1 2 3 4 5 6

A B C
SECONDARY DISTRIBUTION
LINES OF UTILITY COMPANY
(LINE SIDE) (LOAD SIDE)

SER PROPERTY LINE


VIC
4 (NO ED ENTRANCE CAP
CO CO
RMA ROP
RF R LLY
6 5 NOT
4 EX CEE
CO
DIN
G 30
MET
ERS
)
PRIVATE POLE
A
CO OF CUSTOMER
DRIP LOOP RESIDENTIAL
STANDARD VERT. CLEARANCE OF COPPER WIRES
RIGID STEEL CONDUIT BUILDING
CO
ENTRANCE CAP
3

HEIGHT OF ENTRANCE CAP


CO WH

CO
3.05 METERS ABOVE SIDEWALK
7 CONDUIT STRAPS

3.66 METERS ABOVE RESIDENTIAL

8
7

1
CO
DRIVEWAY
WP

2 5.49 METERS ABOVE DRIVEWAYS, WATT-HOUR


ALLEYS & PUBLIC ROADS METER LIGHTING & POWER
WP PANELBOARD (LPP)
CO CO 7.32 METERS ABOVE NATIONAL
HIGHWAYS ENTRANCE ELL

GROUNDING WIRE
CONNECTED TO WATER
CO (SIDEWALK, DRIVEWAY, ALLEY, PIPE
PUBLIC ROAD OR HIGHWAYS)
1 CO

RIGID STEEL
CONDUIT (RSC)

03 SERVICE ENTRANCE
01 GROUND FLOOR POWER LAYOUT E 2 SCALE NTS

E 2 SCALE NTS

COMPUTATION AND LOAD SCHEDULE


A B C
NO. OF LOADS
CIRCUIT BREAKER
CKT NO. LOAD DESCRIPTION DEMAND LOAD (VA) VOLTAGE (V) CURRENT (I) TOTAL (I) PER CKT NO. WIRE SIZE WIRE PROTECTION
RATING
LO CO

45 W - RECESSED PINLIGHT 7 394 230 1.71


1 2.53 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
15 W - DOWNLIGHT 10 188 230 0.82

45 W - RECESSED PINLIGHT 4 225 230 0.98


4 CO CO 2 15 W - DOWNLIGHT 14 263 230 1.14 2.45 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
14
20 W - WALL-MOUNTED LIGHT 3 75 230 0.33
18

DUPLEX TYPE CONVENIENCE OUTLET 10 2500 230 10.87


CO CO CO
3 15.22 20 AMPS 2 - 3.5 MM² THWN WIRE STRANDED 15 MM Ø PVC
WEATHER PROOF DUPLEX
4 1000 230 4.35
CONVENIENCE OUTLET

4 RANGE 1 2250 230 9.78 9.78 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
WH
CO CO 15 5 REF 1 1565 230 6.80 6.80 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC

3 CO 13 6 WATER HEATER 1 2000 230 8.70 8.70 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
CO
10

11

12

13

14

15
9

7 SPARE 230

8 SPARE 230
8
7

16 15 W - DOWNLIGHT 11 207 230 0.90


CO 9 2.13 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
CO WH 45 W - RECESSED PINLIGHT 5 282 230 1.23
2 WP
CO CO 60 W - PENDANT LIGHT 1 125 230 0.54

10 3.24 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC


45 W - RECESSED PINLIGHT 6 338 230 1.47

15 W - DOWNLIGHT 15 282 230 1.23


17
CO WP DUPLEX TYPE CONVENIENCE OUTLET 14 3500 230 15.22
11 17.39 30 AMPS 2 - 5.5 MM² THWN WIRE STRANDED 15 MM Ø PVC
WEATHER PROOF DUPLEX
2 500 230 2.17
CONVENIENCE OUTLET

12 1.5 HP - ACU 1 1400 230 6.09 6.09 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC
CO
1 13 WATER HEATER 1 2000 230 8.67 8.67 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC

14 WATER HEATER 1 2000 230 8.67 8.67 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC

15 1.5 HP - ACU 1 1400 230 6.07 6.07 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC

16 1.5 HP - ACU 1 1400 230 6.07 6.07 15 AMPS 2 - 2.0 MM² THWN WIRE STRANDED 15 MM Ø PVC

17 SPARE 1 230

02 SECOND FLOOR POWER LAYOUT 18 SPARE

TOTAL
1

23894
230

TOTAL CONNECTED LOAD = 23894 VA I@85% DF


E 2 I =[ 23894 VA / 230 V ] (0.85) = 88.30 AMPS
SIZE OF FEEDER: 2 - 38 MM² THWN IN 32 MM Ø PVC FEEDER CIRCUIT PROTECTION: 125 A, 2 POLES, 230 V

STUDENT'S NAME: PROFESSOR: SUBJECT / TIME: PROJECT TITLE: SHEET CONTENT/S: DRAWING NO.

BCE 413L / 8:00 - 10:00 M


PROPOSED TWO (2) STOREY E-2
YVAN ROSS R. ACLARACION ENGR. GEFFREN BERNARDO RESIDENTIAL BUILDING POWER LAYOUT
1511 (CODE) -SHEET NO.-
& KARL ANGELO A. UY LOCATION:
TIGBAWAN, PIGCAWAYAN, NORTH COTABATO 24 OF 25