Predictive Analysis
Predictive Analysis
Detects the
Infrared
Human eyes real-time
Scanning
abnormality
Ultrasound Technology
Tracking
Corona
• Hissing Noise
• Uniform peaks at equal intervals of
time
• Frequency domain pattern has
harmonics of the line frequency and
they are visible in its pattern
• Corona discharge happens at the
peak of the cycle
• Corona discharge produces ozone
and nitrous oxide
• Advantage: Early identification may
result in large scale protection.
TRACKING IDENTIFICATION
• Low current pathway from top
to ground through the insulator.
• Can happen anywhere in the
positive cycle.
• Harmonics are not present.
• Less uniformity in pattern and
popping sound occurs.
• Advantage: In grids tracking
can be missed by infrared
camera scanners but
ultrasound is the best the
equipment to search for
tracking.
ARCING IDENTIFICATION
35.9 °C
35
30
PD in DD Insulator
25
20
18.6
Condition Assessment through Infrared
Thermography
Role of Infrared Thermography in Electrical Network
15
Methodology
Methodology adopted for Identifying criticality in the network Equipments
16
Detection of Hot spots
• Measures adopted for hot spots
1) Reference based (i.e. Min. Temperature rise at any
phase & compared with others, at same load)
2) Temperature rise above Ambient
69.1 °C
ar3
60
ar2 40
ar1
20
0
17 -2.4 °C
Categorization of Temperature rise
18
Thermal Distribution profile Analysis
• Measures adopted for Thermal Distribution profile analysis
– Auditing & Capturing the thermal signature of the equipment along with following data
1) Ambient Temperature
2) Date & Time
3) Load
– Review after six month
19
Identifying Criticality in 50MVA Power Transformer (Case study1)
Thermal Distribution profile Analysis
ar1
64.6 °C
ar2 60
ar4
50
ar3
40
35.3 °C
Tap Collector
changer ring
Carbon
deposition
Identifying Criticality in 20MVA Power Transformer (Case study2)
Thermal Distribution profile Analysis
This is an example of bringing forth the results of reactive thermo scanning being carried out from time to time as per the
requirement wherein it was in formed by the end user that the winding resistance of LV winding of 66 /11kV, 25 MVA was
found to be abnormal.
Thermo scanning was carried out to ascertain whether there was any abnormal temperature rise due to the
unsatisfactory test results.
ANAYLSIS:
1) At the outset it was brought to the notice that there was abnormal rise in the temperature on B phase LV bushing.
2) On a micro analysis it was revealed that the source of temperature rise was localized to the internal busing connection
and this was clearly depicted by the thermal grading.
3) Thereafter the bushing was opened and it was observed that there was a loose connection from the main winding to
the internal bushing which was leading to the rise in the temperature.
4) Corrective action was effected and again the winding resistance was checked and found to be within normal limits.
HT Overhead System with Components
4 RAMA RD-BREAKFAST
30 23 26.5 51.51 78.01
Feedback from Zone 1301: Increasing failure trend in Newly installed Polymeric LA s
Analysis: IR image reveals that Leakage current flowing in the Polymeric LA.
38.6 °C
Ar1 35
30
25
20
18.2
GO Switches
62.2 °C 72.2 °C
60
Ar1:max 197.1
Ar1:max 130.2 60
50
40
40
30
20
19.7 6.8
Distribution Transformers
CA: 1) old bimetallic MS rivet type may be replaced by tinned copper clamps.
2) Cable/ Jumper connections at LV/ HV bushing may be cleaned & tightened properly.
128.1 °C
120
Old bimetallic
MS Rivet type clamp
100
Ar1:max 117.7
80
60
40
New Tinned
Loose/oxidized copper clamp
cable connection:max 130.2 20
0.4
Distribution Transformers
CA: 1) Cable/ Jumper connections at LV/ HV bushing may be cleaned & tightened properly.
2) Thermo scanning may be conducted periodically.
38.8 °C
37.4 °C
Oil Level 32
30
in DT
30
28
25
26
21.2
24.0
Identifying Criticality in RMUs Using Infrared Technology
27.0 °C
27
24 60
ar1
23.9 °C ar2
ar3
40
20
14.8 °C
32
Types of faults in 11kV OH lines
33
Auto re-closer and Sectionalizers
Autorecloser
34
Sectionalisers
Pole Mounting Arrangement
Switchgear unit
PT
35
Sectionalizing function
36
Reclosing function
• The primary function of a recloser is to detect
faults and turn the power off when faults occur
37
Fault Passage Indicators
Working Principle of FPI
Fault Identification through FPI
NOP
Importance of connectors in O/H line
Types of connectors used in O/H network
Application of anti-oxidant
grease after cleaning on
jumper/ main conductor to
prevent Oxidation in between
Shear off head of
Joints
connector for firm
connection
46
Wedge Connector Installation
Hook the “C” member Place the tap conductor in the Insert the wedge
on to the main conductor lower grove of the “C” member
between the two
conductors inside the
“C” member with the
catalogue number
appearing in front
member
Assem
Poly Pro Installation to mitigate bird faults
Wrong Practice- Corrective Action-
Binding connected Polypro should be
along the polypro covered on both sides
causes bird age due without opening the
to potential pin insulators & to be
developed on it tie with the help of
cable tie
48
HT Line Spacer to Mitigate shorting of conductors in long spans
Fuse Co-ordination
Later stage:
Outer Sheath burnt along the Messenger wire & damage of XLPE insulation due to heat of
sparking.
Insulation damage
due to sparking
Sparking spot
Cause of Sparking
The design of ABC is such that a substantial voltage induced at copper screen and is capable to puncture
the outer sheath along the messenger wire which is at earth potential resulted in sparking &
discharging sound.
Don’ts:
1) Temporary joints must be restricted. In emergency case, while making temporary joint, copper
screen continuity must be maintained. Standard joint must be installed at the earliest possible.
2 ) Copper screens connected to messenger wire with fuse/ conductor strand wire.
Partial discharge test of HT ABC
❑ HT ABC failure occurs mainly due to insulation failure, no proper earthing, hot spot generation, improper proper spacing between phase and
earth.
Animal GO Switch
Cantilever
Guards
Monkey Scare
0
Insulation on Iron Pole to restrict current leakage
Animal GO Switch
Cantilever
Guards
After Insulation
Envirogel is the latest alternative of blue silica gel. Envirogel is cobalt free and having high absorbing capacity than blue silica
gel.
Orange Green
60
It indicate orange colour(as shown in pic) when active and changes to green when desiccant becomes saturated(after use pic
also shown)
Line Vegetation Dashboard
Line Vegetation
Dashborad
❖The dashboard with
daily data updation
by linkage with Daily
PSC report.
0
❖Dashboard is on
tableau for better
data visualization.
❖User can check the
poles where
repeated
tree/transient fault
occurred .
❖User can compare
Tree Trimming Activity
62
Overview of cable Types & components
63
Single Core Cable
Conductor:
7
Cleanliness and Date 23/02/2021
conductor shall be circular, and shall have uniform smooth
surface, free from sharp edges and free from any defects.
b) Stranded Conductor shall be free from oil traces & aluminum
uniformity
dust. Conductor (after stranding) shall be super cleaned
c) Traces of aluminum dust on conductor or conductor screen
shall not be acceptable.
Not acceptable in any strand or in any conductor after it is
8 Conductor jointing
stranded.
Raw material Conductor raw material shall be procured from reputed
9
supplier suppliers viz., BALCO/ HINDALCO/ NALCO/ Vedanta only.
Diameter of
10 To be specified by bidder
conductor
Nominal size of conductor Min. weight of conductor
mm2 (kg/km/core)
Min. weight of
11 conductor 300 780
(kg/km/core) 400 1080
630 1650
1000 2600
Quality Design Requisites in Cables
Insulation:
Material and extrusion XLPE insulation shall be applied through CCV/VCV line by triple
1
process extrusion process with ‘Dry Curing’ and Dry/‘Water Cooling’.
Date 23/02/2021
The insulation properties shall be stable under thermal conditions
4 Thermal stability arising out of continuous operation at conductor temperature of 90 deg.
C rising momentarily to 250 deg. C under short circuit conditions.
50.7 °C
50
ar1
45
40
35
34.1 °C
Sp1:L.V Cable earth connection Max. Temp. 86.2°C Load: 170 Amps.
Nature of problem: Hot spot at cable earth connection
Investigation: Earth braid was bolted at Tr. and touching to the panel at other end.
Degradation of Insulation at
the point of hot spot
Identifying criticality in Cable Terminations
60.4 °C
60
40
20
sp1
3.4 °C
Electrical Stress:
• Untreated screen cut back during installation of cable termination
• Phase to Phase & Phase to earth clearance at cable termination.
• Core crossing above cut back area at cable termination
• Application of High voltage DC during testing
Mechanical Stress:
• Improper bending radius
• Mechanical vibrations
• Improper cable supports
• External Damage
Thermal Stress
• Overloading
• High thermal resistivity of soil
• Improper electrical connections
Back
Effect of Electrical Stress
• Effect of Space Charges During DC Testing in XLPE
Insulation :-
Point of
electrical
stress due
to crossing
of cable
cores above
the screen
cutback at
termination
Back
Effect of Mechanical Stress
Bending radius is necessary to take care during fault repairs.
Abnormal
Temp. 62.5
Deg C due to Point of
sharp bend/ Stress
Mech. Stress
at joint
Degrada
Point of
tion of
fault
insulatio
close to
n close
New
to fault
joint
point
Degradation of insulation due to water
ingress
Moisture Detection in Cables at Jointing site
Diagnostic testing
Various solutions have been studied to conduct a number of diagnostic tests may be
termed Condition Assessment Testing (CAT). CAT is not a single go/ no go test, but is
designed to provide a ranking of the cable system and assist in prioritizing future cable
maintenance and replacement. There is as yet no one specific test that determines
the condition of cable insulation. But by conducting the various diagnostic tests help
to predict the insulation condition, Location of Voids and Pre locate & pinpoint the
locations of joints.
we have grouped some tests with Signature Analysis to assess condition of
insulation in the cable section with existing available testing facilities used for fault
location in the TPDDL :
•Insulation Resistance Measurement
•Polarization Index
•Impedance characteristics Measurement
•Leakage current measurement at DC rated voltage
•Very Low Frequency testing
•Audio Frequency Testing
•Infrard Thermography
• Ultrasonic detection
Diagnostic Testing:
Polarization Index
Polarization is the ability for a material’s dipoles (equal and opposite charges separated by some
distance) to line up in the presence of an electric field. As the dipoles align themselves absorption
current is created that decrease over time. Initially the absorption current is high, but as fewer and
fewer dipoles are left to align themselves with the applied field the current drops. Thus an IR
measurement taken after 1 second would yield a lower resistance than an IR measurement taken at
stay, 60 seconds. In fact, the most common test times are a 10 minute test divided by a 1 minute test.
The resulting ratio of the test measurement is known as the polarization index.
Polarization Index = Insulation Resistance after 10 minutes/
Insulation Resistance after 1 minute
A ratio of the 10 min. reading to the 1 min. reading (10 min./ 1 min.) is called the Polarization index.
Range of Polarization Index:-
Poor >> less than 1.0
Fair >> 1.0 – 1.25
Good >> 1.25 – 2.0
Excellent >> above 2.0
Diagnostic Testing:
Purpose:
This test is used to identify the change in impedance characteristics of the cable
Significance:
It is based on pulse reflection method. Suitable measuring pulses are transmitted into the cable being
tested. The pulses pass along the cable at a propagation velocity that is dependent on the connected test
object. The part of the transmission pulse are reflected wherever the electrical characteristics of the cable
change and travel back to TDR equipment
The most important advantage of the pulse reflection method is that it is possible to locate faults as well
as detect them.
Abnormality detection in Cables Using PD
Diagnostic Testing
Significance:
VLF testing methods utilize AC signals in the frequency range from 0.01Hz to 1 Hz. VLF testing method can be
categorized as withstand or diagnostic. In withstand testing; the test object must withstand a specified
voltage applied across the insulation for a specified period of time without breakdown of the insulation. The
magnitude of the withstand voltage is usually greater than that of the applied voltage. If the cable insulation
is sufficiently degraded a breakdown can occur. The cable system may be repaired and the insulation
retested until it passes the withstand test. Diagnostic testing allows the determination of the relative
amount of degradation of a cable system section and establishes, by comparison with figures of merit or
accumulated data, whether a cable system section is likely to continue to perform properly in service.
Diagnostic tests may be nondestructive and are usually performed at lower voltages than withstand tests.
However, when the cable system insulation is in advanced condition of degradation, the diagnostic tests can
cause breakdown before the test can be terminated.
Case Study – 1 (contd.)
8 A s/s
CASE STUDIES
Case Study - 1
Cable section between Wazir Pur Grid 2 to 8A s/s
Type & size of cable: 3X300 sqmm XLPE
Length of section: 400 mtr. Approx.
Av Load: 220A
Failure Rate: 2 faults in 08-09, previous faults - unknown
Diagnostic Tests Measurements’
Measurement Values
S. no. Test Remarks
R ph- E Y ph- E B ph- E Rph-Yph Yph-Bph Bph-Rph
Purpose:
This test is conducted to pinpoint the location of cable joints on route of the cable.
Significance:
The AF generator is a low frequency generator for main operation. When combined with a suitable search
receiver is used to search for and follow cable/ joints laid underground.
The AF tracer is consist of two basic modules:
The transmitter — an ac generator which supplies the signal current on the underground cable/ joint to be
traced.
The receiver — detects the electromagnetic field produced by the transmitted ac current flow.
The test is used to pinpoint the previous failure spots by identification of joints.
TDR OF ‘R’ φ BEFORE & AFTER THE VLF
BEFORE VLF
AFTER VLF
Case Study – 1 contd.
Conclusion:-
•After interpreting the measurement values, It is observed that TDR reflections before & After VLF testing
are identical. All measurement values are satisfactory.
•Previous failure zone is identified. 8 nos joints are pinpointed and uploaded in the GIS.
Recommendations:
It is under stood that joints prone to the weak spots and identified zone has congested joints. A major
digging activity had been done by other utilities on the identified zone.
So It is recommended that affected zone may be revived to enhance the life of cable section
Case Study - 2
Case Study – 2
Cable section between s/s 4/3---- s/s 3/3
Type & size of cable: 3X300 sqmm PILCA + XLPE
Length of section: 390 mtr.
Av Load: 200A
Failure Rate: 2 faults in 08-09, previous faults - unknown
Diagnostic Tests Measurements’
Measurement Values
S. Test Remark
no. R ph- E Y ph- E B ph- E Rph-Yph Yph- Bph-Rph s
Bph
1 IR 110 MΩ 120 MΩ 50 MΩ
3 DD 0.06 0.06 2
Conclusion:-
•After interpreting the measurement values, It is observed that TDR reflections of R & Y ph are identical and
deviation observed in TDR of B ph reflection wrt R&Y ph. before VLF testing.
•VLF testing is conducted at all phase. In B ph, it is observed that initially its showing increasing trend of
leakage and suddenly leakage comes down to zero value.
•After VLF testing, TDR reflection is taken and compared with the related phase of previous reflection and
Deviation observed in reflection of B ph.
•Leakage current value of B phase measured and observed improvement wrt previous value (0.3mA to 0.08
mA)
Recommendations:
Measurement values show the presence of contamination in the dielectric of the cable which requires close
monitoring.
Case Study – 3 Preempting fault
Case Study – 3
Cable section between s/s 4/3---- s/s 3A/2
Type & size of cable: 3X300 sqmm PILCA +XLPE
Length of section: 1180 mtr.
Av Load: 180A
Failure Rate: 3 faults in 08-09, previous faults - unknown
Diagnostic Tests Measurements’
Measurement Values
S. Test Remarks
no. R ph- E Y ph- E B ph- E Rph-Yph Yph-Bph Bph-Rph
2 PI 0.8 1 1.2
3 DD 2 1 0.9
8 TDR after VLF Deviation observed in R ph reflection at 26 mts distance from 4/3 s/s
Contaminated spot at
26 m from 4/3.
Case Study – 3
Conclusion:-
•After interpreting the measurement values, It is observed that TDR reflections before VLF testing are
identical. But After VLF testing, breakdown occurred in R ph..
Condition assessment
Asset Management
Testing Decision-Making Tool
Preempting Faults
Case 1 :The subject cable ( Raja Enclave - Aminabad) is one of the many sick cables to
be replaced under CAPEX Plan 2009-10. As per CEG details, total budget of INR
27.50 lacs is allocated to subject cable for replacing 550 meters from its full length of
590 meters.
SA Outcome : Only 300 meters within full length is sick. Saving of 250 meter of cable length which turns out
to be saving of Rs 12.5 lacs of CAPEX budget.
SOCB (Signature Optimized Capex Budget) Matrix
For Sick Cable Replacement CAPEX
Cable Section Details CAPEX 09-10 Details ( As per CEG) Signature Optimized CAPEX Budget (SOCB)
Saving in
Replacement Allocated Replacement Sick Length CAPEX Optimized
Replacement
Length Budget Cost/meter From SA Saving Budget
ID District Length
(A) (B) ( C= B/A) ( D) (F=E*C) (G=B-F)
( E=C-A)
In Meter In Lac In Rs In Meter In Lac In Lac
(In Meter)
PUMPING STATION-17 BLK MTN 1301/MTN 600 30 5000 465 135 6.75 23.25
1.3725 Crores
WHS NO 1-WHS NO 2 1303/MTN 800 40 5000 650 150 7.5 32.5
Prahladpur I/D S/stn to Sector- 516/BDL 1100 55 5000 Nil 1100 55 Zero
30 crossing DP
There are 103 Sick Cable replacement under CAPEX .SA can provide ample
CAPEX saving to improve bottom-line.
Challenges in HDD Trenchless cable laying
Existing Trenchless Installation Technique
Problem 1 : Cable Damage during Pull- Back
98
Problem in Existing Trenchless Installation Technique
Problem 2 : Performance Degradation by 20%
Cable within
HDPE Pipe
HDPE Pipe
Joint
Joint Joint
XLPE Cable
Fluidic Cable Installation
101
Fluidic Cable Installation
Proposed Fluidic Cable
Parameter "As Is "(Trenchless with HDPE Pipe)
installation ( Na-Bentonite)
20 % additional power from
20% De-rating due to poor heat dissipation
Derating of cable enhancement in thermal
by HDPE
conductivity
102
Fluidic CCD Cable Installation
XLPE Cable
Ageing of U/G Cable- Untimely Failure High Repair & Replacement Cost ROW Permission
1352
1400
1156 1186
1200 1118
1000 60-65 %
Failure due
800
to Moisture
600 ingress
355 326 358
400 315
“As-Is” Philosophy for Ageing & Sick Cable “To- Be” Philosophy Proposed for Ageing & Sick Cable
Run
Run
Replace Repair
Replace Repair
Process +
RLE Product
Innovation
Process Innovation- RLE Concept for Cables
❑ STEP 1: Selection Criteria– Prioritization matrix is prepared for the selection of the cable.
❑ STEP 2: Diagnostic Testing – Polarization Index (PI), DC Leakage Current & Signature
analysis using Time Domain Reflectometer (TDR) for identification of the abnormalities
/contamination
❑ STEP 3: Vacuumizing - Moisture Removal from Conductor, Screen & Outer Jacket
Silica gel
container is
Vacuum Nitrogen
fitted on
pump set Cylinder
affected cable
core.
Methodology
PI Result
Recommended
Core Method PI (Before RLE) PI (After RLE) Value After
Core1 to
5 KV megger 0.78 1.92 Poor => less than
Earth
1.0
Core 2 to
5 KV megger 0.98 1.98 Fair => 1.0 – 1.25
Earth Good => 1.25 – 2.0
Core 3 to Excellent => > 2.0
5 KV megger 1.21 2.02
Earth
Economic Evaluation-RLE vs. Replacement
RLE Replacement
➢ Cost of Replacement (Approx.) : Rs 70 Lakhs/Km
➢ Cost of Life Extension through On-site Curing- Rs 1-2 Lakhs/Km.
➢ Sick Section will be treated In-house during Cable Repair Job
➢ This will Save RR Cost, Excavation Charges.
➢ In-House availability of Testing Equipment ( TDR/Route
115 Tracer/VLF)
Impact & benefit
Cable Fault Fault in Run Joint Failure
1400
1352 Asset Life
1156 1186 enhancement
1118 1076
1200
1000
712
800
600
400
355 326 358 304 Financial Year Feeder Identified Executed
196
200 352 313 336 287 315 280
208
0
FY 20-21
Customer40 26
Fy 17-18 18-19 19-20 20-21 21-22 22-23
Reduction in Reliability
failure satisfaction Enhancement
FY 21-22 90 82
YOY contibution of Joint Failure
355 358
400 326 315 304 FY 22-23 72 63
300 196
200
CAPEX/OPEX
100
optimization
0
Fy 17-18 18-19 19-20 20-21 21-22 22-23
RLE/Cable Maintenance technique
Uniqueness
Scalability
First power Replicable across
distribution all Power
utility to develop Distribution
inhouse cable Utilities.
healing system