0% found this document useful (0 votes)
45 views8 pages

Fire Fighting Panel

Uploaded by

Abhijit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views8 pages

Fire Fighting Panel

Uploaded by

Abhijit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

MARIANA ENTERPRISE

CPRI Tested Electrical Panel Board


ISO 9001:2015 CERTIFIED

PROJECT REPORT
ON
LT PANEL BOARD

Submitted towards the fulfillment of requirements for the completion of Project

CLIENT:- Airport Authority of India


DEPARTMENT:- Dibrugarh Airport Authority
PROJECT:- ATC Project Dibrugarh Airport
ADDRESS:- Dibrugarh, Assam
TABLE OF CONTENTS

Sl No. TITLE PG NO.


1 Panel Description 2
2 System Parameter 3
3 Bill of Material 4-6
4 General Arrangement Drawings 7-8
5 Terms & Conditions 9

Page No.-1
PANEL DESCRIPTION:-
1. SYSTEM SPECIFICATION : 415V, 50Hz, 3PHASE 4WIRE.
2. ENCLOSURES : INDOOR
3. PAINT SHADE : THE PANEL SHALL BE PAINTED WITH POWDER COATED PAINT AS PER FOLLOWING COLOR SCHEME.
DOORS/COVERS AND MAIN FRAME- SIEMENS GREY
MOUNTING PLATE- SIEMENS GREY
BASE FRAME- BLACK
4. GASKET : POLYURETHELENE GASKET SHALL BE PROVIDED TO MAKE THE PANEL DUST AND VERMIN PROOF.
5. BUS BAR : BUS BAR SHALL BE SUPPORTED ON NON HYGROSCOPIC, NON CARBONISING, CORROSION RESISTANCE
SMC/DMC INSULATORS.
6. EARTH BUSBAR : THE EARTH BUS SHALL BE PROVIDED THROUGHOUT LENGTH OF THE PANEL.
7. DEGREE OF PROTECTION : THE PANEL SHALL BE DUST & VERMIN PROOF, FLOOR COMPARTMENTALIZED (FORM-3b) AND SUITABLE FOR
DEGREE OF PROTECTION IP-42 FOR INDOOR.
8. DOOR EARHING : ALL HINGED DOOR SHALL BE EARTHED THROUGH COPPER FLEXIBLE WIRE.
9. CONTROL WIRING : CONTROL WIRING SHALL BE CARRIED OUT WITH 1100V COPPER FRLS FLEXIBLE WIRE AS PER FOLLOWING
COLOUR STANDARD.
AC VOLTAGE CIRCUIT - 2.5 SQMM. BLACK WITH PHASE INDICATION COLOUR AT ENDS.
CURRENT CIRCUIT - 2.5 SQMM. BLACK WITH PHASE INDICATION COLOUR AT ENDS.
10. POWER WIRING : AS PER FEEDER RATING COPPER FRLS FLEXIBLE F WIRE FOR POWER CIRCUIT.
11. METERING INSTRUMENT : ALL METER SHALL BE DIGITAL TYPE, FLUSH MOUNTED 96 X 96 Sqmm.
12. OUTGOING TERMINATION : ALL CABLE TERMINATION SHALL BE BOUGHT AT CABLE ALLEY.
14. HARDWARE : ALL HARDWARE SHALL BE PASSIVE TYPE.
15. DANGER BOARD : DANGER BOARD SHALL BE PROVIDED AS PER STANDARD AT FRONT AND REAR OF EACH BOARD IN HINDI AND
ENGLISH LANGUAGE.
16. DIMENSION : ALL DIMENSION ARE IN MM.

Page No.-2
1 SYSTEM PARAMETERS (FIRE PANEL):- 5 BUSBAR:-
a) AMBIENT TEMPERATURE : 35 degree Celcius i) MAIN BUSBAR
b) MAIN SYSTEM : 3-PHASE 4-WIRE AC, 50HZ±5%
c) RATED OPERATION VOLTAGE : 415V AC±5% a) TEMPERATURE RISE LIMIT : AS PER IEC 60439-1
d) DRY FREQUENCY WITHSTAND VOLTAGE : 2.5KV b) MATERIALS : ALUMINUM

2 CONSTRUCTION:- c) CROSS-SECTION AREA FOR EACH PANEL : REFER GA


a) TYPE OF BOARD : d) COLOR CODING : R,Y,B & N HEAT SHRINKABLE SLEEVE
b) MAIN FRAME : 2 MM CRCA SHEET : WITH RYB COLOR CODE
c) DOORS/COVERS : 2 MM CRCA SHEET ii) EARTH BUSBAR
d) PARTITIONS : 2 MM CRCA SHEET
e) GLAND PLATES : 2 MM CRCA SHEET a) RATED CURRENT : REFER GA
f) LOCATION : INDOOR b) LOCATION THROUGHOUT LENGTH OF THE PANEL
g) MOUNTING : FLOOR MOUNTED AT BOTTOM
h) LIFTING ARRANGEMENT : LIFTING EYES PROVIDED
6 POWER WIRE SIZES:-
j) DEGREE OF PROTECTION : IP-42 FOR INDOOR a) UPTO 8A : 2.5 SQMM. CU. FRLS
k) TYPE OF SEGREGATION : FORM 3b b) 9A TO 25A : 4 SQMM. CU. FRLS
c) 26A TO 32A : 6 SQMM. CU. FRLS
3 PAINTING:- d) 33A TO 50A : 10 SQMM. CU. FRLS
a) PROCEDURE : 9 TANK PHOSPHATING PROCESS e) 51A TO 63A : 16 SQMM. CU. FRLS
b) POWDER THICKNESS : MINIMUM 70 MICRON
c) SHADE FOR FRAME/DOORS/COVERS : PO RED
d) MOUNTING PLATES : PO RED
7 THE MINIMUM CLEARANCE OF MAIN BUSBAR AS FOLLOWS:-
4 NAME PLATE:- a) BETWEEN PHASE TO PHASE : 32MM
a) MATERIAL : PRINTED ALUMINUM (SCFREWED) b) BETWEEN PHASE TO NEUTRAL : 32MM
b) COLOUR OF LETTERING : RED&BLUE c) BETWEEN PHASE TO EARTH : 26MM
c) INDICATION OF EQUIPMENT : SELF ADHESIVE STICKER d) BETWEEN NEUTRAL TO EARTH : 26MM
MOUNTED INSIDE PANEL
d) FEEDER NAME PLATE : ON FRONT DOOR

Page No.-3
BILL OF MATERIAL (APFC PANEL)
SL
NO ITEMS MAKE QTY UNIT
As Incomer
250A 4P 25KA 100% Icu , microprocessor, Earth Fault, MCCB with
1 O/L, S/C protection ABB 2 Nos.
2 Spreader Link For above MCCB ABB 2 Set.
3 LED Indicating Lamp (R,Y,B) Vaishno 3 Nos.
4 2A, SP, MCB ABB 3 Nos.
5 Ammeter L&T 2 Nos.
6 Ammeter Selector Switch L&T 2 Nos.
7 CT 600/5A AE 6 Nos.
8 250A, 4P, ATS L&T 1 No.
9 Controller for above L&T 1 No.
4 3 Phase Voltmeter L&T 1 No.
5 3 Phase Ammeter L&T 1 Nos.
14 CT 600/5A AE 3 Nos.
15 LED Indicating Lamp (R,Y,B) Vaishno 3 Nos.
16 2A, SP, MCB ABB 3 Nos.
As Outgoing
1 For 55Kw, Motor-2No.
200A 3P+N 25KA MCCB ABB 2 Nos.
Spreader Link For above MCCB ABB 2 Set
Soft Starter, 55KW L&T 2 Nos.
3 Phase Voltmeter L&T 2 Nos.
3 Phase Ammeter L&T 2 Nos.
CT 200/5A AE 6 Nos.
LED Indicating Lamp (R,Y,B) Vaishno 6 Nos.
2A, SP, MCB ABB 8 Nos.
Single phase preventor L&T 2 Nos.
PLA Relay, 220AC L&T(Salzer) 2 Nos.
Push Button Start Teknika 2 Nos.
Page No.-4
Push Button Stop Teknika 2 Nos.
Push Button Re-Set Teknika 2 Nos.
Auto Manual Selector Switch L&T 2 Nos.
Local Remote Selector Switch L&T 2 Nos.
2 For 5.5Kw, Motor-2No.
40A 3P+N 10KA MCCB ABB 2 Nos.
Soft Starter, 5.5KW ABB 2 Nos.
3 Phase Voltmeter L&T 2 Nos.
3 Phase Ammeter L&T 2 Nos.
CT 60/5A L&T 2 Nos.
LED Indicating Lamp (R,Y,B) AE 2 Nos.
2A, SP, MCB Vaishno 2 Nos.
Single phase preventor ABB 2 Nos.
PLA Relay, 220AC L&T 2 Nos.
Push Button Start L&T(Salzer) 2 Nos.
Push Button Stop Teknika 2 Nos.
Push Button Re-Set Teknika 2 Nos.
Auto Manual Selector Switch Teknika 2 Nos.
Local Remote Selector Switch L&T 2 Nos.
Local Remote Selector Switch L&T 2 Nos.
3 For 24V Diesel Driven Pump-2No.
20A DP 10KA MCB ABB 2 Nos.
10A DP MCB ABB 2 Nos.
On/ Off Toggle Switch L&T 2 Nos.
Auxiliary Contactor, 220AC ABB 2 Nos.
Cut Out Relay Reputed 4 Nos
PLA Relay, DC L&T(Salzer) 10 Nos
Indicator Lamp, AC Vaishno 2 Nos.
Indicator Lamp, DC Vaishno 14 Nos
Push Button, Start Teknika 2 Nos
Push Button, Stop Teknika 2 Nos
Push Button, Accept Teknika 2 Nos
Push Button, Emergency Teknika 2 Nos
Buzzer Teknika 2 Nos
Page No.-5
Ammeter L&T 2 Nos
Voltmeter L&T 2 Nos
Battery Charger Reputed 2 Nos
ESR Minilec 2 Nos
Auto/Manual Selector Switch L&T 2 Nos

Page No.-6
101 102
GENERAL ARRANGEMENT DRAWINGS
103 104 105 106 107 108 109

A A
This Drawing & any information or descriptive matter set out hereon the confidential property ofM/S

B
used for manufacturing tendering or for any other purpose without their written permission.
MARIANA ENTERPRISE & must not be disclosed. looned. copied or

MANUFACTURER NAME OF WORK:- ELECTRICAL FIRE PANEL BOARD DRG. NO. ME/II/CU-5170 APPROVED BY

M/S MARIANA ENTERPRISE PROJECT:- ATC PROJECT DIBRUGARH AIRPORT DRG. DATE 05.09.2023
AN ISO 9001:2015 CERTIFIED SHEET NO 1 OF 2
EPIP, COMPLEX, AMINGAON GHY-31
DRAWN BY B. GOGOI
9435145349(M), [email protected]
CLIENT:- Airport Authority of India, Dibrugarh CHECK BY R. DAS
1. CPRI APPROVED CONTROL PANEL
MANUFACTURER. OWNER:- SCALE(IN MM) 1:200
2. ELECTRICAL CONTRACTOR
3. SSI UNIT UNDER GOVT. OF ASSAM TITLE:- ALL DIMENTION ARE IN MM

Page No.-7