Simatic Smart s7 -200 & VFD-M

“Modbus RTU

VFD-M Parameters Setting


+Pr00: 03 ( Control Frequency via RS-485 )
+Pr01: 04 ( Control Motor via RS-485)
+Pr88: 01 ( Slave Address)
+Pr89: 01 ( 9600bps)
+Pr92: 04 ( 8bit/1bit/Event)
+Pr157: 01 ( Modbus- RTU
RESISTOR FOR MOTOR CONTROL

SMART S7-200 Holding Registers Address =


“VFD Address (Dec) + 40001“
+ VFD Control Address = 2000 (hex) + 40001 = 8192 (dec) +
40001 = 48193 (dec)
• Set Word “48193” = 18 (dec): Forward Run
• Set Word “48193” = 34 (dec): Reverse Run
• Set Word “48193” = 1 (dec): Stop
+ Frequency Setting Address = 2001 (hex) + 40001= 8193
(dec) + 40001 = 48194 (dec)
REGISTER FOR DATA MONITORING

+Output Frequency = 2103 (Hex) To ( Dec) Conversion


+40001
+Output Current = 2104 (Hex) To ( Dec) Conversion
+40001
+DC-BUS Voltage = 2105 (Hex) To ( Dec) Conversion
+40001
+Output Voltage = 2106 (Hex) To ( Dec) Conversion
+40001

SIMENS S7 200 SMART & DELTA –


M VFD
Modbus Configuration
PLC PROGRAMING
+Modbus Configuration

+Modbus Control Configuration


Write Frequency Data

Write Motor Data


Read/ write Data