E-A
E-A
E-A
LOAD
1. ALL ELECTRICAL WORKS INDICATED HEREIN SHALL BE DONE IN ACCORDANCE WITH LOAD DESCRIPTION CIRCUIT BREAKER WIRE CONDUIT
CKT. VA
LATEST ISSUE OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATIONS OF A V
BULDING ADMINISTRATION. AND THE LOCAL TELEPHONE COMPANIES AND REPUBLIC ELECTRICAL LEGENDS : NO L.
O
C.
O
DESCRIPTION AB RATE POLE KAIC NO.
SIZE
mm²
GRD.
mm²
TYPE
SIZE
mmØ
TYPE
ACT 7920 AS APPLIED IN THE CITY.
20w 20w 20w 20w Tracklights 1 7 Convenience Outlet 1260 5.48 230 20 2 10 2+1 3.5 3.5 THHN 15 EMT
2. POWER SOURCE SHALL BE SYSTEM VOLTAGE: 230V, 1 PHASE, 3 WIRE, 60Hz.
40 watts Weatherproof LED Light fixture 2 7 Convenience Outlet 1260 5.48 230 20 2 10 2+1 3.5 3.5 THHN 15 EMT
3. ALL ELECTRICAL INSTALLATION SHALL BE CONCEALED FROM VIEW BY INSTALLING
CONDUCTORS IN IMC. EMBEDDED IN CONCRETE, EXPOSED CONDUIT WORK ABOVE 2Hp Wall Mounted ACU
REF
Refrigerator C.O 3 1492 6.49 230 30 2 10 2+1 3.5 3.5 THHN 20 EMT
DROP CEILING SHALL BE IMC
Microwave Oven C.O. 4 4Hp Wall Mounted ACU 2984 12.97 230 30 2 10 2+1 3.5 3.5 THHN 20 EMT
4. MINIMUM SIZE OF CONDUCTORS WHEN NOT INDICATED IN THE DRAWINGS SHALL BE MO
3.5mm² (#12 AWG) THHN TYPE.
5 1 Refrigerator C.O 800 3.48 230 20 2 10 2+1 3.5 3.5 THHN 15 EMT
Convenience Outlet
5. MINIMUM SIZE OF CONDUIT WHEN NOT INDICATED IN THE DRAWINGS SHALL BE
6 1 Microwave Oven C.O. 800 3.48 230 30 2 10 2+1 3.5 3.5 THHN 15 EMT
15mmU (1 2") NOMINAL DIAMETER.
Panelboard 2 10 3.5 3.5 THHN 20 EMT
7 1 Tea Pot Table 1500 6.52 230 30 2+1
6. REFER TO TABLE C4 OF THE PHILIPPINE ELECTRICAL CODE FOR PROPER CONDUIT SIZES POS Outlet 9 40 watts LED Light fixture 2
CONTAINING CONDUCTOR WHEN SUCH ARE NOT INDICATED IN THE DRAWINGS. G.I. 8 440 1.91 230 15 10 2+1 3.5 3.5 THHN 15 EMT
WIRE NOT ACCEPTABLE, REFER TO CONDUIT SUPPORT DETAIL. 4 20 watts Tracklights
Telephone Outlet
9 1 Signage 500 2.17 230 20 2 10 2+1 3.5 3.5 THHN 15 EMT
7. ONLY HIGH POWER FACTOR BALLAST PREHEAT TYPE SHALL BE USED FOR FLUORESCENT PP
#
Circuit Homerun
LIGHTING FIXTURE. TOTAL LOAD : 11036 44.5
11. MINIMUM BRANCH CIRCUIT BREAKERS MUST BE 10KAIC,18-50KAIC FOR MAIN AND AC
MAIN. ALL CIRCUIT BREAKER MUST BE BOLT-ON TYPE. (INDUSTRIAL TYPE, MOLDED
CASE. AND OR WITH ACCORDANCE TO MALL STANDARDS)
75AT, 225AF
13. FOR UPS/POS OUTLET USE NATIONAL BRAND WN-1612-8, FOR NORMAL WN 1512-8. 230V, 2P, 1Ø
14. PROVIDE JUNCTION BOX AND FLEXIBLE METAL CONDUIT TO LIGHTING FIXTURE.
E.E. ROOM
2-22 mm² THHN TO TAPPING POINT
1-8.0 mm² THHN BUILDING PROVISION
1. 20AT 2. 20AT IN 32 mmU IMC
MOUNTING HEIGHTS : LP
1. LIGHTS CONTROL SWITCHES : 3. 30AT 4. 30AT PANEL BOARD 230V,1Ø,60 HZ
MAIN C.B. :
1.4m FROM CENTER OF DEVICE TO FINISHED FLOOR LINE. 75AT, 225AF,
5. 20AT 6. 30AT 2P, 230V,
2. CONVENIENCE, TELEPHONE AND INTERCOM OUTLETS :
0.30m (1' - 0") ABOVE FINISHED FLOOR LINE OR FITTED INTO BASEBOARD IF SO 18 KAIC, 60Hz
REQUIRED BY THE ARCHITECT. 7. 30AT 8. 15AT BOLT-ON TYPE
ELECTRICAL ENGINEER : R.A. 9266 SEC. 33 PROJECT TITLE: PROJECT OWNER: ISSUES : SHEET CONTENT/DESCRIPTION: SHEET NO.
- A
FOR ANY PERSON, WITHOUT THE CONSENT OF THE ARCHITECT
OR AUTHOR OF SAID DOCUMENTS TO
PTR NO. DUPLICATE OR TO MAKE COPIES FOR USE IN THE
REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS,
2 ISSUE FOR BID GENERAL NOTES CHECKED BY :
WHETHER EXECUTED PARTLY OR IN A WHOLE.
ELECTRICAL LOAD COMPUTATION APPROVED BY :
ISSUED AT:
PD NO. 49
"PROTECTION OF INTELLECTUAL PROPERTY" NOVEMBER
14,1972.WORK OF ARTS , ARCHITECTURE, MODELS AND DESIGNS ARE
CREATIVE WORK AND CONSIDERED AS A PART OF THE INTELLECTUAL
3
4
ISSUE FOR CONSTRUCTIONS