SIMPLER SOLUTION
Automatic Power Factor Controllers
for contactor and Thyristor based APFC Panels
Power factor correction
– now easier than ever.
Brought to you by Lauritz Knudsen – India’s largest manufacturer of LT switchgear – the etaSMART & etaULTRA Series automatically
corrects the power factor, with the help of contactor & thyristor for the connection and disconnection of capacitor banks.
Packed with a specially formulated optimisation program, the controller ensures accurate power factor control at the set point
and hunt free operation.
Lauritz Knudsen 1
etaSMART Series - 1 CT Input
The L&T Advantage - etaSMART › Site selectable 2 or 4 quadrant operation for industries with
or without Solar plants
› Available upto 16 steps
› Capacitor health check monitoring function ensures that
› Space-saving. Compact size of 96 x 96 mm for controller capacitor is declared faulty if its power falls beyond a
upto 8 steps certain limit
› CT Secondary 1A/5A › Last relay output contact can be configured as Step or
› Automatic detection of CT polarity saves time and effort. Alarm. Second-last relay output can be configured as Step
etaSMART detects the CT reversal and automatically or Fan control
corrects it › Ambient temperature monitoring via internal sensor
› Option of LIFO, FIFO, and Intelligent control mode
2 Lauritz Knudsen
Technical Specifications
Lauritz Knudsen 3
Product Dimensions
70.9
58.3
92
etaSMART 12R, etaSMART 14R etaSMART 16R,
etaSMART 8T, etaSMART 12T and etaSMART 15T
71.6 138
58.3
138
etaULTRA 8R, etaULTRA 16R, etaULTRA 8T+2R,
etaULTRA 14T+2R & etaULTRA 8T+8R
138
71.6
58.3
138
4 Lauritz Knudsen
4.2 Wiring Diagram
Lauritz Knudsen 5
etaSMART6T
6 Lauritz Knudsen
etaULTRA 8R, etaULTRA 16R
L1
L2
MAINS
LOAD
L3
N
ALARM
DI-1
(65 - 285 V AC)
Digital I/P
C3 17 16 15 C2
C1
Alarm
C
R16
DI-2
R1
R1
1
R2
HIGH VOLTAGE
R15
R2
A
2
Cascading
B RT
Fan
R3
3
VOLTAGE I/P 1
U1
FU1 BANK1
R4
4
D+ D-
VOLTAGE I/P 2
U2
K1
Modbus RTU RS 485
R5
5
VOLTAGE I/P 3
U3
RT1 R
R6
6
NEUTRAL
R7
78
S1
CURRENT
1A / 5A
I/P 1
R8
S2
FU2 BANK2
R9
9
S1
K2
CURRENT
1A / 5A1
R10
I/P 2
10
S2
R11
11
S1
CURRENT
R12
I/P 3
12
A / 5A
FU16 (2A)
S2
R13
13
85-300V AC/DC
L
AUX SUPPLY
R14
R14
14
N
etaULTRA - 16R
FU15 (2A) CAT.NO. CS91051OOOO
16 Steps APFC Relay
FU14 BANK14
K14
NOTE:
1. Last two relay output contacts can be configured either to switch the capacitor bank or to energise FAN
and ALARM respectively as shown in wiring diagram.
2. All relay terminals, Voltage & current input terminals are suitable for wire range 12-30 AWG stranded or
Solid copper wire. Modbus and cascading terminals are suitable for 14-30 AWG
etaULTRA 14T+2R
L1
L2
MAINS
LOAD
L3
N
24V DC
SUPPLY
FU17 (5A)
- +
FAN
TSM-1
FU18 (2A) P1 24/12 VDC
P1
T1 GND
ALARM
DI-1
(65 - 285 V AC)
Digital I/P
C3 17 16 15 C2
C1 12
Alarm
C
R2
DI-2
T1
T1 T2 T3 T4 T5 T6 T7 T8
T2 FU1 BANK1
HIGH VOLTAGE
R1
AB
TSM-2
Cascading
Fan
P1
4
RT
T2 GND
5
D+ D-
VOLTAGE I/P 2
6
U2
Modbus RTU RS 485
VOLTAGE I/P 3
U3
RT1 R
NEUTRAL
T2
FU2 BANK2
S1
T9
91
CURRENT
1A / 5A
I/P 1
S2
T10T
0
S1
CURRENT
11
1A / 5A
I/P 2
11
TSM-14
S2
P1 24/12 VDC
T12
12
T14 GND
S1
CURRENT
1A / 5A
T13
I/P 3
13
FU16 (2A)
S2
T14
T14
85-300V AC/DC
14
L
AUX SUPPLY
etaULTRA - 14T + 2R
N
NOTE:
1. Last two relay output contacts can be configured either to switch the capacitor bank or to energise FAN
and ALARM respectively as shown in wiring diagram.
2. All relay terminals, Voltage & current input terminals are suitable for wire range 12-30 AWG stranded or
Solid copper wire. Modbus and cascading terminals are suitable for 14-30 AWG
Lauritz Knudsen 7
etaULTRA 8T+8R
L1
LOAD
MAIN S
L2
L3
N
24V D C TSM-1
Fu 17 (5A) SU PPLY P1
- + 24/12 VDC
FAN T1 GND
Fu 18 (2A) P1
ALARM
Fu 19 (5A)
D I-1
BANK1
(65 -2 8 5 VAC)
Fu 1
Digit al I/P
C4 17 16 15 C3
C1 1 2
C
Ala rm
R8
DI- 2
T1 TSM-8
T1 T2 T3
T2 P1 24/12 VDC
HIGHVOLTAGE
R7
T8 GND
A
3 4 5 6 7
Casc ad ing
B
Fan
T4
RT
VOLTAGE I/P 1
U1
T5 T6 T7
D+
VOLTAGE I/P 2
U2
Mo db u s RTU RS 4 85
D-
VOLTAGE I/P 3
Fu 2 BANK8
U3
T8
R T1 R
T8
8
NEUTRAL
T2
C2
S1
CU RRENT
1 A/ 5 A
R1
I/P 1
R1
9
S2
R2
S1
10
CURRENT
1 A/ 5 A
I/P 2
S2
R3
11
F u 13 BANK9
S1
R4
CURRENT
12
1 A/ 5 A
I/ P 3
F u 16 (2A) K1
S2
R5
13
8 5 -30 0 VAC/DC
L
AUX SUPPLY
R6
R6
14
e taULTRA - 8T + 8R
N
Fu 14
BANK14
K6
NOTE:
1. Last two relay output contacts can be configured either to switch the capacitor bank or to energise FAN
and ALARM respectively as shown in wiring diagram.
2. All relay terminals, Voltage & current input terminals are suitable for wire range 12-30 AWG stranded or
Solid copper wire. Modbus and cascading terminals are suitable for 14-30 AWG
8 Lauritz Knudsen
Salient features of - etaULTRA
CONTROL MODE
› Option of UFO, FIFO, and Intelligent control mode. Choose
any of these control modes. By default. it is set as
intelligent; this mode selects the best with combination of
capacitor bank for compensation with minimum switching
to achieve the desired power factor
RECORD OF STEP-SWITCHING
› You can schedule the maintenance of your installation by
reading the record of the number of switching of each step.
Lauritz Knudsen 9
DISPLAY OF CURRENT & VOLTAGE ANGLES
› Display of current & Voltage angles helps to troubleshoot
the wiring-related problem.
HT Sensing
› The wide band of input voltage measurement allows
etaULTRA to sense the HT voltage with the help of voltage
transformers.
INBUILT RS485
› etaULTRA comes with an inbuilt RS485 port which allows
for seamless digital connectivity.
10 Lauritz Knudsen
Salient features of - etaSAMRT
CONTROL MODE
› Option of UFO, FIFO, and Intelligent control mode. Choose
any of these control modes. By default. it is set as
intelligent; this mode selects the best with combination of
capacitor bank for compensation with minimum switching
to achieve the desired power factor.
RECORD OF STEP-SWITCHING
› You can schedule the maintenance of your installation by
reading the record of the number of switching of each step.
Lauritz Knudsen 11
SITE SELECTABLE 2Q/ 4Q OPERATION
› With the help of 4 quadrant operation etaSMART can
maintain PF in site with or without solar plant.
Load APFC
Recommendation - Use CT with 1 Amp secondary in case the distance between CT and Controller is more than 10 meter
NOTE: Capacitor duty contactor must be used for capacitor switching
12 Lauritz Knudsen
Application note
Lauritz Knudsen 13
Application note
14 Lauritz Knudsen
Application note
Lauritz Knudsen 15
Application note
16 Lauritz Knudsen
Power Quality Solutions