Air System Sizing Summary for Chiller system

Project Name: Train 12/10/2024


Prepared by: sayed rafeek 11:12?

Air System Information


Air System Name ................................ Chiller system Number of zones .......................................................... 3
Equipment Class .......................................... CW AHU Floor Area .............................................................. 850.3 ft²
Air System Type .................................................. VAV Location .................................................. Damitta, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing .................... Peak zone sensible load
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 5.6 Tons Load occurs at .................................................. Jul 1500
Total coil load ....................................................... 67.0 MBH OA DB / WB .................................................. 109.4 / 71.6 °F
Sensible coil load .................................................. 56.5 MBH Entering DB / WB ........................................... 87.5 / 65.7 °F
Coil CFM at Jul 1500 ........................................... 1469 CFM Leaving DB / WB ........................................... 51.4 / 49.5 °F
Max block CFM at Aug 1500 ................................ 1683 CFM Coil ADP .................................................................. 47.4 °F
Sum of peak zone CFM ....................................... 1706 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.844 Resulting RH .............................................................. 42 %
ft²/Ton ................................................................. 152.4 Design supply temp. ................................................ 53.6 °F
BTU/(hr-ft²) ........................................................... 78.7 Zone T-stat Check ................................................. 3 of 3 OK
Water flow @ 18.0 °F rise ..................................... 7.44 gpm Max zone temperature deviation ................................ 0.0 °F

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM at Aug 1500 .............................. 1683 CFM Fan motor BHP ........................................................ 0.65 BHP
Standard CFM ..................................................... 1660 CFM Fan motor kW .......................................................... 0.51 kW
Actual max CFM/ft² ............................................... 1.98 CFM/ft² Fan static ................................................................. 1.41 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 162 CFM CFM/person ............................................................. 6.75 CFM/person
CFM/ft² ................................................................. 0.19 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 7


Zone Sizing Summary for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

Air System Information


Air System Name ................................ Chiller system Number of zones .......................................................... 3
Equipment Class .......................................... CW AHU Floor Area .............................................................. 850.3 ft²
Air System Type .................................................. VAV Location .................................................. Damitta, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing .................... Peak zone sensible load
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 16.3 707 71 Jul 1300 3.9 279.8 2.53
Zone 2 8.1 353 35 Jul 1300 2.0 139.9 2.53
Zone 3 12.9 561 56 Aug 1500 2.2 430.6 1.30

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
01-01-Room 1 8.1 Jul 1300 353 2.0 139.9 2.53
01-02-Room 1 8.1 Jul 1300 353 2.0 139.9 2.53
Zone 2
01-03-Room 1 8.1 Jul 1300 353 2.0 139.9 2.53
Zone 3
01-04-Room 1 12.9 Aug 1500 561 2.2 430.6 1.30

Hourly Analysis Program v4.90 Page 2 of 7


Ventilation Sizing Summary for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................. 162 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
01-01-Room 1 139.9 6.0 353.3 0.00 0.00 0.0 10.0 35.3
01-02-Room 1 139.9 6.0 353.3 0.00 0.00 0.0 10.0 35.3
Zone 2
01-03-Room 1 139.9 6.0 353.3 0.00 0.00 0.0 10.0 35.3
Zone 3
01-04-Room 1 430.6 6.0 561.0 0.00 0.00 0.0 10.0 56.1
Totals (incl. Space Multipliers) 1620.9 162.1

Hourly Analysis Program v4.90 Page 3 of 7


Air System Design Load Summary for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 109.4 °F / 71.6 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 22 ft² 1068 - 22 ft² - -
Wall Transmission 110 ft² 1323 - 110 ft² 1005 -
Roof Transmission 560 ft² 5327 - 560 ft² 6007 -
Window Transmission 22 ft² 379 - 22 ft² 316 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 431 ft² 2374 - 431 ft² 0 -
Partitions 30 ft² 249 - 30 ft² 0 -
Ceiling 650 ft² 3528 - 650 ft² 0 -
Overhead Lighting 536 W 1163 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 288 W 943 - 0 0 -
People 22 5645 9828 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 11430 0 - 0 0
Safety Factor 10% / 10% 3343 983 10% 733 0
>> Total Zone Loads - 36773 10811 - 8061 0
Zone Conditioning - 36512 10811 - -1148 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 70% 12429 - 0 0 -
Plenum Lighting Load 30% 548 - 0 0 -
Return Fan Load 1469 CFM 0 - 171 CFM 0 -
Ventilation Load 141 CFM 3649 -387 32 CFM 519 0
Supply Fan Load 1469 CFM 1550 - 171 CFM -476 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 1839 - 5% 403 -
>> Total System Loads - 56528 10424 - -702 0
Central Cooling Coil - 56528 10426 - -702 0
Preheat Coil - 0 - - 0 -
>> Total Conditioning - 56528 10426 - -702 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 7


System Psychrometrics for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 109.4 0.00815 141 400 3649 -387
Vent - Return Mixing Outlet 87.5 0.00868 1469 2849 - -
Preheat Coil Outlet 87.5 0.00868 1469 2849 0 -
Central Cooling Coil Outlet 51.4 0.00716 1469 2849 56528 10426
Supply Fan Outlet 52.4 0.00716 1469 2849 1550 -
Cold Supply Duct Outlet 53.6 0.00716 1395 2849 - -
Zone Air - 78.2 0.00882 1395 3125 36512 10811
Return Plenum Outlet 86.9 0.00882 1395 3125 12978 -
Duct Leakage Air Outlet 52.4 0.00716 73 2849 - -
Return Duct Outlet 85.2 0.00874 1469 3110 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.065 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4681.7 BTU/(hr-CFM)
Site Altitude = 380.6 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 16011 Cooling 15800 78.1 604 3173 0 0
Zone 2 8005 Cooling 7864 78.1 301 3174 0 0
Zone 3 12757 Cooling 12848 78.2 490 3036 0 0

Hourly Analysis Program v4.90 Page 5 of 7


System Psychrometrics for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 45.0 0.00320 32 400 -519 0
Vent - Return Mixing Outlet 57.2 0.00320 171 439 - -
Preheat Coil Outlet 57.2 0.00320 171 439 0 -
Central Cooling Coil Outlet 53.3 0.00320 171 439 702 0
Supply Fan Outlet 55.9 0.00320 171 439 476 -
Cold Supply Duct Outlet 53.6 0.00320 162 439 - -
Zone Air - 60.2 0.00320 162 449 1148 0
Return Plenum Outlet 60.2 0.00320 162 449 0 -
Duct Leakage Air Outlet 55.9 0.00320 9 439 - -
Return Duct Outlet 60.0 0.00320 171 449 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.065 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4681.7 BTU/(hr-CFM)
Site Altitude = 380.6 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3907 Deadband 411 59.1 71 449 0 0
Zone 2 -1953 Deadband 193 58.7 35 449 0 0
Zone 3 -2201 Deadband 545 62.7 56 449 0 0

Hourly Analysis Program v4.90 Page 6 of 7


Psychrometric Analysis for Chiller system
Project Name: Train 12/10/2024
Prepared by: sayed rafeek 11:12?

Location: Damitta, Egypt


Altitude: 380.6 ft.
Data for: July DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Room Air
7. Return Plenum Outlet
8. Return Duct Outlet 0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010
6 8 72
1
34 5 0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100 110
Temperature ( °F )

Hourly Analysis Program v4.90 Page 7 of 7