Ats480 Ethernetip Modbus Tcp Manual en Nnz85540 02
Ats480 Ethernetip Modbus Tcp Manual en Nnz85540 02
Ats480 Ethernetip Modbus Tcp Manual en Nnz85540 02
NNZ85540.02
04/2022
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Table of Contents
Safety Information.......................................................................................7
Qualification of Personnel ...........................................................................8
Intended Use..............................................................................................8
Product related information .........................................................................8
About the Book ..........................................................................................13
At a Glance ..............................................................................................13
Validity note........................................................................................13
Document Scope ................................................................................13
Related Documents ............................................................................14
Electronic product data sheet...............................................................15
Terminology........................................................................................15
Contact us..........................................................................................16
Presentation...............................................................................................17
Hardware Overview ..................................................................................17
Software Overview ...................................................................................18
Cybersecurity.............................................................................................19
Overview .................................................................................................19
Security Policy....................................................................................22
Product Defense-in-Depth ...................................................................23
ATS480 Security Policy .......................................................................25
Potential Risks and Compensating Controls..........................................27
Data Flow Restriction ..........................................................................28
Initial Setup ..............................................................................................28
Password.................................................................................................28
Security Event Logging .............................................................................29
Upgrades Management.............................................................................30
Clear Device / Secure Decommissioning ....................................................31
Basics .........................................................................................................32
Introduction ..............................................................................................32
Profile ......................................................................................................33
Definition of a Profile ...........................................................................33
Functional Profiles Supported by the Altivar Soft Starter.........................34
Functional Description.........................................................................35
Standard Mode Operating State Diagram .............................................36
Description of Operating States............................................................37
Summary ...........................................................................................38
Command Register CMD ......................................................................39
Stop Commands .................................................................................40
Assigning Control Word Bits ................................................................40
Status Word ETA.................................................................................41
Starting Sequence ..............................................................................42
Sequence for a Soft starter ..................................................................43
Sequence for a Soft starter with Mains Contactor Control.......................46
Automation Commissioning Only .........................................................48
Network Layer Supported Functions/Protocols............................................49
TCP and UDP Protocol .............................................................................51
Modbus TCP Features ..............................................................................53
NNZ85540.02 – 04/2022 3
Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 5
Safety Information Soft Starter for Asynchronous Motor
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this documentation or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
! DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
! WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
! CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.
NNZ85540.02 – 04/2022 7
Soft Starter for Asynchronous Motor Safety Information
Qualification of Personnel
Only appropriately trained persons who are familiar with and understand the
contents of this manual and all other pertinent product documentation are
authorized to work on and with this product. In addition, these persons must have
received safety training to recognize and avoid hazards involved. These persons
must have sufficient technical training, knowledge and experience and be able to
foresee and detect potential hazards that may be caused by using the product, by
changing the settings and by the mechanical, electrical and electronic equipment
of the entire system in which the product is used. All persons working on and with
the product must be fully familiar with all applicable standards, directives, and
accident prevention regulations when performing such work.
Intended Use
This product is intended for industrial use according to this manual.
The product may only be used in compliance with all applicable safety standard
and local regulations and directives, the specified requirements and the technical
data. The product must be installed outside the hazardous ATEX zone. Prior to
using the product, you must perform a risk assessment in view of the planned
application. Based on the results, the appropriate safety measures must be
implemented. Since the product is used as a component in an entire system, you
must ensure the safety of persons by means of the design of this entire system
(for example, machine design). Any use other than the use explicitly permitted is
prohibited and can result in hazards.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and fully understand
the contents of the present manual and all other pertinent product
documentation and who have received all necessary training to recognize
and avoid hazards involved are authorized to work on and with this
equipment.
• Installation, adjustment, repair and maintenance must be performed by
qualified personnel.
• Verify compliance with all local and national electrical code requirements as
well as all other applicable regulations with respect to grounding of all
equipment.
• Only use properly rated, electrically insulated tools and measuring
equipment.
• Do not touch unshielded components or terminals with voltage present.
• Prior to performing any type of work on the equipment, block the motor shaft
to prevent rotation.
• Insulate both ends of unused conductors of the motor cable.
Failure to follow these instructions will result in death or serious injury.
8 NNZ85540.02 – 04/2022
Safety Information Soft Starter for Asynchronous Motor
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before performing work on the equipment:
• Use all required personal protective equipment (PPE).
• Disconnect all power, including external control power that may be present.
Take into account that the circuit breaker or main switch does not de-
energize all circuits.
• Place a "Do Not Turn On" label on all power switches related to the
equipment.
• Lock all power switches in the open position.
• Verify the absence of voltage using a properly rated voltage sensing device.
Before applying voltage to the equipment:
• Verify that the work has been completed and that the entire installation
cannot cause hazards.
• If the mains input terminals and the motor output terminals have been
grounded and short-circuited, remove the ground and the short circuits on
the mains input terminals and the motor output terminals.
• Verify proper grounding of all equipment.
• Verify that all protective equipment such as covers, doors, grids is installed
and/or closed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Never operate energized switch with door open.
• Turn off switch before removing or installing fuses or making load side
connections.
• Do not use renewable link fuses in fused switches.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage
whatsoever.
This equipment has been designed to operate outside of any hazardous location.
Only install this equipment in zones known to be free of a hazardous atmosphere.
DANGER
POTENTIAL FOR EXPLOSION
Install and use this equipment in non-hazardous locations only.
Failure to follow these instructions will result in death or serious injury.
NNZ85540.02 – 04/2022 9
Soft Starter for Asynchronous Motor Safety Information
WARNING
INSUFFICIENT PERFORMANCE LEVEL/SAFETY INTEGRITY LEVEL AND/
OR UNINTENDED EQUIPMENT OPERATION
• Conduct a risk assessment according to EN ISO 12100 and all other
standards that apply to your application.
• Use redundant components and/or control paths for all critical control
functions identified in your risk assessment.
• Verify that the service life of all individual components used in your
application is sufficient for the intended service life of your overall
application.
• Perform extensive commissioning tests for all potential error situations to
verify the effectiveness of the safety-related functions and monitoring
functions implemented, for example, but not limited to, speed monitoring by
means of encoders, short circuit monitoring for all connected equipment,
correct operation of brakes and guards.
• Perform extensive commissioning tests for all potential error situations to
verify that the load can be brought to a safe stop under all conditions.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
• Carefully install the wiring in accordance with the EMC requirements.
• Do not operate the product with unknown or unsuitable settings or data.
• Perform a comprehensive commissioning test.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
10 NNZ85540.02 – 04/2022
Safety Information Soft Starter for Asynchronous Motor
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure
modes of control paths and, for critical control functions, provide a means to
achieve a safe state during and after a path failure. Examples of critical
control functions are emergency stop, overtravel stop, power outage and
restart.
• Separate or redundant control paths must be provided for critical control
functions.
• System control paths may include communication links. Consideration must
be given to the implications of unanticipated transmission delays or failures
of the link.
• Observe all accident prevention regulations and local safety guidelines (1).
• Each implementation of the product must be individually and thoroughly
tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
(1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control
and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and
Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems.
Machines, controllers, and related equipment are usually integrated into networks.
Unauthorized persons and malware may gain access to the machine as well as to
other devices on the network/fieldbus of the machine and connected networks via
insufficiently secure access to software and networks.
WARNING
UNAUTHORIZED ACCESS TO THE MACHINE VIA SOFTWARE AND
NETWORKS
• In your hazard and risk analysis, consider all hazards that result from access
to and operation on the network/fieldbus and develop an appropriate cyber
security concept.
• Verify that the hardware infrastructure and the software infrastructure into
which the machine is integrated as well as all organizational measures and
rules covering access to this infrastructure consider the results of the hazard
and risk analysis and are implemented according to best practices and
standards covering IT security and cyber security (such as: ISO/IEC 27000
series, Common Criteria for Information Technology Security Evaluation,
ISO/ IEC 15408, IEC 62351, ISA/IEC 62443, NIST Cybersecurity
Framework, Information Security Forum - Standard of Good Practice for
Information Security, SE recommended Cybersecurity Best Practices*).
• Verify the effectiveness of your IT security and cyber security systems using
appropriate, proven methods.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NNZ85540.02 – 04/2022 11
Soft Starter for Asynchronous Motor Safety Information
WARNING
LOSS OF CONTROL
Perform a comprehensive commissioning test to verify that communication
monitoring properly detects communication interruptions
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
This product meets the EMC requirements according to the standard CEI 60947-
4-1. This device has been designed for environment A. Use of this product in a
domestic environment (B environment) may cause unwanted radio interference.
WARNING
RADIO INTERFERENCE
• In a domestic environment (B environment), this product may cause radio
interference in which case supplementary mitigation measures may be
required.
• The references from ATS480D17Y to ATS480C11Y can be adapted to a
domestic environment (B environment) by adding an external bypass
contactor. For other ATS480 references, you must consider other mitigation
measures.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the
mains voltage.
Failure to follow these instructions can result in equipment damage.
12 NNZ85540.02 – 04/2022
About the Book Soft Starter for Asynchronous Motor
Step Action
1 Go to the Schneider Electric home page www.se.com.
2 In the Search box type the reference of the product or the name of a
product range.
• Do not include blank spaces in the reference or product range.
• To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search
results and click on the reference that interests you.
If you entered the name of a product range, go to the Product Ranges
search results and click on the product range that interests you.
4 If more than one reference appears in the Products search results,
click on the reference that interests you.
5 Depending on the size of your screen, you may need to scroll down to
see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX
product datasheet.
Document Scope
The purpose of this document is to:
• Show you how to install the Ethernet fieldbus on your drive.
• Show you how to configure the drive to use the Ethernet module for
monitoring and control.
• Provide examples of setup using Ethernet communication.
NOTE: Read and understand this document and all related documents (see
below) before installing, operating, or maintaining your drive.
NNZ85540.02 – 04/2022 13
Soft Starter for Asynchronous Motor About the Book
Related Documents
Use your tablet or your PC to quickly access detailed and comprehensive
information on all our products on www.se.com The Internet site provides the
information you need for products and solutions:
• The whole catalog for detailed characteristics and selection guides
• The CAD files to help design your installation, available in over 20 different
file formats
• All software and firmware to maintain your installation up to date
• A large quantity of White Papers, Environment documents, Application
solutions, Specifications... to gain a better understanding of our electrical
systems and equipment or automation
• And finally all the User Guides related to your soft starter, listed below:
You can download there technical publications and other technical information
from our website at www.se.com/en/download.
14 NNZ85540.02 – 04/2022
About the Book Soft Starter for Asynchronous Motor
Terminology
The technical terms, terminology, and the corresponding descriptions in this
manual normally use the terms or definitions in the relevant standards.
In the area of soft starters this includes, but is not limited to, terms such as error,
error message, failure, fault, fault reset, protection, safe state, safety function,
warning, warning message, and so on.
Among others, these standards include:
European standards:
• IEC 60947–1 Low–Voltage Switchgear and Control Gear – General rules
• IEC 60947–4-2 Semiconductor Motor controllers, Starters and Soft Starters
• IEC 60529 Degrees of protection provided by enclosures (IP Code)
Safety of machinery – Electrical equipment of machines – General
requirements
• IEC 60664–1 Insulation coordination for equipment within low-voltage supply
systems – Principles, requirements, and tests
• IEC 61000–4–2/-4–3/4–4/4–5/4–6/4–11/4–12 Electromagnetic Compatibility
• IEC 60721–3 Classification of environmental conditions
• IEC 61131–2: Programmable controllers – Part 2: Equipment requirements
and tests
• IEC 60068: Environmental testing
• IEC 61158 series: Industrial communication networks – Fieldbus
specifications
• IEC 61784 series: Industrial communication networks – Profiles
• IEC 62443: Security for industrial automation and control systems
European Community directives:
• 86/188/EEC Protection of Workers for the Risks Related to Exposure to Noise
at Work
• 2014/35/EU Low Voltage Directive
• 2014/30/EU EMC Directive
• 2006/42/EC Machine Directive
North American standards:
• UL 60947–4–2: Low–Voltage Switchgear and Control gear – Part 4-2:
Contactors and Motor–Starters – AC Semiconductor Motor Controllers and
Starters
NNZ85540.02 – 04/2022 15
Soft Starter for Asynchronous Motor About the Book
Other standards:
• ISO 12100:2010: Safety of machinery – General principles for design – Risk
assessment and risk reduction
• GB/T 14078.6-2016: Low—Voltage Switchgear and Control Gear - - Part 4-2:
Contactors and motor starters - - AC Semiconductor Motor Controllers and
Starters (including Soft Starters)
• IEC 61800-9-2: Adjustable speed electrical power drive systems – Part 9-2:
Ecodesign for power drive systems, motor starters, power electronics and
their driver applications – Energy efficiency indicators for power drive systems
and motor starters
In addition, the term zone of operation is used in conjunction with the description
of specific hazards, and is defined as it is for a hazard zone or danger zone in the
EC Machinery Directive (2006/42/EC) and in ISO 12100-1.
Also see the glossary at the end of this manual.
Contact us
Select your country on www.se.com/contact.
Schneider Electric Industries SAS
Head Office
35, rue Joseph Monier
92500 Rueil-Malmaison
France
16 NNZ85540.02 – 04/2022
Presentation Soft Starter for Asynchronous Motor
Presentation
Hardware Overview
General
The VW3A3720 is a dual port Ethernet modules that can be used in the following
two industrial communication protocols :
• Modbus TCP
• EtherNet/IP
In addition, of the communication services provided by each protocol, the Ethernet
module provides a set of services at the Ethernet and TCP/IP level.
The adapter offers an embedded Web server (in six languages) which offers
comfortable displaying and commissioning functions directly from a standard web
browser.
The following figure shows the hardware presentation of this module:
NNZ85540.02 – 04/2022 17
Soft Starter for Asynchronous Motor Presentation
Software Overview
Simplified TCP/IP Model
The table provides the basic overview to the simplified TCP/IP model
Network IP
Link Ethernet
18 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
Cybersecurity
Overview
The objective of Cybersecurity is to help provide increased levels of protection for
information and physical assets from theft, corruption, misuse, or accidents while
maintaining access for their intended users.
No single Cybersecurity approach is adequate. Schneider Electric recommends a
defense-in-depth approach. Conceived by the National Security Agency (NSA),
this approach layers the network with security features, appliances, and
processes.
The basic components of this approach are:
• Risk assessment
• A security plan built on the results of the risk assessment
• A multi-phase training campaign
• Physical separation of the industrial networks from enterprise networks using
a demilitarized zone (DMZ) and the use of firewalls and routing to establish
other security zones
• System access control
• Device hardening
• Network monitoring and maintenance
This chapter defines the elements that help you configure a system that is less
susceptible to cyber-attacks.
Network administrators, system integrators and personnel that commission,
maintain or dispose of a device should:
• Apply and maintain the device’s security capabilities. See Device Security
Capabilities sub-chapter for details
• Review assumptions about protected environments. See Protected
Environment Assumptions sub-chapter for details
• Address potential risks and mitigation strategies. See Product Defense-in-
Depth sub-chapter for details
• Follow recommendations to optimize cybersecurity
For detailed information on the system defense-in-depth approach, refer to the
TVDA: How Can I Reduce Vulnerability to Cyber Attacks in the Control Room
(STN V2) on se.com.
To submit a Cybersecurity question, report security issues, or get the latest news
from Schneider Electric, visit the Schneider Electric website.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default password to help prevent unauthorized access to device
settings and information.
• Disable unused ports/services and default accounts, where possible, to
minimize pathways for malicious attacks
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example: least rights, separation of
duties) to help prevent unauthorized exposure, loss or odification of data and
logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NNZ85540.02 – 04/2022 19
Soft Starter for Asynchronous Motor Cybersecurity
WARNING
UNAUTHORIZED ACCESS TO THE MACHINE VIA SOFTWARE AND
NETWORKS
• In your hazard and risk analysis, consider all hazards that result from access
to and operation on the network/fieldbus and develop an appropriate cyber
security concept.
• Verify that the hardware infrastructure and the software infrastructure into
which the machine is integrated as well as all organizational measures and
rules covering access to this infrastructure consider the results of the hazard
and risk analysis and are implemented according to best practices and
standards covering IT security and cyber security (such as: ISO/IEC 27000
series, Common Criteria for Information Technology Security Evaluation,
ISO/ IEC 15408, IEC 62351, ISA/IEC 62443, NIST Cybersecurity
Framework, Information Security Forum - Standard of Good Practice for
Information Security, SE recommended Cybersecurity Best Practices*).
• Verify the effectiveness of your IT security and cyber security systems using
appropriate, proven methods.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
20 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 21
Soft Starter for Asynchronous Motor Cybersecurity
Security Policy
NOTICE
ACCESSIBILITY LOSS
• Setup a security policy to your device and backup the device image with
security administrator user account.
• Define and regularly review the password policy.
• Periodic change of the passwords, Schneider Electric recommends a
modification of the password each 90 days.
Failure to follow these instructions can result in equipment damage.
22 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
The device does not have the capability to transmit data encrypted using the
following protocols: HTTP, Modbus slave over serial, Modbus slave over Ethernet,
EtherNet/IP, SNMP, SNTP. If other users gained access to your network,
transmitted information can be disclosed or subject to tampering.
NOTICE
CYBERSECURITY HAZARD
• For transmitting data over an internal network, physically or logically
segment the network, the access to the internal network needs to be
restricted by using standard controls such as firewalls.
• For transmitting data over an external network, encrypt protocol
transmissions over all external connections using an encrypted tunnel, TLS
wrapper or a similar solution.
Failure to follow these instructions can result in equipment damage.
Product Defense-in-Depth
Use a layered network approach with multiple security and defense controls in
your IT and control system to minimize data protection gaps, reduce single-points
of failure and create a strong cybersecurity posture. The more layers of security in
your network, the harder it is to breach defenses, take digital assets or cause
disruption.
Achilles Level 2
Strong password policy
NNZ85540.02 – 04/2022 23
Soft Starter for Asynchronous Motor Cybersecurity
Confidentiality
Information confidentiality capacity prevents unauthorized access to the device
and information disclosure.
• The user access control helps on managing users that are authorized to
access the device. Protect user credential at usage.
• The user’s passwords are encrypted in non-reversible way at rest
Information affecting the security policy of the device is encrypted in transit.
Device Integrity Protection
The device integrity protection prevents unauthorized modification of the device
with tampered or spoofed information.
This security capability helps protect the authenticity and integrity of the firmware
running on the ATS480 and facilitates protected file transfer: digitally signed
firmware is used to help protect the authenticity of the firmware running on the
ATS480 and only allows firmware generated and signed by Schneider Electric.
• Cryptographic signature of the firmware package executed at the firmware
update
• Secure root of trust ensures integrity and authenticity of the device firmware
at each power-up
Availability
The control system backup is essential for recovery from a control system failure
and/or misconfiguration and participate on preventing denial of service. It also
helps ensure global availability of the device by reducing operator overhead on
security application/deployment.
These security capabilities help manage control system backup with the device:
• Independent security policy import/export for local secure backup and
security policy sharing with other devices.
• Complete device backup/restore available on local HMI, DTM and FDR.
Communication robustness, the ATS480 Ethernet fieldbus module successfully
passed the certification Achilles L2.
User Authenticity and Authorization
The user authentication helps prevent the repudiation issue by managing user
identification and prevents information disclosure and device integrity issues by
unauthorized users.
These security capabilities help enforce authorizations assigned to users,
segregation of duties and least rights:
• User authentication is used to identify and authenticate software processes
and devices managing accounts
• Device Password policy and password strength configurable using SoMove,
DTM or EcoStruxure Control Expert
• Authorization managed according to channels
In line with user authentication and authorization, the device has access control
cryptographic features to check user credential before access is granted to the
system.
In the ATS480, the control of accessibility to the settings, parameters,
configuration, and logging database is done with a user authentication after "Log
in", with a name and password.
The ATS480 controls the access through:
• SoMove DTM (Serial and Ethernet connection)
• The webserver (Ethernet option required)
• EcoStruxure Control Expert
• EADM (EcoStruxure Automation Device Maintenance)
24 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 25
Soft Starter for Asynchronous Motor Cybersecurity
Cryptographic
signature of firmware -
package
Device backup/restore
ADMIN only
Security export/import
ADMIN only
Achilles
-
User management
ADMIN only -
Strong password
policy ADMIN only -
Access control
commissioning tools ADMIN only -
Modbus Serial
Access control
commissioning tools ADMIN only -
Modbus TCP
Access control
commissioning tools ADMIN only -
WebServer
Secure event logging
-
26 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
Password policy
Security events –
The security events base is private property of a
device and cannot be applied to another device
See Protected
Environment
Assumptions.
NNZ85540.02 – 04/2022 27
Soft Starter for Asynchronous Motor Cybersecurity
Initial Setup
Before using the device, it is mandatory to select a security policy, refer to the
Chapter Initial Setup in the User Manual NNZ85515..
Password
Changing Password
The user password can be changed from the DTM Admin options screen.
Reset Password
The Altivar Soft Starter ATS480 stores password in a secure non-reversible
format. It is impossible to retrieve a password that has been lost by his user.
For ADMIN user, a special operation is available with the graphic display terminal
to reset the ADMIN password to a default value unique to the device.
To reset the ADMIN password:
Step Action
Upon first use, the commissioning tools and webserver will request the user to
change this password prior to connecting. The cybersecurity policy does not
change when the password is reset.
Password Policy
By default, the password policy of the Altivar Soft Starter ATS480 complies with
IEEE 1686–2013 as following:
• 8 characters minimum with ASCII [32 to 122] characters
• At least one digit (0-9)
• At least one special character (@ % + ‘ ! # “ $ ^ ? : , ( ) [ ] ~ _ . ; = & / \ –
[SPACE])
In addition, for password changes, the password history is saved and prevents the
reuse of a password that has been set at least once in the last 5 times.
28 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
NOTICE
WRONG TIMESTAMPING RESULT IN NON-REPUDIATION ISSUE
• Verify and regularly realign the synchronization of the device data & time.
Failure to follow these instructions can result in equipment damage.
The security events can be read from SoMove, DTM and EcoStruxure Control
Expert. For security reasons, security logs are stored in a database to which read-
only access is provided. There is no possibility to edit or erase this log database.
The format system log record follows the syntax defined by Syslog RFC–5424
2009 and the semantic normalized by Schneider Electric.
NNZ85540.02 – 04/2022 29
Soft Starter for Asynchronous Motor Cybersecurity
<86>1 2022-01-24T09:59:53.06Z MyDevice ATS480 Credential USERACCOUNT_CHANGE [cred@3833 name="ADMIN"] Password changed
Upgrades Management
When the Altivar Soft Starter ATS480 firmware is upgraded, security configuration
remains the same until changed, including usernames and passwords.
It is recommended that security configuration is reviewed after an upgrade to
analyze rights for new or changed device features and revoke or apply them
according to your company’s policies and standards.
30 NNZ85540.02 – 04/2022
Cybersecurity Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 31
Soft Starter for Asynchronous Motor Basics
Basics
Introduction
Modbus TCP
The Modbus application layer is standard. Many of the manufacturers are already
implementing this protocol. Many have already developed a Modbus TCP/IP
connection and numerous products are currently available. With the simplicity of
its protocol and the fast Ethernet throughput data rate of 100 Mbit/s, Modbus TCP/
IP achieves excellent performance.
EtherNet/IP
EtherNet/IP is a fieldbus based on TCP and UDP. EtherNet/IP extends Ethernet
by an advanced industrial protocol (CIP, Common Industrial Protocol) as an
application layer for automation applications in this way, Ethernet suites for
industrial control. Products from different manufacturers can be networked without
the need for special interface adaptation.
Web Server
The standard webserver (in six languages) provides access to pages such as:
• My dashboard
• Display
• Diagnostics
• Device
• Setup
32 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Profile
Definition of a Profile
Types of Profiles
There are 3 types of profile:
• Communication profiles
• Functional profiles
• Application profiles
Communication Profile
A communication profile describes the characteristics of a bus or network:
• Cables
• Connectors
• Electrical characteristics
• Access protocol
• Addressing system
• Periodic exchange service
• Messaging service
• ...
A communication profile is unique to a type of fieldbus (such as Modbus,
PROFIBUS DP, and so on) and is used by different types of devices.
Functional Profile
A functional profile describes the behavior of a type of device:
• Functions
• Parameters (such as name, format, unit, type, and so on.)
• Periodic I/O variables
• State chart
• ...
Application Profile
Application profile defines the services to be provided by the devices on a
machine.
Interchangeability
The aim of communication and functional profiles is to achieve interchangeability
of the devices connected via the fieldbus.
NNZ85540.02 – 04/2022 33
Soft Starter for Asynchronous Motor Basics
Standard Profile
To be in Standard Profile, [Control Mode] CHCF is set to [Standard Profile] STD.
The Standard Profile supported by the Altivar Soft Starter is based on the CiA402,
which has been adapted to the characteristics of the Altivar Soft Starter and
therefore to all communication ports.
The control word is compliant according to CiA402.
5 bits of the control word (bits 11...15) can be assigned to a function.
NOTE:
• Altivar Soft Starter starts up following a command sequence
• After switching on and when an operating mode is started, Altivar Soft
Starter goes through several operating states
34 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Functional Description
Introduction
Soft starter operation involves one main function, which is illustrated in the
diagrams below.
NNZ85540.02 – 04/2022 35
Soft Starter for Asynchronous Motor Basics
State Diagram
After switching on and when an operating mode is started, the product goes
through a number of operating states.
The state diagram (state machine) shows the relationships between the operating
states and the state transitions. The operating states are internally monitored and
influenced by monitoring functions.
The following figure shows the Standard Mode state diagram:
36 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
1 - Not ready to switch on Initialization starts. This is a transient state invisible to the communication network.
3 - Ready to switch on The power stage is ready to switch on and awaiting power stage supply mains.
NOTE: If mains contactor is wired on a relay ([R1 Assignment] R1 is set to [Isolating Relay]
ISOL or [R3 Assignment] R3 is set to [Mains Contactor] LLC), mains contactor is not closed
and we stay in this state until a run command is given.
The power stage of the soft starter is ready to operate, but voltage has not yet been applied to the
output.
NOTE: By default, Relay R1 [R1 Assignment] R1 is set to [Operating State Fault] FLT then
the mains contactor is closed. The soft starter is locked, no power is supplied to the motor.
NOTE: If mains contactor is wired on a relay ([R1 Assignment] R1 is set to [Isolating Relay]
ISOL or [R3 Assignment] R3 is set to [Mains Contactor] LLC), we reach temporarily this
state once Run command is applied and mains contactor is closed allowing presence of
power stage before switching to 5 - Operation enabled.
5 - Operation enabled Power stage is enabled. The soft starter is in running state
For a separate control stage with mains contactor, the contactor is closed.
The soft starter functions are activated and voltage is applied to the motor terminals.
The reaction of the soft starter to a Disable operation command is to stop following to the
[Type of stop] STT.
6 - Quick stop active The soft starter performs a freewheel stop and remains locked in the operating state 6-Quick stop
active. Before restarting the motor, it is required to go to the operating state 2-switch on disabled.
The soft starter stops according to freewheel stop and then remains in state 6 - Quick stop active
until:
• The STOP key is pressed or
• A freewheel stop command via the digital input of the terminal.
7 - Fault reaction active Transient state during which the soft starter performs a stop due to a detected error.
If behavior of the detected error is configurable, then the reaction will depend on setting of it’s error
response.
8 - Fault End of the stop caused by change to the previous state 7 - Fault reaction active.
Power stage is disabled. The soft starter is locked, no power is supplied to the motor if an error
detection has been triggered. Else the soft starter change to the step 2- switch on disable.
NNZ85540.02 – 04/2022 37
Soft Starter for Asynchronous Motor Basics
Summary
Operating State Power Supply to Power Stage Power Supplied to Motor Modification of Configuration
Parameters
1 - Not ready to switch on Not required No Yes
NOTE:
• Configuration parameters are described in communication parameter file
as R/WS access type parameters. Other parameters can be accessed
whatever the operating state.
• A Setting parameter can be accessed in all operating state of the soft
starter.
38 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 39
Soft Starter for Asynchronous Motor Basics
Stop Commands
Halt Command
The Halt command enables movement to be interrupted without having to leave
the 5 - Operation enabled state. The stop is performed in accordance with the
[Type of stop] S t t parameter.
If the Halt command is active, no power is supplied to the motor and no torque is
applied.
Regardless of the assignment of the [Type of stop] STT parameter ([Freewheel]
F, [Deceleration] D, or [Braking] B) the soft starter remains in the 5 - Operation
enabled state.
Freewheel Command
A Freewheel Stop command using a digital input of the terminal or a bit of the
control word assigned to Freewheel Stop causes a change to operating state 2 -
Switch on disabled.
Function Codes
In the Standard profile, fixed assignment of a function input is possible using the
following codes:
Bit 15 C315
40 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Command
via fieldbus
Operating Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 ETA Masked
State by 006F H (1)
Switch On Quick Voltage Fault Operation Switched Ready to
Disabled Stop Enabled Enabled On Switch On
NNZ85540.02 – 04/2022 41
Soft Starter for Asynchronous Motor Basics
Starting Sequence
Description
The command sequence in the state diagram depends on how power is being
supplied to the soft starter.
There are 2 possible scenarios:
Power stage supply Mains contactor controlled by another device Mains contactor controlled by the soft starter (1)
42 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the
power stage as well. The following sequence must be applied:
Step 1
• The power stage supply is not necessarily present.
• Apply the 2 - Shut down command.
NNZ85540.02 – 04/2022 43
Soft Starter for Asynchronous Motor Basics
Step 2
• Check that the soft starter is in the operating state 3 - Ready to switch on.
• The power stage supply could be present (Voltage enabled of the status
word).
44 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Step 3
• If power supply is present; check that the soft starter is in the operating state
4 - Switched on.
NOTE: If power supply is not present, we stay in 3 - Ready to switch on.
• Then apply the 4- Enable operation command.
• The motor can be started.
NNZ85540.02 – 04/2022 45
Soft Starter for Asynchronous Motor Basics
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the
power stage as well. The soft starter controls the mains contactor.
The following sequence must be applied:
Step 1
• The power stage supply is not present as the mains contactor is not being
controlled.
• Apply the 2 - Shut down command.
NOTE:
R*: R1 or R3:
• [R1 Assignment] R1 is set to [Isolating Relay] ISOL
NOTE: If R1 is set to [Isolating Relay] ISOL, R3 can’t be set to
[Mains Contactor] LLC.
• [R3 Assignment] R3 is set to [Mains Contactor] LLC
NOTE: If R3 is set to [Mains Contactor] LLC, R1 can’t be set to
[Isolating Relay] ISOL.
46 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Step 2
• Check that the soft starter is in the operating state 3 - Ready to switch on.
• Apply the 3 - Switch on command, which closes the mains contactor and
switch on the power stage supply by giving RUN command.
• If the power stage supply is still not present in the operating state 4 - Switched
on after a time delay [Mains V. time out] LCT, the soft starter triggers an
error [Input Contactor] LCF.
NOTE:
R*: R1 or R3:
• [R1 Assignment] R1 is set to [Isolating Relay] ISOL
NOTE: If R1 is set to [Isolating Relay] ISOL, R3 can’t be set to
[Mains Contactor] LLC.
• [R3 Assignment] R3 is set to [Mains Contactor] LLC
NOTE: If R3 is set to [Mains Contactor] LLC, R1 can’t be set to
[Isolating Relay] ISOL.
NNZ85540.02 – 04/2022 47
Soft Starter for Asynchronous Motor Basics
48 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
ICMP Protocol
The VW3A3720 Ethernet modules manage the ICMP protocol.
• ICMP client: not supported
• ICMP server: the managed requests are the following:
Type Description
3 Destination unreachable
4 Sources quench
5 Redirect
6 Alternate host address
8 Echo request (ping)
9 Router advertisement
10 Router solicitation
11 Time exceeded
12 Parameter problem
15 Information request
16 Information reply
IP Protocol
The Ethernet adapter implements the IPV4 and IPV6 (for DPWS) protocols.
SNMP Services
The Ethernet adapter accepts the community name “private” for writing and the
community name “public” for Reading.
MIB
Objects Description Access Default Value
SysDescr Text description of the product Read only Schneider Electric Altivar
Ethernet TCP/IP
SysObjectID Points in the private MIB on the Read only 1.3.6.1.4.1.3833.1.100.4.2
product part number
NNZ85540.02 – 04/2022 49
Soft Starter for Asynchronous Motor Basics
50 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
XID (4 bytes)
CIADDR (4 bytes)
YIADDR (4 bytes)
SIADDR (4 bytes)
GIADDR (4 bytes)
Field Description
xid Transaction identifier, random number chosen by the client allowing to associate the
request and the response
ciaddr Client IP address, only used if the client can respond to ARP request
DHCP Message
The DHCP protocol uses 8 different types of message during the IP assigning
process.
The following table describes the 8 messages:
Message Description
DISCOVER The client tries to discover the DHCP server using a broadcast
REQUEST The client chooses a DHCP server and declines other offers
NNZ85540.02 – 04/2022 51
Soft Starter for Asynchronous Motor Basics
Message Description
RELEASE The client releases Its IP address before the end of the lease
INFORM The client asks for network information (it already has an IP address)
Operating Modes
The choice between DHCP, BOOTP, and fixed configuration is made through one
parameter:
• Fixed: the Ethernet adapter uses the address stored in parameter.
• BOOTP: the Ethernet adapter receives the addresses from BOOTP server.
• DHCP: if the device name [XXX] is valid, the Ethernet adapter receives the
addresses from the DHCP server.
52 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
TCP Telegrams
Modbus TCP telegrams are not only Modbus standard requests and responses
encapsulated in TCP frames.
1 TCP header
2 MBPA: Modbus application protocol header
3 ADU: Application data unit
4 PDU: Protocol data unit (The Modbus message itself)
NNZ85540.02 – 04/2022 53
Soft Starter for Asynchronous Motor Basics
Overview
Unit ID Modbus TCP server Accessible parameters
255 Soft starter I/O scanner See I/O scanner setting, page 55
Write multiple registers 16 10 hex Write N output word Max PDU length: 123
words
Read/write multiple 23 17 hex Read/write multiple Max PDU length: 121
registers (Uint ID 0-248 and registers words (W), 125 words
255) (R)
Identification
Id Value Comment
00 hex Schneider Electric Device manufacturer
01 hex ATSXXX Soft starter commercial part
number
02 hex 0101 Soft starter version
04 hex − −
05 hex − −
54 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Up to output 32 0
Up to Input 32 0
EtherNet/IP Features
EtherNet/IP
NNZ85540.02 – 04/2022 55
Soft Starter for Asynchronous Motor Basics
Overview
This part gives a description of the assembly sets and how to configure them.
Introduction
Parameters of the soft starter can be accessed by R/W as CIP objects.
56 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
CIP Object
Supported Object Classes
Introduction
Two categories of object classes can be defined:
• CIP device on EtherNet/IP
• Communications Adapter Device (0x0C) Profile
These objects are detailed in the following table:
Overview
This object provides identification of and general information about the device.
Class Code
Hexadecimal Decimal
01 hex 1
NNZ85540.02 – 04/2022 57
Soft Starter for Asynchronous Motor Basics
Class Attributes
Attribute Access Name Data Value Details
ID type
Instance Attributes
Attribute Access Name Data Value Details
ID type
USINT
5 Get Status WORD – See definition in the
following table
Second…Fourth byte:
last 3 bytes of MAC-ID
STRING
Attribute 5–Status
Bit Definition How
0 Owned by scanner No interface
(predefined scanner/adapter
connection)
58 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Others Reserved 0 –
1001
1 0 1 0 to Vendor specific –
1111
NNZ85540.02 – 04/2022 59
Soft Starter for Asynchronous Motor Basics
Overview
The Message Router Object provides a messaging connection point through
which a Client may address a service to any object class or instance residing in
the physical device
This is the element through which all the Explicit messages objects pass in
order to be directed towards the truly destined objects.
Class Code
Hexadecimal Decimal
02 hex 2
Class Attributes
Attribute ID Access Name Data type Value Details
60 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Overview
The Assembly Object binds attributes of multiple objects, which allows data to or
from each object to be sent or received over a single connection.
Supported Instances
NNZ85540.02 – 04/2022 61
Soft Starter for Asynchronous Motor Basics
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Overview
Use this object for connection and connectionless communications, including
establishing connections across multiple subnets.
Class Code
Hexadecimal Decimal
06 hex 6
62 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Class Attributes
Attribute Access Name Need Data Value Details
ID type
3: Established
5: Deferred Delete
2 Get Instance_type Req. USINT 0 Explicit Message
3: Deferred Delete
(Default)
14 Get Produced connection path Req. Array of UINT Null Not used
16 Get Consumed connection path Req. Array of UINT Null Not used
NNZ85540.02 – 04/2022 63
Soft Starter for Asynchronous Motor Basics
Overview
ODVA describes how to encapsulate a Modbus frame using a CIP object.
Modbus Class Object presents the ethernet IP interface with the Modbus
encapsulation service defined in the ODVA.
Class Code
Hexadecimal Decimal
44 hex 44
64 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Overview
The whole parameter mapping of the soft starter be accessible through the
Application objects.
NNZ85540.02 – 04/2022 65
Soft Starter for Asynchronous Motor Basics
Overview
The port object represents the underlying interface of CIP which is EtherNet/IP.
Class Code
Hexadecimal Decimal
F4 hex 244
Class Attributes
Attribute ID Access Name Data type Value Details
Overview
The TCP/IP Interface Object provides the mechanism to configure a device’s
TCP/IP network interface. Examples of configurable items include the device’s IP
Address, Network Mask, and Gateway Address.
66 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
0008
0004
6 Get Max ID of class UINT 7 –
attributes
7 Get Max ID of instance UINT 17 –
attribute
2 Get Configuration DWORD Bit 0 = 1 (TRUE) shall indicate that the device is
capability capable of obtaining its network configuration
via BOOTP
NNZ85540.02 – 04/2022 67
Soft Starter for Asynchronous Motor Basics
Domain name
6 Get/Set Host name String Read/write name of the soft starter
8 Get/Set TTL value USINT TTL value for EtherNet/IP multicast packets
01 hex Get_Attribute_All –
68 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
Overview
The Ethernet Link Object maintains link-specific counters and status information
for an IEEE 802.3 communications interface. Each device shall support exactly
one instance of the Ethernet Link Object for each IEEE 802.3 communications
interface on the module.
Class Attributes
Attribute Access Name Data Value Details
ID type
2 Get Interface flags DWORD Bit 0: Link status indicates whether the Ethernet
802.3 communications interface is connected to
an active network. 0 indicates an inactive link; 1
indicates an active link
NNZ85540.02 – 04/2022 69
Soft Starter for Asynchronous Motor Basics
6 Get/Set Interface control – Force auto negotiate, half full and speed
01 hex Get_Attribute_All –
01 hex Get_Attribute_All –
70 NNZ85540.02 – 04/2022
Basics Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 71
Soft Starter for Asynchronous Motor Hardware Setup
Hardware Setup
Hardware Presentation
Ethernet Dual Port
The figure shows VW3A3720 Ethernet Module equipped with 2 RJ45 connectors:
NOTE: The VW3A3721 module has the same comportment as the
VW3A3720.
Firmware Version
VW3A3720 Compatibility
ATS480 soft starters with, at least, V1.1IE01 software version, are only compatible
with VW3A3720 Ethernet module versions V2.1 and higher.
72 NNZ85540.02 – 04/2022
Hardware Setup Soft Starter for Asynchronous Motor
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage
whatsoever.
Step Action
2 Locate the fieldbus module slot on the bottom of the control part.
NNZ85540.02 – 04/2022 73
Soft Starter for Asynchronous Motor Hardware Setup
Step Action
Electrical Installation
Pin Layout
The VW3A3720 Ethernet module is equipped with 2 RJ45 female sockets for the
Ethernet connection.
The table provides the pin out details of each RJ45 connector:
5 − −
8 − −
74 NNZ85540.02 – 04/2022
Hardware Setup Soft Starter for Asynchronous Motor
Cable Specification
Cable specifications are as follows:
• Ethernet cable must be AWG24 & SF/FTP
• Minimum Cat 5e
• Use equipotential bonding conductors (100 BASE-TX, category 5e or
industrial Ethernet fast connect)
• Connector RJ45, no crossover cable
• Shield: both ends grounded
• Twisted-pair cable
• Use pre-assembled cables to reduce the wiring mistakes
• Verify that wiring, cables, and connected interfaces meet the PELV
requirements.
• Maximum cable length per segment = 100 m (328 ft)
NOTE: RSTP function is not compatible with half duplex configuration. All
devices involved in the RSTP topology shall be RSTP capable and configured.
NNZ85540.02 – 04/2022 75
Soft Starter for Asynchronous Motor Hardware Setup
NOTE: When using the ring topology, all the drives in the ring must have
RSTP configuration enabled.
• Redundant star topology with RSTP
76 NNZ85540.02 – 04/2022
Hardware Setup Soft Starter for Asynchronous Motor
The following figure shows the direct connection between the soft starter and PC.
Accessories Presentation
Information
Connection accessories should be ordered separately (See the catalog).
NNZ85540.02 – 04/2022 77
Soft Starter for Asynchronous Motor Software Setup
Software Setup
Basic Settings
Structure of the Parameter Table
General Legend
Pictogram Description
This parameter can be set during operation or when stopped.
NOTE: It is advisable to stop the motor before modifying any of the settings
The motor must be stopped to set this parameter.
Menu Presentation
Below an example of a menu presentation:
[Short Label] CODE
Access path: [Menu] [Sub-menu]
About this menu
Description of the menu.
Parameter Presentation
Below an example of a parameter presentation:
78 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
NNZ85540.02 – 04/2022 79
Soft Starter for Asynchronous Motor Software Setup
IP Parameter Settings
Assigning IP Parameters
If not using IPV6 functionalities for DPWS, following parameters shall be
configured:
• The soft starter IP address.
• The subnet mask.
• The gateway IP address.
These IP addresses can be entered using the display terminal, the embedded
webserver, or the DTM-based PC software.
They can be also provided by:
• A BOOTP server (correspondence between the MAC address and the IP
addresses).
• Or a DHCP server (correspondence between device name [Device Name]
PAN and the IP addresses).
If an IP address other than 0.0.0.0 has been entered manually, assignment using
a server is disabled. Regardless of the type of IP address assignment, if the
address is modified, then the IP address is effective the next time the soft starter is
turned on (control voltage if a separate power supply is being used).
Configuring BOOTP
The BOOTP service is used to assign IP addresses based on the MAC address.
The MAC address consisting of 6 hexadecimal digits (MM-MM-MM-XX-XX-XX)
must be entered in the BOOTP server. The MAC address appears on the fieldbus
adapter dedicated menu on the display terminal.
In the [Communication] COM and [Eth Module Config] ETO submenu:
• Leave the IP address [ETH Option IP] IC11, IC12, IC13, IC14 at the value
[0.0.0.0] 0 0 0 0 .
• Do not enable the FDR service.
Configuring DHCP
The DHCP service is used to assign IP addresses and FDR configuration file path
based on the device name [Device Name] PAN .
The device name consisting of an alphanumeric string must be entered in both the
DHCP server and the soft starter.
In the [Communication] COM and [Eth Module Config] ETO submenu, enter the
[Device Name] PAN
80 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Access
This menu is accessible via [Communication] COM.
Possible Settings
The table presents the parameter settings:
NNZ85540.02 – 04/2022 81
Soft Starter for Asynchronous Motor Software Setup
WARNING
LOSS OF CONTROL
If this parameter is set to [Ignore] NO, fieldbus module communication monitoring is disabled.
• Only use this setting after a thorough risk assessment in compliance with all regulations and standards
that apply to the device and to the application.
• Only use this setting for tests during commissioning.
• Verify that communication monitoring has been re-enabled before completing the commissioning
procedure and performing the final commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
The Restart function performs a Fault Reset and restarts the device.
• Verify that activating this function does not result in unsafe conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
82 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Access
This menu is accessible via: [Communication] COM [Eth Module Config]
ETO
These parameters can be accessed if [ETH Option IP Mode] IM10 is set to
[DHCP] DHCP.
Possible Settings
The table presents the parameter settings:
NNZ85540.02 – 04/2022 83
Soft Starter for Asynchronous Motor Software Setup
Remedy:
To eliminate the FDR error, the following steps must be performed:
• Change [ETH Option IP Mode] IM10 to [DHCP] DHCP and restart the soft starter.
• FDR is active and Automatic Syncho Cycle is off.
• Disable the FDR and restart the soft starter.
• Change the [ETH Option IP Mode] IM10 to [Fixed] MANU and restart the soft starter.
84 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Access
This menu is accessible via: [Communication] COM [Communication map]
CMM
Possible Settings
The table presents the parameter settings:
This parameter displays the MAC address of the device in the format [MM-MM-MM-XX-XX-XX].
[ETH opt Rx frames] ERXO Logic address: FBD2 hex = 64466 Type: UINT (Unsigned32)
Read/write: R
NNZ85540.02 – 04/2022 85
Soft Starter for Asynchronous Motor Software Setup
Remedy:
• A faulty or duplicate address can cause conflicting issues.
• Try setting a different fixed IP address
[Fieldbus Com Interrupt] Logic address: 1BE8 hex = 7144 Type: UINT (Unsigned16)
CNF
CIP Path: 84/01/91 hex = 132/01/145 Read/write: R
Remedy:
Increase the value of [Ethernet Timeout] TOUT.
[InternCom Error1] ILF1 Logic address: 1BDE hex = 7134 Type: UINT (Unsigned16)
CIP Path: 84/01/87 hex = 132/01/135 Read/write: R
Remedy:
• Verify the connections.
• Replace the Ethernet module.
This detected error requires a power reset.
86 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Communication parameters
Logic I/O
Code Settings
[Logic Inputs States] IL1R Logic address: 1452 hex = 5202 Type: WORD (BitString16)
CIP Path: 7B/01/03 hex = 123/01/03 Read/write: R
Unit: -
Logic inputs states
• Bit0 : "DI1" Digital inputs real image
• Bit1 : "DI2" Digital inputs real image
• Bit2 : "DI3" Digital inputs real image
• Bit3 : "DI4" Digital inputs real image
[Logic Outputs States] Logic address: 145C hex = 5212 Type: WORD (BitString16)
OL1R
CIP Path: 7B/01/0D hex = 123/01/13 Read/write: R/W
Unit: -
Logic outputs states
• Bit0 : "R1" relay real image
• Bit1 : "R2" relay real image
• Bit2 : "R3" relay real image
• Bit8 : "DQ1" digital outputs real image
• Bit9 : "DQ2" digital outputs real image
The relay or logic outputs can be controlled via the network. Simply write this parameter. The outputs to be
controlled must not be assigned to a soft starter function, otherwise the write operation has no effect.
NNZ85540.02 – 04/2022 87
Soft Starter for Asynchronous Motor Software Setup
Analog inputs
Code Settings
[AI1] AI1C Logic address: 147A hex = 5242 Type: INT (Signed16)
CIP Path: 7B/01/2B hex = 123/01/43 Read/write: R
Unit: -
Physical value AI1
AI1 customer image (1mV, 0.001mA)
• (AI1T == "PTC") : 0.01 kOhm
• (AI1T == "1PT2") : 0.1 Ohm
• (AI1T == "1PT23") : 0.1 Ohm
• else : 0.001 V
[Analog Input 1 Logic address: 1470 hex= 5232 Type: INT (Signed16)
Standardized Value] AI1R
CIP Path: 7B/01/21 hex = 123/01/33 Read/write: R
Unit: -
Analog input 1 standardized value
AI1 real application image
Analog outputs
The analog outputs can be controlled via the network. Simply write these
parameters. The outputs to be controlled must not be assigned to a soft starter
function, otherwise the write operation has no effect
Code Settings
[AQ1] AO1C Logic address: 1497 hex = 5271 Type: INT (Signed16)
CIP Path: 7B/01/48 hex = 123/01/72 Read/write: R/W
Unit: -
AQ1 physical value
AQ1 customer image (1mV, 0.001mA)
[Analog Output 1 Logic address: 148D hex = 5261 Type: INT (Signed16)
Standardized Value] AO1R
CIP Path: 7B/01/3E hex = 123/01/62 Read/write: R/W
Unit: -
Analog output 1 standardized value
AQ1 real application image
88 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Base Monitoring
Code Settings
[Status Register] ETA Logic address: 0C81 hex = 3201 Type: WORD (BitString16)
CIP Path: 71/01/02 hex = 113/01/02 Read/write: R
Unit: -
Status Register
• Bit0 = 1 : Ready to switch on
• Bit1 = 1 : Switched on
• Bit2 = 1 : Operation enabled
• Bit3 = 1 : Detected error
• Bit4 = 1 : Voltage enabled
• Bit5 = 0 : Quick stop active
• Bit6 = 1 : Switch on disabled
• Bit7 = 1 : Alarm present
• Bit8 : Reserved
• Bit9 = 0 : Local mode control
• Bit10 to Bit13: Reserved
• Bit14 = 1 : Stop imposed by STOP key
• Bit15 : Reserved
[Motor Current] LCR Logic address: 0C84 hex = 3204 Type: UINT (Unsigned16)
CIP Path: 71/01/05 hex = 113/01/05 Read/write: R
Unit: 0.1 A
Motor current
RMS Motor current. Average of the three line currents based on the measurement of the fundamental of the
motor line currents.
[Motor Therm State] THR Logic address: 259E hex = 9630 Type: UINT (Unsigned16)
CIP Path: 91/01/1F hex = 145/01/31 Read/write: R
Unit: 1 %
Motor thermal state
This parameter monitors the motor thermal state. 100% corresponds to the nominal thermal state at the
nominal motor current set to [Motor Nom Current] IN.
Refers to the ATS480 User Manual NNZ85515 for more information.
[Motor Run Time] RTH Logic address: 0CAC hex = 3244 Type: UINT (Unsigned32)
CIP Path: 71/01/2D hex = 113/01/45 Read/write: R
Unit: 1 s
Motor run time
This parameter monitors how long the motor has been energized.
[Elc Energy Cons] OCK Logic address: 299C hex = 10652 Type: UINT (Unsigned32)
CIP Path: 96/01/35 hex = 150/01/53 Read/write: R/WS
Unit: kWh
Electrical energy consumed by the motor (kWh)
NNZ85540.02 – 04/2022 89
Soft Starter for Asynchronous Motor Software Setup
Code Settings
[Active Command Channel] Logic address: 20FA = 8442 Type: WORD (BitString16)
CCC
CIP Path: 8B/01/2B = 139/01/43 Read/write: R
Unit: -
Active command channel
Active command channels status
• Bit0 = 1 : Terminal board
• Bit2 = 1 : Deported keypad
• Bit3 = 1 : Modbus
• Bit6 = 1 : CANopen
• Bit9 = 1 : COM option board
• Bit14 = 1 : Indus
• Bit15 = 1 : SoMove
Command Register
Code Settings
[Cmd Register] CMD Logic address: 2135 hex = 8501 Type: WORD (BitString16)
CIP Path: 8B/01/66 hex = 139/01/102 Read/write: R/W
Unit: -
90 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Code Settings
[Extended Control Word] Logic address: 2138 hex = 8504 Type: WORD (BitString16)
CMI
CIP Path: 8B/01/69 hex = 139/01/105 Read/write: R/W
Unit: -
• Bit0 – Restore factory settings request: Active on rising edge when motor is powered off. Once request
is considered, this bit is automatically reset
• Bit1 – Store customer parameters request: Active on rising edge when motor is powered off. Once
request is considered, this bit is automatically reset
• Bit2 – Restore saved customer parameters: Active on rising edge when motor is powered off. Once
request is considered, this bit is automatically reset
• Bit3 = 1 : External error: Active on rising edge
• Bit4 to Bit12: Reserved
• Bit13 = 1 : Lock device when motor stopped
• Bit14 = 1 : Disable line monitoring
• Bit15 : Disable parameter consistency check
◦ Bit15 = 1 : no check of parameter consistency and device is locked when stopped
◦ Bit15 = 0 : all parameters are validated
NNZ85540.02 – 04/2022 91
Soft Starter for Asynchronous Motor Software Setup
Additional Settings
[EnableOptWeb] EWE
Access
This parameter is accessible via: [Device Management] DMT
[Cybersecurity] CYBS [Access control] CSAC
Possible Settings
The table presents the parameter settings:
WARNING
UNAUTHENTICATED ACCESS AND MACHINE OPERATION
Do not disable the feature if your machine or process is accessible to
unauthorized personnel either directly or via a network.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
92 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Factory setting
NNZ85540.02 – 04/2022 93
Soft Starter for Asynchronous Motor Software Setup
94 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
FDR Settings
Access
The parameters are accessible via the webserver or the DTM-based PC software
FDR Configuration
The following figure shows FDR settings via webserver:
Automatic Syncho Cycle Allows you to select the interval 100...655350 sec
(x 10 Sec) for periodic synchronization of
the soft starter with the FDR Factory setting: 100 sec
server.
NOTE: You can configure
automatic Synchro cycle
only if Synchronization
mode check box is
selected.
NNZ85540.02 – 04/2022 95
Soft Starter for Asynchronous Motor Software Setup
RSTP Settings
Access
The parameters are accessible via the DTM-based PC software.
Bridge Settings
The following figure shows the bridge settings using the DTM:
Bridge Priority The bridge priority is used to control which bridge is elected 0 0 hex
as the root bridge.
4096 1000 hex
Bridge with the smallest (lowest) bridge ID is elected as the
root bridge. Bridge ID consists of the configurable priority 8192 2000 hex
and the MAC address of the bridge.
12288 3000 hex
To compare 2 bridge ids, bridge priorities are compared
first. If the bridge priorities are equal, then the MAC 16384 4000 hex
addresses are compared.
20480 5000 hex
The bridge priority can be set only in increments of 4096
24576 6000 hex
Max age time (6-40 s) The maximum age time correspond to the maximum 6...40 sec
expected arrival time of hello BPDUs. If the timer expires,
the bridge detects acommunication interruption to the root
bridge and initiates a topology convergence.The maximum
age timer should be longer than the configured hello time.
96 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
Ports Configuration
The following figure shows the port settings:
Port Path Cost Allows you to define the cost of sending 0...1,569,325,055
spanning tree traffic through the NOTE: If the port path cost is
interface. set to 0 (auto), the path cost is
based on the port link speed
RSTP uses path cost to determine the
maximum, for details see the
topology with the smallest total path cost
following table.
between each point of the tree and the
root bridge.
Port Select Allows you to select the type of ports. RSTP Port
With the port types defined, RSTP can
quickly reconfigure a network when a Edge Port
change in network topology is detected.
Table provides the value of the path cost based on the port link maximum speed
NNZ85540.02 – 04/2022 97
Soft Starter for Asynchronous Motor Software Setup
Description
The soft starter I/O scanning service can be enabled or disabled with the DTM-
based PC software.
It is not possible to modify the assignment of the I/O scanning periodic variables
using the display terminal. To configure I/O scanning, use the DTM-based PC
software.
DNS Settings
Description
The Domain Name System (DNS) is a distributed naming system for devices
connected to the network.
It translates domain names to IP addresses for locating the devices easily on the
network.
DNS Configuration
The DNS configuration can be done using the DTM-based PC software.
The following figure shows the DNS configuration window:
DNS Configuration window by the Web Server DNS Configuration window by the DTM
Item Description
1 Obtain DNS Server address automatically: When checked, the function is enabled
and allows getting automatically the IP address from the DNS server.
2 Preferred DNS server: Enter the IP address of the preferred DNS server.
3 Alternate DNS server: Enter the IP address of the alternate DNS server.
NOTE: The alternate IP address is used only if the first server is unavailable.
the button.
98 NNZ85540.02 – 04/2022
Software Setup Soft Starter for Asynchronous Motor
SNTP Settings
Description
The Simple Network Time Protocol (SNTP) is networking protocol for clock
synchronization of devices connected to the network.
SNTP Configuration
The SNTP configuration can be done using the DTM-based PC software.
The following figure shows the SNTP Configuration window:
SNTP Configuration window by the Web Server SNTP Configuration window by the DTM
Item Description
3 Server 2 IP Address: Enter the IP address of the second preferred SNTP server.
NOTE: This IP address is used for SNTP only if the first server is unavailable.
4 Polling Interval: Allows you to select the scanning interval for checking the time
change.
Item Description
the button.
NNZ85540.02 – 04/2022 99
Soft Starter for Asynchronous Motor Software Setup
SNMP Settings
Description
Simple Network Management Protocol (SNMP) is an internet-standard protocol
used to manage devices on IP networks.
It is used for collecting and organizing information about the devices on the
network.
SNMP Configuration
The SNMP configuration can be done using the DTM-based PC software.
The following figure shows the SNTP Configuration window:
SNMP Configuration window by the Web Server SNMP Configuration window by the DTM
Manager's IP Address
SNMP manager is a central system used for monitoring and controlling the SNMP
agents.
The table presents Manager’s IP Address settings:
Item Description
1a Manager 1: SNMP manager is a central system, which is used for monitoring and
controlling the SNMP agents.
Agents
Agents are the devices which are connected to the network. The SNMP manager
monitors these devices.
The table presents the Agents settings:
Item Description
1b System Name: Enter the system name used by the soft starter.
Community Names
Community names are used to identify the commands that can be performed by
an SNMP manager on a device.
The table presents the Community Names settings:
Item Description
3c Trap: Requests send from manager to agent to find the available data.
Enabled Traps
Traps are used to inform the SNMP manager of specific events occurring on
device.
The table presents the Enabled Traps settings:
Item Description
FDR Service
The FDR (Fast Device Replacement) service is used to simplify the maintenance
of soft starters connected to an Ethernet network. In the event of a soft starter not
working correctly, this service automatically reconfigures its replacement.
The new soft starter (FDR client) retrieves:
• Its IP addresses and the FDR file path from a DHCP server
• The FDR file from an FTP server if the soft starter is not configured in local
configuration
In practice, the DHCP server and the FTP server are the same device (PAC M580,
M340 PLC, or dedicated PCs).
The FDR file contains:
• The Ethernet parameters (configuration of I/O scanning, FDR, and so on)
• The soft starter parameters (soft starter, functions, application, and so on)
The FDR service is based on identification of the device by a Device Name. In the
case of the soft starter, this is represented by the [Device Name] PAN parameter.
The configuration of the FDR service is accessible via embedded webserver or
DTM-based software or Graphic Display Terminal.
NOTE: Check that all the network devices have different Device Name.
The FDR server controls duplication of Device Name (it does not assign an IP
address that has already been assigned and is active).
If the same IP address is supplied on 2 devices, the second should trigger an IP
address duplication (network management detected error which triggers an
[Fieldbus Error] EPF2 by default).
If the FDR service has been enabled, the Ethernet adapter attempts to restore its
IP addresses on each power-up. Each time the procedure has detected error, the
Ethernet adapter reiterates its FDR requests (DHCP).
After assigning the Ethernet adapter IP addresses, if the configuration is not
downloaded successfully, the Ethernet adapter triggers a [FDR 2 Error] FDR2.
Presentation
Local Configuration
Presentation
IP Assignment Save
If the soft starter parameter configuration is local, the FDR server only assigns the
following IP addresses:
• IP address,
• Subnet mask,
• Gateway IP address.
On connection to the network, the soft starter automatically saves its parameters
in the FDR server.
1 Configure the FDR server See the PLC manual or the section on software setup
using Unity
2 Configure the soft starter This menu is accessible via [Communication] COM,
[Eth Module Config] ETO submenu.
• Configure [ETH Option IP Mode] IM10 =
[DHCP] DHCP
• Enable the FDR service via webserver or DTM-
based software or Graphic Display Terminal.
• Select local soft starter configuration with
webserver or DTM-based software.
• Enter the device name, DEVICE NAME, in the
[Communication] COM, [Eth Module Config]
ETO submenu.
3 Turn off the soft starter Turn off the soft starter and then back on again (control
voltage supply if a separate power supply is being
used), otherwise the device name is not taken into
account
4 Connect the soft starter to the Connect the soft starter and the FDR server (PLC) to
network the Ethernet network
Downloaded Configuration
Presentation
IP Assignment Save
If the soft starter parameter configuration has been downloaded, the FDR server
assigns the following addresses:
• IP address,
• Subnet mask,
• Gateway IP address,
• FDR server IP address.
Periodic Saving
Periodic saving of the soft starter configuration can be configured on the FDR
server in either local configuration or downloaded configuration mode
Using the embedded webserver or the DTM-based software:
• Set FDR synchronization to automatic mode
• Set the synchronization cycle time
NOTE: Saving too often overburden the fieldbus and adversely affects its
performance (factory setting: 2.560 s.).
Limitations
The FDR service is able to store the current configuration of the soft starter, but
does not provide the possibility to store multi-parameters configurations.
1 Configure the soft starter This menu is accessible via [Communication] COM,
[Eth Module Config] ETO submenu.
• Leave the IP address [ETH Option IP] IC11,
IC12, IC13, IC14 at the value [0.0.0.0] 0 0
0 0.
Using the embedded webserver or the DTM-based
software:
• Set FDR synchronization to manual mode.
• Before the first connection, select local soft
starter configuration. The soft starter needs first
to push the configuration to the server.
• Enter the device name, DEVICE NAME, in the
[Communication] COM, [Eth Module Config]
ETO submenu.
2 Turn off the soft starter Turn off the soft starter and then back on again
(control voltage if a separate power supply is being
used), otherwise the device name is not taken into
account
3 Connect the soft starter to the Connect the soft starter and the FDR server (PLC) to
fieldbus the Ethernet fieldbus.
4 Configure the FDR server (see The server downloads the IP addresses to the
the PLC manual) Ethernet adapter.
Check that the operation has proceeded correctly:
you can also check, in the [Communication] COM,
[Eth Module Config] ETO submenu.
5 Supply the FDR server with the Using the embedded webserver or the DTM-based
configuration file software
• Specify that the soft starter configuration is
downloaded from the FDR server on each
power-up
• Send a save command to the FDR server.
6 Check that the system is If the save operation has not been successful, the
operational adapter detects a communication error which, in
factory settings mode, triggers a [FDR 2 Error]
FDR2.
1 Configure the soft starter This menu is accessible via [Communication] COM,
[Eth Module Config] ETO submenu.
• Leave the IP address [ETH Option IP] IC11,
IC12, IC13, IC14 at the value [0.0.0.0] 0 0
0 0.
Using the embedded webserver or the DTM-based
software:
• Set FDR synchronization to manual mode.
• Before the first connection, select served soft
starter configuration. The soft starter needs first
to transfer the configuration from the server.
• Enter the device name, DEVICE NAME, in the
[Communication] COM, [Eth Module Config]
ETO submenu.
2 Turn off the soft starter Turn off the soft starter and then back on again
(control voltage if a separate power supply is being
used), otherwise the device name is not taken into
account
3 Connect the soft starter to the Connect the soft starter and the FDR server (PLC) to
fieldbus the Ethernet fieldbus
4 Check that the soft starter is Check that the operation has proceeded correctly.
operational
If downloading has not been possible after a period of
2 min following assignment of the IP addresses, the
adapter detects a communication error which, in
factory settings mode, triggers an [FDR 2 Error]
FDR2.
Embedded Webserver
Overview
Webserver
The Ethernet adapter provides an integrated Web server (in six languages) which
allows several functions like: display, parameter settings, and diagnostics. This
chapter describes the services provided by this webserver.
The webserver can be accessed from standard browsers like Internet Explorer,
Chrome, Safari, or Firefox.
Access
The webserver can be accessed from standard browsers.
In the following example, the soft starter has received the IP address 10.0.0.5:
First connect the computer to the soft starter by typing http:// followed by the soft
starter IP address.
You are asked to first enter a User Name and a Password.
By default the user name is ADMIN. If you are connecting to the webserver for the
first time, the password is available:
• on the sticker of the ethernet option module.
• with the Graphic Display Terminal in the [Cybersecurity] CYBS submenu and
[Access control] CSAC submenu.
Once logged in you are asked to change the default connection ID (Password),
according to the default security access rule. Access rules can be modified in the
Setup/Access Management web page.
Once connected, the webserver home page is displayed.
Using IPV6 network discovery service, there is no need to set IP parameters. The
soft starter appears automatically in the network explorer of the PC while
physically connected.
The soft starter is identified as ATS••••••••-XXXX where XXXX is the two last bytes
of the MAC address.
Right-click and select Display device web page to open the webserver.
NOTE: If the soft starter was first connected to the SoMove-DTM via the
Ethernet option module, and this user's authentication password has been
changed, the default password is no longer applicable. The new password is
set. This new password is not displayed on the Graphic Display Terminal.
NOTE: A soft starter's configuration with a firmware version or higher can not
be transfered via Webserver to an drive with a firmware version or lower.
My Dashboard
Overview
The following table provides the procedure to add the widget to this page:
Step Action
The following figure shows the widgets that can be added. Various widgets of a
same category are available.
Display - Device
Data Table
The following table provides the procedure to create data tables of soft starter
parameters.
Step Action
1 Type the name of the table. Spaces are not allowed in this field.
2 Select a parameter by clicking the top of the parameter or typing the code and
clicking the button. To delete a parameter while creating the table click the
parameter.
3
Click the Add Table button. To remove a table click the button, only visible
when the table is selected.
Chart Viewer
The following table provides the procedure to create a chart viewer.
Step Action
1 Type the name of the chart. Spaces are not allowed in this field.
5 Select a parameter by clicking the top of the parameter or typing the code and
clicking the button. To delete a parameter while creating the chart click the
parameter. Maximum of five parameters can be selected.
6
Click the Create Chart button. To remove a chart click the button, only visible
when chart is selected.
Setup - My Preference
User Access
In this menu, the access to the Web server can be managed by users with
administrator rights. These users can add, remove, block, unblock, and modify the
access rights of other users.
The following table shows the description of the buttons located in this menu:
Button Description
Add a new user, typing the name of the user; the password and the access rights.
Change the password. The administrator can change the password of other users.
Themes
In this menu, the aspect of the Web server can be changed. Predefined themes
are available, which can be customized.
The following table provides the procedure for creating new themes
Step Action
1
Click the button.
2 Type the name of the theme. Spaces are not allowed in this field.
4
Upload a logo by clicking the button.
Access Management
Select if login credentials are required or not to access to the web server.
Overview
The following figure shows the basic configuration to control the soft starter with a
M580 PLC.
EtherNet/IP Configuration
PLC Configuration
Click on the active port:
The configuration of the memory area of the PLC is set by default and can be
modified.
Overview
In the following example, the soft starter configuration must be done as follows in-
order to establish communication between the soft starter and the M580.
The soft starter configuration is done using the Control Expert software.
Factory Settings
Before configuring the soft starter, make sure that you reset the soft starter to
factory settings.
• Right click on the device, select Device menu > Additional functions >
Factory Settings > Execute:
Command Configuration
To control the soft starter with an Ethernet scanner, select Ethernet scanner as
active command.
Go to:
• Parameters List tab
• Click on Command channel part
Result: Following window is displayed:
Ethernet Configuration
To set the Ethernet address of the soft starter, go to:
• Communication, Slot A - Modbus TCP/EtherNetIP, Generic Setttings.
Result: Following window is displayed:
NOTE:
Click on Apply button to validate the configuration then restart the soft starter.
Result: After setting the previous data, following configuration is entered:
Assemblies Configuration
To configure the assemblies used for EtherNet/IP fieldbus, go to:
• Communication, Slot A - Modbus TCP/EtherNetIP, Protocol & Device
Profiles.
Perform the configuration according to the assemblies used in the application.
NOTE:
Click on Apply button if needed to validate the configuration then restart the
soft starter.
DTM Library
DTM Browser
Select the soft starter from the list and click the Add DTM button to add the DTM.
Overview
In the following example:
• Soft Starter is connected to an Allen-Bradley Control Logix PLC.
• Communication protocol used is EtherNet/IP with assemblies 100/101.
• Soft Starter can be controlled through the PLC.
PC with:
-SoMove + DTM
-RSLogix5000 IP: 192.168.0.5 IP: 192.168.0.01
IP: 192.168.0.20
Ethernet EtherNet/IP
Overview
In the following example, the soft starter configuration must be done as follows in-
order to establish communication between the soft starter and the PLC.
The soft starter configuration is done using the soft starter DTM with SoMove
software.
Factory Settings
Before configuring the soft starter, make sure that you reset the soft starter to
factory settings.
• On the menu bar, select Device > Factory Settings > Execute.
Result: Following window is displayed:
Command Configuration
To control the soft starter with an Ethernet scanner, select Ethernet as active
command.
Go to:
• Parameters List tab
• Click on Command channel part
Result: Following window is displayed:
Ethernet Configuration
To set the Ethernet address of the soft starter, go to:
• Communication, Slot A - Modbus TCP/EtherNetIP, Generic Setttings.
Result: Following window is displayed:
Perform the configuration according to the network settings. In this example, the
soft starter is configured with following data:
• Fixed IP
• IP address: 192.168.0.5
• Mask: 255.255.255.0
Result: After setting the previous data, following configuration is entered:
Assemblies Configuration
To configure the assemblies used for Ethernet/IP fieldbus, go to:
• Communication, Slot A - Modbus TCP/EtherNetIP, Protocol & Device
Profiles.
Perform the configuration according to the assemblies used in the application. In
this example, assemblies used are 100 and 101.
Result: Following window is displayed:
NOTE:
Click on Apply button if needed to validate the configuration then restart the
soft starter.
PLC Configuration
Overview
In the following example, the PLC is configured to use both types of exchanges
available through Ethernet/IP fieldbus:
• Explicit data exchange
• Implicit data exchange
Connect online to the PLC, download the program and run it.
The Read Boolean will trigger the Read_Function to read the [Acceleration] ACC
parameter.
The Write Boolean will trigger the Write_Function to write the [Acceleration] ACC
parameter.
Configuration of Read_Function:
• Click on the "…" button of Read_Function block and do the following
configuration:
On the Configuration tab:
◦ Enter the CIP address of [Acceleration] ACC parameter: 16#8E/01/3D.
◦ The value of the parameter will be stored in the variable Read_ACC.
Configuration of Write_Function:
• Click on the "…" button of Write_Function block and do the following
configuration:
On the Configuration tab:
◦ Enter the CIP address of [Acceleration] ACC parameter: 16#8E/01/3D.
◦ Enter the variable where the value to write will be stored (here: ACC_to_
Write)
Operations
Operating States
WARNING
LOSS OF CONTROL
Perform a comprehensive commissioning test to verify that communication
monitoring properly detects communication interruptions
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
The values of the [Fieldbus Interrupt Resp] CLL parameter, which triggers a soft
starter detected error [Fieldbus Com Interrupt] CNF are:
Value Meaning
Factory setting
The values of the [Fieldbus Interrupt Resp] CLL parameter which does not
trigger a detected error are:
Value Meaning
WARNING
LOSS OF CONTROL
If this parameter is set to [Ignore] NO, fieldbus module communication
monitoring is disabled.
• Only use this setting after a thorough risk assessment in compliance with all
regulations and standards that apply to the device and to the application.
• Only use this setting for tests during commissioning.
• Verify that communication monitoring has been re-enabled before
completing the commissioning procedure and performing the final
commissioning test.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Detected Errors
Access via :[Diagnostics] DIA [Diag. data] DDT [Last Error] LFT
Operating Modes
Configuration of the Soft starter for Operation with STD Profile
This section describes how to configure the settings of the soft starter if it is
controlled in STD mode.
In the [Complete settings] CST- menu, [Command channel] CCP- submenu:
• [Control Mode] CHCF is set to [Standard Profile] STD.
• Check if [Cmd channel 1] CD1 (or [Cmd channel 2] CD2) is set on according
to the communication source ([Com. Module] NET).
1 LNK1
2 MS
3 NS
4 LNK2
LED Description
OFF No link
Blinking Green/ Power on testing
Yellow
Green ON Link established at 100 Mbit/s
Yellow ON Link established at 10 Mbit/s
Red ON Duplicated IP
Blinking Red An established connection to control the command word is closed or timed
out
Blinking red The device has detected a recoverable minor detected error.
LED Behavior
Control word [Cmd Register] CMD [Modbus Cmd] [CANopen Cmd] [COM. Module cmd.]
CMD1 CMD2 CMD3
Extended Control word [Extended Control [Extended Control [Extended Control [Extended Control
Word] CMI Word] CMI Word] CMI Word] CMI
Ethernet module [Fieldbus Error] EPF2 An external error has been • A faulty or duplicate
triggered. address can cause
conflicting issues.
• Try setting a different fixed
IP address
[Fieldbus Com Interrupt] CNF This error is triggered by the Increase the value of [Ethernet
timeout and appears when the Timeout] TOUT.
communication is stopped or
interrupted with the module.
[FDR 2 Error] FDR2 Ethernet fieldbus module FDR To eliminate the FDR error, the
error. following steps must be
performed:
• Change [ETH Option IP
Mode] IM10 to [DHCP]
DHCP and restart the soft
starter.
• FDR is active and
Automatic Syncho Cycle
is off.
• Disable the FDR and
restart the soft starter.
• Change the [ETH Option
IP Mode] IM10 to [Fixed]
MANU and restart the soft
starter.
Control-Signal Diagnostics
Introduction
On the display terminal, the [Communication] COM — [Communication map]
CMM submenu can be used to display control-signal diagnostic information
between the soft starter and the controller:
• Active command channel [Command Channel] CMDC
• Value of the control word [Cmd Register] CMD from the active command
channel [Command Channel] CMDC
• Value of the operating state word [Status Register] ETA
• Specific data for all available fieldbusses are in dedicated submenus.
• In the [Command word image] CWI submenu: control words from all
channels
Bit Description
Bit1 = 1 Switched on
Bit2 = 1 Operation enabled
Bit8 Reserved
Bit9 = 0 Local mode control
Bit10 Reserved
Bit11 Reserved
Bit12 Reserved
Bit13 Reserved
Bit14 = 1 Stop imposed via STOP key
Bit15 Reserved
Glossary
A
Abbreviations:
Req. = Required
Opt. = Optional
AC:
Alternating Current
C
Client:
A client is a device that is actively polling for data from one or multiple devices.
D
DC:
Direct Current
dec.:
Decimal
DP:
Decentralized Periphery
DPWS:
Device Profile for Web Service
E
Error :
Discrepancy between a detected (computed, measured, or signaled) value or
condition and the specified or theoretically correct value or condition.
F
Factory setting:
Factory settings when the product is shipped
Fault Reset:
A function used to restore the soft starter to an operational state after a detected
error is cleared by removing the cause of the error so that the error is no longer
active.
Fault:
Fault is an operating state. If the monitoring functions detect an error, a transition
to this operating state is triggered, depending on the error class. A "Fault reset" is
required to exit this operating state after the cause of the detected error has been
removed. Further information can be found in the pertinent standards such as IEC
61800-7, ODVA Common Industrial Protocol (CIP).
H
hex:
Hexadecimal
L
LSB:
Least Significant Byte
M
MIB:
A management information base (MIB) is a database used for managing the
entities in a communication network.
Monitoring function:
Monitoring functions acquire a value continuously or cyclically (for example, by
measuring) in order to check whether it is within permissible limits. Monitoring
functions are used for error detection.
MSB:
Most Significant Byte
P
Parameter:
Device data and values that can be read and set (to a certain extent) by the user.
PELV:
Protective Extra Low Voltage, low voltage with isolation. For more information:
IEC 60364-4-41.
PLC:
Programmable logic controller.
Power stage:
The power stage controls the motor. The power stage generates current for
controlling the motor.
Q
QoS:
Quality of Service
Quick Stop:
The quick Stop function can be used for fast deceleration of a movement as a
response to a detected error or via a command.
R
R/WS:
Read and write (write only possible when the soft starter is not in RUN mode). It is
not possible to write these parameters in "5-Operation enabled" or "6-Quick stop
active" states. If the parameter is written in the "4-Switched on" state, transition to
"2-Switch on disabled" is activated.
S
Server:
A server is the passive device, waiting for the client to poll for data to actually
send it.
SNMP:
Simple Network Management Protocol
SNTP:
Simple Network Time Protocol
SYNC:
Synchronization Object
W
Warning:
If the term is used outside the context of safety instructions, a warning alerts to a
potential error that was detected by a monitoring function. A warning does not
cause a transition of the operating state.
Z
Zone of operation:
This term is used in conjunction with the description of specific hazards, and is
defined as it is for a hazard zone or danger zone in the EC Machinery Directive
(2006/42/EC) and in ISO 12100-1.