Product overview
The AX-LDPS-FD113 Differential Pressure Switch is a
pressure monitoring solution for liquids and non
aggressive gases. The unit is designed for both flow
proving and flow failure detection to cover the range of
0.3 to 4.5 Bar. Approximate setpoint can be viewed on
the dial at the front of the unit.
●Changeover contacts to suit many applications ●Suitable for use with mains voltage
Product specifications
Range: 0.3 to 4.5 Bar
Differential: 0.2 Bar
Factory Setting: 0.7 Bar
Maximum Pressure: Operating 12 Bar
Test PT 25 Bar
Pressure Connections: 1/4” BSP Female
Electrical Connection: Screw Terminals - max conductor size 1.5mm²
Switch Rating: AC 3A @ 230Vac (inductive)
DC 0.1A @ 230Vdc
Ambient Temperature: -20˚C to 70˚C
Media Temperature: Max. 70˚C
Protection class (EN60529): IP30
Weight: 0.79kg
Vibration Resistance: 4g (10…1000 Hz)
Medium Compatibility: HFC, HCFC
CE according to Low Voltage Directive
Marking:
AB28
Materials: Fittings Brass
Wetted Parts Phosphor Bronze
Switch Back Plate Zinc plated mild steel
Housing Cover Flame resistant polycarbonate
Country of Origin: Czech Republic
Order codes
AX-LDPS-FD113 Liquid Differential Pressure Switch 0.3Bar to 4.5Bar
© Copyright Annicom 2016. All Rights Reserved
! Safety Instructions
● Read the installation instructions thoroughly. Failure to comply can result in device failure, system damage or
personal injury
● It is intended for use by persons having the appropriate knowledge and skill
● Before opening any system make sure pressure in system is brought to and remains at atmospheric pressure
● Ensure supply voltage and current of electric device match rating of the AX-LDPS-FD113. Disconnect supply
voltage from system and AX-LDPS-FD113 before installation or service
● Do not exceed test pressure
● Keep temperature within nominal limits
● Do not apply torsional force to switch housing during assembly (see Fig. 4)
Installation
The AX-LDPS-FD113 should be installed by a suitably qualified technician in accordance with prevailing regulations
and any guidelines for the equipment to which it is to be connected. The AX-LDPS-FD113 is suitable for use with
mains voltage and power must be isolated before opening the cover.
The AX-LDPS-FD113 is for use in systems under pressure and should be installed in accordance with practices
relevant to the intended use only by persons qualified to do so. The AX-LDPS-FD113 should be mounted on a wall
or other suitable surface using the bracket provided (Fig. 5). Pipework should then be installed to the unit and
terminated at the high and low parts using the 1/4” BSP fittings. It is the responsibility of the installer to ensure that
the pipework is suitable for the system pressure.
Reset
The AX-LDPS-FD113 automatically resets
Mounting Direction
The unit can be mounted in any direction, preferably with pressure connections vertically.
Leakage Test
After completion of installation, a test pressure must be carried out as follows:
- According to EN378 for systems which must comply with European pressure equipment directive
97/23/EC
- To a maximum working pressure of system for other applications
Warning : Failure to correctly test the system could result in loss of refrigerant and personal injury. The pressure
test must be conducted by skilled persons with due respect regarding the danger related to pressure.
Maintenance / Service
In case of repair work or replacing the control always use new sealant.
Electrical Connection
Note: Comply with local electrical regulations when wiring. Wire size must be suitable for electric device connected
to the AX-LDPS-FD113.
Connection
Electrical:
Electrical connections are made as follows:
Remove power before opening or closing the cover.
1. Remove the plug from the body by unscrewing the retaining bolt in the top of the plug.
2. Ensure the unit is not subjected to ingress by water.
3. Ensure all wiring passes through the rubber grommet.
4. Always use the supplied screw to mount the unit to the base.
If the supplied screw is lost an M 0.7 x 8 screw can be used (must have a depth of 5mm or less).
5. Connect the wiring as shown in the diagram below depending upon the type of unit.
6. Set the switching point by inserting a screwdriver into the slots wheel above the scale.
Electrical connections
1. Normally Closed
2. Normally Open
3. Common
LP
-
LP +
3
68mm
175mm
2
1
+
HP -
HP
Testing Lever 1
Pushing Lever 1 (Fig. 2)
upwards simulates a pressure
rise at the HP side. Pushing the
level down during operation
simulates a lack of HP.
15 Nm
12.5mm
4.5mm
25mm
40m
m
Every effort has been taken in the production of this data sheet to ensure accuracy. Axio do not accept responsibility for any damage, expense, injury,
loss or consequential loss resulting from any errors or omissions. Axio has a policy of continuous improvement and reserves the right to change this