(v) DUMP ENERGY RELEASING STAGE (t3 ≤ t measurements.Fig.5 shows current differential
< t4) protection scheme In current differential protection
In this stage shows in Fig.3 (d) TRIAC is turned on strategy, differential[13]-[15] current Id is calculated
after the reclosing stage. During this time, capacitor by subtracting both ends of the protected line
voltage is decreased from constant value to zero. currents, i.e., IF and IR. If the value of Id is greater
Both Q1, Q2 and TRIAC are turned on in this stage, than the Ker*Is specified in the comparator1, a signal
however their operation do not interact with each is sent to AND gate and if either end of the line
other. The energy accumulated in capacitance C is current is greater than the reference value set in the
released in the form of thermal energy on resistor comparator 2\3 then a signal is send to the AND gate.
Re. Because TRIAC can be operated bi- During the fault condition, both the inputs of the
directionally, therefore capacitor C can be AND gate are high, then a driving signal will be
discharged in both directions. Figure 4d depicts the generated to control turn ‘ON’ and turn ‘OFF’ the
current flow direction. switches. The following are the differential protection
boundary conditions:
I d
= I F
− I R
I d
> K er
*I s
(1)
I F
> I ref
I R
> I ref
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.
implemented if and only if all the boundary
conditions are satisfied.
I F
K *I
I R
er s
I ref
I ref
Normal
On Off Off
Mode
Fault current
Off Off Off
Blocking
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.
‘OFF’ the switches.
The waveforms of input voltage and current are shown Figure 9: Waveform of output voltage and current.
in Figure 7. When a fault occurs, input voltage
fluctuates and drops down to zero in 4ms, so the The waveform of output voltage and current are
DERs, energy storage devices, loads connected to the shown in figure 9. In normal operating mode, voltage
DC bus, are not affected. During this time input is maintained at normal level. During the fault
current reaches to maximum value and drops down to condition voltage is dropped down to zero. It is shown
zero within 4ms. This shows that BSCCB can in the Figure 8, 9 shows the waveforms of input and
successfully clear the fault current in 4 ms and output currents are nearly the same. The output
protects the devices. Here transport delay is 0.1sec, voltage drops to zero after zero-crossing increases,
so reclosing operation is done at 0.3 sec, input which is caused by the instantaneous oscillation of
voltage and current returns to normal level by 0.3 sec. inductance L load and capacitor C. When capacitor C
This shows that new BSCCB can clear the fault is fully charged, the voltage on inductance load will
rapidly when compared to any other existing not oscillate and attenuate to zero, which means that
protection devices. the load side and the supply side are successfully
isolated.
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.
the capacitor voltage starts to discharge at 0.3 sec. It restoration based on intentional islanding algorithm for
distributed energy resources in disaster
can be seen from Figure that the value of capacitor
management. International Journal of Modelling and
voltage is almost zero at 0.5 sec. At the same time, Simulation, 38(3), 189-206.
the TRIAC current is reduced to zero, and the peak [4]. Lalithya, M., Himaja, P. N. S., Ankush, M., & Laxmi,
of TRIAC current in the discharge stage is only A. J. (2015, December). Implementation of solar
powered DC pumping system for irrigation. In 5th
0.1A. This value is within the safe range and will not
International Conference on Advances in Energy
have an significant impact on TRIAC. Research (pp. 15-17).
[5]. Kumar, M. A., & Laxmi, A. J. (2016, September).
Application of intentional islanding algorithm for
distributed energy resources in disaster management.
In 2016 IEEE International Conference on Power
System Technology (POWERCON) (pp. 1-6). IEEE.
[6]. Ankush Kumar, M., & Jaya Laxmi, A. (2022). DC–DC
Converter for RES-Based Smart Resilient LVDC
Distribution System. In DC—DC Converters for Future
Renewable Energy Systems (pp. 223-232). Springer,
Singapore.
[7]. Kumar, M. A., & Laxmi, A. J. (2021). Machine
Learning Based Intentional Islanding Algorithm for
DERs in Disaster Management. IEEE Access, 9, 85300-
85309.
[8]. Z. Miao, G. Sabui, A. Moradkhani Roshandeh and Z. J.
Shen, "Design and Analysis of DC Solid-State Circuit
Breakers Using SiC JFETs," in IEEE Journal of
Emerging and Selected Topics in Power Electronics,
vol. 4, no. 3, pp. 863-873, Sept. 2016, doi:
10.1109/JESTPE.2016.2558448.
[9]. M. R. K. Rachi, M. A. Khan and I. Husain, "Local
Measurement-Based Protection Coordination System
for a Standalone DC Microgrid," in IEEE Transactions
Figure 11: Waveforms of output voltage, current and power of 9 on Industry Applications, vol. 57, no. 5, pp. 5332-5344,
loads. Sept.-Oct. 2021, doi: 10.1109/TIA.2021.3091945.
[10]. Z. Wang, X. Shi, Y. Xue, L. M. Tolbert, F. Wang and
Figure 11 depicts the output voltage, current and B. J. Blalock, "Design and Performance Evaluation of
power waveforms of 9 loads. Load current and Overcurrent Protection Schemes for Silicon Carbide
voltage waveforms are similar to the input and output (SiC) Power MOSFETs," in IEEE Transactions on
Industrial Electronics, vol. 61, no. 10, pp. 5570-5581,
voltage and current waveforms. Oct. 2014, doi: 10.1109/TIE.2013.2297304.
[11]. M. Salehi, S. A. Taher, I. Sadeghkhani and M.
V CONCLUSION Shahidehpour, "A Poverty Severity Index-Based
Protection Strategy for Ring-Bus Low-Voltage DC
In this paper, a novel bi-directional short-circuit Microgrids," in IEEE Transactions on Smart Grid, vol.
10, no. 6, pp. 6860-6869, Nov. 2019, doi:
current blocking mechanism for a DC micro grid 10.1109/TSG.2019.2912848.
based on Solid State circuit Breaker is introduced. [12]. K. Chenchireddy, V. Kumar, K. R. Sreejyothi and P.
This device provides faster response time, bi- Tejaswi, "A Review on D-STATCOM Control
directional blocking and reclosing functions than Techniques for Power Quality Improvement in
Distribution," 2021 5th International Conference on
typical circuit breaker. The results show that, when a Electronics, Communication and Aerospace
short- circuit fault occurs, it is blocked in with 4 ms. Technology (ICECA), 2021, pp. 201-208, doi:
The designed BSSCB is ideal for a DC micro grid 10.1109/ICECA52323.2021.9676019.
having less rotational inertia and fast developing [13]. M. Komatsu, "Approach and basic evaluation for the
DC circuit breaker with fault current limiting feature,"
short-circuit fault. 2016 IEEE International Telecommunications Energy
Conference (INTELEC), 2016, pp. 1-5, doi:
REFERENCES 10.1109/INTLEC.2016.7749138.
[14]. K. Chenchireddy, B. S. Goud, C. M. Sudhan Mudhiraj,
[1]. R. A. F. Ferreira, P. G. Barbosa, H. A. C. Braga and A. N. Rajitha, B. S. Kumar and V. Jagan, "Performance
A. Ferreira, "Analysis of non-linear adaptive voltage Verification of Full-Bridge DC To DC Converter Used
droop control method applied to a grid connected DC for Electric Vehicle Charging Stations," 2022 8th
microgrid," 2013 Brazilian Power Electronics International Conference on Advanced Computing and
Conference, 2013, pp. 1067-1074, doi: Communication Systems (ICACCS), 2022, pp. 434-
10.1109/COBEP.2013.6785247. 439, doi: 10.1109/ICACCS54159.2022.9785288.
[2]. Wang, L., Feng, B., Wang, Y., Wu, T., & Lin, H. [15]. S. M. Aaqib, M. J. ur Rehman, H. M. Bilal, M. Usman,
(2020). Bidirectional short-circuit current blocker for M. Z. Shabbir and H. E. Gelani, "Protection Schemes
DC microgrid based on solid-state circuit for Low Voltage DC Networks," 2019 International
breaker. Electronics, 9(2), 306. Conference on Electrical, Communication, and
[3]. Kumar, M. A., & Jaya Laxmi, A. (2018). Power Computer Engineering (ICECCE), 2019, pp. 1-5.
Authorized licensed use limited to: JAWAHARLAL NEHRU TECHNOLOGICAL UNIV. Downloaded on October 31,2022 at 07:18:45 UTC from IEEE Xplore. Restrictions apply.