Liquid Differential Pressure Switch

Product overview
The AX-LDPS-FD113 Differential Pressure Switch is a
pressure monitoring solution for liquids and non
aggressive gases. The unit is designed for both flow
proving and flow failure detection to cover the range of
0.3 to 4.5 Bar. Approximate setpoint can be viewed on
the dial at the front of the unit.

The AX-LDPS-FD113 uses the differential pressure


between the two inputs to operate an electrical switch.
Applications include refrigeration and air-conditioning
systems according to EN378 e.g. Compressor oil pressure
control.
Features
●Adjustable Differential ●Fully mechanical switching

●Changeover contacts to suit many applications ●Suitable for use with mains voltage

Product specifications
Range: 0.3 to 4.5 Bar
Differential: 0.2 Bar
Factory Setting: 0.7 Bar
Maximum Pressure: Operating 12 Bar
Test PT 25 Bar
Pressure Connections: 1/4” BSP Female
Electrical Connection: Screw Terminals - max conductor size 1.5mm²
Switch Rating: AC 3A @ 230Vac (inductive)
DC 0.1A @ 230Vdc
Ambient Temperature: -20˚C to 70˚C
Media Temperature: Max. 70˚C
Protection class (EN60529): IP30
Weight: 0.79kg
Vibration Resistance: 4g (10…1000 Hz)
Medium Compatibility: HFC, HCFC
CE according to Low Voltage Directive

Marking:

AB28
Materials: Fittings Brass
Wetted Parts Phosphor Bronze
Switch Back Plate Zinc plated mild steel
Housing Cover Flame resistant polycarbonate
Country of Origin: Czech Republic

Order codes
AX-LDPS-FD113 Liquid Differential Pressure Switch 0.3Bar to 4.5Bar
© Copyright Annicom 2016. All Rights Reserved

Issue 1.5 (12/05/2023) Page 1 of 4


Liquid Differential Pressure Switch

! Safety Instructions
● Read the installation instructions thoroughly. Failure to comply can result in device failure, system damage or
personal injury
● It is intended for use by persons having the appropriate knowledge and skill
● Before opening any system make sure pressure in system is brought to and remains at atmospheric pressure
● Ensure supply voltage and current of electric device match rating of the AX-LDPS-FD113. Disconnect supply
voltage from system and AX-LDPS-FD113 before installation or service
● Do not exceed test pressure
● Keep temperature within nominal limits
● Do not apply torsional force to switch housing during assembly (see Fig. 4)

Installation
The AX-LDPS-FD113 should be installed by a suitably qualified technician in accordance with prevailing regulations
and any guidelines for the equipment to which it is to be connected. The AX-LDPS-FD113 is suitable for use with
mains voltage and power must be isolated before opening the cover.

The AX-LDPS-FD113 is for use in systems under pressure and should be installed in accordance with practices
relevant to the intended use only by persons qualified to do so. The AX-LDPS-FD113 should be mounted on a wall
or other suitable surface using the bracket provided (Fig. 5). Pipework should then be installed to the unit and
terminated at the high and low parts using the 1/4” BSP fittings. It is the responsibility of the installer to ensure that
the pipework is suitable for the system pressure.

Differential Pressure Setting


The cut-out pressure can be adjusted between 0.3 bar and 4.5 bar, the factory setting is 0.7 bar. Cut-in pressure is fixed
at 0.2 bar above cut-out pressure.

Reset
The AX-LDPS-FD113 automatically resets

Mounting Direction
The unit can be mounted in any direction, preferably with pressure connections vertically.

Function / Type of Switch (See Fig. 1)


Differential pressure controls

Pressure Connection (See Fig. 4)


Apply Teflon sealant to adapter thread.

Leakage Test
After completion of installation, a test pressure must be carried out as follows:
- According to EN378 for systems which must comply with European pressure equipment directive
97/23/EC
- To a maximum working pressure of system for other applications

Warning : Failure to correctly test the system could result in loss of refrigerant and personal injury. The pressure
test must be conducted by skilled persons with due respect regarding the danger related to pressure.

Maintenance / Service
In case of repair work or replacing the control always use new sealant.

Electrical Connection
Note: Comply with local electrical regulations when wiring. Wire size must be suitable for electric device connected
to the AX-LDPS-FD113.

© Copyright Annicom 2016. All Rights Reserved Page 2 of 4


Liquid Differential Pressure Switch

Connection
Electrical:
Electrical connections are made as follows:
Remove power before opening or closing the cover.
1. Remove the plug from the body by unscrewing the retaining bolt in the top of the plug.
2. Ensure the unit is not subjected to ingress by water.
3. Ensure all wiring passes through the rubber grommet.
4. Always use the supplied screw to mount the unit to the base.
If the supplied screw is lost an M 0.7 x 8 screw can be used (must have a depth of 5mm or less).
5. Connect the wiring as shown in the diagram below depending upon the type of unit.
6. Set the switching point by inserting a screwdriver into the slots wheel above the scale.

Electrical connections
1. Normally Closed
2. Normally Open
3. Common

Wiring & Dimensions


128mm 48mm

LP
-
LP +
3
68mm
175mm

2
1
+
HP -
HP

Fig. 3 Dimensions & Connectors

Testing Lever 1
Pushing Lever 1 (Fig. 2)
upwards simulates a pressure
rise at the HP side. Pushing the
level down during operation
simulates a lack of HP.

Fig. 2 Switch Positions

© Copyright Annicom 2016. All Rights Reserved Page 3 of 4


Liquid Differential Pressure Switch

Other Drawings & Information


Fig. 3 Example Wiring Diagram for 3 Phase Compressor
L1
This is an application example to further L2
demonstrate appropriate use of the L3
AX-LDPS-FD113 N
PE
A. Thermal overload relay (motor protection)
C B
B. Motor fuses

C. Control circuit fuse gL, max 4A LP


A2 1 3 5
D. Differential pressure control K
D A1 2 4 6
T. Thermostat 96 97
A
HP 95 98
H. Indicator lamp “Oil Pressure” 2 4 6
U1 V1 W2
K. Compressor contactor T
M
M
M. Compressor motor 3~

Fig. 4 Pressure Connection

15 Nm

Fig. 5 Mounting Plate


25
mm

12.5mm

4.5mm
25mm

40m
m

Every effort has been taken in the production of this data sheet to ensure accuracy. Axio do not accept responsibility for any damage, expense, injury,
loss or consequential loss resulting from any errors or omissions. Axio has a policy of continuous improvement and reserves the right to change this
specification without notice.