Synchronus Generator All
Synchronus Generator All
EEE 209
Abid Hasan
Lecturer
Department of Electrical & Electronics Engineering
University of Global Village, Barisal
Introduction of synchronous
machines
Synchronous machines are mostly 3-phase AC machines that
can be used as generator as well as motor.
➢ Synchronous generator also knows as alternator is the
primary source of ac power throughout the world. The
frequency of the generated voltage is proportional to the
speed of the prime mover.
❖ It converts mechanical power into ac electric power. The
source of mechanical power, the prime mover, may be a
diesel engine, a steam turbine, or a water turbine.
❖ For high speed generators, prime movers are usually steam
turbines employing fossil or nuclear energy resources.
❖ Low speed generators are often driven by hydro-turbines
that employ water power.
Introduction of synchronous
machines
EA = 2 NC f = K
where K is a constant representing the construction of the machine, is flux in it
and is its rotation speed.
Distribution factor
E A = k p k d Np / 2
Bnet = BR + BS
Rotor field Stator field
Note that the directions of the net magnetic flux and the phase
voltage are the same.
Equivalent circuit of a
synchronous generator
Assuming that the armature reactance is X, the armature reaction voltage
is
Estat = − jXI A
The phase voltage is then V = E A − jXI A
Armature reactance can be modeled by the
following circuit…
However, in addition to armature reactance
effect, the stator coil has a self-inductance LA
(XA is the corresponding reactance) and the
stator has resistance RA. The phase voltage is
thus
V = E A − jXI A − jX A I A − RI A
Equivalent circuit of a
synchronous generator
Often, armature reactance and self-inductance are combined into the
synchronous reactance of the machine:
XS = X + XA
Therefore, the phase voltage is
V = E A − jX S I A − RI A
3VEA sin
Pout
XS
We observe that electrical losses are assumed to be zero since the resistance is
neglected. Therefore:
Pconv Pout
Here is the torque angle of the machine – the angle between V and EA. It is also
the angle between the rotor magnetic field BR and the net magnetic field Bnet.
3V EA
Pmax =
XS
Power and torque in
synchronous generators
The maximum power is called the static stability limit of the generator.
Normally, real generators do not approach this limit: full-load torque angles
are usually between 150 and 200.
3VEA sin
ind =
m X S
Measuring parameters of
synchronous generator model
The three quantities must be determined in order to describe the
generator model:
1. The relationship between field current and flux (and therefore between
the field current IF and the internal generated voltage EA);
2. The synchronous reactance;
3. The armature resistance.
We conduct first the open-circuit test on the synchronous generator: the
generator is rotated at the rated speed, all the terminals are disconnected
from loads, the field current is set to zero first. Next, the field current is
increased in steps and the phase voltage (which is equal to the internal
generated voltage EA since the armature current is zero) is measured.
We conduct next the short-circuit test on the synchronous generator: the generator
is rotated at the rated speed, all the terminals are short-circuited through
ammeters, the field current is set to zero first. Next, the field current is increased in
steps and the armature current IA is measured as the field current is increased.
The plot of armature current (or line current) vs. the field current is the short-circuit
characteristic (SCC) of the generator.
Measuring parameters of
synchronous generator model
The SCC is a straight line since, for the
short-circuited terminals, the magnitude of
the armature current is
EA
IA =
RA2 + X S2
The resulting
phasor diagram
The magnetic
fields during
Since BS almost cancels BR, the short-circuit test
net field Bnet is very small.
Measuring parameters of
synchronous generator model
An approximate method to determine the synchronous reactance XS at a given
field current:
1. Get the internal generated voltage EA from the OCC at that field current.
2. Get the short-circuit current IA,SC at that field current from the SCC.
3. Find XS from
EA
XS
I A,SC
EA
ZS = R + X =
2
A
2
S XS since X S << RA
I A,SC
Measuring parameters of
synchronous generator model
A drawback of this method is that the internal generated voltage EA is measured
during the OCC, where the machine can be saturated for large field currents, while
the armature current is measured in SCC, where the core is unsaturated.
Therefore, this approach is accurate for unsaturated cores only.
We observe that if XS was estimated via the approximate formula, the result would
be:
EA 311.8
XS = = 1.04
I A,SC 300
Which is close to the previous result.
The error ignoring RA is much smaller
than the error due to core saturation.
The equivalent circuit
The Synchronous generator
operating alone
The behavior of a synchronous generator varies greatly under
load depending on the power factor of the load and on
whether the generator is working alone or in parallel with other
synchronous generators.
EA = V + jX S I A
Armature reaction voltage vector will “move parallel” to its initial position.
The Synchronous generator
operating alone
Increase load effect on generators with
Leading PF
Lagging PF
Unity PF
The Synchronous generator
operating alone
Generally, when a load on a synchronous generator is added, the following
changes can be observed:
Vnl −V fl
VR = 100%
Vfl
Where Vnl is the no-load voltage of the generator and Vfl is its full-load voltage.
The Synchronous generator
operating alone
A synchronous generator operating at a lagging power factor has a fairly large
positive voltage regulation. A synchronous generator operating at a unity power
factor has a small positive voltage regulation. A synchronous generator operating
at a leading power factor often has a negative voltage regulation.
Normally, a constant terminal voltage supplied by a generator is desired. Since the
armature reactance cannot be controlled, an obvious approach to adjust the
terminal voltage is by controlling the internal generated voltage EA = K. This
may be done by changing flux in the machine while varying the value of the field
resistance RF, which is summarized:
1. Decreasing the field resistance increases the field current in the generator.
2. An increase in the field current increases the flux in the machine.
3. An increased flux leads to the increase in the internal generated voltage.
4. An increase in the internal generated voltage increases the terminal voltage of
the generator.
Therefore, the terminal voltage of the generator can be changed by adjusting the
field resistance.
The Synchronous generator
operating alone: Example
Example 7.2: A 480 V, 60 Hz, Y-connected six-pole synchronous generator has a
per-phase synchronous reactance of 1.0 . Its full-load armature current is 60 A at
8.PF lagging. Its friction and windage losses are 1.5 kW and core losses are 1.0 kW
at 60 Hz at full load. Assume that the armature resistance (and, therefore, the I2R
losses) can be ignored. The field current has been adjusted such that the no-load
terminal voltage is 480 V.
V = VT 3 = 277V
At no load, the armature current IA = 0 and the internal generated voltage is EA =
277 V and it is constant since the field current was initially adjusted that way.
a. The speed of rotation of a synchronous generator is
120 120
nm = fe = 60 = 1200 rpm
P 6
which is m = 1200 2 = 125.7 rad s
60
b.1. For the generator at the rated current and the 0.8
PF lagging, the phasor diagram is shown. The phase
voltage is at 00, the magnitude of EA is 277 V,
The Synchronous generator
operating alone: Example
and that jX S I A = j 1 60− 36.87 = 6053.13
Two unknown quantities are the magnitude of V and the angle of EA. From the
phasor diagram:
Then:
V = E 2
A − ( S A cos ) − X S I A sin = 236.8V
X I
2
VT = 3V = 410V
The Synchronous generator
operating alone: Example
b.2. For the generator at the rated current and
the 1.0 PF, the phasor diagram is shown.
Then:
2 − ( X I cos ) − X I sin = 270.4V
2
V = E A S A S A
V = E −2
A
( X I
S A
cos )2
− X I sin = 308.8V
S A
Pin = Pout + Pelec loss + Pcoreloss + Pmech loss = 34.1+ 0 +1.0 +1.5 = 36.6 kW
The efficiency is
Pout 34.1
= 100 % = 100% = 93.2%
Pin 36.6
d. The input torque of the generator is
P
app = in = 36.6 = 291.2 N -m
m 125.7
The Synchronous generator
operating alone: Example
The induced countertorque of the generator is
Pconv 34.1
app = = = 271.3 N -m
m 125.7
e. The voltage regulation of the generator is
480 − 410
Lagging PF: VR = 100% = 17.1%
410
480 − 468
Unity PF: VR = 100% = 2.6%
468
480 − 535
Lagging PF: VR = 100% = −10.3%
535
Parallel operation of
synchronous generators
Most of synchronous generators are operating in parallel with other
synchronous generators to supply power to the same power system.
Obvious advantages of this arrangement are:
1. Several generators can supply a bigger load;
2. A failure of a single generator does not result in a total power loss to the load
increasing reliability of the power system;
3. Individual generators may be removed from the power system for maintenance
without shutting down the load;
4. A single generator not operating at near full load might be quite inefficient.
While having several generators in parallel, it is possible to turn off some of
them when operating the rest at near full-load condition.
Conditions required for
paralleling
A diagram shows that Generator 2
(oncoming generator) will be connected
in parallel when the switch S1 is closed.
However, closing the switch at an
arbitrary moment can severely
damage both generators!
If voltages are not exactly the same in both lines (i.e. in a and a’, b and b’ etc.), a
very large current will flow when the switch is closed. Therefore, to avoid this,
voltages coming from both generators must be exactly the same. Therefore, the
following conditions must be met:
1. The rms line voltages of the two generators must be equal.
2. The two generators must have the same phase sequence.
3. The phase angles of two a phases must be equal.
4. The frequency of the oncoming generator must be slightly higher than the
frequency of the running system.
Conditions required for
paralleling
If the phase sequences are different,
then even if one pair of voltages
(phases a) are in phase, the other two
pairs will be 1200 out of phase creating
huge currents in these phases.
If the frequencies of the generators are different, a large power transient may occur
until the generators stabilize at a common frequency. The frequencies of two
machines must be very close to each other but not exactly equal. If frequencies
differ by a small amount, the phase angles of the oncoming generator will change
slowly with respect to the phase angles of the running system.
If the angles between the voltages can be observed, it is possible to close the
switch S1 when the machines are in phase.
General procedure for
paralleling generators
When connecting the generator G2 to the running system, the following steps
should be taken:
1. Adjust the field current of the oncoming generator to make its terminal voltage
equal to the line voltage of the system (use a voltmeter).
2. Compare the phase sequences of the oncoming generator and the running
system. This can be done by different ways:
1) Connect a small induction motor to the terminals of the oncoming generator
and then to the terminals of the running system. If the motor rotates in the
same direction, the phase sequence is the same;
2)Connect three light bulbs across the
open terminals of the switch. As the phase
changes between the two generators, light
bulbs get brighter (large phase difference)
or dimmer (small phase difference). If all
three bulbs get bright and dark together,
both generators have the same phase
sequences.
General procedure for
paralleling generators
If phase sequences are different, two of the conductors on the oncoming
generator must be reversed.
3. The frequency of the oncoming generator is adjusted to be slightly higher than
the system’s frequency.
4. Turn on the switch connecting G2 to the system when phase angles are equal.
The simplest way to determine the moment when two generators are in phase is by
observing the same three light bulbs. When all three lights go out, the voltage
across them is zero and, therefore, machines are in phase.