Job Key Sub-project

Seq. No. Site ID TAWAL ID Region District


No. Name

Z1E001 1008231 South Jizan


ZJZ670 1005754 South Jizan
ZJZ902 1010319 South Jizan
Site AC
Total
Survey Date by Site Power Actual
Site Type Shelter type Number of
Ops Supply Amper Load
DC Systems
(A)
Shelter DRM generator 18-22-18 1
Shelter single generator 38-40-40 1
Shelter DRM generator 19-17-22 1
Total
Total Total Genrator Fuel Tank
Capacity of Generator Fuel Tank
Number of Number of Capacity Capacity, ATS Status
A/C unit, Status Status
A/C Units Generators Prime, KVA liter
Ton
2 4 1 24 OK OK 1000 NA
2 3 1 24 OK OK 2000 NA
2 4 1 35 OK OK 1000 NA
Telecom
Reqested Approved Design
Reamrks by Load Final D&S Design
Scope by scope by Status
Ops (Feasibility Status Comments
Operation D&S Date
Load)
Job
Seq. Sub-project Survey Date
Key Site ID TAWAL ID Region District Site Type
No. Name by Ops
No.

ZJZ050 South Jizan


ZJZ064 South Jizan
ZJZ067 South Jizan
ZJZ089 South Jizan
ZJZ111 South Jizan
ZJZ128 South Jizan
ZJZ135 South Jizan
ZJZ136 South Jizan
ZJZ252 1008231 South Jizan
ZJZ259 South Jizan
ZJZ287 South Jizan
ZJZ298 South Jizan
ZJZ303 South Jizan
ZJZ305 South Jizan
ZJZ318 South Jizan
ZJZ330 South Jizan
ZJZ333 South Jizan
ZJZ340 South Jizan
ZJZ385 South Jizan
ZJZ840 South Jizan
ZJZ854R11 South Jizan
ZJZ237R11 South Jizan
Site Power Number of
Shelter type
Supply DC Systems

ODU Power Cube - Generator running more than 10 Hrs 1


ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
ODU Power Cube - Generator running more than 10 Hrs 1
Shelter Hybrid System - Generator running more than 10 Hrs 1
#N/A 1
DC Modules Site Running Overall DC Existing
DC System Existing DC
capacity, MCU Status DC Plant Battery
Manufacturer Modules Qyt
Watt Load, A Status Strings , QTY

HUAWEI black 5 3000 OK 71 4


HUAWEI black 3 3000 OK 31 Missing
Huawei black 4 3000 OK 40 4
HUAWEI black 7 3000 OK 66 5
HUAWEI Black 5 3000 OK 69 4
HUAWEI black 5 3000 OK 28 2
HUAWEI Black 5 3000 OK 89 4
HUAWEI Black 4 3000 OK 99 4
HUAWEI black 5 3000 OK 11 4
HUAWEI 3 3000 OK 40 3
HUAWEI Black 3 3000 OK 42 6
HUAWEI Black 3 3000 OK 24 1
HUAWEI Black 6 3000 OK 24 6
HUAWEI Black 4 3000 OK 23 2
HUAWEI black 3 3000 OK 40 1+1
HUAWEI black 3 3000 OK 34 2
HUAWEI black 3 3000 OK 23 8
HUAWEI black 3 3000 OK 53 2
Huawei Black 4 3000 OK 75 4
HUAWEI Black 4 3000 OK 74 2
ENATEK 3 3000 OK 4 4
HUWAI Black 3 3000 OK 4 3
Existing Existing BB Requested Approved Design
Batteries Remarks by Final D&S
Battery Backup Scope by scope by Status
Status Ops Status
Capacity, AH time, Min. Operation D&S Date

200 7 Hr
Missing 0
200 10 Hr
100 7.5 Hr
150 6 Hr
100 5 Hr
200 5.5 Hr
150 2.5 Hr
50 8 Hr
150 5 Hr
100 9 Hr
150 3.5 Hr
100 9 Hr
100 4.5 Hr
100+150 3.5 Hr
100 4.5 Hr
50 9 Hr
150 5 HR
200 7 Hr
150 2.5 Hr
150 12 Hr
150 13 Hr
Design
Comments

You might also like