Module
Module
NORMALLY OPEN
INPUT MODULE
The addressable normally open contact input devices provides the is detected the module communicates the trouble condition to MCU
system with an ability to interface with normally open contact type or SCU. When a short circuit occurs on the IDC the module treats
devices. The module supervises its Initiating Device Circuit (IDC) that this as an activated condition. If the module has been programmed for
is connected to any normally open contact which closes to signal a detecting alarm condition, the module activation condition remains
status change. The status change can be alarm, supervisory or trouble active at FACP until the system is reset. If the module has been
condition that needs to be monitored by the system. The module is programmed for detecting supervisory or trouble condition, the module
connected to addressable Signal Line Circuit (SLC) loop of Main activation condition is cleared when the contact type device on IDC is
Control Unit (MCU) and/or Sub Control Unit (SCU). The module reset to normal condition.
supports NFPA Style 4, 6, and 7 wiring methods for the SLC. The The module contains two status indicators (LEDs): one red and one
module receives its operating power from the SLC and provides the green. The green LED indicates normal monitoring operation of the
IDC supervision and activation detection functions associated with module when flashing. When a status change condition is detected on
contact type devices. The module supports both NFPA Style B and the IDC the green LED extinguishes and the red LED begins flashing.
D for Initiating Device Circuit (IDC). The module uses an electronic When the status change is cleared (reset to normal) the red LED turns
address setting method that eliminates any mechanical switches. off and the green LED resumes flashing. The module informs MCU or
The module supervises the voltage of its IDC. When an open circuit SCU of the status change when it is cleared to normal.
Specifications
Item Specification
Rated voltage range of SLC input power 7.8 to 30.7 VDC
Maximum SLC 24 VDC standby current 310 µA
Maximum SLC 24 VDC alarm current 310 µA
Applicable SLC wiring style NFPA Styles 4, 6, and 7
Maximum wiring resistance of IDC circuit 50 ohms
IDC input circuit wiring style NFPA Style B and D
End-of-line resistor for IDC 56 K, 1/4W
Operating temperature range 32°F to 120°F (0°C to 49°C)
Operating humidity range 0 to 93% (Non-condensing)
Maximum no. of module per loop 255 units
Dimensions 94mm (3.7”) (H) x 45mm (1.77”) (W) x 39mm (1.54”) (D)
Applicable electrical box installation 21/2” (64mm) deep single gang box
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MKT. #8902012 - REV A PAGE 1 OF 2
7/07
FRR01UA-DA
NORMALLY OPEN
INPUT MODULE
Installation and Wiring Information
Notes
• These instructions are not intended to cover all the details or variations in the equipment described, nor provide for every possible installation,
operation, or maintenance.
• Specifications are subject to change without notice. Contact Potter Technical Support for further guidance.
• Actual performance is based on proper installation of the product by a qualified installer.
• If further information is needed which is not covered sufficiently in the literature, please contact Potter or a distributor in your area.