W241-E1-3 PID Control Unit Operation Manual
W241-E1-3 PID Control Unit Operation Manual
W241-E1-03
SYSMAC
C200H-PID0@
PID Control Unit
OPERATION MANUAL
C200H-PID0@
PID Control Unit
Operation Manual
Revised August 2003
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or dam-
age to property.
!DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
!WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
!Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1993
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con-
stantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
3 Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
SECTION 1
System Configuration and Features . . . . . . . . . . . . . . . . 1
1-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECTION 2
Connections and Settings . . . . . . . . . . . . . . . . . . . . . . . . . 7
2-1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
SECTION 3
Data Setting Console Operation . . . . . . . . . . . . . . . . . . . 19
3-1 Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3-2 Data Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3-3 Nomenclature and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3-4 Parameter Displays and Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SECTION 4
PC Memory Allocation and Programming. . . . . . . . . . . 33
4-1 Memory Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4-2 Data Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4-3 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SECTION 5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Error Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Appendices
A Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
B Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C Parameters and Key Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
vii
TABLE OF CONTENTS
viii
About this Manual:
This manual describes the installation and operation of the C200H-PID0@ PID Control Unit and
includes the sections described below. Also briefly described is the basic operation and installation of
the C200H-DSC01 Data Setting Console.
Please read this manual carefully and be sure you understand the information provided before
attempting to install and operate the C200H-PID0@ PID Control Unit and Data Setting Console.
Section 1 provides PID Control Unit features and describes its basic system configuration.
Section 2 provides information on the connections and settings of the PID Control Unit.
Section 3 provides the basic operating procedures of the Data Setting Console including parameter
settings and displays.
Section 4 provides the C200H PC’s memory allocation for the PID Control Unit. Basic programming
procedures and examples are also provided.
Section 5 describes possible errors and provides measures for dealing with them.
The three Appendices provide references dealing with specifications, dimensions, and key opera-
tions.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section
in its entirety and be sure you understand the information provided in the section and
related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the C200H-PID0@ PID Control Unit and related devices.
The information contained in this section is important for the safe and reliable application of the C200H-PID0@
PID Control Unit. You must read this section and understand the information contained before attempting to
set up or operate the C200H-PID0@ PID Control Unit.
xi
Intended Audience 1
1 Intended Audience
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2 General Precautions
The user must operate the product according to the performance specifica-
tions described in the relevant manuals.
Before using the product under conditions which are not described in the
manual or applying the product to nuclear control systems, railroad systems,
aviation systems, vehicles, combustion systems, medical equipment, amuse-
ment machines, safety equipment, and other systems, machines, and equip-
ment that may have a serious influence on lives and property if used
improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide
the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be
sure to read this manual before attempting to use the Unit and keep this man-
ual close at hand for reference during operation.
!WARNING It is extremely important that a PC and all PC Units be used for the specified
purpose and under the specified conditions, especially in applications that can
directly or indirectly affect human life. You must consult with your OMRON
representative before applying a PC system to the above-mentioned applica-
tions.
3 Safety Precautions
!WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing
so may result in electric shock.
!WARNING Do not touch any of the terminals or terminal blocks while the power is being
supplied. Doing so may result in electric shock.
!WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do
so may result in malfunction, fire, or electric shock.
!WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the sys-
tem if an abnormality occurs due to malfunction of the PC or another external
factor affecting the PC operation. Not doing so may result in serious acci-
dents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety
measures must be provided in external control circuits.
• The PC will turn OFF all outputs when its self-diagnosis function detects
any error or when a severe failure alarm (FALS) instruction is executed.
xii
Operating Environment Precautions 4
!WARNING Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
!Caution The operating environment of the PC system can have a large effect on the
longevity and reliability of the system. Improper operating environments can
lead to malfunction, failure, and other unforeseeable problems with the PC
system. Be sure that the operating environment is within the specified condi-
tions at installation and remains within the specified conditions during the life
of the system.
5 Application Precautions
Observe the following precautions when using the PC system.
!WARNING Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
xiii
Application Precautions 5
• Always ground the system to 100 Ω or less when installing the Units. Not
connecting to a ground of 100 Ω or less may result in electric shock.
• Always turn OFF the power supply to the PC before attempting any of the
following. Not turning OFF the power supply may result in malfunction or
electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Memory Units, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
!Caution Failure to abide by the following precautions could lead to faulty operation of
the PC or the system, or could damage the PC or PC Units. Always heed
these precautions.
xiv
Application Precautions 5
• Check the user program for proper execution before actually running it on
the Unit. Not checking the program may result in an unexpected opera-
tion.
• Confirm that no adverse effect will occur in the system before attempting
any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC.
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Resume operation only after transferring to the new CPU Unit the con-
tents of the DM Area, HR Area, and other data required for resuming
operation. Not doing so may result in an unexpected operation.
• Do not pull on the cables or bend the cables beyond their natural limit.
Doing either of these may break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so
may break the cables.
• Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals. Connection of bare stranded wires may result in
burning.
• When replacing parts, be sure to confirm that the rating of a new part is
correct. Not doing so may result in malfunction or burning.
• Before touching a Unit, be sure to first touch a grounded metallic object in
order to discharge any static built-up. Not doing so may result in malfunc-
tion or damage.
!Caution The cycle time of the CPU Unit must be a minimum of 20 ms. If the cycle time
is too short, the PID Control Unit will not operate properly.
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
xv
SECTION 1
System Configuration and Features
This section provides PID Control Unit features and the basic system configuration.
1-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1
Features Section 1-1
1-1 Features
The PID Control Unit scales inputs from connected sensors and then carries
out PID control according to preset parameters.
Advanced PID Control
Stable PID control is achieved using advanced PID control and an auto-tuning
feature. ON/OFF control can also be selected.
Two PID Control Loops with a Single Unit
Two PID control loops are possible with one Unit.
High-speed Sampling Period of 100 ms
A sampling period of 100 ms is achieved with two loops, enabling high-speed
PID control.
Input Noise Reduction with Digital Filter
Mitigation of sudden input fluctuations makes the PID Control Unit effective in
quick-response systems.
Comprehensive Output Specifications
Three types of output specification versions are available: C200H-PID01 for
transistor output, C200H-PID02 for voltage output, and C200H-PID03 for cur-
rent output.
Eight Banks of Data Settings
Eight data values such as set point (SP) and alarm set values can be preset in
eight data banks for easy selection.
Data Input and Display
The C200H-DSC01 Data Setting Console (sold separately) is used to input
data and display present values (PV) and set values (SV). The easy-to-read
display can be panel-mounted.
User Programs Allows Reading and Writing of Data
Data can be set and retrieved by means of C200H user programs.
2
Basic System Configuration Section 1-2
C200H-PID0@
PID Control Unit
Connecting cables:
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Data Setting Console
C200H-DSC01
Recommended cable:
ES1000-CA021-051 (0.5 m)
ES1000-CA021-102 (1 m)
ES1000-CA021-202 (2 m)
24 VDC
Number of Units The PID Control Unit belongs to the C200H Special I/O Unit group. A maxi-
mum of ten Special I/O Units (including PC Link Units) can be mounted on the
CPU Rack, Expansion I/O Rack, and Slave Rack.
Note Configure the Units such that the maximum current supplied for each Rack is
greater than or equal to the total current consumption for the Units.
Refer to the C200H PC Operation Manuals for details on configuring systems.
3
Basic System Configuration Section 1-2
Number of Units The number of Special I/O Units used with a Slave Rack is limited by data
Mountable on Slave Rack transmission considerations, as shown in the table below. The numbers in the
table indicate the maximum number of Units of groups A, B, C, or D which can
be used with a single Slave Rack.
A B C D
High-speed Counter Units High-density and Mixed I/O Temperature Sensor Units Position Control Unit
Position Control Units Units Voice Unit (NC211)
(NC111/112) Temperature Control Units
ASCII Unit Heat/Cool Temperature
Analog I/O Units Control Units
ID Sensor Units PID Control Units
Fuzzy Logic Unit Cam Positioner Unit
4 units max. 8 units max. 6 units max. 2 units max.
Note 1. When a combination of Units from groups A, B, C, and D is used, the num-
ber from each group must satisfy both the following equations:
3A + B + 2C + 6D ≤ 12
A+B+C+D≤8
2. Other Units can be added until the total number of units reaches ten. If PC
Link Units are used, the number of Units including the PC Link Units must
not exceed ten.
Precautions The IR area of the C200H Special I/O Unit is allocated according to the setting
of the unit number switch on the front panel, not the address of the slot where
the unit is mounted. Refer to 4-1 Memory Allocation for the allocation of the
memory area.
With the C200 H, leave the two slots next to the CPU free. It is not possible to
use devices connected to the CPU (such as the Programming Console) if
these slots are occupied.
If the C200H Slave Rack is connected to another SYSMAC model Remote I/O
Master Unit, such as the C120, C500, C1000H, or C2000H, it is not possible
to use a Special I/O Unit with the C200H Slave Rack.
!WARNING Always turn the C200H power off before connecting or disconnecting a Unit,
terminal block, or output connector.
Additional Function The function described below has been added to products with the following
lot number and later ones.
07 Z 4 O
1994 (last digit of the year)
December (X: October, Y: November, Z: December)
07 (7th day of the month)
Description of Function
RAM Write Commands
• Previous commands allowed reading and writing to the EEPROM only.
These new commands allow writing to the RAM.
4
Basic System Configuration Section 1-2
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
• When various settings require frequent rewriting, write to the RAM and,
after confirming the setting values, save the data by writing it to the
EEPROM. The data written to the RAM is deleted when the power is
turned off.
• List of RAM Write Commands
Parameter Command Write Read
Set point 4 0 Yes No
Execution bank number 4 2 Yes No
Alarm SV 1 4 3 Yes No
Alarm SV 2 4 4 Yes No
Input shift value 4 5 Yes No
Proportional band 4 6 Yes No
Integral (reset) time 4 7 Yes No
Derivative (rate) time 4 8 Yes No
Decimal point position 5 2 Yes No
Scaling lower limit 5 3 Yes No
Scaling upper limit 5 4 Yes No
Control period 5 7 Yes No
Hysteresis 5 8 Yes No
Alarm hysteresis 5 9 Yes No
Digital filter 5 E Yes No
Alarm 1 mode 6 4 Yes No
Alarm 2 mode 6 5 Yes No
5
SECTION 2
Connections and Settings
This section provides information on the connections and settings of the PID Control Unit.
2-1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-3-1 Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-3-2 Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-3-3 Data Setting Console Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7
Nomenclature Section 2-1
2-1 Nomenclature
C200H-PID0@
Front Panel Rear Panel
Model label
Cover
RUN indicator
SW2 SW202
(Switching memory contents (Input type setting)
and setting direction under
the cover) SW203
(Operation and function settings)
SW1
(Unit number setting)
Data Setting Console
connector
Rack connector
Output connector
Indicators
RUN Lit when the PID Control Unit is operating normally.
Unit Number
SW1 Unit number setting
4
(3)
2
(1)
0 (5)
(9)
8 (7)
6
The cut-out indicates the selected position. Negative numbers
are not indicated. Turn the switch with a flat-blade screwdriver.
Turn the switch until it clicks in position. Do not leave the switch
between two settings.
8
Switch Settings Section 2-2
The addresses are allocated as shown in the following table according to the
Unit number setting.
Unit no. setting Allocated address
0 Wd 100 to 109
1 Wd 110 to 119
2 Wd 120 to 129
3 Wd 130 to 139
4 Wd 140 to 149
5 Wd 150 to 159
6 Wd 160 to 169
7 Wd 170 to 179
8 Wd 180 to 189
9 Wd 190 to 199
The switch is factory-set to 0.
Note If the Unit number is set to an existing Unit number, an alarm occurs and the
C200H does not operate.
Turn the C200H power off before setting the Unit number. If the setting is
changed with the power on, the new setting is not valid until the power is
turned off and back on again.
Remove the cover and set the switch with the tip of a ballpoint pen or similar
object.
1
ON
O
OFF
F
F
The new setting is valid immediately after the switch setting is changed.
Removing and Attaching the Cover
Removing the Cover Attaching the Cover
9
Switch Settings Section 2-2
Switching Memory The contents of the allocated memory differ according to the Unit number set-
Contents ting.
Normal Parameters can be designated as required using com-
mands (Refer to 4-1 Memory Allocation).
Fixed Parameters are allocated in advance.
Refer to 4-1 Memory Allocation for details of the memory contents.
Setting Direction Selects whether the data settings are made from the Data Setting Console or
from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The setting of the executed bank number is made from the C200H PC,
regardless of the ON/OFF setting of this switch.
Input Type
SW202 Input type setting
3
2
6 5 4
9 01
7
8
Switch number Loop 1 Loop 2
0 4 to 20 mA 4 to 20 mA
1 1 to 5 V 1 to 5 V
2 0 to 5 V 0 to 5 V
3 0 to 10 V 0 to 10 V
4 4 to 20 mA 1 to 5 V
5 4 to 20 mA 0 to 5 V
6 4 to 20 mA 0 to 10 V
7 1 to 5 V 0 to 5 V
8 1 to 5 V 0 to 10 V
9 0 to 5 V 0 to 10 V
NO
OFF ON
10
Switch Settings Section 2-2
11
Wiring Section 2-3
2-3 Wiring
2-3-1 Input Wiring
C200H-PID0@
A0
Voltage input
A1
Loop 1
A2
Current input
A3
A4 Refer to the
Voltage input table below.
A5
Loop 2
A6
Current input
A7
24 VDC A8
0.2 A
A9
The 24-VDC output from the C200H
CPU or the Power Supply Units is
convenient.
12
Wiring Section 2-3
6. The terminal block is removable. Make sure that it is attached correctly af-
ter the input wiring connections are completed.
Terminal Block Use crimp terminals for wiring. Take care not to overtighten the terminal
Connections screws. Tighten the screws to a torque of 0.8 N • m.
Crimp Terminals
The screws on the terminal block are M3.5 self-rising terminal screws. Use
the following types of M3.5 crimp terminals.
7 mm max.
7 mm max.
Soldered Lead
Strip insulation from 7 to 10 mm at the end of the wire and carefully solder the
lead.
7 to 10 mm
10
24 VDC 24 VDC
13
Wiring Section 2-3
Circuit Diagrams
C200H-PID01 Transistor Output
24 VDC
Internal circuits
OUT
COM
OUT (+)
Internal circuits
OUT (−)
OUT (+)
OUT (−)
14
Wiring Section 2-3
Applicable Connectors The following connector set manufactured by Fujitsu is included with the Unit:
FCN-361J032-AU (soldering connector)
FCN-360C032-B (cover)
Connector Wiring After soldering the lead to each pin, insulate with heat-shrink tube to prevent
Precautions shorting with the adjacent terminal.
Connection Precautions Tighten the screws after inserting the connector into the Unit. Push the con-
nector firmly into the Remote I/O Terminal or Connector Terminal Block Con-
verter Unit until it fully locks.
Output Cable The output cables in the table below are recommended.
Model Cable length (L)
ES1000-CA021-051 50 cm
ES1000-CA021-102 1m
ES1000-CA021-202 2m
63 30
28 16.1
46
Wiring Diagrams
Pin no. Wire no. Pin no. Wire no. Pin no. Wire no. Pin no. Wire no.
B16 A16 1 #1 11 #11
B15 A15 2 #2 12 #12
B14 A14 3 #3 13 #13
B13 A13 4 #4 14 #14
B12 A12 5 #5 15 #15
B11 A11 6 #6 16 #16
B10 #1 A10 #11 7 #7 17 #17
B9 #2 A9 #12 8 #8 18 #18
B8 #3 A8 #13 9 #9 19 #19
B7 #4 A7 #14 10 #10 20 #20
B6 #5 A6 #15
B5 #6 A5 #16
B4 #7 A4 #17 Note The pin numbers of the 20-pin con-
B3 #8 A3 #18
B2 #9 A2 #19
nector are marked for convenience.
B1 #10 A1 #20 Refer to them from the ∆ mark.
15
Wiring Section 2-3
Remote I/O Terminal The Remote I/O Terminal in the table below is recommended for transistor
output.
Model Specification Relays used
G7TC-OC08 Common (+) 8 x G7T-1112S (max. resistive load: 220 VAC, 2A)
Note One P7TF-OS08 I/O Terminal and two G7T-1112S Relays may be
purchased separately and used.
Wiring Diagram External View
24 VDC
Connector Terminal Block The Connector Terminal Block Converter Units in the table below are recom-
Converter Unit mended for voltage output and current output type.
Model Terminal screw size
XW2B-20G4 M 2.4
XW2B-20G5 M 3.5
External View
16
Wiring Section 2-3
39 17.3
17.5 16.1
10
Connection Precautions
1,2,3... 1. Tighten the lock screws after inserting the connector into the Unit.
2. Push the connector firmly into the Data Setting Console until the clips fully
lock.
3. The Data Setting Console uses power from input terminals A8 and A9 of
the PID Control Unit, supplied through the connecting cable.
4. Install the supplied connector cover when the Data Setting Console is not
used.
17
SECTION 3
Data Setting Console Operation
This section provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
19
Operating Procedure Section 3-1
1,2,3... 1. Set the switches on the front and rear panels according to the operating
conditions. (Refer to 2-2 Switch Settings.)
Set SW2-2 under the display cover to the OFF position to enable data set-
ting from the Data Setting Console.
2. Mount to Rack.
Turn off the C200H power supply before mounting or dismounting the
C200H on the Rack.
3. Connect the input wiring. (Refer to 2-3 Wiring.)
The 24-VDC power supply must be connected. The Data Setting Console
will not operate unless the 24-VDC power supply is connected. The sen-
sors can be connected immediately before the system is tested.
4. Connect the Data Setting Console. (Refer to 2-3-3 Data Setting Console
Cables.)
5. Turn on the 24-VDC and the C200H power supplies.
Set the C200H to PROGRAM mode.
6. Use the Data Setting Console to make the settings for the parameters that
need to be changed. (Refer to the rest of this section.)
7. Test operation and adjust data. (Refer to the rest of this section.)
Connect the output wiring and turn on the heater power. To start the test
operation, turn ON the RUN bit of the loop that is to be controlled with a
device such as the Programming Console. Monitor the control conditions
and adjust the data until the required control is achieved. During operation,
the “bank no.” is switched to “executed bank no.” and cannot be changed
from the Data Setting Console. To change it, use a device such as the Pro-
gramming Console, or else use the user program.
8. Create the user programs. (Refer to SECTION 4 PC Memory Allocation
and Programming.)
Arrange the data for the test operation, and create the user programs for
data setting, monitoring, switching the bank number, and so on. Set SW2-
2 under the display cover to the ON position to enable data setting from the
C200H PC.
9. Start operation.
20
Data Flow Section 3-2
Read
Write ON
SW2-2
OFF
The read operation and setting the executed bank number are possible from a
user program or from a device, such as the Programming Console, regardless
of the ON/OFF setting of SW2-2.
Data written from the Data Setting Console and data written with the
EEPROM write commands when SW2-1 (switching memory contents) is set
to Normal are written to the PID Control Unit EEPROM and are consequently
retained when the power supply is turned OFF.
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
Data written with RAM write commands when SW2-1 (switching memory con-
tents) is set to Normal, the SP value set when SW2-1 is set to Fixed, and exe-
cuted bank number settings made from the C200H PC are written directly to
RAM and are not saved to EEPROM. This data is lost when the power supply
is turned OFF.
Data Settings from Data Set SW2-2 under the display cover to the OFF position to enable data setting
Setting Console from the Data Setting Console.
The “bank no.” can be set when operation is stopped (i.e., when the RUN bit is
OFF). During operation it is switched to “executed bank no.” and cannot be
changed from the Data Setting Console. To change the executed bank num-
ber, use a user program or a device such as the Programming Console.
Operation begins when the RUN bit of the output relay turns ON. (For informa-
tion on output relays, refer to SECTION 4 PC Memory Allocation and Pro-
gramming.
21
Nomenclature and Features Section 3-3
Data display
Operation indicators
Cover
Down Key
The bottom row of the operation keys have upper and lower labels. The upper
labels apply to PID Control Unit operation. The lower labels are for the Cam
Positioner Unit.
Two display sheets are supplied: one for the PID Control Unit and one for the
Cam Positioner Unit. If the Data Setting Console is to be used with the PID
Control Unit only, attach the display sheet for the PID Control Unit.
Note The Data Setting Console will not operate unless a 24-VDC power supply is
connected to the PID Control Unit input terminals.
22
Nomenclature and Features Section 3-3
3-3-2 Features
Data Display
Name Function
PV (Process Displays the PV or the parameter symbol selected with the Level
Value) or Display Key (Refer to next page).
SV (Set Value) The display is as follows, according to the PV display contents.
PV (process value): SV (set value) is displayed.
Parameter symbol: Setting/monitor data is displayed.
BK (Bank Displays the bank number of the data presently being displayed.
Number) During operation, the executed bank number is displayed. (See
note)
Note Operation begins when the RUN bit of the output relay turns ON.
Operation Indicators
Name Function
LOOP2 Indicates whether the displayed settings relate to Loop 1 or Loop
2. Press the Loop Key and hold down for approximately 2
seconds to switch between Loop 1 and Loop 2.
Indicator OFF: Loop 1
Indicator ON: Loop 2
OUT (Output) Turns ON when the output is These indicators relate to the
ON for transistor output or currently displayed loop.
voltage output types.
AT (Auto-tuning) Blinks at approximately 1
second intervals during
auto-tuning.
HB (Heater Turns ON to indicate a heater
Burnout) burnout alarm.
ALM1 (Alarm) Turns ON to indicate the
temperature is in the alarm
range set with Alarm SV 1
(upper- and lower-limit alarm).
Refer to the following page.
Display Patterns
Display Pattern 1 Display Pattern 2
23
Parameter Displays and Settings Section 3-4
Operation Keys
Name Function
Level Key The parameter items are divided into three display groups (Refer
to display levels 0 to 2 in the table below). Press this key to
switch from one group to another. The display levels automati-
cally cycle in the sequence 0 –> 1 –> 2 –> 0 when the key is held
down for approximately 2 seconds.
Display Key Press this key to select the required parameter from the selected
display level 0 to 2 (Refer to table below).
The parameters cycle automatically when the key is held down.
Loop Key Press this key for approximately two seconds to switch between
Loop 1 and Loop 2.
24
Parameter Displays and Settings Section 3-4
Display Parameter Display Write Read Loop Bank Data range Default value Page
level symbol no. no.
1 Decimal point dp Yes Yes Yes No 0 to 3 1 28
position
Scaling lower limit inl Yes Yes Yes No –999 to (scaling 0 28
upper limit – 1
digit)
Scaling upper limit inh Yes Yes Yes No (Scaling lower 1000 28
limit + 1) to 9999
Digital filter df Yes Yes Yes No 0 to 100 s 0s 28
Control period cp Yes Yes Yes No 1 to 99 s 20 s 29
(see note 1)
Hysteresis (see hys Yes Yes Yes Yes 0.0 to 100.0% FS 0.2% FS 29
note 2)
Alarm hysteresis hysa Yes Yes Yes No 0.0 to 100.0% FS 0.1% FS 29
(see note 4)
2 Control output o No Yes Yes No 0.0 to 100.0% 0.0% 30
variable monitor
Auto-tuning start/ at Yes Yes Yes No --- --- 30
stop (see note 1)
Copy bank bcpy Yes Yes Yes No --- --- 30
Input-type monitor in-t No Yes No No 0 to 9 Setting for 31
SW202
Alarm 1 mode alt1 Yes Yes Yes No 0 to 9 2 31
Alarm 2 mode alt2
Yes: Possible.
No: Not possible or not required.
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
3. The decimal point position is set by the “decimal point position” parameter.
4. Does not apply when Alarm Mode = 0.
5. Writing is not possible during operation (i.e., when RUN is ON).
6. Only when the output relay “MAN” bit = 1.
25
Parameter Displays and Settings Section 3-4
SV
Settings
• This is used to manually manipulate the output volume. It is valid when
the output relay “MAN” bit is ON.
• The “MAN” bit can be turned ON and OFF by means of a device such as
the Programming Console, or by means of the user program. For details,
refer to Section 4 PC Memory Allocation and Programming.
PV and SV (Display Level 0)
Valid SV Range
Set the set point in the range between the scaling lower limit and the scaling
upper limit.
Error Display
When a sensor error occurs, one of the codes below and the detected tem-
perature blink alternately in the PV display.
ser1 The analog input is out of the range: (input measurement range +
10%FS). That is, 10%FS below the lower limit or 10%FS above the
upper limit. Includes broken or incorrect input wiring.
ser2 ser1 : Loop1 or Loop1 and Loop2 simultaneously.
ser2 : Loop2
Settings
• The bank number can be changed.
• The changed SV is reflected in the bank number display (BK).
Bank Number and Executed Bank Number
The executed bank number cannot be changed from the Data Setting Con-
sole. When changing these parameters from the Data Setting Console, stop
operation. While operation is stopped, the bank number setting can be
changed.
26
Parameter Displays and Settings Section 3-4
If the displayed value differs from the actual value due to the sensor position
or some other conditions, set the input shift value such that the correct value
is displayed.
Proportional Band (Display Level 0)
• This sets the proportional band. It is valid only when SW203-1 is set to
OFF (i.e., PID control).
• This value is reflected even when auto-tuning (AT) is executed.
• If this value is set to “0.0,” ON/OFF control is executed with PID control
selected.
Integral (Reset) Time (Display Level 0)
• This sets the integral time. It is valid only when SW203-1 is set to OFF
(i.e., PID control).
• This value is reflected even when auto-tuning (AT) is executed.
Derivative (Rate) Time (Display Level 0)
27
Parameter Displays and Settings Section 3-4
• This sets the integral time. It is valid only when SW203-1 is set to OFF
(i.e., PID control).
• This value is reflected even when auto-tuning (AT) is executed.
Decimal Point Position (Display Level 1)
This sets the scaling lower limit. The default value is 0%.
Scaling Upper Limit (Display Level 1)
This sets the scaling upper limit. The default value is 1000%.
Digital Filter (Display Level 1)
100%
63%
0
(s) →
0 T
28
Parameter Displays and Settings Section 3-4
• This sets the control period. It is valid when SW203-1 is OFF (PID con-
trol).
• The control period is the time required to complete one transistor output
or voltage output ON/OFF cycle.
ON
OFF
ON time
Control period
ON
OFF
Set point
29
Parameter Displays and Settings Section 3-4
vided which may be either higher or lower than the set point, depending
on the ALARM mode.
Upper Limit Mode Lower Limit Mode
Hysteresis Hysteresis
ON ON
OFF
OFF
Alarm SV Alarm SV
The alarm output is OFF if the present value lies within the hysteresis band
when the Unit is turned on.
Control Output Variable Monitor (Display Level 2)
The relationship between the control output variable and control period is
defined by the formula below:
ON time
Control output variable (%) = x 100
Control period
The control output variable during ON/OFF control (when SW203-1 on the
rear panel is ON) is ON = 100% and OFF = 0%.
Auto-tuning Start/Stop (Display Level 2)
PV Process value
SV Set point
PV
SV
Copy bank parameter symbol Execute bank copy Bank being copied Bank copy completed
• When the Up Key is pressed, the data other than the set point is copied
from bank number 1 to banks 2 through 8.
• Use this method to create data in banks 2 through 8 by slightly modifying
the data in bank number 1.
30
Parameter Displays and Settings Section 3-4
Select the desired alarm type from the following chart and set the number (X:
set value)
ALARM Alarm Type Alarm Range
mode 0 SP
0 No alarm
1 Upper- and lower-limit alarm
x x
2 Upper-limit alarm
x
3 Lower-limit alarm
x
Standby Sequence
When the power is turned on, the value is below the set point, so alarm output
status occurs with regard to the lower limit alarm. In this situation, if “lower
limit alarm with standby sequence” is selected, the standby sequence recog-
nizes that the value is out of the alarm range and then outputs an alarm when
the value enters the alarm range once more.
31
Parameter Displays and Settings Section 3-4
Alarm SV
0°C
Alarm output
32
SECTION 4
PC Memory Allocation and Programming
This section provides the C200H PC’s memory allocation for the PID Control Unit. Basic programming procedures
and examples are also provided.
33
Memory Allocation Section 4-1
Note A Duplicate I/O Unit error occurs if the set Unit number corresponds to the
number of an existing Special I/O Unit.
Selecting Allocated Data The data allocated to each IR word due to the Unit number setting is deter-
mined by the setting of SW2-1 on the front of the Unit.
ON Normal All data can be set using commands.
OFF Fixed Parameters are fixed for the set point (SV).
34
Memory Allocation Section 4-1
Note Four digits BCD and the decimal point position are designated by the “decimal
point position” parameter. The most significant digit (F) = minus (–).
SW2-1 in Normal Position
(n=100 + 10 x Unit number)
I/O Word Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output n Read/write instruction
Read/write Loop no. Bank no. Instruction
n+1 Write data (see note)
0 to 9, F 0 to 9 0 to 9 0 to 9
n+2 Loop 1 executed bank Loop 2 executed bank Loop 1 Loop 2 0 0 Write
number number MAN RUN MAN RUN re-
quest
Input n+3 Loop 1 PV (see note)
0 to 9, F 0 to 9 0 to 9 0 to 9
35
Memory Allocation Section 4-1
Note Four digits BCD and the decimal point position are designated by the “decimal
point position” parameter. The most significant digit (F) = minus (–).
36
Memory Allocation Section 4-1
37
Memory Allocation Section 4-1
38
Memory Allocation Section 4-1
39
Memory Allocation Section 4-1
Yes: Possible.
No: Not possible or not required.
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
40
Memory Allocation Section 4-1
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
Yes: Possible.
No: Not possible or not required.
Note 1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
41
Data Flow Section 4-2
3. The decimal point position is designated by the “decimal point position” pa-
rameter.
4. Does not apply when Alarm Mode = 0.
5. RAM write commands write data only to the RAM regardless of the setting
of the Switch 203-3 (SP write mode).
6. Any data written using RAM write commands is deleted when the power is
turned OFF.
7. RAM write commands cannot be used to read data.
4-3 Programming
4-3-1 Example with SW2-1 in the Fixed Position
Description and Conditions
Example: The user program makes the following settings:
Loop 1 SP = 80.0
Loop 2 SP = 90.0
Loop 1 executed bank number = 1
Loop 2 executed bank number = 3
Conditions: C200H-PID01
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set OFF (Fixed) and SW2-2 set ON (C200H PC).
Sample Program
25315 10701 10700
MOV (21) Set #0800 for word 100 (Loop 1 SP).
1 cycle ON (C200H) Fixed #0800
100
101
MOV (21) Set #1350 for word 102 (executed bank number).
#1350
102
#1350
END (01) Run bit ON
Loop 2 executed bank number
Loop 1 executed bank number
Be sure to set the correct values for the Loop 1 and Loop 2 SP.
The SV value is #0000 (0%) if no data is set. If the executed bank number is
set to a value out of the range from 1 to 8 the bank number reverts to the pre-
vious value (default value = 1).
Reading Monitored Data Read monitored data into the program using Wd (n+3) to (n+9).
42
Programming Section 4-3
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
43
Programming Section 4-3
Sample Program
10701 10700
DIFU (13) SW2-2 (10701) switch ON detection
(C200H) Normal 23200
(C200H PC)
23200
23201
MOV (21)
#1250
#1250
Run bit ON
102
Loop 2 executed bank number
MOV (21) Loop 1 executed bank number
#5100
#5100
SP setting instruction
100
Bank number
MOV (21) Bit data : 0101
#0200 Loop 1
Write
101 Write data (20.0)
23202
DIFD (14)
23203
Wait for completion of write,
23201
and then proceed to next step
S
KEEP(11)
23202
23203
MOV (21) #6200
#6200 SP setting command
100 Bank number
Bit data: 0110
MOV (21) Loop 2
#0805 Write
101
23204
Write data (8.05)
DIFD (14)
23205
23203
S Wait for completion of write,
KEEP(11) and then proceed to next step
23204
23205
MOV (21) #5012 Decimal point position
#5012 command
Bank number not required
100
Bit data: 0101
MOV (21) Loop 1
#0001 Write
101 Write data (1st digit)
Next page
44
Programming Section 4-3
23206
DIFD (14)
23207
23207
MOV (21) #6012 Decimal point position
#6012 command
100
Bank number not required
Bit data: 0110
MOV (21) Loop 2
Write
#0002
101 Write data (2nd digit)
23208
S
KEEP(11) Write request
10200
10608 Write complete R
23201
DIFD (14)
23203 23208
23205
23207
END (01)
45
Programming Section 4-3
Timing Chart
1 cycle
25315
(1 cycle ON)
23201
23202
23203
23204
23205
23206
23207
10200
(Write request)
10608
(Write complete)
In addition to the timing above, 23201 turns ON for one cycle on the ON rising
edge of SW2-2 (10701) and a write request (10200) turns ON at a timing one
cycle behind 23208.
Conditions: C200H-PID01
Unit number set to 0 (allocated memory: IR100 to IR109.
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
46
Programming Section 4-3
Sample Program Insert the program below before the END instruction in the program on
page 45.
25313
MOV (21) Read Loop 1 PV from IR103 to DM
0000.
Normally ON 103 Read operation is not affected by
DM0000 SW2-1 and SW2-2 settings.
23208
DIFD (14)
23300
23307
23301
MOV (21)
#1020 Control output variable
#1020
monitor command
100 Bank number not required
Bit data: 0001
DIFD (14)
Loop 1
23302
Read
23302 S
KEEP(11)
23303 Wait for Read Complete
to read data
23303
DIFD (14)
23304
23304
MOV (21) Read data from IR105 to DM 0001.
105
DM0001
100
DIFD (14)
23307
(B)
47
Programming Section 4-3
10701 10700
DIFU (13) SW2-2 (10701) switch ON
(C200H) Normal 23200 detection (C200H PC)
23301
23302
23303
23304
23307
Wd 105
(Read data)
10600
(Read complete)
Note It takes more than 140 ms for the Read Complete Flag (10600) to turn ON
again after it is turned OFF.
48
Programming Section 4-3
ON
Write request
(Wd n+2), bit 00 OFF
Write complete ON
(Wd n+6), bit 08 OFF
Approx.
140 ms
1,2,3... 1. The data is written to the PID Control Unit EEPROM when the Write Re-
quest Flag turns ON.
!Caution The PID Control Unit’s built-in EEPROM can be written to 100,000 times (ser-
vice life). If more than 100,000 EEPROM write operations are performed, the
memory will become corrupted. Do not use a Unit that has processed more
than 100,000 EEPROM write operations.
2. The Write Complete Flag turns ON when the data writing operation is com-
pleted. It takes approximately 140 ms to write the data.
3. The Write Complete Flag automatically turns OFF when the Write Request
Flag turns OFF.
Check to be sure that the Write Complete Flag has turned ON before turn-
ing OFF the Write Request Flag. If the Write Request Flag is set to OFF
before the Write Complete Flag turns ON, the write operation will not be
successful.
Temporarily turn the Write Request Flag OFF before executing the second
and subsequent write operations. Writing is enabled on the ON rising edge
of the Write Request Flag.
The Loop 1 and 2 executed bank number (Wd n+2) sets data directly. The
data is written to the PID Control Unit RAM. If the value is set out of this
range, the bank number reverts to the previous value (default value = 1).
Timing for a Read Operation
Command (n) Command (A) Command (B)
Read complete ON
(Wd n+6),
bit 00 OFF
Approx.
140 ms
1,2,3... 1. The read data is output to Wd (n+5) approximately 140 ms after the Read
command is executed.
2. The read data is updated every 100 ms.
3. When the Read command is modified, turn OFF the Read Complete Flag
to execute the next read operation.
49
Programming Section 4-3
I/O Refresh PID control will not be executed properly unless there are at least 20 ms
between I/O refresh operations. When creating the program, be sure that all
of the conditions descried below are satisfied.
• The cycle time must be a minimum of 20 ms. If the program processing
time is short, it is recommended that the fixed cycle time instruction
(SCAN18) be used.
• When IORF(97) is executed for the PID Control Unit, there must be an
interval of at least 20 ms between prior and subsequent end refreshes.
• The time interval for executing IORF(97) must be a minimum of 20 ms.
Normal I/O refresh (End refresh)
20 ms min. (cycle time)
Normal I/O refresh (End refresh)
20 ms min.
IORF(97) (I/O refresh instruction)
20 ms min.
IORF(97) (I/O refresh instruction)
20 ms min.
Normal I/O refresh (End refresh)
50
SECTION 5
Troubleshooting
This section describes possible errors and provides measures for dealing with them.
Error Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
51
Error Detection Section 5
Error Detection
When an error occurs in an input or in the Unit, details of the error are output
to the Data Setting Console and input relays (words n+8 and n+9).
Sensor Input Errors
The following table shows the Data Setting Console display and error con-
tents.
Display Error name Output status after Cause Remedy
error
ser1 Loop 1 sensor error Control output: Reading is ±10%FS out Check the sensor wiring.
The transistor output or of sensor measurement Replace the sensor.
voltage output turns OFF range (i.e., 10%FS below
or the current output falls the lower limit or 10%FS Replace the Unit.
below 2 mA. above the upper limit). Correctly set switch
Alarm output: Broken or incorrect input SW203-4.
ser2 Loop 2 sensor error The alarm is output wiring
assuming the input is Defective input sensor
±10%FS.
Defective Unit
SW203-4 is OFF (Loop 2
enabled) but no sensor
connected to Loop 2.
Data Setting Console When a sensor error occurs, one of the codes above and the detected value
are displayed alternately.
If a Loop 1 sensor error ser1 and a Loop 2 sensor error ser2 occur simulta-
neously, ser1 is displayed preferentially. Even if a sensor error is detected in
one Loop, the other Loop continues to operate normally. Control operation
restarts automatically five seconds after the cause of the error is corrected.
The following bits are set when a sensor input error occurs.
Loop 1 sensor error Wd. n+8, bit 14 = 1
Loop 2 sensor error Wd. n+9, bit 14 = 1
Alarm
Display Error name Cause Remedy
ALM1 Alarm 1 The value is in the alarm Check the object being
indicator lit range set with Alarm SV 1. controlled.
ALM2 Alarm 2 The value is in the alarm
indicator lit range set with Alarm SV 2.
Error displayed when an abnormality occurs in the loop currently being dis-
played. No indicator is provided to show an ALM2 alarm.
The bits shown in the table below are set to 1 when an alarm occurs.
Wd (n+8) Bit 01 = 1 Alarm 1 Loop 1
Bit 00 = 1 Alarm 2
Wd (n+9) Bit 01 = 1 Alarm 1 Loop 2
Bit 00 = 1 Alarm 2
EEPROM Error
Display Error name Output status after error Cause Remedy
e111 EEPROM Control output: Defective Replace the
error The transistor output or EEPROM Unit
voltage output is OFF or
the current output is less
than 2 mA.
Alarm output is OFF.
52
Error Detection Section 5
53
Appendix A
Specifications
General Specifications
Conforms to the C200H PC specifications.
Item C200H-PID0@ Specifications
Input signal refresh 4 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V
No. of input points (loops) Two points (two loops, each of which consists of a voltage and a current)
Control mode PID, ON/OFF (selectable with a switch on the rear panel)
(advanced PID control with auto-tuning)
Setting/designation accuracy ±0.5% FS ±1 digit max. The SV and displayed value match. There is no relative error.
Hysteresis 0.0 to 100.0% FS (in units of 0.1%FS)
Alarm hysteresis 0.0 to 100.0% FS (in units of 0.1%FS)
Proportional band 0.0 to 999.9 (in units of 0.1)
Integral (reset) time 0 to 9999 s (in units of 1 s)
Derivative (rate) time 0 to 9999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Sampling period 100 ms
Output refresh period 100 ms
Display refresh period 100 ms
Input shift range –999 to 9999 (see note 1)
Scaling setting range –999 to 9999 (see note1)
Digital filter setting range 0 to 100 s (in units of 1 s)
Alarm output setting range –999 to 9,999
Manual output setting range –5 to 105%
No. of banks 8 banks
Internal current consumption 5 VDC, 0.33 A max.
External supply voltage 24 VDC +10%/–15%, 0.2 A min.
Dimensions (see note 2) 34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
Weight 360 g
55
Specifications Appendix A
Output Characteristics
Transistor Output (Pulse) C200H-PID01
External supply voltage 24 VDC +10%/–15%
Max. load voltage 24 VDC (collector supplied voltage) max.
Max. load current 100 mA max.
Residual voltage when ON 3 V max.
Leakage current when OFF 0.3 mA max.
56
Appendix B
Dimensions
130
20 100.5 11
120.5
34.5
131.5
Mounting Dimensions
Base unit
17
Approx. 200
96
91
48 12 45
44
3 57
57
Dimensions Appendix B
Mounting Dimensions
Panel Cutout Clearance
92 +0.8
0
45 +0.6
0
Panel thickness 1 to 4 mm
Allow a clearance of at least 150 mm behind the Data Setting Console when it is installed in the panel to allow
cable connectors to be inserted. A clearance of 50 mm is sufficient if the rear panel can be opened.
58
Appendix C
Parameters and Key Operations
The Data Setting Console key operations and their relation to parameters are shown in the following table.
1
o
inl at
PV Scaling lower limit Auto-tuning
start/stop
PV inh bcpy
SP Scaling upper limit Copy bank
bk df in t
Bank number Digital filter Input-type monitor
al 1 cp alt 1
Alarm 1 SV Control period Alarm 1 mode
al 2
hys alt 2
Alarm 2 SV
Hysteresis Alarm 2 mode
in 5
hysa
Input shift value
Alarm hysteresis
p
Proportional band
i
Integral time
d
Derivative time
59
Index
A–B I
advanced PID control, 2 indicators, 8
alarm indicators, 52 input shift value setting, 27
allocating memory, 34 input wiring
applications precautions, 12
precautions, xiii installation
auto-tuning start/stop setting, 30 precautions, xiii
bank number setting, 26 integral time setting, 27
memory contents, 36
C
command codes
M–O
settings, 40 operating environment
Connector Terminal Block Converter Unit, 16 precautions, xiii
control output variable monitor setting, 30 Operation and Function Setting, 10
control period setting, 29 operation timing, 49
cover output wiring, 13
removal and replacement, 9 circuit diagrams, 14
connectors and cable, 15
diagrams, 15
D precautions, 15
data flow, 21
data setting, 21 P–R
operating procedure, 20
precautions, 4
Data Setting Console
applications, xiii
connecting cable and precautions, 17
general, xii
features, 23
operating environment, xiii
mounting, 58
safety, xii
parameter and setting tables, 24
physical features, 22 programming
examples, 42, 46
data settings, 42
proportional band setting, 27
decimal point position, 28
read operation timing, 49
derivative time setting, 27
Remote I/O Terminal, 16
detecting errors, 52
Duplicate I/O Unit, 53
EEPROM error alarm, 52 S
safety precautions
E–F See also precautions
selecting allocated memory, 34
error display, 26
sensors
errors
setting type, 10
data setting, 52
sensor-type setting, 30
features, 2
setting and displaying parameters
method, 25
settings
61
Index
source, 10
Slave Rack
number of mountable Units, 4
Special I/O Unit error, 53
specifications
general, table, 55
switch settings, 8, 9
switching memory contents, 10
switching memory contents and setting direction, 9
system configuration, 3
T–U
troubleshooting
alarm, 52
data setting errors, 52
duplicate I/O unit, 53
EEPROM error, 52
power supply, 53
RUN Indicator Unlit, 53
Special I/O Unit error, 53
Unit
models, 3
Unit components
dimensions, 57
62
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
Revision code Date Revised content
1 November 1993 Original production
1A March 1995 Page 38: Auto-tuning start/stop in the table corrected.
Page 44: Sample program corrected.
2 March 2000 Added PRECAUTIONS section.
Page 4: Added descriptions about RAM write commands.
Page 9: Added the use of RAM write commands in the SP write mode.
Page 11: Changed descriptions about the terminal block connections.
Page 19: Changed descriptions about the data flow to include information about
EEPROM write commands and RAM write commands.
Page 39: Added the RAM write commands table.
Page 39: Changed some values in the sample program.
Page 40: Added comments about EEPROM write commands and RAM write
commands in the sections on descriptions and conditions.
Page 42: Changed the sample program.
Page 43: Changed the information at the end of timing chart.
Page 44: Changed the sample program.
Page 45: Changed the timing chart.
03 August 2003 Page xiii: Added precautions on cycle time and writing to EEPROM, and
changed application precaution on mounting units to include Power Supply
Units.
Page 4: Added caution on writing to EEPROM.
Page 11: Added information regarding SP Write Mode.
Pages 21, 41, and 42: Added caution on writing to EEPROM.
Page 46: Added information to the diagram on the Read command.
Page 48: Added caution on writing to EEPROM.
63
OMRON CORPORATION
FA Systems Division H.Q.
66 Matsumoto
Mishima-city, Shizuoka 411-8511
Japan
Tel: (81)55-977-9181/Fax: (81)55-977-9045
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
Singapore 239920
Tel: (65)6835-3011/Fax: (65)6835-2711
Authorized Distributor:
Cat. No. W241-E1-03 Note: Specifications subject to change without notice. Printed in Japan
Cat. No. W241-E1-03 C200H-PID0@ PID Control Unit OPERATION MANUAL