Air System Sizing Summary for VRF-001

Project Name: VRF PROJECT G PLUS 5 01-28-2022


Prepared by: SEC 07:15PM

Air System Information


Air System Name ....................................... VRF-001 Number of zones ........................................................... 7
Equipment Class ............................................ TERM Floor Area ............................................................ 4280.0 ft²
Air System Type ................................................ VRF Location .................. Abu Dhabi, United Arab Emirates

Sizing Calculation Information

Calculation Months ................................. Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................. Calculated Space CFM Sizing ........... Individual peak space loads

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Air System Information


Air System Name ....................................... VRF-001 Number of zones ........................................................... 7
Equipment Class ............................................ TERM Floor Area ............................................................ 4280.0 ft²
Air System Type ................................................ VRF Location .................. Abu Dhabi, United Arab Emirates

Sizing Calculation Information

Calculation Months ................................. Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................. Calculated Space CFM Sizing ........... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 13.9 682 682 Jul 1400 1.5 538.0 1.27
Zone 2 12.7 619 619 Jul 1400 0.9 450.0 1.38
Zone 3 21.7 1060 1060 Jul 1400 1.4 727.0 1.46
Zone 4 17.3 844 844 Jul 1400 1.4 727.0 1.16
Zone 5 17.3 844 844 Jul 1400 1.4 727.0 1.16
Zone 6 18.7 915 915 Jul 1400 1.6 774.0 1.18
Zone 7 7.5 365 365 Jul 1400 0.5 337.0 1.08

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.0 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 14.8 14.6 80.4 / 65.9 60.5 / 58.9 - Jul 1400
Zone 2 13.1 12.9 80.2 / 66.0 60.9 / 59.2 - Jun 1400
Zone 3 21.7 21.5 80.0 / 66.2 61.2 / 59.6 - Jun 1500
Zone 4 18.4 18.1 80.5 / 65.9 60.6 / 58.9 - Jul 1400
Zone 5 18.4 18.1 80.5 / 65.9 60.6 / 58.9 - Jul 1400
Zone 6 19.7 19.5 80.5 / 66.0 60.7 / 59.0 - Jul 1400
Zone 7 7.8 7.6 80.3 / 66.0 60.8 / 59.2 - Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 2.4 68.8 / 72.0 - 682 0.000 0.000 42
Zone 2 1.6 68.9 / 71.3 - 619 0.000 0.000 37
Zone 3 2.4 69.0 / 71.1 - 1060 0.000 0.000 54
Zone 4 2.4 68.6 / 71.3 - 844 0.000 0.000 54
Zone 5 2.4 68.6 / 71.3 - 844 0.000 0.000 54
Zone 6 2.7 68.7 / 71.5 - 915 0.000 0.000 56
Zone 7 0.7 68.7 / 70.5 - 365 0.000 0.000 20

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
OFFICE-1 1 13.9 Jul 1400 682 1.5 538.0 1.27
Zone 2

Hourly Analysis Program v4.90 Page 2 of 13


Zone Sizing Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
OFFICE-2 1 12.7 Jul 1400 619 0.9 450.0 1.38
Zone 3
OFFICE-3 1 21.7 Jul 1400 1060 1.4 727.0 1.46
Zone 4
OFFICE-4 1 17.3 Jul 1400 844 1.4 727.0 1.16
Zone 5
OFFICE-5 1 17.3 Jul 1400 844 1.4 727.0 1.16
Zone 6
OFFICE-6 1 18.7 Jul 1400 915 1.6 774.0 1.18
Zone 7
CORRIDOOR 1 7.5 Jul 1400 365 0.5 337.0 1.08

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 1468 ft² 4164 - 1468 ft² 2398 -
Roof Transmission 4280 ft² 33284 - 4280 ft² 6266 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 4280 ft² 11184 - 4280 ft² 0 -
Partitions 402 ft² 5252 - 402 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 5136 W 17523 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5992 W 20444 - 0 0 -
People 12 2940 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 14219 246 0% 0 0
>> Total Zone Loads - 109010 2706 - 8665 0
Zone Conditioning - 101244 2706 - 8638 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 0 CFM 0 -
Ventilation Load 317 CFM 10837 -1370 317 CFM 6078 1
Ventilation Fan Load 0 CFM 0 - 0 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 112080 1336 - 14716 1
Terminal Unit Cooling - 112080 1403 - 0 0
Terminal Unit Heating - 0 - - 14716 -
>> Total Conditioning - 112080 1403 - 14716 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 421 ft² 1275 - 421 ft² 688 -
Roof Transmission 538 ft² 4184 - 538 ft² 788 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 538 ft² 1406 - 538 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 646 W 2203 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 753 W 2570 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 1819 41 0% 0 0
>> Total Zone Loads - 13946 451 - 1475 0

Zone 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 171 ft² 433 - 171 ft² 279 -
Roof Transmission 450 ft² 3499 - 450 ft² 659 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 450 ft² 1176 - 450 ft² 0 -
Partitions 109 ft² 1424 - 109 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 540 W 1842 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 630 W 2150 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 1652 41 0% 0 0
>> Total Zone Loads - 12666 451 - 938 0

Hourly Analysis Program v4.90 Page 5 of 13


Zone Design Load Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Zone 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 192 ft² 527 - 192 ft² 314 -
Roof Transmission 727 ft² 5654 - 727 ft² 1064 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 727 ft² 1900 - 727 ft² 0 -
Partitions 293 ft² 3828 - 293 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 872 W 2976 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1018 W 3473 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 2827 41 0% 0 0
>> Total Zone Loads - 21675 451 - 1378 0

Zone 4 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 192 ft² 527 - 192 ft² 314 -
Roof Transmission 727 ft² 5654 - 727 ft² 1064 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 727 ft² 1900 - 727 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 872 W 2976 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1018 W 3473 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 2253 41 0% 0 0
>> Total Zone Loads - 17273 451 - 1378 0

Hourly Analysis Program v4.90 Page 6 of 13


Zone Design Load Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Zone 5 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 192 ft² 527 - 192 ft² 314 -
Roof Transmission 727 ft² 5654 - 727 ft² 1064 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 727 ft² 1900 - 727 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 872 W 2976 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1018 W 3473 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 2253 41 0% 0 0
>> Total Zone Loads - 17273 451 - 1378 0

Zone 6 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 300 ft² 875 - 300 ft² 490 -
Roof Transmission 774 ft² 6019 - 774 ft² 1133 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 774 ft² 2023 - 774 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 929 W 3169 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1084 W 3697 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 2441 41 0% 0 0
>> Total Zone Loads - 18713 451 - 1623 0

Hourly Analysis Program v4.90 Page 7 of 13


Zone Design Load Summary for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

Zone 7 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 73.8 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 337 ft² 2621 - 337 ft² 493 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 337 ft² 881 - 337 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 404 W 1380 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 472 W 1610 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 974 0 0% 0 0
>> Total Zone Loads - 7464 0 - 493 0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

July DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 110.3 0.00957 317 400 10837 -1370
Vent - Return Mixing Outlet 0.0 0.00000 0 0 - -
Ventilation Fan Outlet 0.0 0.00000 0 0 0 -
Zone Air - 78.5 0.01050 5329 27 101244 2706
Return Plenum Outlet 0.0 0.01050 5329 27 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.077 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4731.5 BTU/(hr-CFM)
Site Altitude = 88.0 ft

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 ( Cooling )
Ventilation Air - - - 42 - - -
Cooling Coil Inlet - 80.4 0.01030 682 0 - -
Cooling Coil Outlet - 60.5 0.01024 682 0 14594 196
Heating Coil Inlet - 60.5 0.01024 682 0 - -
Heating Coil Outlet - 60.5 0.01024 682 0 0 -
Zone Air - 78.5 0.01035 682 0 13144 -
Zone 2 ( Cooling )
Ventilation Air - - - 37 - - -
Cooling Coil Inlet - 80.5 0.01053 619 0 - -
Cooling Coil Outlet - 61.1 0.01048 619 0 12903 135
Heating Coil Inlet - 61.1 0.01048 619 0 - -
Heating Coil Outlet - 61.1 0.01048 619 0 0 -
Zone Air - 78.6 0.01057 619 0 11638 -
Zone 3 ( Cooling )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 80.4 0.01076 1060 0 - -
Cooling Coil Outlet - 61.7 0.01073 1060 0 21301 132
Heating Coil Inlet - 61.7 0.01073 1060 0 - -
Heating Coil Outlet - 61.7 0.01073 1060 0 0 -
Zone Air - 78.8 0.01082 1060 0 19479 -
Zone 4 ( Cooling )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 80.5 0.01033 844 0 - -
Cooling Coil Outlet - 60.6 0.01026 844 0 18087 268
Heating Coil Inlet - 60.6 0.01026 844 0 - -
Heating Coil Outlet - 60.6 0.01026 844 0 0 -
Zone Air - 78.5 0.01038 844 0 16250 -
Zone 5 ( Cooling )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 80.5 0.01033 844 0 - -
Cooling Coil Outlet - 60.6 0.01026 844 0 18087 268
Heating Coil Inlet - 60.6 0.01026 844 0 - -
Heating Coil Outlet - 60.6 0.01026 844 0 0 -
Zone Air - 78.5 0.01038 844 0 16250 -
Zone 6 ( Cooling )
Ventilation Air - - - 56 - - -
Cooling Coil Inlet - 80.5 0.01037 915 0 - -
Cooling Coil Outlet - 60.7 0.01030 915 0 19463 276
Heating Coil Inlet - 60.7 0.01030 915 0 - -
Heating Coil Outlet - 60.7 0.01030 915 0 0 -
Zone Air - 78.5 0.01041 915 0 17530 -
Zone 7 ( Cooling )
Ventilation Air - - - 20 - - -
Cooling Coil Inlet - 80.3 0.01044 365 0 - -
Cooling Coil Outlet - 60.8 0.01037 365 0 7645 129
Heating Coil Inlet - 60.8 0.01037 365 0 - -
Heating Coil Outlet - 60.8 0.01037 365 0 0 -
Zone Air - 78.5 0.01049 365 0 6953 -

Hourly Analysis Program v4.90 Page 10 of 13


System Psychrometrics for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 52.0 0.00409 317 400 -6078 -1
Vent - Return Mixing Outlet 0.0 0.00000 0 0 - -
Ventilation Fan Outlet 0.0 0.00000 0 0 0 -
Zone Air - 69.8 0.00409 5329 0 -8638 0
Return Plenum Outlet 0.0 0.00409 5329 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.077 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4731.5 BTU/(hr-CFM)
Site Altitude = 88.0 ft

Hourly Analysis Program v4.90 Page 11 of 13


System Psychrometrics for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 ( Heating )
Ventilation Air - - - 42 - - -
Cooling Coil Inlet - 68.8 0.00410 682 0 - -
Cooling Coil Outlet - 68.8 0.00410 682 0 0 0
Heating Coil Inlet - 68.8 0.00410 682 0 - -
Heating Coil Outlet - 72.0 0.00410 682 0 2368 -
Zone Air - 69.9 0.00409 682 0 -1555 -
Zone 2 ( Heating )
Ventilation Air - - - 37 - - -
Cooling Coil Inlet - 68.9 0.00410 619 0 - -
Cooling Coil Outlet - 68.9 0.00410 619 0 0 0
Heating Coil Inlet - 68.9 0.00410 619 0 - -
Heating Coil Outlet - 71.3 0.00410 619 0 1643 -
Zone Air - 69.9 0.00409 619 0 -928 -
Zone 3 ( Heating )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 69.0 0.00410 1060 0 - -
Cooling Coil Outlet - 69.0 0.00410 1060 0 0 0
Heating Coil Inlet - 69.0 0.00410 1060 0 - -
Heating Coil Outlet - 71.1 0.00410 1060 0 2398 -
Zone Air - 69.9 0.00409 1060 0 -1362 -
Zone 4 ( Heating )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 68.6 0.00410 844 0 - -
Cooling Coil Outlet - 68.6 0.00410 844 0 0 0
Heating Coil Inlet - 68.6 0.00410 844 0 - -
Heating Coil Outlet - 71.3 0.00410 844 0 2412 -
Zone Air - 69.8 0.00409 844 0 -1386 -
Zone 5 ( Heating )
Ventilation Air - - - 54 - - -
Cooling Coil Inlet - 68.6 0.00410 844 0 - -
Cooling Coil Outlet - 68.6 0.00410 844 0 0 0
Heating Coil Inlet - 68.6 0.00410 844 0 - -
Heating Coil Outlet - 71.3 0.00410 844 0 2412 -
Zone Air - 69.8 0.00409 844 0 -1386 -
Zone 6 ( Heating )
Ventilation Air - - - 56 - - -
Cooling Coil Inlet - 68.7 0.00410 915 0 - -
Cooling Coil Outlet - 68.7 0.00410 915 0 0 0
Heating Coil Inlet - 68.7 0.00410 915 0 - -
Heating Coil Outlet - 71.5 0.00410 915 0 2741 -
Zone Air - 69.8 0.00409 915 0 -1661 -
Zone 7 ( Heating )
Ventilation Air - - - 20 - - -
Cooling Coil Inlet - 68.7 0.00410 365 0 - -
Cooling Coil Outlet - 68.7 0.00410 365 0 0 0
Heating Coil Inlet - 68.7 0.00410 365 0 - -
Heating Coil Outlet - 70.5 0.00410 365 0 742 -
Zone Air - 69.6 0.00409 365 0 -359 -

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for VRF-001
Project Name: VRF PROJECT G PLUS 5 01-28-2022
Prepared by: SEC 07:15PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.90 Page 13 of 13