Service Manual iCOM Control A9H-PCW Application Dubai4
Service Manual iCOM Control A9H-PCW Application Dubai4
Service Manual
iCOM Control
A9H-PCW
Application
Restart sequence
1.1.3 Fan Failure
1.1.3.1 Main Fan Overload
1. Main Fan Overload is not used in PCW configurations.
1.1.10 Humidification
1. The Humidification Enabled parameter allows enabling / disabling the humidifier function.
Selected Steamrate
on external hum board deadband
Humidification
- hum.
- 100% 1/2 Proportional Band 0% Setpoint
In fr a r e d H u m id ifie r H u m o ff
H um on
deadband
- hum .
- 100% 1 /2 P r o p o rtio n a l B a n d 0% S e tp o in t
Infrared humidifier
8. An autoflush system automatically controls the Fill Valve and Humidifier Lamps to maintain proper levels in the
infrared humidifier water pan during humidifier operation. When humidification is needed, the control calculates a
[flush_time] and a [re_fill_time]. The [flush_time] is equal to (Internal Variable (flush_constant)) multiplied by the
percent set in (S414 Infrared Flush Rate). The [re_fill_time] is equal to (A148 Fill Time) multiplied by the percent set
in (S414 Infrared Flush Rate). The control also checks to see if the [pre_fill_flag] is set. The [pre_fill_flag] gets set
when the humidifier has been OFF for the amount of time set in (A147 Humidity in Last xx Hours).
9. When there is a call for humidification and the [pre_fill_flag] is set, the Humidifier Lamps are held OFF until the valve
completes an initial fill of the humidifier pan. Therefore, the control will first turn ON the Fill Valve and start the
flush timer. Once the [flush_timer] reaches the value of the [re_fill_time], the control will turn ON the humidifier
Lamps. The control will continue filling the humidifier pan to flush the system until the [flush_timer] reaches the
value of the [flush_time]. Once this time has elapsed, the [pre_fill_flag] is cleared, the [flush_timer] is reset, and the
humidifier can be considered “flushed” and ready for normal operation.
10. When humidification is needed and the [pre_fill_flag] is not set, or the humidifier is ON and has just completed a
“flush” (see paragraph above), the Fill Valve and Humidifier Lamps are controlled in the following manner cyclic. If
the humidifier is OFF (i.e. not coming out of the auto flush sequence stated in the paragraph above), the control will
turn ON the Fill Valve and start the [cyclic_timer], one second later the control will turn ON the Humidifier Lamps. If
the humidifier is ON (i.e. just finished a flush sequence), the Fill Valve and Humidifier Lamps are left ON, and the
[cyclic_timer] is started. Once the [cyclic_timer] equals the calculated value [re_fill_time], the Fill Valve is turned
OFF. Once the [cyclic_timer] equals the (A149 Humidifier On Time) value, the Fill Valve is tuned ON, the
[cyclic_timer] is reset to 0, and restarted. The control continues use the [cyclic_timer] to control the Fill Valve as
described above until the control determines that humidification is not needed any more. When that happens, the
Humidifier Lamps are turned OFF, the Fill Valve is turned OFF if it is ON, the [cyclic_timer] is reset, and the humidifier
OFF timer is started.
11. If the [humidifier_off_timer] reaches the value set in (A147 Humidity in Last xx Hours), before the next call for
humidification, or if power is lost to the control, the [pre_fill_flag] is set.
1.1.11 Dehumidification
1. The _S415 “Dehum Enabled” parameter allows enabling / disabling the dehumidification function w/o the need to
remove fuses or cheat other settings to achieve no start for dehumidification.
2. % Cooling (compressor(s) or valve(s)will always be the greater between CFC and CFD; if CFD asks for i.e.70% and CFC
asks for 80%, the cooling device will operate at 80%.
3. Variable Fanspeed: Basically the Fanspeed during dehumidification is the greater request between CFC and CFD. See
below scenarios for details.
Supply Sensor
1. Once a Supply Sensor is connected, it can be set to operate in 4 possible modes.
2. _S124 “Supply Sensor” can be set to:
a. Disabled
i. In that case a connected Supply Sensor will show the value on the Display, no alarm if
disconnected.
b. Limit
i. In order to avoid too low supply temperatures, _U105 / _S124 “Supply Sensor” can be enabled,
and the lowest allowed supply air temperature can be set on U106 / S125 “Supply Setpoint”.
ii. The Supply Limit influences the opening of chilled water / freecooling valves, analog actuators.
iii. The Fanspeed output is not affected by the Supply Limit.
iv. 2 control circuits are always active:
1. The return air control calculates the control deviation
2. The supply air control calculates the control deviation
v. The value used to drive the valves capacity is the smaller of the two calculations.
vi. Note: Supply Limit is a local function; only local unit values (return temperature, supply
temperature) are used to calculate it.
c. Control
i. Selectable Control Types: P, PI and Intelligent.
ii. When Supply Control is set, all activities which usually are managed by the return air deviation
will be swapped to the supply air deviation.
iii. Speed filters are applied for Supply Control (only) depending on the position inside the p-band to
avoid overshoot and unstable operation.
1. The Filters are affecting the speed of change of the Call for Cooling (CFC) for the chilled
water valve and for the digital scroll capacity.
2. The filters can be set to allow a max change from 0.01%-100.00%/sec.
3. Different values can be set at p-band setpoint (0%) and at max p-band value (100%).
4. Typically the filter will be slow near the setpoint and fast at the end of the P-band.
5. The actual CFC filter will be modulated depending on the position in the P-band and the
max change settings at each end of the range.
6. The filter values are set using parameter _S132 “Capacity Change” (at 0%/100%)
iv. The humidity control will remain on the return air control.
v. Supply Control can be set only on:
1. CW unit if _S408 “Valve Control” set to 1 (Feedback) or if one of _A163-_A166 (Analog
Output 1-4) is set to 0 (CW 0-10V) or 25 (CW 2-10V).
vi. Supply Control on Fans:
1. Only Auto, Manual or Delta can be set on _S146 “VSD Fanspeed” (Economy and Supply
Limit are disabled).
2. In AUTO mode the fanspeed follows the same strategy as in Return Air Control.
vii. Supply Control on Heaters:
1. The heaters control follows the same strategy as in Return Air Control.
viii. Supply Control on Chilled Water Valve(s):
1. See section
Chilled Water Valves – Freecooling Valves, Note 4, Valve Control - Supply Air Control
[_S124 “Supply Sensor” set to “Control”]
ix. Low Limit during Dehum in Supply Control:
1. The Low Limit control follows the same strategy as in Return Air Control.
x. Return Compensation (_S133):
1. As long as the Return Air Temperature is above its Setpoint, the Supply Air Setpoint
remains unchanged.
2. Between Return Air Temperature Setpoint and the left part of the Return Air
Proportional Band the Supply Air Setpoint will be increased, reaching the value of
Supply Setpoint + S133 Return Compensation at the left end of the Return Air
Proportional Band.
Return Compensation
d. Cooling Only
i. Selectable Control Types: P, PI and Intelligent.
ii. Cooling Only can be set only on:
1. CW unit if _S408 “Valve Control” set to 1 (Feedback) or if one of _A163-_A166 (Analog
Output 1-4) is set to 0 (CW 0-10V) or 25 (CW 2-10V).
iii. Cooling Only on FANS:
iv. Only Auto, Manual or Delta can be set on _S146 “VSD Fanspeed” (Economy and Supply Limit are
disabled).
v. In AUTO mode the fanspeed follows the same strategy as in Return Air Control. The fanspeed
follows the Return CFC, up to 100% _S148 “VSD Setpoint STD” and down to _S148 “VSD Setpoint
MIN”.
vi. All fanspeed settings are visible.
vii. The CFC for the fan is the one calculated from the Return Temperature control.
viii. The fanspeed ramp is calculated between 0 and 100% of the (return) proportional band.
ix. Humidity is controlled via Return Temperature control.
x. Cooling / Heating is controlled via Supply Temperature control.
xi. During Heating and Humidification the Fanspeed will be set to the value of _A161 “Fanspeed
Heat/Hum”.
Fanspeed “Economy”
e. During Dehumidification the fan will operate at the fixed speed set in _S149 “VSD Setpoint Dehum”.
f. When the “No Power” event is active the fan will operate at the fixed speed set in _S149 “VSD Setpoint No
Power”.
g. During Heating and Humidification the Fanspeed will be set to the value of _A161 “Fanspeed Heat/Hum”.
h. If Supply Air Limit Control is selected, the valve is not going to be closed if the supply air control reports a
lower deviation than the return air control, but the difference (in %) is added to the fanspeed (directly on
the output, with the maximum limit set on _S148 “VSD Fanspeed STD”.
i. Only if the Fan is already operating on STD speed, the valve will operate with the smaller deviation
between return control and supply control, while the fan operates on _S148 “VSD Fanspeed STD”.
j. During Dehum and No Power operation the supply control is switched to inactive.
10. _S146 “VSD Fanspeed” set to “Delta”
a. All fanspeed settings are visible.
b. Sensor A (U301 Optional Sensor A Temperature) and Sensor B (_U303 “Optional Sensor B Temperature”)
are mandatory for this operation mode.
vi. In case “A” or “B” is disconnected, the fanspeed changes to _S148 “VSD Setpoint STD”.
c. The control has to achieve a constant delta t between those 2 sensors, set in _S153 “Fanspeed Delta”.
vii. If delta (Sensor “A” – Sensor “B”) = less than setpoint, decrease speed
viii. If delta (Sensor “A” – Sensor “B”) = greater than setpoint, increase speed
d. During Dehumidification the fan will operate at the fixed speed set in _S149 “VSD Setpoint Dehum” or
higher, if the delta requires.
e. When the “No Power” event is active the fan will operate at the fixed speed set in _S149 “VSD Setpoint No
Power”.
f. During Heating and Humidification the Fanspeed will be set to the value of _A161, “Fanspeed Heat/Hum”
or higher, if the delta requires.
g. “Delta” is controlled in PI mode, settings are _S154 “Fanspeed P-Band“ and _S155 “Fanspeed Integration”.
Fanspeed “Delta”
ON ON ON
OFF OFF OFF
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
iCOM Network
Grouping by Subnet
2. Note that this is the preferred way of grouping iCOM units as it reduces the (computing) load on all units. The router
between the 2 groups of iCOM units provides an almost physical separation between the networks as none of the
iCOM units in either network will send IP packets that are supposed to be forwarded by the router.
3. Still, it is possible to access both groups of iCOM units from a company intranet or some other additional network
connected to the router. For instance: The “iCOM Service Tool” could be executing on a PC somewhere in the
company intranet and would be able to access both groups of iCOM units at the same time.
4. But it might happen that due to the already existing IT infrastructure at some customer’s site, several groups of
iCOM units must be able to co-exist within the same IP subnet. In such a case the iCOM network parameter “U2U
group” needs to be used, which is described in the following section.
3.1.3 Grouping by Using the “U2U Group” Parameter
• If - for whatever reason – iCOM units can not be grouped by placing them into different IP subnets, there is also the
option of using the “U2U Group” parameter.
• This parameter is accessible through any iCOM display and defines the U2U group a specific iCOM unit belongs to.
The value of this parameter is transmitted in the header of any GBP message. Upon reception of such a message,
each iCOM unit first checks whether it matches its own setting. Messages sent by iCOM units belonging to the same
U2U group will be processed further, others will simply be discarded.
CAN chain
• The CAN chain must be set in the correct way following this rule:
a. Only one CAN cable connected to the device means that the device is the last on CAN chain and then it must be
terminated.
b. Two CAN cables connected to the device means the device is intermediate on CAN chain and then it has not to
be terminated.
• CDL, CDS, Medium Board, Large Board, HCB:
Jumper P78 on 2-3 = Last device.
Jumper P78 on 1-2 = Intermediate device.
• THB, 2T Sensor:
Jumper P3 on 2-3 = Last device.
Jumper P3 on 1-2 = Intermediate device.
• EEV:
Jumper J410 set = Last device.
Jumper J410 not set = Intermediate device
Level Icons and Parameter Description
Level 1 – User Level 2 – Service Level 3 – Advanced
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 6 – Humidity Control
S112 PASSWORD - W - - - - -
S113 Humidity Setpoint HUM SET W Yes (1.0-19.9=20.0) (1.0-19.9=20.0) 1.0 50.0%
20.0-80.0% 20.0-80.0%
The humidity of the air desired in the room. It is the reference value used by iCOM, together with Return Air Humidity, Humidity Proportional Band
and Humidity Integration Factor to decide the Hum or Dehum status.
S114 Humidity Control Type HUM CTRL W Yes Relative, Rel, - Compensated
Compensated, Comp,
Predictive Pred
Relative
control starts hum / dehum according the reading of the humidity sensor
Compensated
Humidity Setpoint is recalculated with the actual deviation from the temperature setpoint.
For 1°C deviation from the temperature setpoint the humidity setpoint is changed by 3%rH, indirect proportional: if the temperature increases, the
hum setpoint is decreased, and vice versa. Recalculated setpoint is shown as Actual Humidity Setpoint. Together with the modification of the
humidity setpoint also the thresholds (high or low humidity) will be recalculated.
Predictive
actual humidity reading from the humidity sensor is recalculated with the actual deviation from the temperature setpoint. For 1°C deviation from
the temperature setpoint the humidity reading is changed by 3%rH, direct proportional: if the temperature increases, the hum reading is
increased, and vice versa. Together with the modification of the humidity reading also the thresholds (high or low humidity) will be recalculated.
The Graphs will show the real (unchanged) reading of the sensor.
S115 Humidity Proportional HUM PB W Yes 1.0-20.0% 1.0-20.0% 0.1 10.0%
Band (autoset) (autoset)
The S115 Humidity Proportional Band is divided in two parts: equal size for humidification and dehumidification. In the center there is the U103 /
S113 Humidity Setpoint. A S117 Humidity Deadband can be set around the setpoint, which shifts the humidification / dehumidification steps apart.
S116 Humidity Integration HUM INT W Yes 0-15min 0-15m 1 0
Time (autoset) (autoset)
Normally best results will be reached if the “AUTOSET” is enabled. If set to any value, the PI control is enabled. The integration factor doubles the
actual, real deviation from the Setpoint within the selected time. This will force Hum / Dehum to add more steps to reach the Setpoint. To be used
if P-Band must be wide because of bigger number of units connected, and working in Teamwork 1.
S117 Humidity Deadband HUM DB W Yes 0.0-50.0% 0.0-50.0% 0.1 0.0%
The Humidity Deadband is divided 50:50 for both, hum and dehum and shifts the hum / dehum steps apart.
S118 Dehum/Heat Low Limit 1 LO LIM 1 W No (-)10°F-2°F (-)10°F-2°F 0.1
(-)5.5K-1.1K (-)5.5K-1.1K 0.1
Low Limit 1 is disabled for PCW configurations.
S119 Dehum/Heat Low Limit 2 LO LIM 2 W No (-)10°F-2°F (-)10°F-2°F 0.1 -3°F
(-)5.5K-1.1K (-)5.5K-1.1K 0.1 -1.7K
Low Limit 2 will disable dehum. It will allow dehum again when the temperature increases up to the Setpoint.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 6 - Supply Temperature Control
S123 PASSWORD - W - - - - -
S124 Supply Sensor SUPSENS W yes Disabled, No, - Disabled
Limit, Lim,
Control, Ctrl,
Cooling Only Cool
S125 Supply Setpoint SUP TEMP W yes 41-81°F 41-81°F 1 64°F
5.0-27.0°C 5.0-27.0°C 0.1 18.0°C
S126 Supply Control Type SUP TYPE W yes Proportional, P, - PI
PI, PI,
not used, No,
Intelligent Intel
S127 Supply Proportional SUPPB w yes 2-54°F 2-54°F 1 22°F
Band 2.0-30.0°C 2.0-30.0°C 0.1 12.0K
S128 Supply Integration SUINT W yes 0-15min 0-15m 1 0min
S132 Cooling Filter at 0% CF0 W yes 0.01 - 100.00% 0.01 - 100.00% 0.01 0.20%/s
CW: 100.00%/s
S132 Cooling Filter at 100% CF100 W yes 0.01 - 100.00% 0.01 - 100.00% 0.01 4.00%/s
CW: 100.00%/s
S133 Return Compensation RET CO W yes 0-18°F 0-18°F 1 0°F
0.0-10.0K 0.0-10.0K 0.1 0.0K
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 6 - Supply Temperature Control
S134 PASSWORD - W - - - - -
S135 DT1 (Room / Outdoor) AMB TYPE W no Disabled, No, - FC: Value
Type Contact, CONT, DX,CW:
EFC, EFC, Disabled
Temp TMP,
Set SET
This parameter is useful for FC units only. The Freecooling mode will be activated when also the condition on DT Room-FC fluid is fulfilled.
• If set to Contact, the control expects to get a command with a switch instead of a temperature sensor (Open: FC, closed: no FC).
• If set to EFC the unit will not go in Freecooling mode during normal operation, but only in case of “NO POWER” operation or compressor
failure (Emergency Freecooling only).
• If set to Temp the unit will read the Outdoor sensor.
• If Set to Set reads the value of the Outdoor sensor.
S136 DT1 (Room / Outdoor) AMB DT W no 2-72°F 2-72°F 1 5°F
Value 1.0-40.0°C 1.0-40.0°C 0.1 3.0°C
The value of the difference between the return air temperature and the outdoor temperature over which (with a hysteresis of+/-1.5 C) the unit will
enable the Freecooling mode (if there are not other conditions that disable the Freecooling operation).
ONLY LOCAL VALUES ARE USED TO IDENTIFY THE STATUS OF THE DT
S137 DT2 (Room / FC Fluid) FC TYPE W no Disabled, No, - FC: Value
Type Contact, CONT, DX,CW:
Value VAL Disabled
DT2 Room and FC Fluid Type:
• Set to Value: reads the value of the Freecooling sensor: U307 Freecooling Fluid Temperature.
• Set to Contact: allows connecting a volt-free contact instead of the sensor to toggle between Freecooling and none Freecooling. The
contact has to be connected to the same input where usually the sensor is connected (Open: FC, closed: no FC).
S138 DT2 (Room / FC Fluid) FC DT W no 0-36°F 0-36°F 1 8°F
Value 0.0-20.0°C 0.0-20.0°C 0.1 4.5°C
DT2 between Room and FC Fluid (valid only if S137 DT2 (Room / FC Fluid) Type is set to “Value”): This determines if the U307 Freecooling Fluid
Temperature is low enough to give (at least partial) capacity for Freecooling.
Note: only local values (sensor values from the unit only, no shared values between several units) are used to identify the status of the delta T.
If the temperature between room air and S138 DT2 (Room / FC Fluid) Value is true (the difference is the same or greater than the value of S138
DT2 (Room / FC Fluid) Value or the contact is open), for a time of 2 minutes, then Freecooling will be activated:
The U309 Freecooling Status indication will show “ON” instead of “OFF”.
The compressor band will be shifted to the right by 100%, and within the first 100% the Freecooling valve band will take place. This could,
depending on the actual temperature position inside the S104 Temperature Proportional Band, stop one or both compressors.
ONLY LOCAL VALUES ARE USED TO IDENTIFY THE STATUS OF DT
S139 Minimum CW Temp MIN CW W no Disabled, No, - FC: Enabled
Enabled Yes DX,CW:
Disabled
Once enabled (default) the unit will check the U307 Freecooling Fluid Temperature and compare it with S140 Minimum CW Temp value - this
feature permits the user to select the minimum chilled water temperature that permits simultaneous operation of the chilled water control and
compressor control.
If disabled, the S140 Minimum CW Temp value is ignored, the control will always operate Freecooling and compressors simultaneously.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 6 - Fanspeed Control
S145 PASSWORD - W - - - - -
S146 VSD Fanspeed FANSPEED W no Auto, AUTO, - Auto
Manual, MAN,
Economy, ECO,
Supply Limit (not SUP (not
Selectable), Selectable),
Delta, DELTA,
S147 Airflow Calibration AIR CAL W no 3.2-10.0V 3.2-10.0V 1 10.0V
S148 VSD Setpoint MIN / STD VSD MIN W no 0-100% 0-100% 1 CW: 60%
VSD STD DX: 70%
and
100%
S149 VSD Setpoint Dehum / VSD DEH W no 0-100% 0-100% 1 CW: 60%
No Power VSD NOP DX: 100%
and
CW: 60%
DX: 70%
S151 Fanspeed Change FF0% W yes 0.01 - 100.00% 0.01 - 100.00% 0.01 0.20%
(at 0%)
S151 Fanspeed Change FF100% W yes 0.01 - 100.00% 0.01 - 100.00% 0.01 1.00%
(at 100%)
S152 Fanspeed Reposition FRD W yes 0-300sec 0-300s 1 0sec
Delay
S153 Fanspeed Delta HAD W yes 2-10°F 2-10°F 1 2
1.1K-5.6K 1.1K-5.6K 0.1 1.1K
S154 Fanspeed P-Band HAP W yes 2-54°F 2-54°F 1 11°F
2.0-30.0°C 2.0-30.0°C 0.1 6.0K
S155 Fanspeed Integration HAI W yes 0-15min 0-15m 1 5min
S503 Rotation Frequency ROTATION W yes No, Daily, Every No, Daily, MON, - No
Mon, Every Tue, TUE, WED, THU,
Every Wed, Every FRI, SAT, SUN, M-
Thu, Every Fri, MO, M-TU, M-WE,
Every Sat, M-TH, M-FR, M-
Every Sun, Montly SA, M-SU
Mon, Montly Tue,
Montly Wed,
Montly Thu,
Montly Fri, Montly
Sat,
Montly Sun
S504 Rotate at (hour) ROT HOUR W yes 00-23 00-23 1 00
If the unit works in good condition, next maintenance can be shifted to later time, adding the bonus (or part of it) from the next planned service
time. The bonus is given in months.
S004 Max Penalty PENALTY W yes 0-12 0-12 1 0
If the unit works in bad condition, next maintenance must be shifted to earlier time, reducing the penalty (or part of it) from the next planned
service time. The penalty is given in months.
S005 Last Maintenance LAST PM W yes Date Date - -
This date sets automatically if the service engineer sets the “reset” parameter (see next lines).
S006 Service Engineer NAME W yes Name Name - -
The service engineer has to put his name in the name - field after service.
S007 Confirm PM CONFIRM W yes No, No, - No
Yes Yes
S008 Calculated Next NEXT PM W yes Date Date - -
Maintenance
This is the result of the settings done in this area. It shows the calculated next service time, respecting bonus & penalty as well as std. maintenance
frequency.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
motor settings (2 of 9) MOTOR
S012 PASSWORD - W - - - - -
S013 Number of Starts STARTS R no 0-32000 0-32000 1 -
A counter (read only) which indicates the number of starts of the specific component since the last maintenance. The counter will be reset when
last maintenance is set (reset).
S014 Run Hours RUN HRS R no 0-32000hrs 0-32000hr 1 -
A counter (read only) which indicates the number of starts of the specific component since the last maintenance. The counter will be reset when
last maintenance is set (Reset).
S015 Average Run Time AVG RUN R no 0-999min 0-999m 1 -
Calculated from number of starts and working hours. This is the basic information for the next maintenance calculation.
S016 Starts per Day Best BEST W no 1-240 1-240 1 1
Number of starts per day for the specific component, which can be considered as best working condition.
S017 Starts per Day Worst WORST W no 1-240 1-240 1 24
Number of starts per day for the specific component, which can be considered as worst working condition.
S018 Number of Alarms ALARMS R no 0-32000 0-32000 1 -
A counter (read only) which indicates the number of alarm occurred to the specific component since last maintenance (split in HP/LP/TH for
compressor. The counter will be reset when last maintenance is set (Reset).
S019 Actual Bonus BONUS R no 0-12 0-12 1 -
Actual calculation of wellness for the specific component. The system will always take the value from the worst component for the next
maintenance indication.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Compressor1 settings (3 COMP1
of 9)
S023 PASSWORD - W - - - - -
S024 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Compressor2 settings (4 COMP.2
of 9)
S034 PASSWORD - W - - - - -
S035 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
el heater 1 settings (5 of HEAT1
9)
S045 PASSWORD - W - - - - -
S046 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
el heater 2 settings (6 of HEAT2
9)
S056 PASSWORD - W - - - - -
S057 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
el heater 3 settings (7 of HEAT3
9)
S067 PASSWORD - W - - - - -
S068 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
humidifier settings (8 of HUM
9)
S078 PASSWORD - W - - - - -
S079 Number of Starts STARTS R no 0-32000 0-32000 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 8
S312 PASSWORD - W - - - - -
S313 Manual Mode MANUAL W no No, No, - -
Yes Yes
This window allows running all components in manual mode, with all safety devices on. At the first the parameter “Manual Mode” has be set to ON
after that the Unit fan must be started, before being able start any other components.
S314 Motor(s) MOTOR(S) W no Off, Off, - -
On On
Turns on the Fan in Manual Mode.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 8
S323 PASSWORD - W - - - - -
S324 Electric Heat 1 EL HEAT1 W no Off, Off, - -
(or HG/HW) On On
Turns on the electric heat 1 ( or Hot Gas/Hot Water if selected) in manual mode.
S325 Electric Heat 2 EL HEAT2 W no Off, Off, - -
(or E.Heat 1) On On
Turns on the electric heat 2 ( or electric heat 1 if Hot Gas/Hot Water are selected) in manual mode.
S326 Electric Heat 3 EL HEAT3 W no Off, Off, - -
(or E.Heat 2) On On
Turns on the electric heat 3 ( or electric heat 2 if Hot Gas/Hot Water are selected) in manual mode.
S327 SCR Heat SCR Heat W no 0-100% 0-100% 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 8
S334 PASSWORD - W - - - - -
S335 Alarm Relay ALM REL W no Off, Off, - -
On On
Activates the alarm relay in manual mode.
S336 K11 Relay K11 REL W no Off, Off, - -
On On
Activates the K11 relay in manual mode.
S337 3P 1/2 Actuator Open 3P1 OPEN W no Off, Off, - -
On On
S337 3P 1/2 Actuator Open 3P2 OPEN W no Off, Off, - -
On On
Opens the 3P1 or 3P2 Actuator in manual mode.
S338 3P 1/2 Actuator Close 3P1 CLOS W no Off, Off, - -
On On
S338 3P 1/2 Actuator Close 3P2 CLOS W no Off, Off, - -
On On
Closes the 3P1 or 3P2 Actuator in manual mode.
S339 BV Control BV CTRL W no Manual, Man, - -
Auto Auto
S340 MBV Position MBV1 POS W no 0-100 0-100 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 8
S345 Status Remote Shutdown RSD R no Off, Off, - -
On On
Shows the Remote Shutdown input status.
S346 Status Airflow Loss AIR LOSS R no OK, OK, - -
Act Act
Shows the Airflow Loss input status.
S347 Status Motor Overload / MOTOR OL R no OK, OK, - -
EC Fan Fault Act Act
Shows the Motor Overload input status.
S348 Status Filter FILTER R no OK, OK, - -
Act Act
Shows the Filter input status.
S349 Status Customer Input 1 CUSTOM 1 R no OK, OK, - -
Act Act
Shows the Customer Input 1 status.
S350 Status Customer Input 2 CUSTOM 2 R no OK, OK, - -
Act Act
Shows the Customer Input 2 status.
S351 Status Customer Input 3 CUSTOM 3 R no OK, OK, - -
Act Act
Shows the Customer Input 3 status.
S352 Status Customer Input 4 CUSTOM 4 R no OK, OK, - -
Act Act
Shows the Customer Input 4 status.
S353 Status Heaters Safety HEAT SAF R no OK, OK, - -
Act Act
Shows the Heaters safety input status.
S354 Loss of Airflow at FLOW AT W no 0-100% 0-100% 1 40%
Defines the threshold of the Loss of Airflow alarm. For medium board the value is set to 35%.
S355 Actual Airflow FLOW ACT R no 0-100% 0-100% 1 -
Shows the actual airflow value. If the value is below of the S354 threshold the Loss of Airflow alarm becomes active.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 7of 8
S367 Status Humidifier HUM PROB R no OK, OK, - -
Problem Act Act
Shows the Humidifier Problem status.
S368 Status DT1 DT1 R no Off, Off, - -
(Room/Outdoor) Act Act
Shows the DT1 status.
S369 Status DT2 (Room/FC DT2 R no Off, Off, - -
Fluid) Act Act
Shows the DT2 status.
S370 Status DT3 DT3 R no Off, Off, - -
(Room/Setpoint) Act Act
Shows the DT3 status.
S371 Status DT4 (Eco Zone) DT4 R no Off, Off, - -
Act Act
Shows the DT4 status.
S372 Status Min CW MIN CW R no Off, Off, - -
Act Act
Shows the Min CW status.
S373 LWD Value LWD Val R no 0-100% 0-100% 1 -
Shows the LWD value.
S374 Status LSI LSI R no OK, OK, - -
Full Full
Shows the LSI input status.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 8 of 8
S378 PASSWORD - W - - - -
S379 Valve Control V_CTRL W no Time, Time, - Time
Feedback Feedb
S380 Start Valve Calibration V_CAL W no No, No, - No
Yes Yes
S381 Calibration Status CAL_STAT R no Idle, Idle, - -
Ongoing Run
S382 V1: 0% open = CLSD 1 W no 0.00-10.00V 0.00-10.00V 0.01 3.90V
S206 Low Return Humidity LOW HUM W yes 1.0-99.0% 1.0-99.0% 0.1 40.0%
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 8
S212 PASSWORD - W - - - - -
S213 Supply Sensor Alarms SUP SNSR W yes Disabled, No, - Disabled
Enabled Yes
S214 High Supply HI SUP T W yes 34-210°F 34-210°F 1 75°F
Temperature 1.0-99.0°C 1.0-99.0°C 0.1 23.9°C
S215 Low Supply LO SUP T W yes 34-210°F 34-210°F 1 Control/Temp
Temperature 1.0-99.0°C 1.0-99.0°C 0.1 Only:
50F / 10.0°C
Limit:
34F / 1.1°C
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 8
S223 PASSWORD - W - - - - -
S224 Customer Input 1 CUST IN1 W no See below See below - C-Input 1
Setting: Reaction:
0 = Smoke Activates the SMOKE DETECTED event, no further action.
1 = Water Alarm Activates the WATER UNDER FLOOR event, no further action.
2 = C PMP Alarm Activates the COND PUMP-HIGH WATER event, no further action.
3 = Flow Alarm Activates the LOSS OF FLOW event, no further action.
4 = Stdby G Pmp Activates the STBY GLYCOL PUMP ON event, no further action.
5 = Stdby Unit Activates the STANDBY UNIT ON event, no further action.
6 = C-Input 1 Activates the CUSTOMER INPUT 1 event, no further action. If the parameter SB60 “Fan and
Cooling 100% by User” is enabled Fan and cooling is forced to 100%.
7 = C-Input 2 Activates the CUSTOMER INPUT 2 event, no further action.
8 = C-Input 3 Activates the CUSTOMER INPUT 3 event, no further action.
9 = C-Input 4 Activates the CUSTOMER INPUT 4 event, no further action.
10 = Rht Lockout Activates the REHEAT LOCKOUT event, and locks the heater out.
11 = Hum Lockout Activates the HUMIDIFIER LOCKOUT event, and locks the humidifier out.
12 = Rht+Hum Lock Rht Lockout + Hum Lockout together.
13 = Comp Lockout Activates the COMPRESSOR LOCKOUT event, and locks the compressor out.
14 = Call Service Activates the CALL SERVICE event, no further action.
15 = High Temp Activates the HIGH TEMPERATURE event, no further action.
16 = Air Loss Activates the LOSS OF AIR BLOWER 1 event, no further action.
17 = FC Lockout Activates the FC LOCKOUT event, and locks freecooling or economizer out.
18 = Heater Alarm Activates the HEATERS OVERHEATED event, and locks the el. heater s out.
19 = Flow AL SD Activates the LOSS OF FLOW event, and shuts the unit down.
20 = Flow AL LC Activates the LOSS OF FLOW event, and locks the compressor out.
21 = Comp Lock PD Activates the COMPRESSOR LOCKOUT event, and locks the compressor out - with pump-down.
22 = Enable FC Activates no event, but enables Freecooling (sets all DT true).
23 = HTRJ VFD Activates the HEAT REJ VFD event, no further action.
24 = HTRJ TVSS Activates the HEAT REJ TVSS event, no further action.
25 = Fire Alarm Activates the FIRE ALARM event, and shuts the unit down.
26 = 2nd Setpoint Activates no event, but switches to the second setpoint.
27 = No Power Activates the NO POWER event, and disables the unit (no compressors, heat, hum or dehum;
only fans and valves are allowed to operate).
28 = LSI Internal Humidifier:
a) stops filling when bottle is full
b) activates the HUMIDIFIER CYLINDER WORN event, and locks the humidifier out (when input
is active for 24 hours and steam remains below 50%).
External Humidifier:
Activates the HUMIDIFIER PROBLEM event, and locks the humidifier out.
29 = Cond 1 Fail Activates the CONDENSER 1 FAILURE event, no further action.
30 = Cond 2 Fail Activates the CONDENSER 2 FAILURE event, no further action.
31 = D-Scroll Red Activates the COMP POWER REDUCTION ACTIVE event, and reduces the requested
compressor capacity by 20%.
32 = Swap Valve Changes priority of valves in Double Chilled Water configurations. This Customer Input setting
doesn’t create any event.
33 = EC Fan Fault Activates the EC FAN FAULT event, and sets the analog output to 10V (not used in PCW)
34 = ECO Airflow Activates the REDUCED ECO AIRFLOW event.
S225 Customer Input 1 C1 ACT W no Opened, closed OPEN, CLOSE - Opened
active when
S226 Customer Input 2 CUST IN2 W no Like Customer Like Customer - LSI
Input 1 Input 1
S227 Customer Input 2 C2 ACT W no Opened, closed OPEN, CLOSE - Opened
active when
S228 Customer Input 3 CUST IN3 W no Like Customer Like Customer - Cond 1 Fail
Input 1 Input 1
S229 Customer Input 3 C3 ACT W no Opened, closed OPEN, CLOSE - Opened
active when
S230 Customer Input 4 CUST IN4 W no Like Customer Like Customer - Fire Alarm
Input 1 Input 1
S231 Customer Input 4 C4 ACT W no Opened, closed OPEN, CLOSE - Opened
active when
S232 WARNING ACTIVATES WA AC AL W no No, No, - Yes
ALARM RELAY Yes Yes
S233 Water Alarm Shuts Unit WAT OFF W Yes, No, No, - No
Down No Yes Yes
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 8
S234 PASSWORD - W - - - - -
x DELAY - - - - - - -
S236 MAIN FAN OVERLOAD FOL W no 0 -9999sec 0 -9999s 1 5sec
S237 LOSS OF AIRFLOW (first - W no 0 -9999sec - 1 120sec
value)
S237 LOSS OF AIRFLOW LOA W no 0 -9999sec 0 -9999s 1 0sec
(second value)
S238 CLOGGED FILTERS CF W no 0 -9999sec 0 -9999s 1 2sec
S239 HIGH ROOM TEMP HRT W no 0 -9999sec 0 -9999s 1 30sec
S240 LOW ROOM TEMP LRT W no 0 -9999sec 0 -9999s 1 30sec
S241 HIGH ROOM HUM HRH W no 0 -9999sec 0 -9999s 1 30sec
S242 LOW ROOM HUM LRH W no 0 -9999sec 0 -9999s 1 30sec
S243 HIGH AISLE TEMP. HTW W no 0 -9999sec 0 -9999s 1 30sec
WARNING
S244 HIGH AISLE TEMP. HTA W no 0 -9999sec 0 -9999s 1 30sec
ALARM
S245 HIGH AISLE HUMI. HHW W no 0 -9999sec 0 -9999s 1 30sec
WARNING
S246 HIGH AISLE HUMI. HHA W no 0 -9999sec 0 -9999s 1 30sec
ALARM
x EN-DIS - - - - - - -
S236 MAIN FAN OVERLOAD FOL W no DISAB, No, - ENABLE
ENABLE Yes
S237 LOSS OF AIRFLOW LOA W no DISAB, No, - ENABLE
ENABLE Yes
S238 CLOGGED FILTERS CF W no DISAB, No, - ENABLE
ENABLE Yes
S239 HIGH ROOM TEMP HRT W no DISAB, No, - DISAB
ENABLE Yes
S240 LOW ROOM TEMP LRT W no DISAB, No, - DISAB
ENABLE Yes
S241 HIGH ROOM HUM HRH W no DISAB, No, - DISAB
ENABLE Yes
S242 LOW ROOM HUM LRH W no DISAB, No, - DISAB
ENABLE Yes
S243 HIGH AISLE TEMP. HTW W no DISAB, No, - DISAB
WARNING ENABLE Yes
S244 HIGH AISLE TEMP. HTA W no DISAB, No, - DISAB
ALARM ENABLE Yes
S245 HIGH AISLE HUMI. HHW W no DISAB, No, - DISAB
WARNING ENABLE Yes
S246 HIGH AISLE HUMI. HHA W no DISAB, No, - DISAB
ALARM ENABLE Yes
x TYPE - - - - - - -
S236 MAIN FAN OVERLOAD FOL W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S237 LOSS OF AIRFLOW LOA W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S238 CLOGGED FILTERS CF W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S239 HIGH ROOM TEMP HRT W no WRN WRN - WRN
S240 LOW ROOM TEMP LRT W no WRN WRN - WRN
S241 HIGH ROOM HUM HRH W no WRN WRN - WRN
S242 LOW ROOM HUM LRH W no WRN WRN - WRN
S243 HIGH AISLE TEMP. HTW W no WRN WRN - WRN
WARNING
S244 HIGH AISLE TEMP. HTA W no WRN WRN - WRN
ALARM
S245 HIGH AISLE HUMI. HHW W no WRN WRN - WRN
WARNING
S246 HIGH AISLE HUMI. HHA W no WRN WRN - WRN
ALARM
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 8
S247 PASSWORD - W - - - - -
X DELAY - - - - - - -
S259 EL HEAT HIGH TEMP EHO W no 0-9999sec 0-9999sec 1 5sec
x EN-DIS - - - - - - -
S259 EL HEAT HIGH TEMP EHO W no DISAB, No, - ENABLE
ENABLE Yes
x TYPE - - - - - - -
S259 EL HEAT HIGH TEMP EHO W no MSG, WRN, ALM MSG, WRN, ALM - WRN
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 8
S260 PASSWORD - W - - - - -
X DELAY - - - - - - -
S262 WORKING HRS WHE W no 0-9999sec 0-9999s 1 0sec
EXCEEDED
S263 SMOKE DETECTED SMO W no 0-9999sec 0-9999s 1 2sec
S264 WATER UNDER FLOOR WUF W no 0-9999sec 0-9999s 1 2sec
S265 COND PUMP-HIGH CPH W no 0-9999sec 0-9999s 1 2sec
WATER
S266 LOSS OF FLOW LOF W no 0-9999sec 0-9999s 1 5sec
S267 STBY GLYCOL PUMP ON SGP W no 0-9999sec 0-9999s 1 2sec
S268 STANDBY UNIT ON STB W no 0-9999sec 0-9999s 1 2sec
S269 HUMIDIFIER PROBLEM HUP W no 0-9999sec 0-9999s 1 2sec
S270 NO CONN. w/Unit1 NOC W no internal internal - -
S271 UNIT X DISCONNECTED DIS W no internal internal - -
S272 LOSS OF POWER LOP W no internal internal - -
x EN-DIS - - - - - - -
S262 WORKING HRS WHE W no DISAB, No, - ENABLE
EXCEEDED ENABLE Yes
S263 SMOKE DETECTED SMO W no DISAB, No, - ENABLE
ENABLE Yes
S264 WATER UNDER FLOOR WUF W no DISAB, No, - ENABLE
ENABLE Yes
S265 COND PUMP-HIGH CPH W no DISAB, No, - ENABLE
WATER ENABLE Yes
S266 LOSS OF FLOW LOF W no DISAB, No, - ENABLE
ENABLE Yes
S267 STBY GLYCOL PUMP ON SGP W no DISAB, No, - ENABLE
ENABLE Yes
S268 STANDBY UNIT ON STB W no DISAB, No, - ENABLE
ENABLE Yes
S269 HUMIDIFIER PROBLEM HUP W no DISAB, No, - ENABLE
ENABLE Yes
S270 NO CONN. w/Unit1 NOC W no DISAB, No, - ENABLE
ENABLE Yes
S271 UNIT X DISCONNECTED DIS W no DISAB, No, - ENABLE
ENABLE Yes
S272 LOSS OF POWER LOP W no DISAB, No, - DISAB
ENABLE Yes
x TYPE - - - - - - -
S262 WORKING HRS EXC. WHE W no WRN WRN - WRN
S263 SMOKE DETECTED SMO W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S264 WATER UNDER FLOOR WUF W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S265 COND PUMP-HIGH CPH W no MSG, WRN, ALM MSG, WRN, ALM - ALM
WATER
S266 LOSS OF FLOW LOF W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S267 STBY GLYCOL PUMP ON SGP W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S268 STANDBY UNIT ON STB W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S269 HUMIDIFIER PROBLEM HUP W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S270 NO CONN. w/Unit1 NOC W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S271 UNIT X DISCONNECTED DIS W no WRN WRN - WRN
S272 LOSS OF POWER LOP W no MSG, WRN, ALM MSG, WRN, ALM - WRN
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 7 of 8
S273 PASSWORD - W - - - - -
X DELAY - - - - - - -
S275 CUSTOMER INPUT 1 CI1 W no 0-9999sec 0-9999s 1 2sec
S276 CUSTOMER INPUT 2 CI2 W no 0-9999sec 0-9999s 1 2sec
S277 CUSTOMER INPUT 3 CI3 W no 0-9999sec 0-9999s 1 2sec
S278 CUSTOMER INPUT 4 CI4 W no 0-9999sec 0-9999s 1 2sec
S279 CALL SERVICE CS W no 0-9999sec 0-9999s 1 2sec
S280 HIGH TEMPERATURE HTD W no 0-9999sec 0-9999s 1 2sec
S281 LOSS OF AIR BLOWER 1 LB1 W no 0-9999sec 0-9999s 1 2sec
S282 REHEAT LOCKOUT RL W no 0-9999sec 0-9999s 1 2sec
S283 HUMIDIFIER LOCKOUT HL W no 0-9999sec 0-9999s 1 2sec
S284 FC LOCKOUT FCL W no 0-9999sec 0-9999s 1 2sec
X EN-DIS - - - - - - -
S275 CUSTOMER INPUT 1 CI1 W no DISAB, No, - ENABLE
ENABLE Yes
S276 CUSTOMER INPUT 2 CI2 W no DISAB, No, - ENABLE
ENABLE Yes
S277 CUSTOMER INPUT 3 CI3 W no DISAB, No, - ENABLE
ENABLE Yes
S278 CUSTOMER INPUT 4 CI4 W no DISAB, No, - ENABLE
ENABLE Yes
S279 CALL SERVICE CS W no DISAB, No, - ENABLE
ENABLE Yes
S280 HIGH TEMPERATURE HTD W no DISAB, No, - ENABLE
ENABLE Yes
S281 LOSS OF AIR BLOWER 1 LB1 W no DISAB, No, - ENABLE
ENABLE Yes
S282 REHEAT LOCKOUT RL W no DISAB, No, - ENABLE
ENABLE Yes
S283 HUMIDIFIER LOCKOUT HL W no DISAB, No, - ENABLE
ENABLE Yes
S284 FC LOCKOUT FCL W no DISAB, No, - ENABLE
ENABLE Yes
X TYPE - - - - - - -
S275 CUSTOMER INPUT 1 CI1 W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S276 CUSTOMER INPUT 2 CI2 W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S277 CUSTOMER INPUT 3 CI3 W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S278 CUSTOMER INPUT 4 CI4 W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S279 CALL SERVICE CS W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S280 HIGH TEMPERATURE HTD W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S281 LOSS OF AIR BLOWER 1 LB1 W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S282 REHEAT LOCKOUT RL W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S283 HUMIDIFIER LOCKOUT HL W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S284 FC LOCKOUT FCL W no MSG, WRN, ALM MSG, WRN, ALM - WRN
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 8 of 8
S286 PASSWORD - W - - - - -
X DELAY - - - - - - -
S290 NO POWER NOP W no 0-9999sec 0-9999s 1 0sec
S293 EC FAN FAULT EFF W no 0-9999sec 0-9999s 1 20sec
S294 HIGH SUP TEMP HST W no 0-9999sec 0-9999s 1 30sec
S295 LOW SUP TEMP LST W no 0-9999sec 0-9999s 1 30sec
S296 REDUCED ECONOMIZER REA W no 0-9999sec 0-9999s 1 0sec
AIRFLOW
S297 ECO EMERGENCY EMO W no 0-9999sec 0-9999s 1 0sec
OVERRIDE
x EN-DIS - - - - - - -
S290 NO POWER NOP W no DISAB, No, - ENABLE
ENABLE Yes
S293 EC FAN FAULT EFF W no DISAB, No, - ENABLE
ENABLE Yes
S294 HIGH SUP TEMP HST W no DISAB, No, - DISAB
ENABLE Yes
S295 LOW SUP TEMP LST W no DISAB, No, - DISAB
ENABLE Yes
S296 REDUCED ECONOMIZER REA W no DISAB, No, - ENABLE
AIRFLOW ENABLE Yes
S297 ECO EMERGENCY EMO W no DISAB, No, - ENABLE
OVERRIDE ENABLE Yes
x TYPE - - - - - - -
S290 NO POWER NOP W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S293 EC FAN FAULT EFF W no MSG, WRN, ALM MSG, WRN, ALM - ALM
S294 HIGH SUP TEMP HST W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S295 LOW SUP TEMP LST W no MSG, WRN, ALM MSG, WRN, ALM - WRN
S296 REDUCED ECONOMIZER REA W no MSG, WRN, ALM MSG, WRN, ALM - WRN
AIRFLOW
S297 ECO EMERGENCY EMO W no MSG, WRN, ALM MSG, WRN, ALM - WRN
OVERRIDE
3.2.6 S720 iCOM DO Setup (Not used in PCW, Cold Fire Large Display only)
S720 iCOM DO Setup Configures iCOM DO setup.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 1 of 3
S720 PASSWORD - W - - - - -
S721 iCOM-DO #0 - R - not connected, - - -
connected
S725 Override #0 - W - No, - 1 -
relay1-relay15
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 3
S731 PASSWORD - W - - - - -
S732 Event Description: ID
S733 Cooling Status - W - No, 0 - 1 No
S734 Heating Status - W - No, 0 - 1 No
S735 Humidifying Status - W - No, 0 - 1 No
S736 Dehumidifying Status - W - No, 0 - 1 No
S737 High Temperature - W - No, 0 - 1 No
S738 High Humidity - W - No, 0 - 1 No
S739 Low Temperature - W - No, 0 - 1 No
S740 Low Humidity - W - No, 0 - 1 No
S732 Event Description: Output #
S733 Cooling Status - W - 1-15 - 1 1
S734 Heating Status - W - 1-15 - 1 2
S735 Humidifying Status - W - 1-15 - 1 3
S736 Dehumidifying Status - W - 1-15 - 1 4
S737 High Temperature - W - 1-15 - 1 5
S738 High Humidity - W - 1-15 - 1 6
S739 Low Temperature - W - 1-15 - 1 7
S740 Low Humidity - W - 1-15 - 1 8
S732 Event Description: Status
S733 Cooling Status - R - 0-1 - 1 -
S734 Heating Status - R - 0-1 - 1 -
S735 Humidifying Status - R - 0-1 - 1 -
S736 Dehumidifying Status - R - 0-1 - 1 -
S737 High Temperature - R - 0-1 - 1 -
S738 High Humidity - R - 0-1 - 1 -
S739 Low Temperature - R - 0-1 - 1 -
S740 Low Humidity - R - 0-1 - 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 3
S742 PASSWORD - W - - - - -
S743 Event Description: ID
S744 High Head Pressure C1 - W - No, 0 - 1 No
S745 High Head Pressure C2 - W - No, 0 - 1 No
S746 Loss of Airflow - W - No, 0 - 1 No
S747 Change Filters - W - No, 0 - 1 No
S748 Water Alarm - W - No, 0 - 1 No
S749 Condensing Pump Alarm - W - No, 0 - 1 No
S750 Glycool Status - W - No, 0 - 1 No
S751 Unit On - W - No, 0 - 1 No
S743 Event Description: Output #
S744 High Head Pressure C1 - W - 1-15 - 1 9
S745 High Head Pressure C2 - W - 1-15 - 1 9
S746 Loss of Airflow - W - 1-15 - 1 10
S747 Change Filters - W - 1-15 - 1 11
S748 Water Alarm - W - 1-15 - 1 12
S749 Condensing Pump Alarm - W - 1-15 - 1 13
S750 Glycool Status - W - 1-15 - 1 14
S751 Unit On - W - 1-15 - 1 15
S743 Event Description: Status
S744 High Head Pressure C1 - R - 0-1 - 1 -
S745 High Head Pressure C2 - R - 0-1 - 1 -
S746 Loss of Airflow - R - 0-1 - 1 -
S747 Change Filters - R - 0-1 - 1 -
S748 Water Alarm - R - 0-1 - 1 -
S749 Condensing Pump Alarm - R - 0-1 - 1 -
S750 Glycool Status - R - 0-1 - 1 -
S751 Unit On - R - 0-1 - 1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 8: pressure circuit 2
S956 PASSWORD - W - - - - -
S957 Refrigerant - W no R22, - - R22
R407C,
R410A
S958 HP2 Sensor 0V= - W no (-)145-725psi - 1 -87psi
(-)10.0-50.0bar 0.1 -6.0bar
S959 HP2 Sensor 10V= - W no (-)145-725psi - 1 435psi
(-)10.0-50.0bar 0.1 30.0bar
S960 Actual HP2 Voltage - R no 0.0-10.0V - 0.1 -
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 3
S612 PASSWORD - W - - - - -
S613 Optional Sensor A1 TEMP A W no (-)18-18°F (-)18-18°F 1 0°F
(-)9.9-9.9K (-)9.9-9.9K 0.1 0.0K
S614 Calibrated Optional CAL A R no 32-122°F 32-122°F 1 -
Sensor A1 0.0-50.0 °C 0.0-50.0 °C 0.1
S615 Optional Sensor A2 HUM A W no (-)9.9-9.9% (-)9.9-9.9% 0.1 0.0%
or or
(-)18.0-18.0°F (-)18.0-18.0°F(%) 0.1 0.0°F
(-)9.9-9.9K (-)9.9-9.9K(%) 0.1 0.0K
S616 Calibrated Optional CAL A R no 20.0-80.0% 20.0-80.0% 0.1 -
Sensor A2 or or
32.0-122.0°F 32.0-122.0°F(%) 0.1
0.0-50.0 °C 0.0-50.0 °C(%) 0.1
S617 Optional Sensor B Type TYPE B W no TH, TH, - 2T
2T 2T
S618 Optional Sensor B1 TEMP B W no (-)18-18°F (-)18-18°F 1 0°F
(-)9.9-9.9K (-)9.9-9.9K 0.1 0.0K
S619 Calibrated Optional CAL B R no 32-122°F 32-122°F 1 -
Sensor B1 0.0-50.0 °C 0.0-50.0 °C 0.1
S620 Optional Sensor B2 HUM B W no (-)9.9-9.9% (-)9.9-9.9% 0.1 0.0%
or or
(-)18.0-18.0°F (-)18.0-18.0°F(%) 0.1 0.0°F
(-)9.9-9.9K (-)9.9-9.9K(%) 0.1 0.0K
S621 Calibrated Optional CAL B R no 20.0-80.0% 20.0-80.0% 0.1 -
Sensor B2 or or
32.0-122.0°F 32.0-122.0°F(%) 0.1
0.0-50.0 °C 0.0-50.0 °C(%) 0.1
S622 Optional Sensor C Type TYPE C W W no TH, - TH
2T
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 3
S623 PASSWORD - W - - - - -
S625 Freecool Sensor FC SNSR W no (-)18-18°F (-)18-18°F 1 0°F
(-)9.9-9.9K (-)9.9-9.9K 0.1 0.0K
S626 Calibrated Freecool CAL FC R no 4-113°F 4-113°F 1 -
Sensor (-)15.0-45.0°C (-)15.0-45.0°C 0.1
S628 Supply/Return Sensor SUP TEMP W no (-)18-18°F (-)18-18°F 1 0°F
(-)9.9-9.9K (-)9.9-9.9K 0.1 0.0K
S629 Calibrated Supply Sensor CAL SUP R no 32-122°F 32-122°F 1 -
or 0.0-50.0°C 0.0-50.0°C 0.1
Calibrated Return Sensor
S630 Offset Optional Sensor TEMP C W no (-)18-18°F (-)18-18°F 1 0°F
C1 or (-)9.9-9.9K (-)9.9-9.9K 0.1 0.0K
or AMB TEMP
Offset Outdoor
Temperature
S631 Calibrated Optional CAL C R no 32-122°F 32-122°F 1 -
Sensor C1 or 0.0-50.0°C 0.0-50.0°C 0.1
or CAL AMBT
Calibrated Outdoor
Temperature
S632 Offset Optional Sensor HUM C W no (-)9.9-9.9% (-)9.9-9.9% 0.1 0.0%
C2 or or or
or AMB HUM (-)18.0-18.0°F (-)18.0-18.0°F(%) 0.1 0.0°F
Offset Outdoor Humidity (-)9.9-9.9K (-)9.9-9.9K(%) 0.1 0.0K
S633 Calibrated Optional CAL C R no 20.0-80.0% 20.0-80.0% 0.1 -
Sensor C2 or or or
or CAL AMBH 32.0-122.0°F 32.0-122.0°F(%) 0.1
Calibrated Outdoor 0.0-50.0 °C 0.0-50.0 °C(%) 0.1
Humidity
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 3
SA12 PASSWORD - W - - - - -
SA13 Outdoor Air Sensor OUT TEMP R no °F °F 1 -
Temperature °C °C 0.1
SA14 Outdoor Air Sensor OUT HUMI R no % % 0.1 -
Humidity
SA15 Outdoor Air Pressure OUT PRES W no 100.0-1200.0hPa 100-1200hP 0.1 1013.2hPa
SA16 Saturation Pressure SAT PR W R no hPa hP 0.1 -
WaterVapor
SA17 Saturation Pressure Ice SAT PR I R no hPa hP 0.1 -
SA18 Partial Pressure (Water PA PRES R no hPa hP 0.1 -
Vapor)
SA19 Volume Mixture Ratio V MIX RAT R no ppm pp 0.1 -
(ppm/Vol)
SA20 Humidity Ratio (g/kg HUMI RAT R no g/k gk 0.1 -
wet)
SA21 Wet Bulb Temperature WET BULB R no °F, °F, 1 -
°C °C 0.1
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 3
SA23 PASSWORD - W - - - - -
SA24 Return Damper Open RET OPEN W no 0.0-10.0V 0.0-10.0V 1 0.0V
0.1
SA25 Return Damper Closed RET CLOS W no 0.0-10.0V 0.0-10.0V 1 10.0V
0.1
SA26 Return Damper RET MIN W no 0-100% 0-100% 1 15%
Minimum Limit At
SA27 Outdoor Damper Open OUT OPEN W no 0.0-10.0V 0.0-10.0V 1 10.0V
0.1
SA28 Outdoor Damper Closed OUT CLOS W no 0.0-10.0V 0.0-10.0V 1 0.0V
0.1
SA29 Outdoor Damper OUT POS R no 0-100% 0-100% 1 -
Position
SA30 Return Damper Position RET POS R no 0-100% 0-100% 1 -
SA31 Enable Digital Outputs ECO DIG W no No, No, - Yes
Yes Yes
SA32 Damper Runtime DAM RUN W no 30-500sec 30-500s 1 165sec
SA33 Pause Time DAM PAU W no 1-20sec 1-20s 1 5sec
Groups of units, connected to a network, can be selected to work together in 3 teamwork modes:
No Teamwork: All units are working independently. No values or sensors are shared (except the outdoor temperature sensor, if present).
Standby function + unit rotation is possible; cascading is not possible in that configuration.
The unit controls cooling/heating and hum/dehum by calculating the deviation between actual setpoint and return air temperature/humidity,
creating 2 values from -100 to + 100%, (one for temperature control, the other one for humidity control) where 0 deviation means the value is on
the setpoint. According to the type of unit and options installed (single compressor, double compressor etc.) the resources are started and stopped
on this -100 / + 100% deviation line.
Teamwork Mode 1
In this teamwork mode most of parameters are shared (see list of parameters table); if set in any of the units, all other units will follow with the
same settings.
Return temperature and humidity of all units in operation (fan on) are averaged (from unit #1) and used for control.
Unit #1 calculates the system deviation and sends the relative parts of the proportional band to the units, which start the requested operations.
The width of the proportional band in multiple unit configuration is shown as normal, but internally unit #1, which sends the requests to the other
units, multiplies the width by the number of available units internally.
The number of available units is calculated like:
a) In no standby configuration: all units with fan on
b) In typical standby function (no cascade): all units with fan on
c) In cascade mode: all units that could operate (no alarm which forces the unit to switch off, unit not switched off etc.)
heating cooling
- temp. + temp.
- 100% 1/2 Proportional Band 0% 1/2 Proportional Band + 100%
Setpoint
cooling cooling
+ temp. + temp.
0% 1/2 Proportional Band + 100% 0% 1/2 Proportional Band + 100%
Setpoint Setpoint
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 2 (System / CF Display)
S812 PASSWORD - W - - - - -
S813 IP Address IP #1-IP #4 W no IP Range IP Range 1 -
IP Address: need to be unique inside the network, to be requested from the IT responsible when the group shall be connected into a company
network. If a private network is used (no connection to the outside) the standard numbers can be used: 192.168.254.001 to 192.168.254.254. The
first 3 sets of numbers must be the same within the network, the 4th set of numbers must be unique for each board / display.
S814 Netmask NM #1-NM #4 W no Netmask Netmask 1 -
Range Range
Netmask: to be requested from the IT responsible when the group shall be connected into a company network. If a private network is used (no
connection to the outside) the standard numbers can be used: 255.255.255.000 for ALL boards / displays inside the network.
S815 Gateway GW #1-GW #4 W no Gateway Gateway 1 -
Range Range
Gateway: to be requested from the IT responsible when the group shall be connected into a company network. If a private network is used (no
connection to the outside) the standard numbers can be used: 192.168.1.55 for ALL boards / displays inside the network.
S816 MAC MAC R no MAC Range MAC Range 1 -
MAC: a MAC address is already preset from the manufacturer and is a worldwide unique network address which usually must not be changed. Only
in case of duplication inside the network the MAC ID shall be changed to avoid duplicate numbers.
S817 U2U Protocol U2U PROT W no GBP GBP - GBP
U2U protocol defines the communication protocol and in the PA it is always GBP (Global Bus Protocol).
U2U Address: this address defines the ID number of the board / display inside the network.
Boards: address range: 1 – 32 (needs to be addressed consecutively, starting with 1, no duplication)
Displays: address range: 33 – 64 (choose any number, no duplication)
S819 U2U Group U2U GRP W no 1-99 1-99 1 -
U2U Group: usually all units, connected to the same network are belonging together and need to follow the rules of the above mentioned address
system. If within the same network / switch / hub units belonging to several groups (rooms) are connected together, but without any relation
between the groups, the group parameter would allow to divide the various units into groups of units, whereas a unit or display of group 1 has no
logical connection to a unit / display of another group, even if connected to the same network / switch / hub.
S821 Bootloader Variables BL STAT R no Not Available, Not A, - -
Invalid, OK, Inval, Valid,
Changed, Chang,
Updating Updat
S821 Bootloader Variables BL CTRL W no No, No, - No
Save+Reboot S+R
Save + Reboot command saves the bootloader variables and restarts the device.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 1 of 2 (Unit)
S823 PASSWORD - W - - - - -
S824 Monitoring Address MON ADD W no 1-99 1-99 1 3
When the ‘’BMS Disconnected’’ Warning is not active the Monitoring Timeout is set automatically to no, and it is set to yes if the warning is active.
For reset the warning must be put the Monitoring Handshake to a value different to 0 and than restore the value to 0.
The iCOM application incorporates a remote communication timer which allows it to determine if communication from a remote management
system has failed. This timer consists of an internal event called "BMS Disconnected" (Type: Warning). This event will be true if a remote
management system has not reset the timer within a specified time period, in minutes. The default status of the Remote Communication Timer is
zero (0). The value in the timer is the number of minutes until the timer event will become true. For example, if a remote management system
sets the Remote Communication Timer to 5, then iCOM controller will wait for 5 minutes until the Remote Communication Timer Expired event
becomes true.
S827 Unit Name - W no 6 digits 6 digits - UNIT
This parameter allows to change the name to the device (max 6 digits).
S831 Configuration Safe CS STAT R no Not Available, Not A, - -
Invalid, OK, Inval, Valid,
Changed, Chang,
Updating Updat
Status of configurationsafe .xml.
S831 Configuration Safe CS CTRL W no No, Save, No, Save, - No
Load Load
To safe the actual configuration into the configurationsafe .xml; or to load from an existing configurationsafe .xml.
S832 Network Safe NW STAT R no Not Available, Not A, - -
Invalid, OK, Inval, Valid,
Changed, Chang,
Updating Updat
Status of networksafe .xml.
S832 Network Safe NW CTRL W no No, Save, No, Save, - No
Load Load
To safe the actual configuration into the networksafe .xml; or to load from an existing networksafe .xml.
S833 SW Version SW# R no String String - -
Shows the Software Version.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 2 (Unit)
S834 PASSWORD - W - - - - -
S835 Monitoring Protocol MON PROT W no No, Velocity, No, Vlcty, - -
Hironet, IGM HN, IGM
Defines the monitoring protocol type.
S836 IP Address IP #1-IP #4 W no IP Range IP Range 1 -
IP Address: need to be unique inside the network, to be requested from the IT responsible when the group shall be connected into a company
network. If a private network is used (no connection to the outside) the standard numbers can be used: 192.168.254.001 to 192.168.254.254. The
first 3 sets of numbers must be the same within the network, the 4th set of numbers must be unique for each board / display.
S837 Netmask NM #1-NM #4 W no Netmask Netmask 1 -
Range Range
Netmask: to be requested from the IT responsible when the group shall be connected into a company network. If a private network is used (no
connection to the outside) the standard numbers can be used: 255.255.255.000 for ALL boards / displays inside the network.
S838 Gateway GW #1-GW #4 W no Gateway Gateway 1 -
Range Range
Gateway: to be requested from the IT responsible when the group shall be connected into a company network. If a private network is used (no
connection to the outside) the standard numbers can be used: 192.168.1.55 for ALL boards / displays inside the network.
S839 MAC MAC R no MAC Range MAC Range 1 -
MAC: a MAC address is already preset from the manufacturer and is a worldwide unique network address which usually must not be changed. Only
in case of duplication inside the network the MAC ID shall be changed to avoid duplicate numbers.
S840 U2U Protocol U2U PROT W no GBP GBP - GBP
U2U protocol defines the communication protocol and in the PA it is always GBP (Global Bus Protocol).
S841 U2U Address U2U ADD W no 1-32 1-32 1 -
U2U Address: this address defines the ID number of the board / display inside the network.
Boards: address range: 1 – 32 (needs to be addressed consecutively, starting with 1, no duplication)
Displays: address range: 33 – 64 (choose any number, no duplication)
S842 U2U Group U2U GRP W no 1-99 1-99 1 -
U2U Group: usually all units, connected to the same network are belonging together and need to follow the rules of the above mentioned address
system. If within the same network / switch / hub units belonging to several groups (rooms) are connected together, but without any relation
between the groups, the group parameter would allow to divide the various units into groups of units, whereas a unit or display of group 1 has no
logical connection to a unit / display of another group, even if connected to the same network / switch / hub.
S843 Bootloader Variables BL STAT R no Not Available, Not A, - -
Invalid, OK, Inval, Valid,
Changed, Chang,
Updating Updat
Shows the status of the bootloader status. As soon as such a parameter was changed, the status will show ‘’changed’’.
S843 Bootloader Variables BL CTRL W no No, No, - No
Save+Reboot S+R
To activate changes done on the bootloader variable the device needs to rebooted using the ‘’save + reboot’’ command.
S844 Static RAM SR STAT R no Not Available, Not A, - -
Invalid, OK, Inval, Valid,
Changed, Chang,
Updating Updat
S844 Static RAM SR CTRL W no No, No, - No
Clear+Reboot C+R
To ‘’clear + reboot’’ allows to empty the static ram and to reboot the board.
The heating proportional band is divided into 3 equal parts which represent the steps programmed.
S407 LWD Connected LWDconn W No No, No, - No
Yes Yes
S408 Valve Control V_CTRL W no Time, Time, - Time
Feedback Feedb
S409 3P Actuator Runtime 3P RUN W no 30-500sec 30-500s 1 170sec
The 3P actuators are used for cooling (Chilled water or Freecooling), valves or dampers. They are driven through 2 digital outputs: open and close.
S410 3P Actuator Direction 3P DIR W no Direct, DIR, - Direct
Reverse REV
The S410 3P Actuator Direction defines if the valve/damper works in direct or reverse mode (the outputs are exchanged when the parameter is
changed from direct to reverse: ex open will be close, and ex close will be open).
S411 Loss of Flow CFC LOF THRH W no 0-30% 0-30% - 10%
Threshold
Loss of Flow event (customer input) is disabled on CW unit when the call for cooling for CW is lower than what is set in S411 "Loss of Flow CFC
Threshold". It is disabled on DX unit when no compressors are ON when the input is active
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 6
S412 PASSWORD - W - - - - -
S413 Humidification Enabled HUM ENAB W no No, Yes No, Yes - Yes
The S413 Humidification Enabled parameter allows enabling / disabling the humidifier function w/o the need to remove fuses or cheat other
settings to achieve no start of the humidifier.
S414 Infrared Flush Rate IR FLUSH W No 110-500% 110-500% 1 150%
When set to 100% the humidifier will produce the nominal amount of steam, if set to a lower value the humidifier will produce less steam
according the setting. This is valid for both operating modes: ON-Off and proportional.
S416 Humidifier Control HUMCONT W No On-Off, OnOff, - On-Off
Proportional Prop
The control behavior of the humidifier: hen set to ON/OFF the humidifier will start at the left-end of humidity proportional band at its maximum
capacity (defined with STEAM RATE) and stop when the room humidity Setpoint is reached.
When set to proportional, the steam output will be proportional to the deviation of return air humidity from room humidity Setpoint.
S417 Humidifier Bottle Flush HUM.TIME W No 5-30sec 5-30s 1 5sec
Time
S418 Humidifier Bottle Manual HUM.MAN V No No, No, - No
Flush Yes Yes
S419 Dehumidification DEHUM EN W No No, No, - Yes
Enabled Yes Yes
The Dehum Enabled parameter allows enabling / disabling the dehumidification function w/o the need to remove fuses or cheat other settings to
achieve no start of dehumidification.
S419 Dehun Fan Ctrl DEH FAN W No No, No, - Yes
Yes Yes
If it is set to “Yes” the fan will operate at the speed set on S149 “VSD Setpoint Dehum” in case of call for dehumidification. If it is set to “No” the fan
will operate at the S148 "VSD Setpoint STD" speed when there is a call for dehumidification. This function is available only if the parameter S146
"VSD Fanspeed" is set to “Manual”.
S420 Auto Restart Enabled REST EN W no No, No, - Yes
Yes Yes
Enable the S421 (Single unit Auto restart)
S421 Single Unit Auto Restart RESTART W no 0-999sec 0-999s 1 5sec
The time delay, in seconds, between the power on and the start of the unit. NOTE: Each unit multiplies the time with its iCOM ID Number.
S422 On-Off Enabled ONOFF EN W no No, No, - Yes
Yes Yes
“YES” to accept the ON/OFF command from a connected display.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 6
S423 PASSWORD - W - - - - -
S424 CW Flush CW FLUSH W No 0-99hrs 0-99hr 1 0hrs
Every selected number of hours, the CW valve is opened at 100% for a time (min.) defined into the Factory Settings, page 4 and 5. This is to mix the
water. 0 = disabled
S425 Freecooling Flush FC FLUSH W no 0-99hrs 0-99hr 1 0hrs
Every selected number of hours, the Freecooling valve is opened at 100% for a time (min.) defined into the Factory Settings, page 4 and 5. This is to
mix the water. 0 = disabled
S426 Hot Water Flush HW FLUSH W no 0-99hrs 0-99hr 1 0hrs
Every selected number of hours, the Hot Water valve is opened at 100% for a time (min.) defined into the Factory Settings, page 4 and 5. This is to
mix the water. 0 = disabled
S427 Ball Valve Setpoint Offset BALL OFF W no +0.0-+4.8bar +0.0-+4.8br 0.1 +2.1bar
+0-+70psi +0-+70pa 1 +30psi
S428 Heaters output as HEAT AS W No OFF,LQT, FCF, LQT, FCF, CHF, - OFF
CHF, LTA, HTA LTA, HTA
In case the total heat stages = 0, the related digital outputs can be used for alternative purpose:
The outputs are normally ON. They are de-activated (OFF) as soon as one of the listed events are active.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 6
S434 PASSWORD - W - - - - -
S435 Minimu CW Valve CW OPEN W no 0-50% 0-50% 1 0%
Opening
It defines the minimum CW valve opening position when, unit is ON.
S436 DX-CW Overlap DX-CW W No No, No, - No
Yes Yes
It enables the DX-CW Overlapping function.
S437 DX-CW Overlap Time DX-CW T W No 0-500sec 0-500sec 1 0sec
It defines the length of DX-CW Overlapping time.
S438 Max Overlap Activations DX-CW A W no 2-6 2-6 1 6
It defines the maximum number of DX-CW Overlapping function activation, within one hour. The event 237 “Check Chilled Water System” is
activated when the number of activation exceeds the limit; In such condition control disables the use of freecooling. The number of function
activation is automatically set to zero when, the event is reset or after one hour, if the limit is not reached or when unit is set to OFF.
S439 CW Valve Reset CW RESET W No No, No, - No
Yes Yes
It enables or disables the CW valve reset function. If it is set to Disabled the control will not perform a valve reset, the valve will be reset only in
case of fan off. If it is set to Enabled the CW valve reset function works as standard.
S440 Freecooling On Delay FC ON D W no 0-300sec 0-600sec 1 60sec
It defines the minimum condition time before to enable the use of freecooling.
S441 Stop Fc at Setpoint by STOP FC W No Return, Ret, - Return
Supply, Sup,
Aisle Ais
It defines which temperature, Return, Supply or Aisle, has to be considered by control on “Stop Fc at Setpoint” function management.
S442 Stop Fc at Setpoint Delay STOP DEL W no 0-300sec 0-600sec 1 60sec
It defines the delay considered by control before stopping the freecooling operating mode when, the temperature is higher than the limit.
S443 High CW Temperature HI CW D W No 0-60sec 0-60sec 1 2sec
Delay
It defines the delay considered by control before disabling the DX-CW Overlapping function. On such condition control keeps active (if ON) the
compressor even if there are conditions to use the freecooling (indication of _S372 “Status Min CW” = “Act”).
S444 High CW Temperature HI CW R W no 0-60sec 0-60sec 1 2sec
Reset
It defines the delay considered by control before enabling the DX-CW Overlapping function (indication of _S372 “Status Min CW” = “Off”).
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 6
S445 PASSWORD - W - - - - -
S447 Analog Input 1: (Measure - W no Factory Std, - - Factory Std
Type) Not Config,
not used,
Air Pres 1,
Air Pres 2,
Air Pres 3,
Air Pres 4,
Pressure 1,
Pressure 2,
Pressure 3,
Pressure 4,
Temp 1,
Temp 2,
Temp 3,
Temp 4,
Percent 1,
Percent 2,
Percent 3,
Percent 4
S447 Analog Input 1: - W no 0-5V, - - 0-5V
(Precision) 0-10V,
Invalid,
Invalid,
Invalid,
Invalid
S448 Analog Input 2: (Measure - W no See Analog Input - - Factory Std
Type) 1: (Measure
Type)
S448 Analog Input 2: - W no See Analog Input - - 0-5V
(Precision) 1: (Precision)
S449 Analog Input 3: (Measure - W no See Analog Input - - Factory Std
Type) 1: (Measure
Type)
S449 Analog Input 3: - W no See Analog Input - - 0-5V
(Precision) 1: (Precision)
S450 Analog Input 4: (Measure - W no See Analog Input - - Factory Std
Type) 1: (Measure
Type)
S450 Analog Input 4: - W no See Analog Input - - 0-5V
(Precision) 1: (Precision)
S452 Units System for Custom - W no Metric, - - Metric
Inputs English
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 6
S456 PASSWORD - W - - - - -
S457 Analog Input 1 Start - W no (-)320.00-320.00 - - -
Point
S457 Analog Input 1 Units - W no °C, - - -
bar,
Pas,
%,
°F,
PSI,
inWG
S457 Analog Input 1 Start - W no 0.0-10.0V - - -
Point
Not used in PCW units.
S458 Analog Input 1 End Point - W no (-)320.00-320.00 - - -
S458 Analog Input 1 Units - W no See Analog Input - - -
1 Units
S458 Analog Input 1 End Point - W no 0.0-10.0V - - -
Not used in PCW units.
S459 Analog Input 2 Start - W no (-)320.00-320.00 - - -
Point
S459 Analog Input 2 Units - W no See Analog Input - - -
1 Units
S459 Analog Input 2 Start - W no 0.0-10.0V - - -
Point
Not used in PCW units.
S460 Analog Input 2 End Point - W no (-)320.00-320.00 - - -
S460 Analog Input 2 Units - W no See Analog Input - - -
1 Units
S460 Analog Input 2 End Point - W no 0.0-10.0V - - -
Not used in PCW units.
S461 Analog Input 3 Start - W no (-)320.00-320.00 - - -
Point
S461 Analog Input 3 Units - W no See Analog Input - - -
1 Units
S461 Analog Input 3 Start - W no 0.0-10.0V - - -
Point
Not used in PCW units.
S462 Analog Input 3 End Point - W no (-)320.00-320.00 - - -
S462 Analog Input 3 Units - W no See Analog Input - - -
1 Units
S462 Analog Input 3 End Point - W no 0.0-10.0V - - -
Not used in PCW units.
S463 Analog Input 4 Start - W no (-)320.00-320.00 - - -
Point
S463 Analog Input 4 Units - W no See Analog Input - - -
1 Units
S463 Analog Input 4 Start - W no 0.0-10.0V - - -
Point
Not used in PCW units.
S464 Analog Input 4 End Point - W no (-)320.00-320.00 - - -
S464 Analog Input 4 Units - W no See Analog Input - - -
1 Units
S464 Analog Input 4 End Point - W no 0.0-10.0V - - -
Not used in PCW units.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 6
SB12 PASSWORD - W - - - - -
SB13 Cascade Control CASCADE W Yes Mode 1, MOD 1 - Mode 1
Mode 2 MOD 2
Enables and defines the units cascade control mode:
• Mode 1: the maximum speed of fan is limited to the SB19 parameter setting, the required standby units are added, step by step, if
the current speed request is higher than the limit set and, such condition persists for the time delay set with the SB15 parameter.
Fans are allowed to run at maximum speed (SB18) after that all required standby units have been activated. Control applies the
limit (SB19) again when the current speed request is lower than the SB19 limit. The added units are removed step by step when,
the speed of fan is at minimum value, the cold aisle temperature is lower than setpoint and, such condition persists for the time
delay set with the SB16 parameter.
• Mode 2: as per Mode 1 with the difference that the speed of fans is modulated from SB17 to SB18 parameters settings.
Note: Humidity control is performed by the active units only; units are activated / deactivated in accordance with the temperature deviation only.
Note: All units drive the fan using the value calculated by this function.
SB14 Cascade Units Number CASC NR W Yes No, No, 1 No
1-31 1-31
Defines the number of standby units (defined with the S502 parameter) which can be used by the Cascade Control Type function.
SB15 Unit ON Delay TIME ON W Yes 1-60min 1-60min 1 10min
Defines the minimum condition time considered by the control before to active one of the standby unit.
SB16 Unit OFF Delay TIME OFF W Yes 1-60min 1-60min 1 30min
Defines the minimum condition time considered by the control before to setback to standby one of the activated unit.
SB17 VSD Fanspeed Min VSD MIN W Yes 30-50% 30-50% 1 30%
Defines the minimum speed of fan.
SB18 VSD Fanspeed Max VSD MAX W Yes 50-100% 50-100% 1 80%
Defines the maximum speed of fan.
SB19 Cascade VSD Limit VSD CASC W Yes 30-100% 30-100% 1 40%
Define the limit of fan speed used by the control Mode 1 and 2.
SB20 Cascade Status CASC R YES Deactivated, Dact, - -
Activated Act
Indicates if the cascade function is activated or deactivated (read only).
SB21 Cascade Counter COUNT R YES 1-32 1-32 - -
Indicated the number of the standby units (read only).
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 6
SB23 PASSWORD - W - - - - -
SB24 Temperature Limits TEMP-LIM W Yes No, No, - No
Yes Yes
Enables the high temperature limits managed by the THB sensor located inside the cold aisle.
Note: this parameter is automatically set to Disabled and hidden when the SB02 parameter is set to No.
SB25 High Temperature TEMP.WA W Yes 1.0-99.0°C 1.0-99.0°C 0.1 30°C
Warning
Defines the first temperature limit. The 022 ΗΤ1 (High Aisle Temperature) warning event is activated when such limit is reached.
The event is automatically reset when the temperature drops 2.0°C below the limit set.
Note: Standby units are activated only if the S509 parameter is enabled.
Note: The warning condition is ignored for a time of 1 minute when the system is activated (ON), the minimum condition time, after the initial one,
is defined by the S243 parameter setting.
SB26 High Temperature Alarm TEMP.AL W Yes 1.0-99.0°C 1.0-99.0°C 0.1 35°C
Defines the second temperature limit. The 023 ΗΤ2 (High Aisle Temperature) alarm event is activated when such limit is reached.
Note: standby units are always activated.
Note: the warning condition is ignored for a time of 1 minute when the system is activated (ON), the minimum condition time, after the initial one,
is defined by the S244 parameter setting.
SB27 Humidity Limits HUM.LIM W Yes No, No, - No
Yes Yes
Enables the high humidity limits managed by the THB sensor located inside the cold aisle.
Note: this parameter is automatically set to Disabled and hidden when the SB02 parameter is set to No.
SB28 High Humidity Warning HUM.WA W Yes 1.0-99.0% 1.0-99.0% 0.1 75%
Defines the first high humidity limit. The 024 ΗΗ1 (High Aisle Humidity) warning event is activated when the limit is reached.
The event is automatically reset when the humidity drops 3% below the limit set.
Note: The warning condition is ignored for a time of 1 minute when the system is activated (ON), the minimum condition time, after the initial one,
is defined by the S245 parameter setting.
SB29 High Humidity Alarm HUM.AL W Yes 1.0-99.0% 1.0-99.0% 0.1 80%
Defines the second high humidity limit. The 025 ΗΗ2 (High Aisle Humidity) alarm event is activated when the limit is reached.
Note: The warning condition is ignored for a time of 1 minute when the system is activated (ON), the minimum condition time, after the initial one,
is defined by the S246 parameter setting.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 6
SB34 PASSWORD - W - - - - -
SB35 Remote THB 1 Enabled THB 1 EN W No No, No, - No
Yes Yes
Enables the use of sensor 1.
SB36 Remote THB 1 THB1 SET W No (-)9.9-9.9K (-)9.9-9.9K 0.1 -
Sensor 1 calibration.
SB37 Calibrated Remote THB 1 THB 1 R No (-)100.0-100.0°C (-)100.0-100.0°C 0.1 -
Actual Aisle Temperature 1 value.
SB38 Remote THB 2 Enabled THB 2 EN W No No, No, - No
Yes Yes
Enables the use of sensor 2.
SB39 Remote THB 2 THB2 SET W No (-)9.9-9.9K (-)9.9-9.9K 0.1 -
Sensor 2 calibration.
SB40 Calibrated Remote THB 2 THB 2 R No (-)100.0-100.0°C (-)100.0-100.0°C 0.1 -
Actual Aisle Temperature 2 value.
SB41 Remote THB 3 Enabled THB 3 EN W No No, No, - No
Yes Yes
Enables the use of sensor 3.
SB42 Remote THB 3 THB3 SET W No (-)9.9-9.9K (-)9.9-9.9K 0.1 -
Sensor 3 calibration.
SB43 Calibrated Remote THB 3 THB 3 R No (-)100.0-100.0°C (-)100.0-100.0°C 0.1 -
Actual Aisle Temperature 3 value.
SB44 Value Sent to Master THB T R No (-)100.0-100.0°C (-)100.0-100.0°C 0.1 -
Represents the temperature value (of enabled THB sensors) used by control in according with the SB06 parameter setting.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 6
SB45 PASSWORD - W - - - - -
SB46 Remote THB 1 Enabled THB 1 EN W No No, No, - No
Yes Yes
Enables the use of sensor 1.
SB47 Remote THB 1 THB1 SET W No (-)9.9-9.9% (-)9.9-9.9% 0.1 -
Sensor 1 calibration.
SB48 Calibrated Remote THB 1 THB 1 R No (-)100.0-100.0% (-)100.0-100.0% 0.1 -
Actual Aisle Humidity 1 value.
SB49 Remote THB 2 Enabled THB 2 EN W No No, No, - No
Yes Yes
Enables the use of sensor 2.
SB50 Remote THB 2 THB2 SET W No (-)9.9-9.9% (-)9.9-9.9% 0.1 -
Sensor 2 calibration.
SB51 Calibrated Remote THB 2 THB 2 R No (-)100.0-100.0% (-)100.0-100.0% 0.1 -
Actual Aisle Humidity 2 value.
SB52 Remote THB 3 Enabled THB 3 EN W No No, No, - No
Yes Yes
Enables the use of sensor 3.
SB53 Remote THB 3 THB3 SET W No (-)9.9-9.9% (-)9.9-9.9% 0.1 -
Sensor 3 calibration.
SB54 Calibrated Remote THB 3 THB 3 R No (-)100.0-100.0% (-)100.0-100.0% 0.1 -
Actual Aisle Humidity 3 value.
SB55 Value Sent to Master THB H R No (-)100.0-100.0% (-)100.0-100.0% 0.1 -
Represents the humidity value (of enabled THB sensors) used by control in according with the SB10 parameter setting.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 6
SB56 PASSWORD - W - - - - -
SB57 Damper Control DAMPER W No No, No, - No
Yes Yes
Enable the use of the damper; fan is activated after that the damper is completely open.
SB58 Damper Feedback Input FEEDBACK W No NO, NO, - NO
as NC NC
Defines which has to be the status of input when the damper is completely open.
If the status of such input does not match with the position requested the 073 ΠΟΣ (Wrong Damper Position) event is activated.
Note: Unit is forced OFF when the event is activated.
Note: Control checks the status of input when unit is On as well as is Off (input has to be in opposite status when unit is Off).
SB59 Damper Running Time RUN TIME R No 30-180sec 30-180sec 1 60sec
Defines the damper running time. The value set is used by control to define the delay on 073 ΠΟΣ event activation.
Note: Control automatically adds 30 seconds to the value set.
SB60 Fan and Cooling 100% by FAN.COOL W No No, No, - No
User Yes Yes
If enabled the user input 1 is automatically set to “C-Input 1”. Fan and cooling is forced to 100% when the related input is active.
SB61 Sensor Visualization SENSOR W No Return, Ret, - Return
(Unit) Aisle Ais
Defines which sensors return or aisle to show in the unit main page. If aisle option is selected the cold aisle icons are shown.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 9
A134 PASSWORD - W - - - - -
A135 K11 active on K11 ACT W no Dehum, DEH, - Dehum
Warning, WNG,
No Power, NOP,
Freecooling FC
It is used to manage the dehumidification. Warning relay will activate when the dehum is requested.
A136 CW Flush Duration CW F DUR W no 0-3min 0-3m 1 0min
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 9
A145 PASSWORD - W - - - - -
A146 Humidifier Model HUM TYPE W no No, No, - No
External , EXT,
IFS, IFS,
IFL, IFL,
PeX @ 6A *, PEX6 *,
PeX @ 9A *, PEX9 *,
PeX @ 12A *, PEX12 *,
21L-CLA, 21LLA,
53L-CLC, 53LLC,
53H-CLB, 53HLB,
93L-CLE, 93LLE,
93H-CLD, 93HLD,
d3H, d3H,
HT2, HT2,
HT5, HT5,
HT9, HT9,
SGH * SGH *
Defines the Humidifier model. Models with * are typically Not used in PCW models.
A147 Humidifier Voltage HUM VOLT W no 230V, 230V, - ---
400V, 400V,
460V, 460V,
575V, 575V,
---, ---,
208V, 208V,
380V 380V
Defines the Humidifier voltage.
A148 Humidity in Last xxx HUM LAST W no 1-120hrs 1-120hr 1 -
Hours
This parameter is used for Infrared humidifier.
A149 Prefill Time PREFILL W no 1-120sec 1-120s 1 -
This parameter is used for Infrared humidifier.
A150 Fill Time FILL W no 1-120sec 1-120s 1 -
This parameter is used for Infrared humidifier.
A151 Humidifier On Time HUM ON W no 60-3600sec 60-3600s 1 -
This parameter is used for Infrared humidifier.
A152 Dehumidification with DEH COMP W no 1, 1, - 1
Comp 2, 2,
both, BOTH,
1 or 2 1or2
This parameter defines which compressor is used for dehumidification.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 7 of 9
A156 PASSWORD - W - - - - -
A157 Analog Output 1 low ANOUT1LO W no 0.0-10.0V 0.0-10.0V 0.1 3.0V
limit
This parameter defines the low limit of the analog output 1.
If the analog output 1 is set to ‘’Var Speed Drive’’ the low limit is locked to 30%.
A157 Analog Output 1 high ANOUT1HI W no 0.0-10.0V 0.0-10.0V 0.1 10.0V
limit
This parameter defines the high limit of the analog output 1.
A158 Analog Output 2 low ANOUT2LO W no 0.0-10.0V 0.0-10.0V 0.1 0.0V
limit
This parameter defines the low limit of the analog output 2.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 8 of 9
A167 PASSWORD - W - - - - -
A168 Analog Output 1 A01 STA W no (-)100-100% (-)100-100% 1 0%
Start Point
A168 Analog Output 1 A01 STA W no 0.0-10.0V 0.0-10.0V 0.1 0.0V
Start Point
The parameters A168 define the analog output 1 start point (valid only if “configurable” is set).
A169 Analog Output 1 A01 END W no (-)100-100% (-)100-100% 1 100%
End Point
A169 Analog Output 1 A01 END W no 0.0-10.0V 0.0-10.0V 0.1 10.0V
End Point
The parameters A169 define the analog output 1 end point (valid only if “configurable” is set).
A170 Analog Output 2 A02 STA W no (-)100-100% (-)100-100% 1 0%
Start Point
A170 Analog Output 2 A02 STA W no 0.0-10.0V 0.0-10.0V 0.1 0.0V
Start Point
The parameters A170 define the analog output 2 start point (valid only if “configurable” is set).
A171 Analog Output 2 A02 END W no (-)100-100% (-)100-100% 1 100%
End Point
A171 Analog Output 2 A02 END W no 0.0-10.0V 0.0-10.0V 0.1 10.0V
End Point
The parameters A171 define the analog output 2 end point (valid only if “configurable” is set).
A172 Analog Output 3 A03 STA R no (-)100-100% (-)100-100% 1 0%
Start Point
A172 Analog Output 3 A03 STA R no 0.0-10.0V 0.0-10.0V 0.1 0.0V
Start Point
The parameters A172 define the analog output 3 start point (valid only if “configurable” is set).
A173 Analog Output 3 A03 END R no (-)100-100% (-)100-100% 1 100%
End Point
A173 Analog Output 3 A03 END R no 0.0-10.0V 0.0-10.0V 0.1 10.0V
End Point
The parameters A173 define the analog output 3 end point (valid only if “configurable” is set).
A174 Analog Output 4 A04 STA W no (-)100-100% (-)100-100% 1 0%
Start Point
A174 Analog Output 4 A04 STA W no 0.0-10.0V 0.0-10.0V 0.1 0.0V
Start Point
The parameters A174 define the analog output 4 start point (valid only if “configurable” is set).
A175 Analog Output 4 A04 END W no (-)100-100% (-)100-100% 1 100%
End Point
A175 Analog Output 4 A04 END W no 0.0-10.0V 0.0-10.0V 0.1 10.0V
End Point
The parameters A175 define the analog output 4 end point (valid only if “configurable” is set).
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 9 of 9
A178 PASSWORD - W - - - - -
A179 LL1 Sensor LL1 LOW W no 0-100% 0-100% 1 10%
A179 LL1 Sensor LL1 LOW W no (-)10.0-50.0bar (-)10.0-50.0br 0.1 -0.2bar
(R407c/R22) -
0.1bar (R410A)
A180 LL1 Sensor LL1 HIGH W no 0-100% 0-100% 1 90%
A180 LL1 Sensor LL1 HIGH W no (-)10.0-50.0bar (-)10.0-50.0br 0.1 34.5bar
(R407c/R22) -
45.0bar
(R410A)
A181 Actual LL1 Signal LL1 ACT R no 0-100% 0-100% 1 -
A182 Actual LL1 Pressure LL1 ACT R no (-)10.0-50.0bar (-)10.0-50.0br 0.1 -
A183 LL2 Sensor LL2 LOW W no 0-100% 0-100% 1 10%
A183 LL2 Sensor LL2 LOW W no (-)10.0-50.0bar (-)10.0-50.0br 0.1 -0.2bar
(R407c/R22) -
0.1bar (R410A)
A184 LL2 Sensor LL2 HIGH W no 0-100% 0-100% 1 90%
A184 LL2 Sensor LL2 HIGH W no (-)10.0-50.0bar (-)10.0-50.0br 0.1 34.5bar
(R407c/R22) -
45.0bar
(R410A)
A185 Actual LL2 Signal LL2 ACT R no 0-100% 0-100% 1 -
A186 Actual LL2 Pressure LL2 ACT R no (-)10.0-50.0bar (-)10.0-50.0br 0.1 -
LL1 sensor is the condenser transducer.
LL2 sensor is the HP transducer.
A187 EEV Alarm Board Relay ALMB EEV W no N.O., N.O., - N.O.
Status N.C. N.C.
The EEV outputs (all together) can be set to N.O. (normally open) or N.C. (normally closed).
A188 Manual Mode Override MM OVR W no No, No, - No
(S313) Yes Yes
The normal timeout for the manual mode (activated via S313) is 30 minutes. If A188 is set to “Yes” the timeout is disabled and the unit can
operate in manual mode for an unlimited time. “Yes” falls back to “No” after a power cycle.
For the time set in _A611 the valve is not allowed to close,
but is allowed to open in case the call for cooling is asking
for. After _A611 is elapsed the valve will continue normal
operation, i.e. close if CFC requires the valve to close.
3.3.3 A500: Virtual Master System Settings (Cold Fire Large Display only)
A500 Virtual Master Allows Enables the use of virtual network management and shows the actual
status of the virtual system
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 1 of 2
A501 PASSWORD - W - - - - -
A502 Virtual Master Enabled - W No No, - - No
Yes
Enables the Virtual Master management.
A503 Virtual Master Status - R No Not Active, - - -
Active
Indicates if the system is operating in virtual mode or not.
A504 Virtual Master is Unit: - R No 1-32 - 1 -
Indicates which is the virtual master unit.
A505 Number of Virtual Units - R No 1-32 - 1 -
Represents the number of available units when the system is operating in virtual mode.
A506 Number of Virtual Stby - R No 1-31 - 1 -
Units
Represents the number of standby units when the system is operating in virtual mode.
A507 Virtual Return - R No (-)28.0-100.0°C - 0.1 -
Sys.Temperature
Represents the current system temperature value calculated by the virtual master and used to control units.
Note: Value is shown only when the system is operating in virtual mode.
A508 Virtual Return - R No 0.0-99.0% - 0.1 -
Sys.Humidity
Represents the current system humidity value calculated by the virtual master and used to control units.
Note: Value is shown only when the system is operating in virtual mode.
A509 Virtual Supply - R No (-)28.0-100.0°C - 0.1 -
Sys.Temperature
Represents the current system supply temperature value calculated by the virtual master.
Note: Value is shown only when the system is operating in virtual mode.
A510 Virtual Aisle - R No (-)28.0-100.0°C - 0.1 -
Sys.Temperature
Represents the current aisle temperature value calculated by the virtual master.
Note: Value is shown only when the system is operating in virtual mode.
A511 Virtual Aisle - R No 0.0-99.0% - 0.1 -
Sys.Humidity
Represents the current aisle humidity value calculated by the virtual master.
Note: Value is shown only when the system is operating in virtual mode.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 2
A512 PASSWORD - W - - - - -
A513 Virtual Sys. - R No 5.0-40.0°C - 0.1 -
Temp.Setpoint
Shows the current system temperature setpoint used by the virtual master.
A514 Virtual Sys. - R No 1.0-80.0% - 0.1 -
Hum.Setpoint
Shows the current system humidity setpoint used by the virtual master.
A515 Virtual Aisle. - R No 5.0-40.0°C - 0.1 -
Temp.Setpoint
Shows the current aisle temperature setpoint used by the virtual master.
A516 Virtual Aisle. - R No 1.0-80.0% - 0.1 -
Hum.Setpoint
Shows the current aisle humidity setpoint used by the virtual master.
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 2 of 13
PASSWORD - W -
E020 HrH - W no ON-OFF - - OFF
E021 LrH - W no ON-OFF - - OFF
E022 HTE - W no ON-OFF - - OFF
E023 LTE - W no ON-OFF - - OFF
E024 HHE - W no ON-OFF - - OFF
E025 LHE - W no ON-OFF - - OFF
E026 WaCondHo - W no ON-OFF - - OFF
E027 WaCompHo - W no ON-OFF - - OFF
E028 WaHumiHo - W no ON-OFF - - OFF
E029 WaPTC - W no ON-OFF - - OFF
E030 ALDiScrSe2 - W no ON-OFF - - OFF
E031 AlRoomSe - W no ON-OFF - - OFF
E032 WaEEAPFa - W no ON-OFF - - OFF
E033 AL_SuctTr2 - W no ON-OFF - - OFF
E034 WaNet - W no ON-OFF - - OFF
E035 N/A - W no N/A - - N/A
E036 MeUnitOn - W no ON-OFF - - OFF
E037 MeUnitOff - W no ON-OFF - - OFF
E038 MeSleepMod - W no ON-OFF - - OFF
E039 MeStdBy - W no ON-OFF - - OFF
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 3 of 13
PASSWORD - W -
E040 MePowerOn - W no ON-OFF - - OFF
E041 MePowerOff - W no ON-OFF - - OFF
E042 N/A - W no N/A - - N/A
E043 N/A - W no N/A - - N/A
E044 N/A - W no N/A - - N/A
E045 N/A - W no N/A - - N/A
E046 N/A - W no N/A - - N/A
E047 N/A - W no N/A - - N/A
E048 N/A - W no N/A - - N/A
E049 N/A - W no N/A - - N/A
E050 N/A - W no N/A - - N/A
E051 N/A - W no N/A - - N/A
E052 N/A - W no N/A - - N/A
E053 N/A - W no N/A - - N/A
E054 N/A - W no N/A - - N/A
E055 N/A - W no N/A - - N/A
E056 N/A - W no N/A - - N/A
E057 N/A - W no N/A - - N/A
E058 AlHP2 - W no ON-OFF - - OFF
E059 AlLP2 - W no ON-OFF - - OFF
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 4 of 13
PASSWORD - W -
E060 WaComp2Ho - W no ON-OFF - - OFF
E061 ALDiSCRSe1 - W no ON-OFF - - OFF
E062 WaGlycolSe - W no ON-OFF - - OFF
E063 N/A - W no N/A - - N/A
E064 N/A - W no N/A - - N/A
E065 Wa_WaterSe - W no ON-OFF - - OFF
E066 N/A - W no N/A - - N/A
E067 N/A - W no N/A - - N/A
E068 AL_BatFail - W no ON-OFF - - OFF
E069 AL_LowMem - W no ON-OFF - - OFF
E070 WaNetMast - W no ON-OFF - - OFF
E071 AlTH1 - W no ON-OFF - - OFF
E072 AlTH2 - W no ON-OFF - - OFF
E073 N/A - W no N/A - - N/A
E074 N/A - W no N/A - - N/A
E075 WaHP1_NOK - W no ON-OFF - - OFF
E076 WaHP2_NOK - W no ON-OFF - - OFF
E077 WaCoPowRed - W no ON-OFF - - OFF
E078 Wa_NoPower - W no ON-OFF - - OFF
E079 MeUnitDisa - W no ON-OFF - - OFF
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 5 of 13
PASSWORD - W -
E080 MeUnShutDo - W no ON-OFF - - OFF
E081 N/A - W no N/A - - N/A
E082 N/A - W no N/A - - N/A
E083 N/A - W no N/A - - N/A
E084 N/A - W no N/A - - N/A
E085 N/A - W no N/A - - N/A
E086 AlHumHiTe - W no ON-OFF - - OFF
E087 N/A - W no N/A - - N/A
E088 WaDehumHo - W no ON-OFF - - OFF
E089 Wa_FC_Ho - W no ON-OFF - - OFF
E090 Me_FreezC1 - W no ON-OFF - - OFF
E091 AL_PumpDo1 - W no ON-OFF - - OFF
E092 AL_FlashPa - W no ON-OFF - - OFF
E093 AL_FlashSe - W no ON-OFF - - OFF
E094 AL_HCB_nc - W no ON-OFF - - OFF
E095 Wa_BMS_Tim - W no ON-OFF - - OFF
E096 AL_PumpDo2 - W no ON-OFF - - OFF
E097 ALScroHiT1 - W no ON-OFF - - OFF
E098 ALScroHiT2 - W no ON-OFF - - OFF
E099 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 6 of 13
PASSWORD - W -
E100 N/A - W no N/A - - N/A
E101 N/A - W no N/A - - N/A
E102 N/A - W no N/A - - N/A
E103 N/A - W no N/A - - N/A
E104 ALCusInp_0 - W no ON-OFF - - OFF
E105 ALCusInp_1 - W no ON-OFF - - OFF
E106 ALCusInp_2 - W no ON-OFF - - OFF
E107 ALCusInp_3 - W no ON-OFF - - OFF
E108 ALCusInp_4 - W no ON-OFF - - OFF
E109 ALCusInp_5 - W no ON-OFF - - OFF
E110 WaHoHotWa - W no ON-OFF - - OFF
E111 WaHoHeatE1 - W no ON-OFF - - OFF
E112 WaHoHeatE2 - W no ON-OFF - - OFF
E113 WaHoHeatE3 - W no ON-OFF - - OFF
E114 AL_UC_Miss - W no ON-OFF - - OFF
E115 N/A - W no N/A - - N/A
E116 N/A - W no N/A - - N/A
E117 N/A - W no N/A - - N/A
E118 N/A - W no N/A - - N/A
E119 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 7 of 13
PASSWORD - W -
E120 N/A - W no N/A - - N/A
E121 N/A - W no N/A - - N/A
E122 N/A - W no N/A - - N/A
E123 N/A - W no N/A - - N/A
E124 N/A - W no N/A - - N/A
E125 N/A - W no N/A - - N/A
E126 N/A - W no N/A - - N/A
E127 N/A - W no N/A - - N/A
E128 N/A - W no N/A - - N/A
E129 N/A - W no N/A - - N/A
E130 N/A - W no N/A - - N/A
E131 N/A - W no N/A - - N/A
E132 N/A - W no N/A - - N/A
E133 N/A - W no N/A - - N/A
E134 N/A - W no N/A - - N/A
E135 N/A - W no N/A - - N/A
E136 N/A - W no N/A - - N/A
E137 N/A - W no N/A - - N/A
E138 N/A - W no N/A - - N/A
E139 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 8 of 13
PASSWORD - W -
E140 N/A - W no N/A - - N/A
E141 N/A - W no N/A - - N/A
E142 AL_LossPow - W no ON-OFF - - OFF
E143 MeHeatLock - W no ON-OFF - - OFF
E144 AL_HeatVFD - W no ON-OFF - - OFF
E145 MeHumiLock - W no ON-OFF - - OFF
E146 AL_HeatTVS - W no ON-OFF - - OFF
E147 MeCompLock - W no ON-OFF - - OFF
E148 Wa_AmbSens - W no ON-OFF - - OFF
E149 AL_PexCuFa - W no ON-OFF - - OFF
E150 MeShoCycC1 - W no ON-OFF - - OFF
E151 MeShoCycC2 - W no ON-OFF - - OFF
E152 AL_PexHiCu - W no ON-OFF - - OFF
E153 AL_PexLoWa - W no ON-OFF - - OFF
E154 N/A - W no N/A - - N/A
E155 N/A - W no N/A - - N/A
E156 N/A - W no N/A - - N/A
E157 N/A - W no N/A - - N/A
E158 N/A - W no N/A - - N/A
E159 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 9 of 13
PASSWORD - W -
E160 N/A - W no N/A - - N/A
E161 N/A - W no N/A - - N/A
E162 N/A - W no N/A - - N/A
E163 N/A - W no N/A - - N/A
E164 N/A - W no N/A - - N/A
E165 N/A - W no N/A - - N/A
E166 N/A - W no N/A - - N/A
E167 N/A - W no N/A - - N/A
E168 N/A - W no N/A - - N/A
E169 N/A - W no N/A - - N/A
E170 N/A - W no N/A - - N/A
E171 N/A - W no N/A - - N/A
E172 Me_FreezC2 - W no ON-OFF - - OFF
E173 AL_Fire - W no ON-OFF - - OFF
E174 WA_EHO_HPM - W no ON-OFF - - OFF
E175 WA_Conden1 - W no ON-OFF - - OFF
E176 WA_Conden2 - W no ON-OFF - - OFF
E177 Wa_HumiCyl - W no ON-OFF - - OFF
E178 Me_Stop_FC - W no ON-OFF - - OFF
E179 MeMainDone - W no ON-OFF - - OFF
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 10 of 13
PASSWORD - W -
E180 MeDoMaint - W no ON-OFF - - OFF
E181 Wa_Red_Air - W no ON-OFF - - OFF
E182 N/A - W no N/A - - N/A
E183 N/A - W no N/A - - N/A
E184 N/A - W no N/A - - N/A
E185 N/A - W no N/A - - N/A
E186 N/A - W no N/A - - N/A
E187 N/A - W no N/A - - N/A
E188 N/A - W no N/A - - N/A
E189 N/A - W no N/A - - N/A
E190 N/A - W no N/A - - N/A
E191 N/A - W no N/A - - N/A
E192 N/A - W no N/A - - N/A
E193 N/A - W no N/A - - N/A
E194 N/A - W no N/A - - N/A
E195 N/A - W no N/A - - N/A
E196 N/A - W no N/A - - N/A
E197 N/A - W no N/A - - N/A
E198 N/A - W no N/A - - N/A
E199 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 11 of 13
PASSWORD - W -
E200 N/A - W no N/A - - N/A
E201 N/A - W no N/A - - N/A
E202 N/A - W no N/A - - N/A
E203 N/A - W no N/A - - N/A
E204 N/A - W no N/A - - N/A
E205 N/A - W no N/A - - N/A
E206 N/A - W no N/A - - N/A
E207 N/A - W no N/A - - N/A
E208 N/A - W no N/A - - N/A
E209 N/A - W no N/A - - N/A
E210 N/A - W no N/A - - N/A
E211 N/A - W no N/A - - N/A
E212 N/A - W no N/A - - N/A
E213 AL_FB_Sig - W no ON-OFF - - OFF
E214 N/A - W no N/A - - N/A
E215 N/A - W no N/A - - N/A
E216 N/A - W no N/A - - N/A
E217 N/A - W no N/A - - N/A
E218 N/A - W no N/A - - N/A
E219 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 12 of 13
PASSWORD - W -
E220 N/A - W no N/A - - N/A
E221 N/A - W no N/A - - N/A
E222 N/A - W no N/A - - N/A
E223 N/A - W no N/A - - N/A
E224 N/A - W no N/A - - N/A
E225 N/A - W no N/A - - N/A
E226 N/A - W no N/A - - N/A
E227 N/A - W no N/A - - N/A
E228 N/A - W no N/A - - N/A
E229 N/A - W no N/A - - N/A
E230 N/A - W no N/A - - N/A
E231 Wa_HiSupte - W no ON-OFF - - OFF
E232 Wa_LoSupTe - W no ON-OFF - - OFF
E233 N/A - W no N/A - - N/A
E234 N/A - W no N/A - - N/A
E235 N/A - W no N/A - - N/A
E236 N/A - W no N/A - - N/A
E237 N/A - W no N/A - - N/A
E238 N/A - W no N/A - - N/A
E239 N/A - W no N/A - - N/A
Large Display Small Display R/W TW1 Range Large Range Small Res. Std.
Page 13 of 13
PASSWORD - W -
E240 N/A - W no N/A - - N/A
E241 N/A - W no N/A - - N/A
E242 N/A - W no N/A - - N/A
E243 N/A - W no N/A - - N/A
E244 N/A - W no N/A - - N/A
E245 N/A - W no N/A - - N/A
E246 N/A - W no N/A - - N/A
E247 N/A - W no N/A - - N/A
E248 N/A - W no N/A - - N/A
E249 Wa_DO0_nc - W no ON-OFF - - OFF
E250 Wa_DO1_nc - W no ON-OFF - - OFF
E251 Wa_DO2_nc - W no ON-OFF - - OFF
E252 AL_FB_Sig2 - W no ON-OFF - - OFF
E253 N/A - W no N/A - - N/A
E254 AL_EC_FanF - W no ON-OFF - - OFF
E255 N/A - W no N/A - - N/A
E256 N/A - W no N/A - - N/A
E257 N/A - W no N/A - - N/A
E258 N/A - W no N/A - - N/A
E259 N/A - W no N/A - - N/A
4 Connections
P105:
Serial port connector.
To be used for service purpose only.
P103:
BDM Programmer. Not used in standard
purpose (programming only).
5 Unit code
FIELD Unit Code 1 Unit Code 2 Unit Code 3 Unit Code 4 Unit Code 5 Unit Code 6
Value 2 Basic Unit 3 No. of compressors 4 Air Discharge 5 Version 6 Fan
Defines CW or type of Defines normal, constant Defines cooling type
Notes Not used Fixed
compressor(s) or displacement operation
0 0 0 No compressor (CW) 0 O, U, G (std) 0 0 Standard
1 1 1 1 D (displacement) 1 1 EC-Fan
2 2 2 2 K, L (constant) 2 2
3 3 3 3 3 3
4 4 4 4 4 4
5 5 5 5 5 C = CW 5
6 6 6 6 6 6
7 7 7 7 7 7
8 8 8 8 8 8
9 9 9 9 9 9
10 10 10 10 10 10
11 -- 11 11 11 11
12 24 PCW 12 12 12 12
FIELD Unit Code 7 Unit Code 8 Unit Code 9 Unit Code 10 Unit Code 11 Unit Code 12
Value 7 Power supply 8 Electric heating 9 Humidifier 10 Micro Control 11 Re-Heating 12 Air Filter
Defines Humidifier Defines the hum bottle type Defines sensors,
Notes Not used
voltage hum and dehum setpoints
0 400 / 3 0 No 0 External 0 Temperature only 0 None 0
1 230 / 3 1 Yes 1 21L - CLA 1 Temp + Hum 1 1
2 230 / 1 2 2 53L - CLC 2 2 2
3 208 / 3 3 3 53H - CLB 3 3 3
4 380 / 3 4 4 93L - CLE 4 4 4
5 460 / 3 5 5 93H - CLD 5 5 5
6 6 6 d3H 6 6 6
7 7 7 HT2 7 7 7
8 8 8 HT5 8 8 8
9 9 9 HT9 9 9 9
10 10 10 IFS 10 10 10
11 11 11 IFL 11 11 11
FIELD Unit Code 13 Unit Code 14 Unit Code 15 Unit Code 16 Unit Code 17 Unit Code 18
Value 13 Refrigerant 14 Color 15 MCB 16 Air Economizer 17 EEV 18 Cond. Mode
Enable the Air Economizer
Notes Not used Not used Enable the EEV
function
0 0 0 0 No 0 None 0 None
1 1 1 1 Air Econimizer 1 1
2 2 2 2 2 2
3 3 3 3 3 3
4 4 4 4 4 4
5 5 5 5 5 5
6 Revision History
REVISION HISTORY
Revision Date Description Of Changes
Level
1.0 2011-10-31 First emission
2.0 2015-5-12 Second emission done specialy for PCW students in MENA, Dubai
90 Service Manual iCOM Control PA-HPM Application PAG130899Error! Bookmark not defined.9