Simatic Smart s7 -200 & VFD-M
“Modbus RTU
VFD-M Parameters Setting
+Pr00: 03 ( Control Frequency via RS-485 ) +Pr01: 04 ( Control Motor via RS-485) +Pr88: 01 ( Slave Address) +Pr89: 01 ( 9600bps) +Pr92: 04 ( 8bit/1bit/Event) +Pr157: 01 ( Modbus- RTU RESISTOR FOR MOTOR CONTROL
SMART S7-200 Holding Registers Address =
“VFD Address (Dec) + 40001“ + VFD Control Address = 2000 (hex) + 40001 = 8192 (dec) + 40001 = 48193 (dec) • Set Word “48193” = 18 (dec): Forward Run • Set Word “48193” = 34 (dec): Reverse Run • Set Word “48193” = 1 (dec): Stop + Frequency Setting Address = 2001 (hex) + 40001= 8193 (dec) + 40001 = 48194 (dec) REGISTER FOR DATA MONITORING
+Output Frequency = 2103 (Hex) To ( Dec) Conversion
+40001 +Output Current = 2104 (Hex) To ( Dec) Conversion +40001 +DC-BUS Voltage = 2105 (Hex) To ( Dec) Conversion +40001 +Output Voltage = 2106 (Hex) To ( Dec) Conversion +40001
SIMENS S7 200 SMART & DELTA –
M VFD Modbus Configuration PLC PROGRAMING +Modbus Configuration