Transformers
Transformers
TRANSFORMERS
1. STEP-UP Transformer
- the secondary side has more
windings than the primary side
2. STEP-DOWN Transformer
- the primary side has more
windings than the secondary side
Types of Transformers
According to Size & Purpose 2. Distribution Transformers
1. Power Transformers - steps down the voltage level from
- transformers used in distribution lines to customers
large power distribution
and transmission lines
Types of Transformers
According to Size & Purpose
3. Instrument Transformers
- used for metering (energy billing and
transactions and protection control)
Working Principle
Transformer works on Faraday's
law of mutual induction. Faraday's
law of electromagnetic induction states
that, when a change takes place in the
magnetic flux which is linked with a
circuit, an electromotive force will be
induce in the circuit.
Food for thoughts!
✓ No secondary voltage
A. 3780 V C. 3590 V
B. 3945 V D. 3850 V
Answer: A
Sample Problem 2
❖ The maximum flux density in the core of a 3000/240 V, 50-Hz
single-phase transformer is 1.25 tesla. If the voltage induced
per turn is 8 volts, determine the cross sectional area of the
core in cm^2.
A. 292 C. 288
B. 375 D. 362
Answer: C
Sample Problem 3
❖ Calculate the total magnetic flux in a 60-cycle transformer
in which the induced emf per turn is equal to 2 V.
Answer: D
Sample Problem 4
❖ The maximum flux density in the core of a 250/3000-volts, 50-Hz
single-phase transformer is 1.2 T. If the emf per turn is 8 volts,
determine:
Answer: 10.4 V
Ideal Transformer
A transformer is ideal if: Transformation Ratios:
✓ No power loss
✓ No magnetic flux leakage
✓ Infinite permeability of the core
A. 10 A C. 20 A
B. 12 A D. 15 A
Answer:
Sample Problem 7
❖ A single-phase transformer is rated 4160 V primary and 250 V
secondary. It has 1500 turns in the primary and a voltage
regulation of 8 %. What should be the number of turns in the
secondary winding?
A. 88 turns C. 90 turns
B. 92 turns D. 86 turns
Answer:
Sample Problem 8
❖ A 25 kVA, single-phase transformer has 250 turns on the primary
and 40 turns on the secondary winding. The primary is connected
to 1500 volt, 50 Hz mains. Calculate:
V1 ≠ E1 & V2 ≠ E2
Shifting Parameters
Secondary to Primary:
Shifting Parameters
Primary To Secondary:
Sample Problem 11
❖ A 30-kVA, 2400/120-V, 50-Hz transformer has a high voltage
winding resistance of 0.1 ohm and a leakage reactance of 0.22
ohm. The low voltage winding resistance is 0.035 ohm and the
leakage reactance is 0.012 ohm. Find the equivalent winding
resistance, reactance and impedance referred to the (i) high
voltage side and (ii) the low voltage side
A. 2450 V C. 2496 V
B. 2572 V D. 2632 V
Answer: C
Sample Problem 13
❖ A 10-kVA, 2000/400 V, single-phase distribution transformer
has a primary and secondary winding impedances of (5+j10)
and (0.2+j0.45) Ω, respectively. Calculate the voltage across
the secondary terminals at full-load, 80 % power factor lagging,
when the primary is supplied with 2,000 volts?
A. 400 V C. 385 V
B. 394 V D. 379 V
Answer: D
Power Loss in Transformer
Due to winding resistances
Due to alternating
magnetizic force
Deterioration of
insulations such as oil
A. 703.5 W C. 863.6 W
B. 942.6 W D. 874.7 W
Answer: C
Sample Problem 15
❖ The eddy current and hysteresis losses of a 4,400-V, 60-Hz,
single-phase distribution transformer are 280 and 560 watts,
respectively. Determine the core loss when the transformer is
connected across a 4,600-volt, 50-Hz source.
A. 977 W C. 994 W
B. 983 W D. 967 W
Answer: A
Tests on Transformers
1. Open-Circuit (OC) Test
- The voltmeter, ammeter and
wattmeter are all connected on the
low-voltage side of the transformer,
which is supplied at rated voltage
(V1). The secondary winding side is
left open, so which a small amount of
current(I0) is flowing in primary
winding. Here, I0 is called as no - load
current.
A. 5.29 % C. 5.50 %
B. 4.93 % D. 5.13 %
Answer: C
Sample Problem 17
❖ A short circuit test was performed upon a 10-kVA, 2300/230
volt transformer with the following results: Esc = 137 volts,
Psc = 192 W, Isc = 4.34 A. Calculate the primary terms the
reactance of the transformer.
Answer: B
Sample Problem 18
❖ The following data were obtained when a short circuit test was
performed upon a 100 kVA, 2400/240 volts distribution transformer:
Esc = 72 volts, Isc = 41.6 A, Psc = 1,180 W. All instruments are on
the high side during the short circuit test. Calculate the equivalent
resistance and reactance of the transformer.
Answer: A
Sample Problem 19
❖ The following data were obtained when a short circuit test was
performed upon a 100 kVA, 2400/240 volts distribution transformer:
Esc = 72 volts, Isc = 41.6 A, Psc = 1,180 W. All instruments are on
the high side during the short circuit test. Calculate the percent
regulation at a power factor of 0.75 lagging.
A. 2.54 % C. 2.62 %
B. 2.86 % D. 2.71 %
Answer: D
Sample Problem 20
❖ A 200-kVA transformer with impedance of 5 % and the power
factor of the load is 85 %. The primary voltage is 6,000 volts
while the copper loss is 5 kW. Find the percent regulation.
A. 5.03 % C. 4.43 %
B. 5.21 % D. 4.03 %
Answer: C
Transformer Efficiency
NOTE:
A. 97.55 % C. 98.45 %
B. 98.69 % D. 97.80 %
Answer: B
Sample Problem 22
❖ The full-load copper loss of a 75 kVA, single-phase transformer is
thrice the iron losses. At half-load unity pf, the efficiency is 97 %.
Determine the full-load efficiency at 0.8 pf lagging.
A. 95.77 % C. 94.78 %
B. 98.45 % D. 97.86 %
Answer: A
Sample Problem 23
❖ Given that full load copper losses are exactly twice the iron
losses in a 50-kVA transformer, and that the quarter load
efficiency at unity pf is 96.5 %. Calculate the full load
efficiency at unity power factor.
A. 97.48 % C. 97.64 %
B. 98.12 % D. 96.25 %
Answer: C
Sample Problem 24
❖ A 15-kVA, 2300/230-V transformer is under test. With the low side
supplied with rated voltage and the high side open circuited, input
power through a wattmeter reads 245 W. With the high side supplied
with 65 V while the low side short circuited, input power at rated
current reads 350 W. Determine the maximum efficiency that can be
expected from this transformer at unity pf.
A. 97.29 % C. 97.83 %
B. 96.25 % D. 98.21 %
Answer: B
Sample Problem 25
❖ A 10-kVA, 2300/230 V transformer has an equivalent
resistance referred to the secondary winding of 0.05 ohm.
The core loss of this transformer is 75 W. At what kVA load
will this transformer operate at maximum efficiency?
Answer: D
Sample Problem 26
❖ The core loss of a 5-kVA single-phase transformer with normal
voltage applied to the primary is 75 watts. The maximum efficiency
occurs at 60 % of full load kVA. What is the full load efficiency of the
transformer at 0.80 power factor?
A. 95.16 % C. 89.52 %
B. 93.38 % D. 91.36 %
Answer: B
All-Day Efficiency
Sample Problem 27
❖ The full load copper loss and iron loss of a 75 kVA transformer are
each equal to 1 kW. During a given day, the transformer is loaded
as follows: full load at unity pf for 8 hours, one-half load at unity pf
for 8 hrs and no-load the rest of the day. Calculate the all-day
efficiency.
A. 96.36 % C. 96.47 %
B. 97.23 % D. 98.32 %
Answer: A
Sample Problem 28
❖ A 25-kVA distribution transformer operates at 20 % overload, 0.3 pf
lagging for 1 hr; at full load, 0.9 lagging pf for 3 hrs; 50 % load at
unity pf for 8 hrs and 10 % load at 0.8 leading pf for the rest of the
day. If the core loss is 150 watts and full load copper loss is 500 W,
what is the all-day efficiency of the transformer?
A. 94.23 % C. 97.14 %
B. 92.86 % D. 96.68 %
Answer: D
Parallel Operation of Transformers
Conditions for Parallel Operation
of Transformers
A. 78, 97 C. 80, 95
B. 76, 99 D. 75, 100
Answer: B
Sample Problem 30
❖ A 500-kVA, single-phase transformer “A” with percentage
impedance of 0.01+j0.05 is connected in parallel with a 250-kVA
transformer “B” with a percentage impedance of 0.015+j0.04. If the
transformers are serving a single-phase load rated 800-kVA, 80 %
lagging pf, determine the operating pf of each transformer.
Answer: C
Three-Phase Transformers (Banking)
1. Delta-delta
Three-Phase Transformers (Banking)
2. Wye-wye
Three-Phase Transformers (Banking)
3. Delta-Wye
Three-Phase Transformers (Banking)
4. Wye-Delta
Sample Problem 31
❖ A balanced 3-phase transformer bank has delta-connected primary
and wye-connected secondary windings. The primary to secondary
winding voltage ratio is 2400/277. Solve for the primary line current
if the low side (secondary) load draws a line current of 1000 A.
A. 200 A C. 150 A
B. 115 A D. 175 A
Answer: A
Sample Problem 32
❖ A three-phase, 150 kVA, 4160-V, 0.8 lagging pf load is to be
supplied by three single-phase transformers having a turns ratio of 2.
Calculate the current that flows in the primary windings if the
transformers are connected delta-delta.
A. 10.41 A C. 20.82 A
B. 6.01 A D. 12.02 A
Answer: B
Sample Problem 33
❖ What should be the turns ratio of a three-phase transformer to
transform 10,000 kVA from 230 kV to 4160 V if the transformer is to
be connected delta-wye?
A. 94 C. 96
B. 98 D. 97
Answer: C
Sample Problem 34
❖ A bank of three 50:1 single-phase transformers connected wye-delta
is used to step down the HV transmission line rated 13,800 kV.
Determine the magnitude of the stepdown voltage
A. 126 kV C. 138.55 kV
B. 6.90 kV D. 159.35 kV
Answer: D
Sample Problem 35
❖ The potential transformer of a line has a ratio of 132,000/66. These
are connected wye-delta. The voltmeter reads 64 volts. What is the
voltage of the line?
A. 221.7 kV C. 135.2 kV
B. 112.5 kV D. 132 kV
Answer: A
Open-Delta (V-V) Bank Transformers
Sample Problem 36
❖ A V or open-delta connected transformer bank, composed of two
identical units serves a balanced 3-phase load of 16 kVA at 230
volts. Solve for the minimum size in kVA of the transformers needed.
A. 8 kVA C. 16 kVA
B. 9.24 kVA D. 8.25 kVA
Answer: B
Sample Problem 37
❖ Two single-phase distribution transformers are banked in V (open-
delta). If each transformer is rated 37.5 kVA, solve for the maximum
3-phase load that the bank can carry without overloading,
considering that the load has a power factor of 0.85 lagging.
A. 52.5 kW C. 53.6 kW
B. 49.5 kW D. 55.2 kW
Answer: D
Sample Problem 38
❖ Two single-phase distribution transformers, connected in open-delta
will supply power to a 200 hp, 3-phase induction motor, operating at
0.70 power factor and 0.90 efficiency. Solve for the minimum size in
kVA of each transformer needed to supply the power without being
overloaded?
Answer: A
Sample Problem 39
❖ Three single-phase transformers each rated 75 kVA are banked in
delta and supplying a 3-ph load drawing 160 kVA at 0.8 lagging pf.
If one transformer is removed for repairs, solve for the amount of
overloading of the remaining units.
A. 30 kVA C. 20 kVA
B. 10 kVA D. 25 kVA
Answer: A
Auto-Transformer
A. 30 A C. 50 A
B. 40 A D. 10 A
Answer: D
Sample Problem 42
❖ The two windings of a 10-kVA, 2300/230 volt, distribution transformer
is connected in series to form an autotransformer giving a small
reduction to potential difference from a 2300 volt line. Determine its
new kVA rating as an ideal autotransformer.
Answer: B