Product data sheet 3RH1131-1HB40

COUPLING RELAY, 3NO+1NC, DC 24 V,


0.7...1.25*US, SCREW CONNECTION,
SIZE S00

General details:
Product brand name SIRIUS

product designation contactor relay

Size of the contactor S00

Protection class IP / on the front IP20

Degree of pollution 3

Insulation voltage / with degree of pollution 3 / rated value V 690

Installation altitude / at a height over sea level / maximum m 2,000

Ambient temperature

• during transport °C -55 … 80

• during storage °C -55 … 80

• during operating phase °C -25 … 60

Resistance against shock 10g / 5 ms and 5g / 10 ms

Impulse voltage resistance / rated value kV 6

Item designation

• according to DIN EN 61346-2 K

• according to DIN 40719 extendable after IEC 204-2 / according K


to IEC 750

Mechanical operating cycles as operating time

• of the contactor / typical 30,000,000

3RH1131-1HB40 subject to modifications


Page 1/ 5 08/16/2011 © Copyright Siemens AG 2011
Control circuit:
Type of voltage / of the controlled supply voltage DC

Control supply voltage / 1

• for DC / rated value V 24

Working range factor supply voltage rated value / of the magnet


coil

• for DC 0.7 … 1.25

Pull-in power / of the solenoid / for DC W 2.3

Holding power / of the solenoid / for DC W 2.3

Auxiliary circuit:
Product extension / auxiliary switch No

Identification number and letter for switching elements 31 E

Contact reliability / of the auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)

Number of NC contacts / for auxiliary contacts 1

• delayed switching 0

• instantaneous switching 1

• asynchronous switching 0

• lagging switching 0

Number of NO contacts / for auxiliary contacts 3

• instantaneous switching 3

• delayed switching 0

• asynchronous switching 0

• leading switching 0

Number of changeover contacts

• for auxiliary contacts 0

• of the auxiliary contacts / instantaneous switching 0

Operating current / of the auxiliary contacts

• at AC-12 / maximum A 10

• at AC-15

• at 230 V A 6

• at 400 V A 3

• at 500 V A 2

• at 690 V A 1

• with 1 current path

• at DC-12

• at 24 V A 10

• at 110 V A 3

• at 220 V A 1

• at DC-13

3RH1131-1HB40 subject to modifications


Page 2/ 5 08/16/2011 © Copyright Siemens AG 2011
• at 24 V A 10

• at 110 V A 1

• at 220 V A 0.22

Short-circuit:
Design of the fuse link / for short-circuit protection of the fuse gL/gG: 10 A
auxiliary switch / required

Installation/mounting/dimensions:
Built in orientation with vertical mounting surface +/-180° rotatable, with
vertical mounting surface +/- 30° tiltable to the front
and back

Type of mounting screw and snap-on mounting

Width mm 45

Height mm 57.5

Depth mm 72

Distance, to be maintained, to the ranks assembly / sidewards mm 0

Connections:
Design of the electrical connection / for auxiliary and control screw-type terminals
current circuit

Type of the connectable conductor cross-section

• for auxiliary contacts

• solid 2x (0.5 ...1.5 mm2), 2x (0.75 ... 2.5 mm2), max. 2x (1


... 4 mm2)

• finely stranded

• with conductor end processing 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2)

• for AWG conductors / for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 1x 12

Certificates/approvals:
Verification of suitability CSA / UL / CCC / GL / LRS / BV / DNV / RMRS /
RINA

General Product Approval Functional Safety / Test Certificates


Safety of
Machinery

CQC ROSTEST SUVA Manufacturer

Shipping Approval

ABS PRS

Shipping Approval other

Manufacturer

3RH1131-1HB40 subject to modifications


Page 3/ 5 08/16/2011 © Copyright Siemens AG 2011
Safety:
Proportion of dangerous failures

• with high demand rate / according to SN 31920 % 75

• with low demand rate / according to SN 31920 % 40

T1 value / for proof test interval or service life / according to IEC a 20


61508

Protection against electrical shock finger-safe

B10 value / with high demand rate / according to SN 31920 1,000,000

Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system)


http://www.siemens.com/industrial-controls/mall

CAx-Online-Generator
http://www.siemens.com/cax

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)


http://support.automation.siemens.com/WW/view/en/3RH1131-1HB40/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RH1131-1HB40

3RH1131-1HB40 subject to modifications


Page 4/ 5 08/16/2011 © Copyright Siemens AG 2011
last change: Aug 1, 2011

3RH1131-1HB40 subject to modifications


Page 5/ 5 08/16/2011 © Copyright Siemens AG 2011