You are on page 1/ 19

Specifications

for
Gas Detection System
Customer Name

Honda Vietnam Co., Ltd.

Job Name

Bumper line

Agency Name

TAIKISHA LTD.

NEW COSMOS ELECTRIC CO.,LTD.

December 27,2016
SALES ENGINEERING DEPT.

No. Date Contents Drawing Approval Customers P.O. No. Revision No.

0 Dec.27 2016 Draw up S.Matsumoto N.Fujiwara

Internal
Order No.
0000447604 0

Date of issue Dec.27 2016


Specifications
No. AC-1266
In Charge T.Tsuzuki
Drawing S.Matsumoto
Check K.Masuoka
Approval N.Fujiwara

V-7.2
AC-1266 1/

List of articles delivered


No. Name Model(code), DWG. No. Q’ty Remarks

1 Indicator/alarm panel UVB-810-6(-000-0000) 1

2 Alarm unit VAS(-00-0000-0) 1

3 Indicator unit V3(-Cv40JL-030/01110) 3 F.S.100%LEL

4 Indicator unit V3(-Ci40JL-030/01110) 1 F.S.100%LEL

5 Gas detector KD-5B(-10000-C2A10) 1 LPG, F.S.100%LEL

LPG, F.S.100%LEL
6 Gas detector PE-2DC(-03150-C2A10) 1
Possess a Gas sampling panel

7 Gas detector KD-5B(-10000-C2T10) 2 Toluene, F.S.100%LEL

8 Gas sampling panel DWG. No. P-4999 1

9 Accessories

Fuse for panel 7A(φ5.2×20L) (2pcs/unit) 1set for UVB-810-6

Fuse for battery 1A(φ5.2×20L) 1 for UVB-810-6

Fuse for alarm unit 0.5A(φ5.2×20L) 1 for VAS

Fuse for indicator unit 1A(φ5.2×20L) 4 for V3

Mounting bracket
1 set for UVB-810-6
(for Wall mount)

Screw
M5×8 (4pcs /unit) 1 set for UVB-810-6
(for body fixed)

Gas collector PF-N3 1 For PE-2DC

Overhaul tool L-wrenches 1 set For KD-5B, PE-2DC

NEW COSMOS ELECTRIC CO.,LTD.


AC-1266 2/

1. General description

This Gas Detection System is designed to detect the leakage of flammable gas into the fresh air and to
give the alarm when the gas concentration exceeds alarm set value.

2. General specifications

1). Target Gas : LPG (reference gas : i-C4H10) : Toluene

2). Detection Principle : Catalytic combustion


(Sensor may pick up gases other than the gas it is calibrated to.)

3). Full Scale Concentration : 100%LEL (=1.8vol%) : 100%LEL (=1.2vol%)

4). Alarm Set Value : 1st stage 24%LEL


: 2nd stage 24%LEL

5). Repeatability : ±5% of full scale (under same condition)

6). Alarm Accuracy : ±25% of alarm set value (under same condition)

7). Alarm Delay : Within 30 seconds at gas concentration of 1.6 times alarm set value.
(excluding a delay time due to suction piping of Gas Detector)

8). Operating Condition : Continuous monitoring


There is fear with degrading sensor sensitivity in the place where
gas always exists in the detection atmosphere.
Also, there is fear which influences the performance and the service
life of the sensor in the place where chloric gases, sulfuric gases or
silicon vapor are present.

9). Applicable Standard : The General High Pressure Gas Safety Regulations
The Liquefied Petroleum Gas Safety Regulations
The Industrial Complex Safety Regulations

10). Special Instructions : Use of output signal of this instrument is user's own risk.
New cosmos shall not be responsible for consequential or indirect
damages caused by the output signal of this instrument.
AC-1266 3/

3. Indicator/alarm panel Specifications


1). Model : UVB-810-6
2). Installation style : Wall mount type
3). Protection grade : IP2X
4). Dimension : W642×H342×D93(mm)
5). Coating color : Panel color/Munsell N6.0, Case color/ Munsell N8.0
6). Power source : AC100 to 240V±10%, 50/60Hz
7). Power consumption : approx. 57VA (mounting unit only)
8). Operating temperature and humidity range
: 0 to 40℃,10 to 90%R.H. or less (without dewing)
9). Insulation resistance : 20MΩ or more (for DC500V)
10). Withstanding voltage : AC1500V, 60 sec.
11). Number of Indicator units mounted
: 4 units (Space 2 unit)
12). Type of gas detector : Diffusion type / 3 units
Suction type / 1 unit
13). Alarm indication : In accordance with VAS type Alarm unit and V3 type Indicator unit
14). External output
Analog output : In accordance with V3 type Indicator unit
Collective alarm terminal : 2nd stage alarm contact 1a no-voltage
1st stage alarm contact 1a no-voltage
Buzzer contact 1a no-voltage
Failure contact 1a no-voltage (Automatic restoration)
(Contact capacity : AC100V 1A, DC24V 1A max in resistance load)
Individual alarm contact : 2nd stage alarm contact 1a no-voltage
1st stage alarm contact 1a no-voltage
(Contact capacity : AC250V 2A, DC24V 2A max in resistance load)
(When the sensor heater of V3 type Ci indicator unit is disconnected, a
failure alarm may be generated after a leakage alarm is generated.)
15). Operation at the maintenance mode
Maintenance mode 1 : Collective alarm contact Operation stops (both 1st & 2nd stage)
Buzzer contact Operates for 3 sec. in gas alarm
Operates in failure
Failure contact Operates
Individual alarm contact Operation stops (both 1st & 2nd stage)
Maintenance mode 2 : Collective alarm contact Operation stops (both 1st & 2nd stage)
Buzzer contact Operation stops in gas alarm
Operates in failure
Failure contact Operation stops for failure detector
Individual alarm contact Operation stops (both 1st & 2nd stage)
16). External input : External alarm reset terminal、External alarm stop terminal
17). Backup power source
Battery : The small control valve system lead storage battery 12V×2
Backup time : More than 30 minutes
Charge time : More than 24 hours
Battery life : 2 years
18). Power output terminal : DC24V (for Gas detector)
19). Special Instruction : In order to satisfy the degree of protection "IP2X", you need to be
treated so that it does not touch the charging section contains the
finger from the cable inlet.
AC-1266 4/

4. Alarm unit Specifications


1). Model : VAS

2). Number of alarm stages : 2 stage alarm

3). Power lamp (Green) : Turn on under normal operation

4). Alarm lamp (Red) : Turn off under normal operation


(both 1st & 2nd stage) Turn on when the Indicator unit(s) show in gas alarm

5). Trouble lamp (Yellow) : Turn off under normal operation


Turn on when the Indicator unit(s) show in trouble

6). Buzzer : Pulse tone in gas alarm / Continuous tone in trouble


(over 70dB/1m)

Operation at the maintenance mode


Maintenance mode 1 : works for 3 sec. in gas alarm / works in trouble

Maintenance mode 2 : doesn’t work (both gas alarm & trouble)

7). Alarm mode : Accord with Indicator unit

8). Operating temperature and humidity range


: -10 to 40℃, 10 to 90%RH (without dewing)

9). Power source : 24VDC±10%

10). Power consumption : Approx. 3.5W/unit

11). Insulation resistance : over 5MΩ (at 250VDC)

12). Withstanding voltage : 500VAC, 60 sec.

13). Degree of protection : IP2X (After installation)

14). Options : -----

15). Remarks : -----


AC-1266 5/

5. Indicator unit Specifications

5-1. for Diffusion type gas detector


1). Model : V3 Type Cv
2). Target Gas : LPG (reference gas : i-C4H10) : Toluene
3). Detection Principle : Catalytic combustion
4). Indication Range : 0 - 100% LEL
5). Alarm Set Value : 1st stage 24% LEL
: 2nd stage 24% LEL
6). Gas Concentration Indicator : Three-color LED bar-graph meter (50 partition)
Indicator Scale : 0 - 100% LEL (equally divided real scale)
Bar-graph Color : When normal: green; on 1st stage alarm: orange; on 2nd stage alarm: red
7). Power Lamp : When switched on: green lamp flashes (initial delay when switched on:
approx. 30 seconds)
When normal: illuminates green (when the fuse is disconnected: not
illuminated)
8). Failure Lamp : When normal: not illuminated
With failure: yellow lamp flashes (when the fuse is disconnected: not
illuminated)
9). Factors Determining Failure : Input voltage drop, fuse disconnection, internal communication
abnormality, and sensor heater disconnection
10). Alarm Lamp : When normal: not illuminated
(both 1st and 2nd stages) On alarm: flashes red (after reset: illuminates)
11). Test Lamp : When normal: not illuminated
On test: flashes red
12). Alarm Mode (both 1st and 2nd stages)
: Upper limit alarm latching (recovers automatically after reset)
13). Analog Output for Recorder : DC4 - 20mA / On failure: 0.9mA or less
(Load resistance: 300Ω or less)
Range of output is 1.44mA (-16%F.S.) - 21.6mA (110%F.S.).
When setting a threshold of failure at analog output, please set it to
1.0mA.
14). Cable length of Detection : 1km and shorter for 2mm2 cables
(one-way line resistance is 10Ω or less)
15). Operating Temperature
and Humidity Range : -10 to 40℃, 10 - 90% RH (non-condensing)
16). Power Supply : DC24V±10%
17). Power Consumption : Approx. 5W/unit
18). Insulation Resistance : 5MΩ or more (for DC250V)
19). Withstand Voltage : AC500V, 1 minute
20). Protection Grade : IP2X (when installed)
21). Maintenance Functions : Use the MNT button to shift to the maintenance mode.
Maintenance Mode 1 : Maintenance lamp Flashes red
Analog output for recorder Operates
Maintenance Mode 2 : Maintenance lamp Illuminates red
Analog output for recorder 4mA fixed
(For external alarm contact operation at the time of maintenance, see
the specifications of the indication alarm panel.)
22). Standard Functions : With zero suppression (6%F.S.)
23). Options : -----
24). Special Instructions : -----
AC-1266 6/

5-2. for Pump extractive type gas detector


1). Model : V3 Type Ci
2). Target Gas : LPG (reference gas : i-C4H10)
3). Detection Principle : Catalytic combustion
4). Indication Range : 0 - 100% LEL
5). Alarm Set Value : 1st stage 24% LEL
: 2nd stage 24% LEL
6). Gas Concentration Indicator : Three-color LED bar-graph meter (50 partition)
Indicator Scale : 0 - 100% LEL (equally divided real scale)
Bar-graph Color : When normal: green; on 1st stage alarm: orange; on 2nd stage alarm: red
7). Power Lamp : When switched on: green lamp flashes (initial delay when switched on:
approx. 30 seconds)
When normal: illuminates green (when the fuse is disconnected: not
illuminated)
8). Failure Lamp : When normal: not illuminated
With failure: yellow lamp flashes (when the fuse is disconnected: not
illuminated)
9). Factors Determining Failure : Input voltage drop, fuse disconnection, internal communication
abnormality, and sensor heater disconnection
(When the sensor heater is disconnected, a failure alarm may be generated
after a leakage alarm is generated.)
10). Alarm Lamp : When normal: not illuminated
(both 1st and 2nd stages) On alarm: flashes red (after reset: illuminates)
11). Test Lamp : When normal: not illuminated
On test: flashes red
12). Alarm Mode (both 1st and 2nd stages)
: Upper limit alarm latching (recovers automatically after reset)
13). Analog Output for Recorder : DC4 - 20mA / On failure: 0.9mA or less
(Load resistance: 300Ω or less)
Range of output is 1.44mA (-16%F.S.) - 21.6mA (110%F.S.).
When setting a threshold of failure at analog output, please set it to
1.0mA.
(When the sensor heater is disconnected, 21.6mA may be output.)
14). Cable length of Detection : 1km and shorter for 2mm2 cables
(one-way line resistance is 10Ω or less)
15). Operating Temperature
and Humidity Range : -10 to 40℃, 10 - 90% RH (non-condensing)
16). Power Supply : DC24V±10%
17). Power Consumption : Approx. 4W/unit
18). Insulation Resistance : 5MΩ or more (for DC250V)
19). Withstand Voltage : AC500V, 1 minute
20). Protection Grade : IP2X (when installed)
21). Maintenance Functions : Use the MNT button to shift to the maintenance mode.
Maintenance Mode 1 : Maintenance lamp Flashes red
Analog output for recorder Operates
Maintenance Mode 2 : Maintenance lamp Illuminates red
Analog output for recorder 4mA fixed
(For external alarm contact operation at the time of maintenance, see
the specifications of the indication alarm panel.)
21). Standard Functions : With zero suppression (6%F.S.)
22). Options : -----
23). Special Instructions : -----
AC-1266 7/

6. Gas detector Specifications

6-1. Diffusion type

1). Model : KD-5B

2). Detection gas : LPG (reference gas : i-C4H10) : Toluene

3). Principle of detection : Catalytic combustion

4). Sampling method : Diffusion type

5). Full scale concentration : 100%LEL

6). Explosion proof : d2G4

7). Certificate number : T53339

8). Number of conductors for connection cable to Indicator unit


: 3 cores shield cable

9). Applicable cable : Control cable


(Use a control cable which fitted in with the installation environment.)

10). Cable connection : Pressure proof packing Φ12


(Because the packings with size except Φ12 are attached when
shipping, use a packing which fits in with the cable outside diameter.)

11). Conduit connection size : G22

12). Coating color : Munsell 7.5BG6/1.5

13). Operating temperature and humidity range

: -10 to 60℃, 85%R.H. or less (without dewing)

14). Sintered metal material : SUS

15). Recommendation exchange period of the sensor

: 3 years (in the pure atmosphere)

16). Remarks : -----


AC-1266 8/

6-2. Pump extractive type


1). Model : PE-2DC

2). Target Gas : LPG (reference gas : i-C4H10)

3). Detection Principle : Catalytic combustion

4). Detection Method : Pump extractive type

5). Full Scale Concentration : 100%LEL

6). Explosion-Proof Structure : d2G4

7). Japan TIIS Certificate


Approval No. : No. T37155

8). Number of Wiring Conductors : 6-core cable

9). Suitable Electric Cable : Control cables


(Please use control cables suitable for the installation location.)

10). Wiring Lead Method : Pressure-resistant packing type, φ15

11). Conduit Connection Size : G22

12). Paint Color : Munsell 5YR6/13

13). Operating Temperature


and Humidity Range : -10 to 40℃, 30 to 85% RH (non-condensing)

14). Gap Plate Material : BsBM

15). Piping Connection Size : Rc1/8

16). Pump Power Supply : DC24V±10% (approx. 5W per unit)

17). Recommended Exchange


Cycle of Sensor : 3 years (in clean air)

18). Special Instructions : Possess a Gas sampling panel [P-4999]


AC-1266 9/

7. Gas sampling panel Specifications

1). DWG. No. : P-4999

2). Installation : The indoor self standing type

3). Dimensions : W400×H1200×D300(mm) (exclusive of a protruding object)

4). Material Base : SPC t2.3


Stand : SPC t6

5). Coating color : Munsell 5YR6/13 (All-gloss)

6). Operating temperature range


: 0 to 40℃ (without freezing)

7). Gas temperature at entrance


: Circumference atmosphere temperature

8). Flow rate : approx. 1L/min or less

9). Joint : Rc1/4

10). Recommendation plumbing size


: φ10/8

11). Drain discharge method : Water seal-type automatic discharge

12). Gas pressure : -4 to +0.4kPaG

13). Remarks : Avoid installation in the place with high temperature (40℃ or more)
and the place which the direct sunlight, the radiation heat hit.

: Make sampling plumbing downhill in 3/10 or more.


When the plumbing has a standing-up part, a drain is choked up and
gas becomes not sampled.
Moreover, the water of the water seal cup is sucked up and there is
fear to damage a gas sensor by.

: When the drain doesn't come out, close a water seal cup valve.

: The soluble gas has the possibility to dissolve in the dewfall in


sampling plumbing.
The gas which was dissolved in water can not be detected.
A B C D E F G

Indicator/alarm panel
B8
UVB-810-6 B7
B6
B5
1 Noise filter B4
B3
B2
B1 to E02

+
-

CN CN CN CN
Backup
Power unit DC power unit Alarm unit VAS Indicator unit V3 Type Cv Indicator unit V3 Type Ci Indicator unit V3 Type Cv
(DC24V output) AC VBH3 (0A) (1A) (2A) (3A)
CN CN CN CN

RY RY RY RY RY RY
1 2 1 2 1 2
Power switch

+ (ANALOG OUT)
- (ANALOG OUT)

+ (ANALOG OUT)
- (ANALOG OUT)

+ (ANALOG OUT)
- (ANALOG OUT)
RY2 RY1 RY2 RY1 RY2 RY1

+ (DC24V OUT)
- (DC24V OUT)

+ (DC24V OUT)
- (DC24V OUT)

+ (DC24V OUT)
- (DC24V OUT)
Fuse 1 Fuse 2
ZC2

ZC1

A/F

A/F

A/F
ZA2

ZA1

ZA2

ZA1

ZA2

ZA1

ZA2

ZA1
BC

AR
TC

AS

ZC

ZC

ZC
BZ

TZ

C
D

D
N

B
Battery 1 Battery 2
R

3
Power source (※1) (※2) (※3) (※4) (※5) (※3) (※4) (※3) (※4) (※5)
AC100~240V
50/60Hz
3-core 6-core cable 3-core
shield cable shield cable

B C D A B C D PA PB B C D

KD-5B PE-2DC KD-5B


Diffusion type gas detector Pump extractive type gas detector Diffusion type gas detector
4 No. 1 LPG No. 2 LPG No. 3 Toluene
Gas sampling panel
[P-4999]

(※1) Collective alarm terminal (※2) External input terminal


AS-N :External alarm reset terminal
AR-N :Do not use
ZC2

ZC1
ZA2

ZA1

BC

(※3) Analog output terminal (DC4~20mA)


TC
BZ

TZ

(※4) Individual alarm contact Gas Alarm System


5 ZA2-ZC2 :2nd stage alarm contact (Closed in 2nd stage alarm) ZA2-ZC :2nd stage alarm contact (Closed in 2nd stage alarm)
ZA1-ZC1 :1st stage alarm contact (Closed in 1st stage alarm) ZA1-ZC :1st stage alarm contact (Closed in 1st stage alarm)
Wiring Diagram (1/2)
BZ-BC :Buzzer contact (Closed in buzzer sounds) (Contact capacity : AC250V 2A, DC24V 2A max in resistance load) APP. CH. DR. ANGLE UNIT SCALE
TZ-TC :Failure contact (Closed in failure) N. wara Y. sukawa S. umoto *** ** --/--
(※5) Power output terminal (DC24V, for Gas detector) ji
Fu t ts
Ma
(Contact capacity : AC100V 1A, DC24V 1A max in resistance load) 0 Dec.27.'16 Draw up S.Matsumoto N.Fujiwara
Ma
No. Date Outline DR. APP. Dec.27.'16 Dec.27.'16 Dec.27.'16 No.
DWG.
AC-1266-E01
A B C D E F G

Indicator/alarm panel
B8
UVB-810-6 B7
B6
B5
1 B4
B3
B2
from E01 B1

+
-

CN CN CN

Indicator unit V3 Type Cv Indicator unit Spare space Indicator unit Spare space
(4A) (5A) (6A)
CN CN CN

RY RY RY RY RY RY
1 2 1 2 1 2

+ (ANALOG OUT)
- (ANALOG OUT)

+ (ANALOG OUT)
- (ANALOG OUT)

+ (ANALOG OUT)
- (ANALOG OUT)
RY2 RY1 RY2 RY1 RY2 RY1

+ (DC24V OUT)
- (DC24V OUT)

+ (DC24V OUT)
- (DC24V OUT)

+ (DC24V OUT)
- (DC24V OUT)
A/F

A/F

A/F
ZA2

ZA1

ZA2

ZA1

ZA2

ZA1
ZC

ZC

ZC
C

C
D

D
B

B
3
(※3) (※4) (※5) (※3) (※4) (※5) (※3) (※4) (※5)

3-core
shield cable

B C D No.5,6 Spare

KD-5B
Diffusion type gas detector
4 No. 4 Toluene

(※3) Analog output terminal (DC4~20mA)

(※4) Individual alarm contact Gas Alarm System


5 ZA2-ZC :2nd stage alarm contact (Closed in 2nd stage alarm)
ZA1-ZC :1st stage alarm contact (Closed in 1st stage alarm)
Wiring Diagram (2/2)
(Contact capacity : AC250V 2A, DC24V 2A max in resistance load) APP. CH. DR. ANGLE UNIT SCALE
N. wara Y. sukawa S. umoto *** ** --/--
(※5) Power output terminal (DC24V, for Gas detector) ji
Fu t ts
Ma
0 Dec.27.'16 Draw up S.Matsumoto N.Fujiwara
Ma
No. Date Outline DR. APP. Dec.27.'16 Dec.27.'16 Dec.27.'16 No.
DWG.
AC-1266-E02
A B C D E F G

642 93 10
Detail of Backup power unit No. Name Q'ty Remarks
4-φ6 558 21
(Mounting holes) (Model VBH3) 1 Backup power unit 1 -----
1 2 3 8 2 Alarm unit 1 0A
Power lamp
3 Indicator unit 1-6 1A - 6A
1
Backup lamp 4 Terminal box lid 1 -----
0A 1A 2A 3A 4A 5A 6A 5 Snap lock 2 -----
Battery 6 Cable inlet (Bottom) 2 with Knockout plate
350

Check lamp
342

7 Cable inlet (Rear) 1 -----


5 8 Mounting bracket (for Wall mount) 2 Accessories
UVB-810
Voltage indicator
4 9 Mounting bracket (for Panel mount) 4 Options
Battery
Check button 10 Power unit 1 -----
2 (Inside of front cover)
11 Battery 2 -----
6 12 Power switch 1 -----
Inlet direction
Inlet dimensions 13 Fuse holder 2 7A(φ5.2×20L)
(Bottom・Rear common) 14 Power terminal block 1 M3.5

39
15 Comprehensive connection terminal block 1 M3.5
84 124 109
16 Individual connection terminal block 6 M3.5
80 20
Rear view
3 Panel mount type (When using the optional mounting bracket)
4-φ6 (※1) 482 (34) Inside of terminal box Panel(1.6~5mm)
+1
636-0 ⑨

332±1
280

4 (19)
Panel cut dimensions UVB-810

146
7 10 11 12 13 14 15 16
Indicator/alarm panel UVB-810-6
External view
5 APP. CH. DR. ANGLE UNIT SCALE
H . uki Ka.kayama M .otoh 3RD mm 1/10
(※1) It used to be mounted directly to the wall, 0 Sep. 8 '14 Draw up M.Gotoh H.Onuki On T G
without the use of a mounting bracket.
No. Date Outline DR. APP. Sep. 8 '14 Sep. 8 '14 Sep. 8 '14 No.
DWG.
M-8805
1 2 3 4 5 6 7 8

Parts list

36 8 62 No. Name Remarks


A Power lamp
① Green

② Trouble lamp Yellow
⑨ ③ Alarm lamp (2nd stage alarm) Red
① Alarm lamp (1st stage alarm)
④ Red
② ⑤ Buzzer
③ ⑩
⑥ Front cover Fixed
B ④ ⑦ Panel lock knob

⑧ TAG NO. plate


116
⑨ Fuse
144

⑩ Connector
⑪ Reset button

C ⑪


(6.5)

with Reset button Alarm unit / VAS


External View
APP. CH. DR. ANGLE UNIT SCALE
F
3RD mm 1/2
Jun 13,2012 Draw up M.G N.F DWG.
Date Comments DR. APP. Jun 13,2012 Jun 13,2012 Jun 13,2012 No. M-8773E
1 2 3 4 5 6 7 8

Parts list

36 8 62 No. Name Remarks


A ① Power lamp Green
⑩ ② Failure lamp Yellow
③ Alarm lamp (2nd stage alarm) Red
⑪ ④ Alarm lamp (1st stage alarm) Red
① ⑤ Maintenance lamp Red
**

② ⑥ Test lamp Red


⑫ 3 colors LED bar graph
**
③ ⑦ Indication scale
⑧ Front cover Cover with operating portion
B ④
** ⑨ Panel lock knob
⑤ ⑩ TAG NO. plate
**
⑥ ⑪ Fuse

116
⑫ Connector for Single case connection
144

**
⑬ Adjustment button Use at zero adjustment function
⑭ Test button Switch to test mode
**
*** ⑮ Maintenance button Switch to maintenance mode
C ⑦ ⑯ High button Use at test mode
⑰ Low button Use at test mode


Apply Model Detection Principle
V3 Type Ci Catalytic combustion
(6.5)
V3 Type Cv Catalytic combustion
D V3 Type Hi Hot wire semi-conductor
Inside of Front cover V3 Type Hv Hot wire semi-conductor
V3 Type Ti Thermal conductivity of gases
V3 Type Tv Thermal conductivity of gases
⑬ Electrochemical cell
ADJ HIGH ⑯ V3 Type D
⑭ TEST Electrochemical cell (Gel electrolysis)
MNT LOW
V3 Type O Galvanic cell
⑮ ⑰ V3 Type M Direct current input
E
V3 Type ZN 03 type semi-conductor

Indicator unit / V3
External View
3 Jun.2,2015 03 type semi-conductor add. T.Tokin H.Onuki APP. CH. DR. ANGLE UNIT SCALE
F
2 Apr.2,2014 Gel electrolysis add. T.Satake H.Onuki 3RD mm 1/2
0 May.28,2012 Draw up M.Gotou N.Fujiwara DWG.
Date Comments DR. APP. Jun.2,2015 Jun.2,2015 Jun.2,2015 No. M-8770
16 Weather proof cover 1 Nylon6 Option
15 Weather proof cap 1 Nylon6 Option
14 Earth terminal 1 SUS-305 M4×8
78
13 Screw with hexagon socket (M4) 1 SUS-305 6mm , Nominal dia.:2
⑦ ⑩ 12 Clump shield 1 Neoprene
11 Gland packing adapter 1 BsBM
⑬ ⑫ ⑪
10 Screw 2 SUS-305 M5×15
9 Saddle 1 SUS-304

□□□□
G3/4

77
8 Stand 1 SUS-304
7 Bolt with hexagon socket (M5) 3 SUS-305 16mm , Nominal dia.:4
6 Bolt with hexagon socket (M4) 1 SUS-305 8mm , Nominal dia.:3
5 Guard mount 1 ADC-12
⑭ 4 Sensor guard 1 ADC-12

53 46 3 Sensor module 1
2 Terminal cap 1 ADC-12

42 99 1 Terminal box 1 ADC-12


No. Name Q'ty Material Remarks

Cable outer dia. Packing hole dia. Washer hole dia.
① ② ⑨ φ10 to φ10.9 φ11 φ12
φ11 to φ11.9 φ12 φ12
φ12 to φ12.9 φ13 φ14

39
φ13 to φ13.9 φ14 φ14
φ14 to φ14.9 φ15 φ15

※1. φ12 pressure tight packing and φ12 flat washer are included
123

in the detector with shipping.


192

※2. φ10 to φ14.9 of cable can be used by standard attachment.



135

Apply Model Construction Temperature



KD-5A d3aG4 -10 to 60℃
④ ③ KD-5B d2G4 -10 to 60℃
⑥ KD-5O d2G4 0 to 40℃

KD-5S d2G4 -10 to 60℃
KD-5H d3aG4 -10 to 60℃
KD-5D d2G4 0 to 40℃
2-9×12(long hole)
67±0.2
Gas Detector / Model:KD-5
94
External View
APP. CH. DR. ANGLE UNIT SCALE
Jul.7.2011 Trace M.G H.O 3RD mm 1/2
H.O T.S M.G
This figure is a drawing where A3 was reduced to A4. Jan.13.1998 Draw up T.I T.I DWG.
Date Comments DR. APP. Jul.7.2011 Jul.7.2011 Jul.7.2011 No. B-4695E
1 2 3 4 5 6 7 8

No. Name Q'ty Material Remark


146 96
1 Body 1 AC3A-F -----
A 20 76 10
122 2 Terminal box 1 AC3A-F -----
4-φ7
① 3 Gap plate 2 depend on the spec -----
4 Half joint 2 depend on the spec Rc1/8-φ6

⑩ 5 Fitting metal 2 SPC -----

EXPLOSION PROOF
6 Sensor element 1 ----- -----
④ d2G4
7 Pump 1 ----- -----
GAS
B No.
8 Terminal block 2 ----- M3.5

135
177

9 Cable guard 1 AC -----
IN OUT
10 Name plate 1 ----- -----


Cable Packing Washer
Apply
outer dia. hole dia. hole dia.

390
C φ10 to φ10.9 φ11 φ12
φ11 to φ11.9 φ12 φ12
A
B PA φ12 to φ12.9 φ13 φ14
137

C PB ⑧
D φ13 to φ13.9 φ14 φ14
φ14 to φ14.9 φ15 φ15
Cross section view
⑨ of Cable guard
D
Ground terminal
34

(M4)
42

G3/4

E 49 Explosion proof :d2G4


G3/4 Pump power :24VDC
Cable connection :Pressure proof packing

Gas Detector / PE-2DC


External View
2 Sep 24.2012 Trace M.Gotoh H.Onuki APP. CH. DR. ANGLE UNIT SCALE
F
1 Dec 16.2004 Deleted TIIS Certificate Number J.Endo M.Onishi 3RD mm 1/4
S. T.
0 Oct 18.1995 Draw up DWG.
Date Comments
Hoshihara Nakamura
DR. APP. Sep 24.2012 Sep 24.2012 Sep 24.2012 No. P-4687E
A B C D E F G

φ10/8
Flow diagram
400
φ6/4 φ6/4 φ6/4 φ6/4
CuT Nylon CuT CuT
GAS IN
Atomosphere FC DH
GAS IN FC 3 AD MF
1 sampling 10 P
OUT

AD
Rc1/4 Rc1/4

MF 6c

DT

Drain OUT To Gas Monitor Panel


2 DH
Note
980
1. Installation style : Self standing type (Indoor)
2. Material : SPC t2.3 etc.
1200 レ
3. Painting colar : □Munsell 5YR6/13
□Munsell 5Y7/1
CuT 6 □Others (View Specification)
L=60mm 4. Pipe materials : Copper (Nylon tube used connection between
FC and MF)
3 5. Fitting material : BsBM
6. Precaution : The sampling pipe line from drainer to the
OUT
DT sampling panel must have a down gradient.

Name Symbol Model


L50×50×t6.0 Gas Detector DH レ PE-2DC
□ □ PE-2CC
Drain Auto Drainer AD AD-40G(-Z0)
OUT Drain Tank DT P-4982E
4 Flow Checker FC FC-32-B0
(1.5L/minF.S)
Membrane Filter MF MF-01
100 100 30 30
300
Anchor hole
4-φ14 Gas Sampling Panel
External view/Flow diagram
5 2 Dec.10,'14 Structure change of the stand K.Takayama H.Onuki APP. CH. DR. ANGLE UNIT SCALE
1 Jun.11,'14 The thickness of L-angle changed T.Fujikawa H.Onuki
H. ki Y. iai K.ayama 3RD mm 1/10
0 Apr.26,'13 Draw up M.Gotoh H.Onuki O nu O ch Tak
No. Date Outline DR. APP.
DWG.
Dec.10,'14 Dec.10,'14 Dec.10,'14 No. P-4999
A B C D

1 (Pipe)

φ6
φ10

2

80
3

φ60

No. Name Remarks

1 Body Neoplene

2 Filter Non-woven cloth

1 May 8, 2013 Trace M.Gotoh H.Onuki

0 Oct. 18,1995 Draw up S. T.Nak


Hoshihara
Date Comments DR. APP.
APP. CH. DR. ANGLE UNIT SCALE
Pipe flare / PF-N3 --- mm ---
DWG.
May 8, 2013 May 8, 2013 May 8, 2013
External View No. P-4304E