q172 & q173dcpu manual
q172 & q173dcpu manual
q172 & q173dcpu manual
Motion Controllers
User's Manual
Q173DCPU
Q172DCPU
01 01 2008
B(NA)-0300133 MITSUBISHI ELECTRIC INDUSTRIAL AUTOMATION
Version A
SAFETY PRECAUTIONS
(Please read these instructions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual
carefully and pay full attention to safety to handle the product correctly.
These precautions apply only to this product. Refer to the Users manual of the QCPU module to use for a
description of the PLC system safety precautions.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
Please save this manual to make it accessible when required and always forward it to the end user.
A-1
For Safe Operations
1. Prevention of electric shocks
DANGER
Never open the front case or terminal covers while the power is ON or the unit is running, as this
may lead to electric shocks.
Never run the unit with the front case or terminal cover removed. The high voltage terminal and
charged sections will be exposed and may lead to electric shocks.
Never open the front case or terminal cover at times other than wiring work or periodic
inspections even if the power is OFF. The insides of the Motion controller and servo amplifier are
charged and may lead to electric shocks.
Completely turn off the externally supplied power used in the system before mounting or removing the
module, performing wiring work, or inspections. Failing to do so may lead to electric shocks.
When performing wiring work or inspections, turn the power OFF, wait at least ten minutes, and
then check the voltage with a tester, etc.. Failing to do so may lead to electric shocks.
Be sure to ground the Motion controller, servo amplifier and servomotor. (Ground resistance :
100 or less) Do not ground commonly with other devices.
The wiring work and inspections must be done by a qualified technician.
Wire the units after installing the Motion controller, servo amplifier and servomotor. Failing to do
so may lead to electric shocks or damage.
Never operate the switches with wet hands, as this may lead to electric shocks.
Do not damage, apply excessive stress, place heavy things on or sandwich the cables, as this
may lead to electric shocks.
Do not touch the Motion controller, servo amplifier or servomotor terminal blocks while the power
is ON, as this may lead to electric shocks.
Do not touch the built-in power supply, built-in grounding or signal wires of the Motion controller
and servo amplifier, as this may lead to electric shocks.
A-2
3. For injury prevention
CAUTION
Do not apply a voltage other than that specified in the instruction manual on any terminal.
Doing so may lead to destruction or damage.
Do not mistake the terminal connections, as this may lead to destruction or damage.
Do not mistake the polarity ( + / - ), as this may lead to destruction or damage.
Do not touch the heat radiating fins of controller or servo amplifier, regenerative resistor and
servomotor, etc., while the power is ON and for a short time after the power is turned OFF. In this
timing, these parts become very hot and may lead to burns.
Always turn the power OFF before touching the servomotor shaft or coupled machines, as these
parts may lead to injuries.
Do not go near the machine during test operations or during operations such as teaching.
Doing so may lead to injuries.
4. Various precautions
Strictly observe the following precautions.
Mistaken handling of the unit may lead to faults, injuries or electric shocks.
(1) System structure
CAUTION
Always install a leakage breaker on the Motion controller and servo amplifier power source.
If installation of an electromagnetic contactor for power shut off during an error, etc., is specified in
the instruction manual for the servo amplifier, etc., always install the electromagnetic contactor.
Install the emergency stop circuit externally so that the operation can be stopped immediately and
the power shut off.
Use the Motion controller, servo amplifier, servomotor and regenerative resistor with the correct
combinations listed in the instruction manual. Other combinations may lead to fire or faults.
Use the CPU module, base unit and motion module with the correct combinations listed in the
instruction manual. Other combinations may lead to faults.
If safety standards (ex., robot safety rules, etc.,) apply to the system using the Motion controller,
servo amplifier and servomotor, make sure that the safety standards are satisfied.
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in the
system.
In systems where coasting of the servomotor will be a problem during the forced stop, emergency
stop, servo OFF or power supply OFF, use dynamic brakes.
Make sure that the system considers the coasting amount even when using dynamic brakes.
In systems where perpendicular shaft dropping may be a problem during the forced stop,
emergency stop, servo OFF or power supply OFF, use both dynamic brakes and electromagnetic
brakes.
A-3
CAUTION
The dynamic brakes must be used only on errors that cause the forced stop, emergency stop, or
servo OFF. These brakes must not be used for normal braking.
The brakes (electromagnetic brakes) assembled into the servomotor are for holding applications,
and must not be used for normal braking.
The system must have a mechanical allowance so that the machine itself can stop even if the
stroke limits switch is passed through at the max. speed.
Use wires and cables that have a wire diameter, heat resistance and bending resistance
compatible with the system.
Use wires and cables within the length of the range described in the instruction manual.
The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and
servomotor.
Install a cover on the shaft so that the rotary parts of the servomotor are not touched during
operation.
There may be some cases where holding by the electromagnetic brakes is not possible due to the
life or mechanical structure (when the ball screw and servomotor are connected with a timing belt,
etc.). Install a stopping device to ensure safety on the machine side.
A-4
CAUTION
Use the program commands for the program with the conditions specified in the instruction
manual.
Set the sequence function program capacity setting, device capacity, latch validity range, I/O
assignment setting, and validity of continuous operation during error detection to values that are
compatible with the system application. The protective functions may not function if the settings
are incorrect.
Some devices used in the program have fixed applications, so use these with the conditions
specified in the instruction manual.
The input devices and data registers assigned to the link will hold the data previous to when
communication is terminated by an error, etc. Thus, an error correspondence interlock program
specified in the instruction manual must be used.
Use the interlock program specified in the intelligent function module's instruction manual for the
program corresponding to the intelligent function module.
A-5
CAUTION
The Motion controller, servo amplifier and servomotor are precision machines, so do not drop or
apply strong impacts on them.
Securely fix the Motion controller, servo amplifier and servomotor to the machine according to
the instruction manual. If the fixing is insufficient, these may come off during operation.
Always install the servomotor with reduction gears in the designated direction. Failing to do so
may lead to oil leaks.
Store and use the unit in the following environmental conditions.
Conditions
Environment
Motion controller/Servo amplifier Servomotor
Ambient 0°C to +40°C (With no freezing)
According to each instruction manual.
temperature (32°F to +104°F)
80% RH or less
Ambient humidity According to each instruction manual.
(With no dew condensation)
Storage -20°C to +65°C
According to each instruction manual.
temperature (-4°F to +149°F)
Indoors (where not subject to direct sunlight).
Atmosphere
No corrosive gases, flammable gases, oil mist or dust must exist
Altitude 1000m (3280.84ft.) or less above sea level
Vibration According to each instruction manual
When coupling with the synchronous encoder or servomotor shaft end, do not apply impact such
as by hitting with a hammer. Doing so may lead to detector damage.
Do not apply a load larger than the tolerable load onto the synchronous encoder and servomotor
shaft. Doing so may lead to shaft breakage.
When not using the module for a long time, disconnect the power line from the Motion controller
or servo amplifier.
Place the Motion controller and servo amplifier in static electricity preventing vinyl bags and store.
When storing for a long time, please contact with our sales representative.
Also, execute a trial operation.
A-6
(4) Wiring
CAUTION
Correctly and securely wire the wires. Reconfirm the connections for mistakes and the terminal
screws for tightness after wiring. Failing to do so may lead to run away of the servomotor.
After wiring, install the protective covers such as the terminal covers to the original positions.
Do not install a phase advancing capacitor, surge absorber or radio noise filter (option FR-BIF)
on the output side of the servo amplifier.
Correctly connect the output side (terminal U, V, W). Incorrect connections will lead the
servomotor to operate abnormally.
Do not connect a commercial power supply to the servomotor, as this may lead to trouble.
Do not mistake the direction of the surge absorbing diode
installed on the DC relay for the control signal output of brake Servo amplifier
signals, etc. Incorrect installation may lead to signals not being VIN
(24VDC)
output when trouble occurs or the protective functions not
functioning. Control output
RA
Do not connect or disconnect the connection cables between signal
each unit, the encoder cable or PLC expansion cable while the
power is ON.
Securely tighten the cable connector fixing screws and fixing mechanisms. Insufficient fixing may
lead to the cables combing off during operation.
Do not bundle the power line or cables.
A-7
(6) Usage methods
CAUTION
Immediately turn OFF the power if smoke, abnormal sounds or odors are emitted from the Motion
controller, servo amplifier or servomotor.
Always execute a test operation before starting actual operations after the program or
parameters have been changed or after maintenance and inspection.
Do not attempt to disassemble and repair the units excluding a qualified technician whom our
company recognized.
Do not make any modifications to the unit.
Keep the effect or electromagnetic obstacles to a minimum by installing a noise filter or by using
wire shields, etc. Electromagnetic obstacles may affect the electronic devices used near the
Motion controller or servo amplifier.
When using the CE Mark-compliant equipment, refer to the "EMC Installation Guidelines" (data
number IB(NA)-67339) for the Motion controllers and refer to the corresponding EMC guideline
information for the servo amplifiers, inverters and other equipment.
Use the units with the following conditions.
Conditions
Item
Q61P-A1 Q61P-A2 Q61P Q62P Q63P Q64P
+10% +10% +10% +30% +10%
100 to 120VAC 200 to 240VAC 100 to 240VAC 24VDC 100 to 120VAC /
-15% -15% -15% -35% -15%
+10%
Input power 200 to 240VAC -15%
(85 to 132VAC) (170 to 264VAC) (85 to 264VAC) (15.6 to 31.2VDC) (85 to 132VAC/
170 to 264VAC)
Input frequency 50/60Hz ±5%
Tolerable
momentary 20ms or less
power failure
A-8
(7) Corrective actions for errors
CAUTION
If an error occurs in the self diagnosis of the Motion controller or servo amplifier, confirm the
check details according to the instruction manual, and restore the operation.
If a dangerous state is predicted in case of a power failure or product failure, use a servomotor
with electromagnetic brakes or install a brake mechanism externally.
Use a double circuit construction so that the electromagnetic brake operation circuit can be
operated by emergency stop signals set externally.
Shut off with the
Shut off with servo ON signal OFF, emergency stop
alarm, electromagnetic brake signal. signal(EMG).
Servomotor
RA1 EMG
Electro-
magnetic 24VDC
brakes
If an error occurs, remove the cause, secure the safety and then resume operation after alarm
release.
The unit may suddenly resume operation after a power failure is restored, so do not go near the
machine. (Design the machine so that personal safety can be ensured even if the machine
restarts suddenly.)
A-9
CAUTION
When replacing the Motion controller or servo amplifier, always set the new module settings
correctly.
When the Motion controller or absolute value motor has been replaced, carry out a home position
return operation using one of the following methods, otherwise position displacement could occur.
1) After writing the servo data to the Motion controller using programming software, switch on the
power again, then perform a home position return operation.
2) Using the backup function of the programming software, load the data backed up before
replacement.
After maintenance and inspections are completed, confirm that the position detection of the
absolute position detector function is correct.
Do not drop or impact the battery installed to the module.
Doing so may damage the battery, causing battery liquid to leak in the battery. Do not use the
dropped or impacted battery, but dispose of it.
Do not short circuit, charge, overheat, incinerate or disassemble the batteries.
The electrolytic capacitor will generate gas during a fault, so do not place your face near the
Motion controller or servo amplifier.
The electrolytic capacitor and fan will deteriorate. Periodically replace these to prevent secondary
damage from faults. Replacements can be made by our sales representative.
CAUTION
This product is not designed or manufactured to be used in equipment or systems in situations
that can affect or endanger human life.
When considering this product for operation in special applications such as machinery or systems
used in passenger transportation, medical, aerospace, atomic power, electric power, or
submarine repeating applications, please contact your nearest Mitsubishi sales representative.
Although this product was manufactured under conditions of strict quality control, you are strongly
advised to install safety devices to forestall serious accidents when it is used in facilities where a
breakdown in the product is likely to cause a serious accident.
A - 10
REVISIONS
The manual number is given on the bottom left of the back cover.
Print Date Manual Number Revision
Jan., 2008 IB(NA)-0300133-A First edition
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
A - 11
INTRODUCTION
CONTENTS
1. OVERVIEW 1- 1 to 1- 4
1.1 Overview................................................................................................................................................... 1- 1
1.2 Differences between Q173DCPU/Q172DCPU and Q173HCPU/Q172HCPU ...................................... 1- 3
3. DESIGN 3- 1 to 3-16
APPENDIX 1 Cables..................................................................................................................................App- 1
APPENDIX 1.1 SSCNET cables.........................................................................................................App- 1
APPENDIX 1.2 Serial absolute synchronous encoder cable................................................................App- 4
APPENDIX 1.3 Battery cable.................................................................................................................App- 6
APPENDIX 1.4 Forced stop input cable ................................................................................................App- 7
A - 13
APPENDIX 2 Exterior Dimensions ............................................................................................................App- 8
APPENDIX 2.1 CPU module .................................................................................................................App- 8
APPENDIX 2.2 Servo external signals interface module (Q172DLX)..................................................App- 9
APPENDIX 2.3 Synchronous encoder interface module (Q172DEX)..................................................App- 9
APPENDIX 2.4 Manual pulse generator interface module (Q173DPX)...............................................App-10
APPENDIX 2.5 Power supply module (Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P).................App-11
APPENDIX 2.6 Battery holder unit (Q170DBATC) ...............................................................................App-12
APPENDIX 2.7 Connector .....................................................................................................................App-13
APPENDIX 2.8 Manual pulse generator (MR-HDP01) .........................................................................App-16
APPENDIX 2.9 Serial absolute synchronous encoder (Q170ENC) .....................................................App-16
A - 14
About Manuals
Related Manuals
A - 15
(2) PLC
Manual Number
Manual Name
(Model Code)
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
This manual explains the specifications of the QCPU modules, power supply modules, base modules, SH-080483ENG
extension cables, memory card battery and others. (13JR73)
(Optional)
Fully Closed Loop Control MR-J3- B-RJ006 Servo amplifier Instruction Manual
This manual explains the I/O signals, parts names, parameters, start-up procedure and others for Fully SH-030056
Closed Loop Control MR-J3- B-RJ006 Servo amplifier. (1CW304)
(Optional)
A - 16
1 OVERVIEW
1. OVERVIEW
1.1 Overview 1
This User's Manual describes the hardware specifications and handling methods of the
Motion Controller's Model Q173DCPU/Q172DCPU for the Q series PLC Multiple CPU
system.
The Manual also describes those items related to the specifications of the option
module for the Motion controller, Manual pulse generator, Synchronous encoder and
cables.
In this manual, the following abbreviations are used.
Generic term/Abbreviation Description
Q173DCPU/Q172DCPU or
Q173DCPU/Q172DCPU Motion CPU module
Motion CPU (module)
Q172DLX Servo external signals interface module/
Q172DLX/Q172DEX/Q173DPX or (Note-1)
Q172DEX Serial Synchronous encoder interface module /
Motion module
Q173DPX Manual pulse generator interface module
MR-J3- B Servo amplifier model MR-J3- B
AMP or Servo amplifier General name for "Servo amplifier model MR-J3- B"
QCPU, PLC CPU or PLC CPU module QnUD(H)CPU
Multiple CPU system or Motion system Abbreviation for "Multiple PLC system of the Q series"
Abbreviation for "CPU No.n (n= 1 to 4) of the CPU module for the Multiple CPU
CPUn
system"
Self CPU Motion CPU being programmed by the currently open MT Developer project
Programming software package General name for MT Developer/GX Developer/MR Configurator
Operating system software General name for "SW8DNC-SV Q "
Operating system software for conveyor assembly use (Motion SFC) :
SV13
SW8DNC -SV13Q
Operating system software for automatic machinery use (Motion SFC) :
SV22
SW8DNC -SV22Q
Abbreviation for "Motion controller programming software
MT Developer
MT Developer2 (Version 1.00A or later)"
Abbreviation for "MELSEC PLC programming software package
GX Developer
GX Developer (Version 8.48A or later)"
Abbreviation for "Servo setup software package
MR Configurator
MR Configurator (Version C0 or later)"
Manual pulse generator or MR-HDP01 Abbreviation for "Manual pulse generator (MR-HDP01)"
Serial absolute synchronous encoder
Abbreviation for "Serial absolute synchronous encoder (Q170ENC)"
or Q170ENC
(Note-2) High speed synchronous network between Motion controller and servo
SSCNET
amplifier
General name for "system using the servomotor and servo amplifier for
Absolute position system
absolute position"
Battery holder unit Battery holder unit (Q170DBATC)
External battery General name for "Q170DBATC" and "Q6BAT"
Abbreviation for "MELSECNET/H module/Ethernet module/CC-Link module/
Intelligent function module
Serial communication module"
(Note-1) : Q172DEX can be used in SV22.
(Note-2) : SSCNET: Servo System Controller NETwork
1-1
1 OVERVIEW
REMARK
For information about the each module, design method for program and parameter,
refer to the following manuals relevant to each module.
1-2
1 OVERVIEW
1-3
1 OVERVIEW
MEMO
1-4
2 SYSTEM CONFIGURATION
2. SYSTEM CONFIGURATION
This section describes the Q173DCPU/Q172DCPU system configuration, precautions
on use of system and configured equipments.
2
(1) Equipment configuration in Q173DCPU/Q172DCPU system
Extension of the Q series module
(Note-2)
Motion module Main base unit Extension cable Q6 B extension base unit
(Q172DLX, Q172DEX, Q173DPX) (Q38DB, Q312DB) (QC B) (Q63B, Q65B, Q68B, Q612B)
(Note-1)
(Note-1)
MITSUBISHI
LITHIUM BATTERY
Servo amplifier
(MR-J3- B)
2-1
2 SYSTEM CONFIGURATION
2-2
2 SYSTEM CONFIGURATION
interface module
interface module
interface module
Servo external
Manual pulse
Synchronous
generator
encoder
signals
PLC CPU/
Motion CPU
Main base unit
(Q3 DB) Q61P QnUD(H) Q173D QI60 QX Q6 AD Q172D Q172D Q173D
CPU CPU LX EX PX
QY Q6 DA I/O module/
Intelligent function module
100/200VAC
Extension cable
(QC B) SSCNET (CN2) d1 d16 d1 d16
UP to 7 extensions
M M M M
E E E E
2-3
2 SYSTEM CONFIGURATION
CAUTION
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in
the system.
The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and
servomotor.
Set the parameter values to those that are compatible with the Motion controller, servo amplifier,
servomotor and regenerative resistor model and the system application. The protective functions
may not function if the settings are incorrect.
2-4
2 SYSTEM CONFIGURATION
interface module
interface module
interface module
Servo external
Manual pulse
Synchronous
generator
encoder
signals
PLC CPU/
Motion CPU
Main base unit
(Q3 DB) Q61P QnUD(H) Q172D QI60 QX Q6 AD Q172D Q172D Q173D
CPU CPU LX EX PX
QY Q6 DA I/O module /
Intelligent function module
100/200VAC
SSCNET cable
(MR-J3BUS M(-A/-B))
module
Extension cable
(QC B)
SSCNET (CN1) d1 d2 d3 d8
UP to 7 extensions
M M M M
E E E E
2-5
2 SYSTEM CONFIGURATION
CAUTION
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in
the system.
The ratings and characteristics of the parts (other than Motion controller, servo amplifier and
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and
servomotor.
Set the parameter values to those that are compatible with the Motion controller, servo amplifier,
servomotor and regenerative resistor model and the system application. The protective functions
may not function if the settings are incorrect.
2-6
2 SYSTEM CONFIGURATION
(1) Up to 32 axes servo amplifiers per 2 systems (up to 16 axes per 1 system) can be
used in Q173DCPU. Up to 8 axes servo amplifiers per 1 system can be used in
Q172DCPU.
(2) It is possible to set the program which synchronized with the motion operation
cycle and executed at fixed cycle (0.88[ms], 1.77[ms], 3.55[ms], 7.11[ms],
14.2[ms]).
(7) Data exchange between CPU modules is possible by Multiple CPU high speed
transmission memory or automatic refresh in the Multiple CPU system.
2-7
2 SYSTEM CONFIGURATION
(b) Only Multiple CPU high speed main base unit (Q38DB/Q312DB) can be
used.
(e) It takes about 10 seconds to startup (state that can be controlled) of Motion
CPU. Make a Multiple CPU synchronous startup setting suitable for the
system.
(f) Execute the automatic refresh of the Motion CPU modules and PLC CPU
modules (Q03UDCPU/Q04UDHCPU/Q06UDHCPU) by using the automatic
refresh of Multiple CPU high speed transmission area setting.
When the High performance PLC CPU module/Process CPU module/PC
CPU module/C controller module is installed in the combination of Multiple
CPU system, the Motion CPU module cannot be execute the automatic
refresh with these modules.
(g) Use the Motion dedicated PLC instructions that starts by "D(P).". The Motion
dedicated PLC instructions that starts by "S(P)." cannot be used. When the
High performance PLC CPU module/Process CPU module/PC CPU
module/C controller module is installed in the combination of Multiple CPU
system, the Motion dedicated PLC instruction from these modules cannot be
executed.
2-8
2 SYSTEM CONFIGURATION
(e) Be sure to use the Motion CPU as the control CPU of Motion modules
(Note-1)
(Q172DLX, Q172DEX , Q173DPX, etc.) for Motion CPU. They will not
operate correctly if PLC CPU is set and installed as the control CPU by
mistake. Motion CPU is treated as a 32-point intelligent module by PLC
CPU of other CPU.
2-9
2 SYSTEM CONFIGURATION
(c) There are following methods to execute the forced stop input.
• Use a EMI terminal of Motion CPU module
• Use a device set in the forced stop input setting of system setting
(d) Forced stop input for EMI terminal of Motion CPU module cannot be
invalidated by the parameter.
When the device set in the forced stop input setting is used without use of
EMI terminal of Motion CPU module, apply 24VDC voltage on EMI terminal
and invalidate the forced stop input of EMI terminal.
(e) Be sure to use the cable for forced stop input (sold separately). The forced
stop cannot be released without using it.
(f) When the operation cycle is 0.4[ms], set the system setting as the axis select
switch of servo amplifier "0 to 7".
If the axis select switch of servo amplifier "8 to F" is set, the servo amplifiers
are not recognized.
(g) When a Multiple CPU system is configured, make sure to configure the
modules so that the total current consumption of individual modules on the
main base does not exceed the 5VDC output capacity of power supply
module.
(Refer to Section 2.4.2 (3) "Selection of the power supply module".)
(h) It is impossible to mount the main base unit by DIN rail when using the
Motion CPU module.
Doing so could result in vibration that may cause erroneous operation.
(i) The module name displayed by "System monitor" - "Product information list"
of GX Developer is different depending on the function version of Motion
modules (Q172DLX, Q172DEX, Q173DPX).
(Note): Even if the function version "C" is displayed, it does not correspond
to the online module change.
Model display
Module name
Function version "B" Function version "C"
Q172DLX Q172LX Q172DLX
Q172DEX MOTION-UNIT Q172DEX
Q173DPX MOTION-UNIT Q173DPX
2 - 10
2 SYSTEM CONFIGURATION
2 - 11
2 SYSTEM CONFIGURATION
2 - 12
2 SYSTEM CONFIGURATION
(Note-1) : =Cable length (015: 0.15m(0.49ft.), 03: 0.3m(0.98ft.), 05: 0.5m(1.64ft.), 1: 1m(3.28ft.), 2: 2m(6.56ft.),
3: 3m(9.84ft.), 5: 5m(16.40ft.), 10: 10m(32.81ft.), 20: 20m(65.62ft.), 25: 25m(82.02ft.), 30:
30m(98.43ft.), 40: 40m(131.23ft.), 50:50m(164.04ft.)
(Note-2) : 5VDC internal current consumption of shared equipments with PLC might be changed.
Be sure to refer to the PLC Manuals.
(Note-3) : Be sure to use the power supply module within the range of power supply capacity.
(Note-4) : Battery Q6BAT is not attached to Battery holder unit Q170DBATC. Please purchase it separately.
(Note-5) : Be sure to use the cable for forced stop input (sold separately). The forced stop cannot be released
without using it.
Cable for forced stop input is not attached to the Motion CPU module. Please purchase the cable for
length according to system separately.
(Note-6) : These modules can be used in Q172DLX. It cannot be controlled using Q173DPX.
(Note-7) : Please contact your nearest Mitsubishi sales representative for the cable of less than 30m(98.43ft.).
2 - 13
2 SYSTEM CONFIGURATION
(Note-2)
QY42P
64 points(32 points/common), Connector (TYP, All points ON)
Output 12V/24VDC, 0.5A/point, 4A/common, 0.08
QY50
module 16 points(16 points/common), Terminal block (TYP, All points ON)
12V/24VDC, 0.5A/point, 4A/common, 0.08
QY80
Source 16 points(16 points/common), Terminal block (TYP, All points ON)
Type 12V/24VDC, 0.1A/point, 2A/common, 0.095 (Note-2)
QY81P
32 points(32 points/common), Connector (TYP, All points ON)
5/12VDC, 16mA/point, 16 points(16 points/common), 0.095
QY70
TTL•CMOS Terminal block (TYP, All points ON)
(Sink) 5/12VDC, 16mA/point, 32 points(32 points/common), 0.15 (Note-2)
QY71
Connector (TYP, All points ON)
24VDC Positive common: 32 points
DC12-24V/0.1A Output Sink type: 32 points, Connector, 0.13 (Note-2)
QH42P
Provided (Thermal protectors, protector against short (TYP, All points ON)
Input/Output DC Input/
circuit)
composite Transistor
24VDC Positive common: 8 points
module output
DC12-24V/0.5A Output Sink type: 7 points, Terminal block, 0.08
QX48Y57
Provided (When face is broken, LED lights and signal is (TYP, All points ON)
output to CPU)
0.06
Interrupt module QI60 DC24V/4mA, Positive common, 16 points, Terminal block
(TYP, All points ON)
2 - 14
2 SYSTEM CONFIGURATION
Current consumption
Part name Model name Description Remark
5VDC[A] (Note-1)
2ch, A/D conversion, (Note-2)
Q62AD-DGH 0.33
Current input (Channel-isolated • High resolution)
Q64AD 4ch, A/D conversion, Voltage • Current input 0.63
4ch, A/D conversion, (Note-2)
Q64AD-GH 0.89
Voltage • Current input (Channel-isolated • High resolution)
Q68ADV 8ch, A/D conversion, Voltage input 0.64
Analogue module Q68ADI 8ch, A/D conversion, Current input 0.64
Q62DA 2ch, D/A conversion, Voltage • Current output 0.33
2ch, D/A conversion, (Note-2)
Q62DA-FG 0.37
Voltage • Current output (Channel-isolated)
Q64DA 4ch, D/A conversion, Voltage • Current output 0.34
Q68DAV 8ch, D/A conversion, Voltage output 0.39
Q68DAI 8ch, D/A conversion, Current output 0.38
(Note-1) : 5VDC internal current consumption of shared equipments with PLC might be changed.
Be sure to refer to the PLC Manuals.
(Note-2) : Connectors are not provided.
2 - 15
2 SYSTEM CONFIGURATION
2 - 16
2 SYSTEM CONFIGURATION
GX Developer SW8D5C-GPPW-E
MR Configurator MRZJW3-SETUP221E
POINTS
(1) When the operation of Windows is not unclear in the operation of this software,
refer to the manual of Windows or guide-book from the other supplier.
(2) The following functions cannot be used when the computer is running under
R R R
Windows Vista, Windows XP or Windows 2000.
This product may not perform properly, when these functions are used.
R R
< Windows Vista/Windows XP>
R
• Activating the application with Windows compatibility mode
• Fast user switching
• Remote desktop
• Large size
R
• x64 Edition (64 bit Windows )
R
< Windows 2000>
• Large fonts
2 - 17
2 SYSTEM CONFIGURATION
Item Specification
Operating ambient temperature 0 to 55°C (32 to 131°F)
Storage ambient temperature -25 to 75°C (-13 to 167°F) (Note-3)
Operating ambient humidity 5 to 95% RH, non-condensing
Storage ambient humidity 5 to 95% RH, non-condensing
Frequency Acceleration Amplitude Sweep count
0.075mm
Under intermittent 10 to 57Hz ——
(0.003inch) 10 times each
Vibration resistance vibration 2
57 to 150Hz 9.8m/s —— in X, Y, Z
0.035mm directions
Under continuous 10 to 57Hz ——
(0.001inch) (For 80 min.)
vibration 2
57 to 150Hz 4.9m/s ——
2
Shock resistance 147m/s , 3 times in each of 3 directions X, Y, Z
(Note-1) : This indicates the section of the power supply to which the equipment is assumed to be connected between the
public electrical power distribution network and the machinery within premises.
Category applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
(Note-2) : This index indicates the degree to which conductive material is generated in terms of the environment in which
the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing
must be expected occasionally.
(Note-3) : Do not use or store the Motion controller under pressure higher than the atmospheric pressure of altitude 0m.
Doing so can cause an operation failure.
CAUTION
The Motion controller must be stored and used under the conditions listed in the table of
specifications above.
When not using the module for a long time, disconnect the power line from the Motion controller
or servo amplifier.
Place the Motion controller and servo amplifier in static electricity preventing vinyl bags and store.
When storing for a long time, please contact with our sales representative.
Also, execute a trial operation.
2 - 18
2 SYSTEM CONFIGURATION
(1) Q173DCPU/Q172DCPU
Q172DCPU Q173DCPU
1) 1)
F01 F01 F01 F01
SW SW
2) 3) 2) 3)
AB E
AB E
AB E
AB E
23 6
23 6
23 6
23 6
CD
CD
CD
CD
45
45
45
45
1 2 1 2
789 789 789 789
5) 5)
6) 6)
CN1
CN1
7)
CN2
FRONT FRONT
BAT BAT
8) 8)
9)
10)
(Note) 12)
11)
(Note): Unusable
(Under manufacturer test)
2 - 19
2 SYSTEM CONFIGURATION
6) SSCNET CN1 connector (Note-2) Connector to connect the servo amplifier of system 1 (up to 16 axes)
SSCNET CN2 connector
7) Connector to connect the servo amplifier of system 2 (up to 16 axes)
(Note-2), (Note-3)
8) Module loading lever Used to install the module to the base unit
9) Module fixing hook (Note-4) Hook used to fix the module to the base unit. (Auxiliary use for installation)
10) Module fixing screw Screw used to fix to the base unit. (M3×13)
11) Module fixing latch Hook used to fix to the base unit.
12) Battery connector (BAT) (Note-5) Connector to connect the battery holder unit Q170DBATC
(Note-1) : Be sure to use the cable for forced stop input. The forced stop cannot be released without using it.
If the cable for forced stop input is fabricated on the customer side, make it within 30m(98.43ft.).
(Note-2) : Put the SSCNET cable in the duct or fix the cable at the closest part to the Motion CPU module with bundle
material in order to prevent SSCNET cable from putting its own weight on SSCNET connector.
(Note-3) : Q173DCPU only
(Note-4) : This screw is auxiliary use for module installation to the main base unit. Be sure to fix modules to the main base
unit using supplied fixing screws.
(Note-5) : Be sure to use the external battery. The programs, parameters, absolute position data, and latch data of SRAM
built-in Motion CPU module are backed up if the battery cable is not set correctly.
2 - 20
2 SYSTEM CONFIGURATION
2 - 21
2 SYSTEM CONFIGURATION
POINTS
(1) An error is displayed at the 7-segment LED, confirm the error number etc. using
MT Developer.
(2) Refer to the Motion CPU error batch monitor of MT Developer or error list of
Programming Manual for error details.
4 56
78 9
6 Mode operated by ROM parameters wrote to the FLASH ROM built-in
Motion CPU module.
C SRAM clear SRAM "0" clear
(Note): Not to be set except above setting.
CAUTION
Be sure to turn OFF the Multiple system power supply before the rotary switch setting change.
2 - 22
2 SYSTEM CONFIGURATION
POINTS
Be sure to turn OFF the Multiple system power supply before the rotary switch
setting change.
2 - 23
2 SYSTEM CONFIGURATION
2 - 24
2 SYSTEM CONFIGURATION
2 - 25
2 SYSTEM CONFIGURATION
2 - 26
2 SYSTEM CONFIGURATION
2 - 27
2 SYSTEM CONFIGURATION
2 - 28
2 SYSTEM CONFIGURATION
POINTS
(Note-1) : Overcurrent protection
The overcurrent protection device shuts off the 5V, 24VDC circuit and
stops the system if the current flowing in the circuit exceeds the specified
value.
The LED of the power supply module is turned off or lights up in dim
green when voltage is lowered. If this device is activated, switch the
input power supply off and eliminate the cause such as insufficient
current capacity or short. Then, a few minutes later, switch it on to restart
the system.
The initial start for the system takes place when the current value
becomes normal.
2 - 29
2 SYSTEM CONFIGURATION
POINTS
(Note-3) : Allowable momentary power failure period
(1) For AC input power supply
(a) An instantaneous power failure lasting less than 20ms will cause
AC down to be detected, but operation will continue.
(b) An instantaneous power failure lasting in excess of 20ms may
cause the operation to continue or initial start to take place
depending on the power supply load.
Further, when the AC supply of the AC input module is the same
as that of the power supply module, it prevents the sensor
connected to the AC input module, which is ON at power-off,
from turning OFF by switching off the power supply.
However, if only the AC input module is connected to the AC line,
which is connected to the power supply, detection of the AC
down for the power supply module may be delayed by the
capacitor in the AC input module. Thus, connect a load of
approx. 30mA per AC input module to the AC line.
(2) For DC input power supply
(Note)
(a) An instantaneous power failure lasting less than 10ms will
cause 24VDC down to be detected, but operation will continue.
(Note)
(b) An instantaneous power failure lasting in excess of 10ms
may cause the operation to continue or initial start to take place
depending on the power supply load.
(Note) : This is for a 24VDC input. This is 10ms or less for less
then 24VDC.
2 - 30
2 SYSTEM CONFIGURATION
9) 1)
Q62P POWER 8)
INPUT
100-240VAC
50/60Hz 105VA
OUTPUT 5VDC 3A 24VDC 0.6A
6) ERR.
+24V 2)
L
(Q62P only) 24G
+ -
24VDC 0.5A
(FG) 3)
(LG) 4)
INPUT N 5)
100-240VAC
L
Q62P
10) 7)
2 - 31
2 SYSTEM CONFIGURATION
2 - 32
2 SYSTEM CONFIGURATION
POINTS
(1) The Q61P-A1 is dedicated for inputting a voltage of 100VAC.
Do not input a voltage of 200VAC into it or trouble may occur on the Q61P-A1.
Power Supply power voltage
module type 100VAC 200VAC
Power supply module causes
Q61P-A1 Operates normally.
trouble.
Power supply module does
not cause trouble.
Q61P-A2 Operates normally.
CPU module cannot be
operated.
(5) When the Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P or Q64P is loaded on the
extension base unit, a system error cannot be detected by the ERR terminal.
(The ERR terminal is always OFF.)
2 - 33
2 SYSTEM CONFIGURATION
MR-HDP01
MR-HDP01
Q170ENC
(Note) : Configure the system in such a way that the total current
consumption at 5VDC of all the modules is less than the
allowable value.
2 - 34
2 SYSTEM CONFIGURATION
This section describes the specifications of the extension cables for the base units
(Main base unit or extension base unit) used in the system, and the specification
standards of the extension base unit.
5VDC internal current consumption of base unit might be changed. Be sure to refer to
the PLC Manuals.
2 - 35
2 SYSTEM CONFIGURATION
Type
QC05B QC06B QC12B QC30B QC50B QC100B
Item
Cable length[m(ft.)] 0.45(1.48) 0.6(1.97) 1.2(3.94) 3.0(9.84) 5.0(16.40) 10.0(32.81)
Connection between the main base unit and extension base unit,
Application
or connection between the extension base units.
Mass [kg] 0.15 0.16 0.22 0.40 0.60 1.11
POINT
When the extension cables are used in combination, limit the overall length of the
combined cable to 13.2m (43.31ft.).
5) 4)
OUT
1) 5V
2) SG
POWER CPU I/O0 I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7 I/O8 I/O9 I/O10 I/O11
FG Q312DB
3)
2 - 36
2 SYSTEM CONFIGURATION
I/O Allocations
0 1 2 3 4 5 6 7 8 9
Power supply
QnUD(H) QnUD(H) Q173D QX41 QY41 QY41 Q172DLX QX41 QY41 QY41
CPU CPU CPU
module
X0 to X1F Y20 to Y3F Y40 to Y5F Intelligent PX0 to PX1F PY20 to PY3F YC0 to YDF
32 points
(X60 to X7F) (Y80 to Y9F) (YA0 to YBF)
CPU No.1 CPU No.2 CPU No.3 Module of Module of Module of Module of Module of Module of Module of
control control control control control control control
CPU No.1 CPU No.1 CPU No.2 CPU No.3 CPU No.3 CPU No.3 CPU No.1
POINT
I/O device of the Motion CPU can be set in the range PX/PY000 to PX/PYFFF.
The real I/O points must be 256 points or less. (As for the I/O No., it is possible not
to continue.)
2 - 37
2 SYSTEM CONFIGURATION
Q172DLX receives external signals (servo external signals) required for positioning
control.
1)
5) Q172DLX
2)
3)
CTRL
6) Q172DLX
4)
POINT
Mode judging LED of the proximity dog/speed-position switching signal (DOG/
CHANGE) turns ON at the following conditions.
• Q172DLX is set on the system setting display of MT Developer.
• The proximity dog/speed-position switching signal (DOG/CHANGE) is input.
2 - 38
2 SYSTEM CONFIGURATION
(b) Input
Item Specifications
Servo external signals : 32 points
(Upper stroke limit, Lower stroke limit, Stop input,
Number of input points
Proximity dog/Speed-position switching signal)
(4 points 8 axes)
Input method Sink/Source type
Isolation method Photocoupler
Rated input voltage 12/24VDC
Rated input current 12VDC 2mA/24VDC 4mA
10.2 to 26.4VDC
Operating voltage range
(12/24VDC +10/ -15%, ripple ratio 5% or less)
ON voltage/current 10VDC or more/2.0mA or more
OFF voltage/current 1.8VDC or less/0.18mA or less
Input resistance Approx. 5.6k
Response time of the OFF to ON
Upper/Lower stroke limit and 1ms
STOP signal ON to OFF
2 - 39
2 SYSTEM CONFIGURATION
Number of points
Servo external signal Application
on one Q172DLX
Upper stroke limit input (FLS)
For detection of upper and lower stroke limits.
Lower stroke limit input (RLS)
Stop signal input (STOP) For stopping under speed or positioning control. 32 points
Proximity dog/ For detection of proximity dog at proximity dog or count (4 points/8 axes)
Speed-position switching input type home position return of for switching from speed to
(DOG/CHANGE) position switching control.
2 - 40
2 SYSTEM CONFIGURATION
CTRL connector
Pin No. Signal Name Pin No. Signal Name Signal No.
Signal No.
B20 FLS1 A20 FLS5
B19 RLS1 A19 RLS5
1 5
B18 STOP1 A18 STOP5
B17 DOG1/CHANGE1 A17 DOG5/CHANGE5
B16 FLS2 A16 FLS6
B15 RLS2 A15 RLS6
2 6
B14 STOP2 A14 STOP6
B13 DOG2/CHANGE2 A13 DOG6/CHANGE6
DOG/CHANGE, STOP, RLS, FLS functions of each axis(1 to 8) For information about
signal details, refer to
DOG/CHANGE Proximity dog/Speed-position
the programming manual.
switching signal
STOP Stop signal
RLS Lower stroke limit
FLS Upper stroke limit
POINT
Signal No. 1 to 8 can be assigned to the specified axis. Make the assignment in the
system settings of MT Developer.
2 - 41
2 SYSTEM CONFIGURATION
(Note): As for the connection to power line (B1, B2), both "+" and "–" are possible.
CAUTION
Always use a shield cable for connection of the CTRL connector and external equipment, and
avoid running it close to or bundling it with the power and main circuit cables to minimize the
influence of electromagnetic interface. (Separate them more than 200mm (0.66ft.) away.)
Connect the shield wire of the connection cable to the FG terminal of the external equipment.
Make parameter setting correctly. Incorrect setting may disable the protective functions such
as stroke limit protection.
Always wire the cables when power is off. Not doing so may damage the circuit of modules.
Wire the cable correctly. Wrong wiring may damage the internal circuit.
2 - 42
2 SYSTEM CONFIGURATION
Q172DEX receive external signals required for serial absolute synchronous encoder.
The installation position of Q172DEX is only main base.
1)
5) Q172DEX
SY.ENC TREN
1 1 2)
2 2
SY.ENC1 3)
8)
LITHIUM BATTERY
MITSUBISHI
SY.ENC2
6) Q172DEX
9) 7) 4)
LED Details
Display for signal input status of each serial
SY.ENC absolute synchronous encoder.
1, 2 (LED turns ON at the normal connection (first
2) Mode judging LED
switching to virtual mode).)
TREN
Display for signal status of tracking enable.
1, 2
The tracking enable signal does not turn ON without
setting Q172DEX in the system setting.
3) SY. ENC connector Input connector of the serial absolute synchronous encoder.
4) Module loading lever Used to install the module to the base unit.
Module fixing screw Hole for the screw used to fix to the base unit
5)
hole (M3×12 screw : Purchase from the other supplier)
6) Module fixing hook Hook used to fix to the base unit.
7) Battery connector For connection of battery lead wire.
8) Battery holder Used to the set the Battery (A6BAT/MR-BAT) to the holder.
Battery
9) For Serial absolute synchronous encoder battery backup.
(A6BAT/MR-BAT)
2 - 43
2 SYSTEM CONFIGURATION
POINT
(1) Mode judging LED of the serial absolute synchronous encoder signal turns ON
at the normal connection (first switching to virtual mode).
(2) Mode judging LED of the tracking enable signal turns ON at the following
conditions.
• Q172DEX is set on the system structure screen of MT Developer.
• The tracking enable signal is input.
2 - 44
2 SYSTEM CONFIGURATION
2 - 45
2 SYSTEM CONFIGURATION
2 - 46
2 SYSTEM CONFIGURATION
SW
1 2
STOP RUN
CAUTION
EMI
CN1
CN2
FRO NT
BA T
SY.ENC connector
2 - 47
2 SYSTEM CONFIGURATION
P5 10 18 19 20
5VDC
LG 1 2 3 11 12
Input Battery
BAT 9
TREN 4 5.6k
(Note)
TREN.
COM 14
(Note)
12VDC to 24VDC
SD plate
(Note) : As for the connection to power line (TREN, TREN.COM), both "+" and "–" are possible.
CAUTION
Always use a shield cable for connection of the SY.ENC connector and external equipment, and
avoid running it close to or bundling it with the power and main circuit cables to minimize the
influence of electromagnetic interface. (Separate them more than 200mm (0.66 ft.) away.)
Connect the shield wire of the connection cable to the FG terminal of the external equipment.
When increasing the cable length, use the cable 50m(164.04ft.) or less. Note that the cable
should be run in the shortest possible distance to avoid induced noise.
Always wire the cables when power is off. Not doing so may damage the circuit of modules.
Wire the cable correctly. Wrong wiring may damage the internal circuit.
2 - 48
2 SYSTEM CONFIGURATION
P5 19 S
LG 11 R
P5 20
LG 12
P5 18
LG 2
BAT 9 E
LG 1
MR 7 K
MRR 17 L
MD 6 H
MDR 16 J
SDplate N
P5 19 S
LG 11 R
P5 20
LG 12
P5 18
LG 2
BAT 9 E
LG 1
MR 7 K
MRR 17 L
MD 6 H
MDR 16 J
SDplate
TREN 4 N
TREN.COM 14
24VDC
:Twisted pair cable
2 - 49
2 SYSTEM CONFIGURATION
(a) Specifications
The specifications of the battery for memory back-up are shown in the table
below.
Battery Specifications
Model name
A6BAT/MR-BAT
Item
Classification Manganese dioxide lithium primary battery
Normal voltage [V] 3.6
Nominal current [mAh] 1600
Storage life 5 years
Lithium content [g] 0.48
For backup absolute positioning data of the serial absolute
Applications
synchronous encoder (Q170ENC)
Exterior dimensions [mm(inch)] 16(0.63) × 30(1.18)
(Note) : The 44th Edition of the IATA (International Air Transportation Association) Dangerous Goods Regulations
was effected in January 1st, 2003 and administered immediately.
In this edition, the provisions relating to lithium and lithium ion batteries have been revised to strengthen
regulations on the air transportation of battery.
This battery is not dangerous goods (not class 9). Therefore, these batteries of 24 units or less are not
subject to the regulations.
These batteries more than 24 units require packing based on Packing Instruction 903.
If you need the self-certification form for the battery safety test, contact Mitsubishi.
For more information, contact Mitsubishi.
A6BAT/MR-BAT
LITHIUM BATTERY
MITSUBISHI
2 - 50
2 SYSTEM CONFIGURATION
(Note-1) : The actual service value indicates the average value, and the guaranteed time indicates the minimum time.
(Note-2) : The power-on time ratio indicates the ratio of Multiple CPU system power-on time to one day (24 hours).
(When the total power-on time is 17 hours and the total power-off time is 7 hours, the power-on time ratio is 70%.)
(Note-3) : The guaranteed value (MIN) ; equivalent to the total power failure time that is calculated based on the characteristics value of
the memory (SRAM) supplied by the manufacturer and under the storage ambient temperature range of -25°C to 75°C (-13 to
167°F) (operating ambient temperature of 0°C to 55°C (32 to 131°F)).
(Note-4) : The guaranteed value (TYP) ; equivalent to the total power failure time that is calculated based on the normal air-conditioned
environment (40°C (104°F)).
(Note-5) : The actual service value (Reference value) ; equivalent to the total power failure time that is calculated based on the measured
value and under the storage ambient temperature of 25°C (77°F). This value is intended for reference only, as it varies with
characteristics of the memory.
POINTS
The self-discharge influences the life of battery without the connection to Q172DEX.
The external battery should be exchanged approximately every 4 or 5 years.
And, exchange the battery with a new one in 4 to 5 years even if a total power
failure time is guaranteed value or less.
CAUTION
Do not short a battery.
Do not charge a battery.
Do not disassemble a battery.
Do not burn a battery.
Do not overheat a battery.
Do not solder the battery terminals.
Before touching the battery, always touch grounded metal, etc. to discharge static electricity from
human body. Failure to do so may cause the module to fail or malfunction.
Do not directly touch the module's conductive parts and electronic components. Touching them
could cause an operation failure or give damage to the module.
2 - 51
2 SYSTEM CONFIGURATION
Q173DPX receive external signals required for Manual pulse generator and
Incremental synchronous encoder (Voltage-output/Open collector type/Differential-
output type).
PULSER
3)
ON
1 2 3 4 5 6
6)
KSD06S
7) Q173DPX
4)
LED Details
Display for input signal status of
PLS.A 1 to 3
manual pulse generator/incremental
PLS.B 1 to 3
2) Mode judging LED synchronous encoder phases A, B
Display for signal status of tracking
TREN 1 to 3
enable.
The manual pulse generator/incremental synchronous
encoder phases A, B and tracking enable signal does not
turn ON without setting Q173DPX in the system setting.
Input connector of the Manual pulse generator/Incremental
3) PULSER connector
synchronous encoder.
4) Module loading lever Used to install the module to the base unit.
Module fixing screw Hole for the screw used to fix to the base unit
5)
hole (M3×12 screw : Purchase from the other supplier)
2 - 52
2 SYSTEM CONFIGURATION
ON
1 2 3 4 5 6
Detection setting of TREN2 signal
Dip switch 3 SW3 SW4
OFF OFF
TREN is detected at leading
6) ON ON
edge of TREN signal.
ON OFF
Dip switch 4
TREN is detected at trailing
OFF ON
(Shipped from the edge of TREN signal.
factory in OFF Detection setting of TREN3 signal
position) Dip switch 5 SW5 SW6
OFF OFF
TREN is detected at leading
ON ON
edge of TREN signal.
ON OFF
Dip switch 6
TREN is detected at trailing
OFF ON
edge of TREN signal.
7) Module fixing hook Hook used to fix to the base unit.
(Note-1) : The function is different according to the operating system software installed.
CAUTION
Before touching the battery, always touch grounded metal, etc. to discharge static electricity
from human body. Failure to do so may cause the module to fail or malfunction.
Do not directly touch the module's conductive parts and electronic components. Touching them
could cause an operation failure or give damage to the module.
POINTS
Mode judging LED of the manual pulse generator/incremental synchronous encoder
phases A, B and tracking enable signal turns ON at the following conditions.
(1) PLS.A 1 to 3, PLS.B 1 to 3
• Q173DPX is set on the system structure screen of MT Developer.
• All axes servo ON command (M2042) turned on.
• Manual pulse generator enable flag (M2051, M2052, M2053) turned on.
• Manual pulse generator signal is input.
(2) TREN 1 to 3
• Q173DPX is set on the system structure screen of MT Developer.
• The tracking enable signal is input.
2 - 53
2 SYSTEM CONFIGURATION
2 - 54
2 SYSTEM CONFIGURATION
Q173DCPU Up to 3 modules
Q172DCPU ( Up to 1 module )
2 - 55
2 SYSTEM CONFIGURATION
2 - 56
2 SYSTEM CONFIGURATION
2 - 57
2 SYSTEM CONFIGURATION
Phase A
Select type
(Note-2) Phase B
signal A18 A13 A8 2.5 s or
more
HPSEL (1) Positioning address
increases if Phase A
leads Phase B.
(Note-1) Power supply (2) Positioning address
P5 B18 B13 B8 5VDC decreases if Phase B
5V leads Phase A.
Power
supply SG
A19 A14 A9
SG
B19 B14 B9
(Note-1) : The 5V(P5)DC power supply from the Q173DPX must not be connected if a separated power
supply is used as the Manual pulse generator/Incremental synchronous encoder power supply.
Use a 5V stabilized power supply as a separated power supply. Any other power supply may
cause a failure.
(Note-2) : Connect HPSEL to the SG terminal if the manual pulse generator (differential output type)
/incremental synchronous encoder is used.
2 - 58
2 SYSTEM CONFIGURATION
(Note) : The 5V(P5)DC power supply from the Q173DPX must not be connected if a separated power
supply is used as the Manual pulse generator/Incremental synchronous encoder power supply.
Use a 5V stabilized power supply as a separated power supply. Any other power supply
may cause a failure.
(Note) : As for the connection to tracking enable (TREN +, TREN –), both "+" and "–" are possible.
2 - 59
2 SYSTEM CONFIGURATION
(Note-1) : The 5V(P5)DC power supply from the Q173DPX must not be connected if a separated
power supply is used as the Manual pulse generator/Incremental synchronous
encoder power supply.
Use a 5V stabilized power supply as a separated power supply. Any other power supply
may cause a failure.
(Note-2) : Connect HPSEL to the SG terminal if the manual pulse generator (differential output
type/incremental synchronous encoder is used.
CAUTION
If a separate power supply is used as the manual pulse generator/incremental synchronous
encoder power supply, use a 5V stabilized power supply. Any other power supply may cause a
failure.
2 - 60
2 SYSTEM CONFIGURATION
2 - 61
2 SYSTEM CONFIGURATION
2 - 62
2 SYSTEM CONFIGURATION
This section describes how to connect between the Motion CPU module and servo
amplifiers.
Between the Motion CPU module and servo amplifiers is connected by SSCNET
cable. When using the Q172DCPU, only 1 SSCNET cable for connection to servo
amplifier can be used. (Connect to CN1.) When using the Q173DCPU, up to 2
SSCNET cables for connection to servo amplifier can be used. (Connect to CN1 and
CN2.)
Up to 16 servo amplifies can be connected to 1 SSCNET cable.
(However, when using the Q172DCPU, up to 8 servo amplifiers can be connected.)
Attach a cap to
Cap connectors of system
not being used.
SSCNET SYSTEM1
1)
CN1A CN1A
1)
Cap
CN1B
CN1B
SSCNET SYSTEM2
1)
CN1A CN1A
1)
Cap
CN1B
CN1B
2 - 63
2 SYSTEM CONFIGURATION
1)
CN1A CN1A
1)
Cap
CN1B
CN1B
2 - 64
2 SYSTEM CONFIGURATION
POINTS
(1) Be sure to connect SSCNET cable with the above connector. If the
connection is mistaken, between the Motion CPU module and servo amplifier
cannot be communicated.
(2) SSCNET connector is put a cap to protect light device inside connector from
dust. For this reason, do not remove a cap until just before connecting
SSCNET cable. Then, when removing SSCNET cable, make sure to put a
cap.
(3) Be sure to keep a cap and the tube for protecting light code end of SSCNET
cable in a plastic bag with a zipper of SSCNET cable to prevent them from
becoming dirty.
(4) Do not remove the SSCNET cable while turning on the power supply of
Multiple CPU system and servo amplifier.
Do not see directly the light generated from SSCNET connector of Motion
CPU module or servo amplifier and the end of SSCNET cable. When the
light gets into eye, may feel something is wrong for eye. (The light source of
SSCNET cable complies with class1 defined in JISC6802 or
IEC60825-1.)
(5) When exchanging the servo amplifier or Motion CPU module, make sure to put
a cap on SSCNET connector. When asking repair of servo amplifier or
Motion CPU module for some troubles, make also sure to put a cap on
SSCNET connector. When the connector is not put a cap, the light device
may be damaged at the transit. In this case, exchange and repair of light
device is required.
2 - 65
2 SYSTEM CONFIGURATION
(4) Setting of the axis No. and axis select switch of servo amplifier
Axis No. is used to set the axis numbers of servo amplifiers connected to
SSCNET connector(CN ) in the program.
Axis No. of 1 to 32 can be set for Q173DCPU, and axis No. of 1 to 8 can be set
for Q172DCPU.
Axis No. is set for each system with SSCNET structure screen of system setting
of MT Developer. Axis No. (Q173DCPU:1 to 32/Q172DCPU:1 to 8) is allocated
and set for the setting axis number (d01 to d16) of servo amplifier.
Since the axis number (d01 to d16) of servo amplifier on the SSCNET structure
screen corresponds to axis select switch (0 to F) of servo amplifier, set the axis
select switch referring to the table of next page.
• SSCNET structure (Allocation of axis No.) • Axis select switch (Servo amplifier)
7 8 9
3 4 5 6
A
B C DE
2
F 0 1
(Note) : Correspondence between dno. and axis select switch of servo amplifiers is shown in the next
page.
2 - 66
2 SYSTEM CONFIGURATION
(Note) : The dno. is number of servo amplifier axis displayed with SSCNET structure screen of
MT Developer.
Axis No. is set relative to dno. in the SSCNET structure screen of system settings.
Correspondence between SSCNET system No. and connector No. of CPU module
SSCNET system No. Connector No. of CPU
1 SSCNET CN1
2 SSCNET CN2
(Note) : Number of SSCNET systems: Q173DCPU : 2 systems / Q172DCPU : 1 system
2 - 67
2 SYSTEM CONFIGURATION
This section describes the battery specifications used in the Motion CPU, handling
precautions and equipments.
2 - 68
2 SYSTEM CONFIGURATION
(Note-1) : The actual service value indicates the average value, and the guaranteed time indicates the minimum time.
(Note-2) : The power-on time ratio indicates the ratio of Multiple CPU system power-on time to one day (24 hours).
(When the total power-on time is 17 hours and the total power-off time is 7 hours, the power-on time ratio is 70%.)
(Note-3) : The guaranteed value (MIN) ; equivalent to the total power failure time that is calculated based on the characteristics value of
the memory (SRAM) supplied by the manufacturer and under the storage ambient temperature range of -25°C to 75°C (-13 to
167°F) (operating ambient temperature of 0°C to 55°C (32 to 131°F)).
(Note-4) : The guaranteed value (TYP) ; equivalent to the total power failure time that is calculated based on the normal air-conditioned
environment (40°C (104°F)).
(Note-5) : The actual service value (Reference value) ; equivalent to the total power failure time that is calculated based on the measured
value and under the storage ambient temperature of 25°C (77°F). This value is intended for reference only, as it varies with
characteristics of the memory.
POINTS
The self-discharge influences the life of battery without the connection to Motion
CPU module. The external battery should be exchanged approximately every 4 or
5 years.
And, exchange the battery with a new one in 4 to 5 years even if a total power
failure time is guaranteed value or less.
CAUTION
Do not short a battery.
Do not charge a battery.
Do not disassemble a battery.
Do not burn a battery.
Do not overheat a battery.
Do not solder the battery terminal.
The programs, parameters, absolute position data and latch data of SRAM built-in Motion
CPU module are backed up without using the external battery.
2 - 69
2 SYSTEM CONFIGURATION
BAT
Battery holder unit
Battery cable (Q170DBATC)
(Q170DBATCBL )
0.5[m]
(1.64[ft.])
Q6BAT
2 - 70
2 SYSTEM CONFIGURATION
Item Specifications
Number of input points Forced stop signal : 1 point
Input method Sink/Source type
Isolation method Photocoupler
20.4 to 26.4VDC
Operating voltage range
(+10/ -15%, ripple ratio 5% or less)
ON voltage/current 17.5VDC or more/3.0mA or more
OFF voltage/current 1.8VDC or less/0.18mA or less
Input resistance Approx. 10k
OFF to ON
Response time 1ms
ON to OFF
External connector type 2 pin connector
2
Applicable wire size 0.3mm (AWG22)
2 - 71
2 SYSTEM CONFIGURATION
MEMO
2 - 72
3 DESIGN
3. DESIGN
Design the system which uses the Multiple CPU system in the following procedure.
Select the number of Q172DLX's and design according to the each Refer to section 2.4.4
axis control system and whether servo external signals are required
or not.
When there is mechanical home position and home position return is
made: Proximity dog required
For speed control: Speed-position switching control signal required
When overrun prevention is necessary: Stroke limit required
When each axis stop is necessary: STOP signal required
Select Q173DPX, Q172DEX and design according to whether manual Refer to section 2.4.5
pulse generators and synchronous encoders are required or not. Refer to section 2.4.6
Select I/O modules according to the specifications of the external Refer to MELSEC-Q
equipment to be controlled. series manual.
Select the main base unit, extension base units, extension power Refer to section 2.4.4
supply module and extension cables, and make I/O assignment Refer to section 2.4.5
according to necessary number of Q172DLX's, Q172DEX's, Refer to section 2.4.6
Q173DPX's, QX 's, QY 's and the number of I/O modules.
Select the servo amplifier and servo motor according to the motor Refer to the servo
capacity and number of revolution from the machine mechanism to be amplifier manual.
controlled each axis.
3-1
3 DESIGN
! CAUTION
Provide appropriate circuits external to the Motion CPU to prevent cases where danger may result
from abnormal operation of the overall system in the event of an external power supply fault or
Motion CPU failure.
Mount the Motion controller, servo amplifier, servomotor and regenerative resistor on
incombustible. Mounting them directly or close to combustibles will lead to fire.
If a fault occurs in the Motion controller or servo amplifier, shut the power OFF at the servo
amplifier’s power source. If a large current continues to flow, fire may occur.
When using a regenerative resistor, shut the power OFF with an error signal. The regenerative
resistor may abnormally overheat due to a fault in the regenerative transistor, etc., and may lead
to fire.
Always take heat measures such as flame proofing for the inside of the control panel where the
servo amplifier or regenerative resistor is mounted and for the wires used. Failing to do so may
lead to fire.
Do not apply a voltage other than that specified in the instruction manual on any terminal. Doing
so may lead to destruction or damage.
Do not mistake the polarity ( + / - ), as this may lead to destruction or damage.
3-2
3 DESIGN
! CAUTION
Do not touch the heat radiating fins of controller or servo amplifier, regenerative resistor and
servomotor, etc. while the power is ON and for a short time after the power is turned OFF. In this
timing, these parts become very hot and may lead to burns.
Always turn the power OFF before touching the servomotor shaft or coupled machines, as these
parts may lead to injuries.
Do not go near the machine during test operations or during operations such as teaching.
Doing so may lead to injuries.
Always mount a leakage breaker on the Motion controller and servo amplifier power source.
If mounting of an electromagnetic contactor for power shut off during an error, etc., is specified in
the instruction manual for the servo amplifier, etc., always mount the electromagnetic contactor.
Mount an emergency stop circuit externally so that the operation can be stopped immediately and
the power shut off.
Use the Motion controller, servo amplifier, servomotor and regenerative resistor with the correct
combinations listed in the instruction manual. Other combinations may lead to fire or faults.
If safety standards (ex., robot safety rules, etc.,) apply to the system using the Motion controller,
servo amplifier and servomotor, make sure that the safety standards are satisfied.
Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal
operation of the Motion controller or servo amplifier differ from the safety directive operation in
the system.
In systems where coasting of the servomotor will be a problem during the forced stop, the
emergency stop, servo OFF or when the power is shut OFF, use dynamic brakes.
Make sure that the system considers the coasting amount even when using dynamic brakes.
In systems where perpendicular shaft dropping may be a problem during the forced stop, the
emergency stop, servo OFF or when the power is shut OFF, use both dynamic brakes and
electromagnetic brakes.
The dynamic brakes must be used only during the forced stop, the emergency stop and errors
where servo OFF occurs. These brakes must not be used for normal braking.
The brakes (electromagnetic brakes) assembled into the servomotor are for holding applications,
and must not be used for normal braking.
The system must have a mechanical allowance so that the machine itself can stop even if the
stroke limits switch is passed through at the max. speed.
Use wires and cables that have a wire diameter, heat resistance and bending resistance
compatible with the system.
Use wires and cables within the length of the range described in the instruction manual.
The ratings and characteristics of the parts (other than Motion controller, servo amplifier,
servomotor) used in a system must be compatible with the Motion controller, servo amplifier and
servomotor.
Install a cover on the shaft so that the rotary parts of the servomotor are not touched during
operation.
There may be some cases where holding by the electromagnetic brakes is not possible due to
the life or mechanical structure (when the ball screw and servomotor are connected with a
timing belt, etc.). Mount a stopping device to ensure safety on the machine side.
3-3
3 DESIGN
As to the ways to design the external circuits of the Motion system, this section
explains the method and instructions for designing the power supply circuits and
safety circuits, etc.
(1) Sample system circuit design for motion control 1
3-phase
200/220VAC
Power Supply PLC CPU Motion CPU Input module Output module Servo external
NFB1 Q61P-A2 QnUD(H)CPU Q173DCPU/ signals interface
Q172DCPU QX40 QY10 module
R S T CP1
200VAC Forced stop (Note-1) Q172DX
PYm
EMI.COM Ra1 (Note-2) FLS1
200VAC
Servo normal output
EMI (Servo normal:ON
Alarm:OFF) DOG8/
CHANGE8
FG COM
LG
COM
FLS1
DOG8/
CHANGE8
CP2 EMG
24VDC +24V
Power
supply 24G
Emergency Stop
EMG
Operation Ready
CP3 Ra1 OFF ON
MC
MC
SK
3-4
3 DESIGN
POINT
<Example> For control axis 1 and axis 2
(1) (Note-1) : Make the forced stop input cable within 30m(98.43ft.).
The forced stop by the forced stop terminal of input module is also Servo error detection
possible.
(2) (Note-2) : Motion SFC program example is shown in the right record. [F 1]
SET PYm PYm ON with initial
(3) (Note-3) : It is also possible to use a full wave rectified power supply as the (ON : normal)
power supply for the electromagnetic brake. [G 1]
(4) (Note-4) : It is also possible to use forced stop signal of the servo amplifier. M2408+M2428 Servo error detection
of the axis 1, axis 2
(5) (Note-5) : It recommends using one leakage breaker for one servo amplifier.
[F 2]
When electric power is supplied to multiple servo amplifiers for one RST PYm OFF : abnormal (error)
leakage breaker, select the wire connected to the servo amplifier
according to the capacity of the leakage breaker. END
CN1B EM1
DOCOM
(Note-4)
24VDC
CN1B EM1
DOCOM
(Note-4)
24VDC
CN1B EM1
CP4 DOCOM
(Note-4)
24VDC
(Note-1) : When the control power supply of servo amplifier is shut off, it is not possible to communicate with the servo amplifier after that.
Example) When the control power supply L11/L21 of servo amplifier in above B figure is shut off, it is also not possible to
communicate with the servo amplifier C .
If only a specific servo amplifier power supply is shut off, be sure to shut off the main circuit power supply L1/L2/L3, and do not
shut off the control power supply L11/L21.
(Note-2) : Be sure to shut off the both of main circuit power supply L1/L2/L3 and control power supply L11/L21 at the time of exchange of
servo amplifier. At this time, it is not possible to communicate between the servo amplifier and Motion controller. Therefore, be
sure to exchange the servo amplifier after stopping the operating of machine beforehand.
3-5
3 DESIGN
3-6
3 DESIGN
Power supply
FOR AC/DC
Transformer Transformer
Input switched
when power supply Fuse Fuse
established.
CPU module
XM
Set time for DC power
TM supply to be established.
N0 TM
MC1 N0 M10
M10
Program
START SW
RA1 RA3
MC
MC STOP SW
RA2
Voltage relay
is recommended
RA2 XM
output module
Ym Low battery alarm
L (Lamp or buzzer)
Yn
RA1
output module MC MC
Interlock circuits as
Output by ERR contact OFF
necessary. Provide
Power OFF of equipment
external interlock
circuits for conflicting
operations, such as
forward rotation and MC2 In the case of an
reverse rotation,
MC1 emergency stop or a
and for parts that could stop caused by a limit
MC1 switch.
damage the machine or MC2
cause accident if no
interlock were used.
3-7
3 DESIGN
This section describes the protective coordination and noise suppression techniques of
the power supply circuit.
(1) Separation and protective coordination (leakage current protection,
over current protection) of power supply lines
Separate the lines for Multiple CPU system power supplies from the lines for I/O
devices and servo amplifiers as shown below.
When there is much noise, connect an insulation transformer.
Insulation
Main power PLC power transformer
supply supply
Multiple CPU
100/200VAC
NFB CP system
I/O power T1
supply
I/O devices
CP
Main circuit
power supply
Main circuit device
CP
Servo amplifier
power supply
200VAC Servo amplifier
NFB
(2) Grounding
The Motion system may malfunction as it is affected by various noises such as
electric path noises from the power supply systems, radiated and induced noises
from other equipment, servo amplifiers and their cables, and electromagnetic
noises from conductors. To avoid such troubles, connect the earthing ground of
each equipment and the shield grounds of the shielded cables to the earth.
For grounding, use the exclusive ground terminal wire of each equipment or a
single-point earth method to avoid grounding by common wiring, where possible,
since noises may sneak from other equipment due to common impedances.
SSCNET
Servo-
Servo amplifier motor
(Note): Be sure to ground the line noise filter, Multiple CPU system, servo amplifier and
servomotor. (Ground resistance : 100 or less)
3-8
3 DESIGN
The wiring example for the EMI forced stop input of Motion CPU module is
shown below.
Q61P QnUD(H) Q17 D
CPU CPU
EMI.COM
EMI
Forced stop
24VDC
<Motion CPU module>
24VDC (Note-1)
EMI.COM
R
R
EMI
Forced stop
(Note): The EMI forced stop input can be invalidated in the system
settings.
(Note-1): Both of positive common and negative common can be used.
3-9
3 DESIGN
(b) The forced stop of all servo amplifiers is possible in a lump by using the
forced stop input of input modules. After forced stop, the forced stop factor is
removed and the forced stop canceled.
(The servo error detection signal does not turn on with the forced stop.)
The forced stop input can be set by allocation of the device number in the
parameter setting of system setting. When the device is used, apply 24VDC
voltage on EMI terminal and invalidate the forced stop input of EMI terminal.
The wiring example for the forced stop input (QX10) of input module is
shown below.
Q61P QnUD(H) Q17 D QX10
CPU CPU
EMI.COM Xn
EMI
COM
Forced stop
100VAC
24VDC
<Input module QX10>
100VAC
TB17
TB16
LED
Internal
R
R
circuit
TB1
R
Forced stop
(Note): The forced stop input can be set in the system settings.
(c) It is also possible to use the forced stop signal of the servo amplifier.
Refer to manual of the servo amplifier about servomotor capacity.
Operation status of the emergency stop and the forced stop are as follows.
Operation of
Item Remark
the signal ON
Shut off the power supply to the external servo amplifier
Emergency stop
by external circuit, make the servomotor stopped.
Servo OFF
The servomotor is stopped according to the stop
Forced stop
instruction from Motion controller to the servo amplifier.
3 - 10
3 DESIGN
(5) There must not be a lot of conductible dust, iron filings, oil mist, or salt, organic
solvents.
3 - 11
3 DESIGN
! CAUTION
Due to ventilation problems, do not mount the base units vertically or horizontally.
Mount the base units on a flat surface. Unevenness or warping of the surface can apply undue
force to printed circuit boards and lead to operation failures.
Avoid mounting the base units close to a vibration source, such as a large electromagnetic
contactor or no-fuse breaker. Mount them on a separate panel or at a safe distance.
To limit the effects of reflected noise and heat, leave 100mm(3.94inch) or more clearance to
instruments fitted in front of the Motion controller (on the rear of the door).
Similarly, leave 50mm(1.97inch) or more clearance between instruments and the left and right
sides of the base units.
3 - 12
3 DESIGN
The ambient temperature inside the panel storing the Motion controller must be
suppressed to an ambient temperature of 55°C(131°F) or less, which is specified for
the Motion controller.
For the design of a heat releasing panel, it is necessary to know the average power
consumption (heating value) of the devices and instruments stored inside.
Here the method of obtaining the average power consumption of Q173DCPU/
Q172DCPU system is described. From the power consumption, calculate a rise in
ambient temperature inside the control panel.
The power consuming parts of the Motion controller are roughly classified into six
blocks as shown below.
(2) Total power consumption for 5VDC logic circuits of all modules
(including CPU module)
The power consumption of the 5 VDC output circuit section of the power supply
module is the power consumption of each module (including the current
consumption of the base unit).
W5V = I5V 5 [W]
3 - 13
3 DESIGN
From this overall power consumption [W], calculate the heating value and a rise
in ambient temperature inside the panel.
The outline of the calculation formula for a rise in ambient temperature inside the
panel is shown below.
W
T= [C]
UA
W : Power consumption of overall Motion system (value obtained above)
2
A : Surface area inside the panel [m ]
U : When the ambient temperature inside the panel is uniformed by a fan ...... 6
When air inside the panel is not circulated.............................................. 4
POINT
If the temperature inside the panel has exceeded the specified range, it is
recommended to mount a heat exchanger to the panel to lower the temperature.
If a normal ventilating fan is used, dust will be sucked into the Motion controller
together with the external air, and it may affect the performance of the Motion
controller.
3 - 14
3 DESIGN
(f) Average power consumption due to voltage drop in the output section of the
output module
WOUT = 0 [W]
(g) Average power consumption of the input section of the input module
WIN = 0.004 24 32 1 = 3.07 [W]
(h) Power consumption of the power supply section of the intelligent function
module.
WS = 0 [W]
3 - 15
3 DESIGN
At the worksite, copy the following table for use as a check sheet.
3 - 16
4 INSTALLATION AND WIRING
CAUTION
Use the Motion controller in an environment that meets the general specifications contained in this
manual. Using this Motion controller in an environment outside the range of the general specifications
could result in electric shock, fire, operation failure, and damage to or deterioration of the product.
While pressing the installation lever located at the bottom of module, insert the module fixing tab into
the fixing hole in the base unit until it stops. Then, securely install the module with the fixing hole as a
supporting point. Incorrect installation of the module can cause an operation failure, failure or drop.
When using the Motion controller in the environment of much vibration, tighten the module with a screw. 4
Tighten the screw in the specified torque range. Under tightening may cause a drop, short circuit or
operation failure. Over tightening may cause a drop, short circuit or operation failure due to damage to
the screw or module.
Be sure to connect the extension cable to connectors of the base unit correctly. After connecting,
check them for looseness. Poor connections could cause an input or output failure.
Completely turn off the externally supplied power used in the system before installation or removing
the module. Not doing so could result in electric shock or damage to the product.
Do not install/remove the module onto/from base unit or terminal block more than 50 times, after the
first use of the product. Failure to do so may cause the module to malfunction due to poor contact of
connector.
Do not directly touch the module's conductive parts and electronic components. Touching them
could cause an operation failure or give damage to the module.
This section describes instructions for handling the CPU, I/O, intelligent function and
power supply modules, base units and so on.
(1) Module, terminal block connectors and pin connectors are made of resin; do not
drop them or subject them to strong impact.
(2) Do not remove modules' printed circuit boards from the enclosure in order to avoid
changes in operation.
(3) Tighten the module fixing screws and terminal block screws within the tightening
torque range specified below.
Location of screw Tightening torque range
Motion CPU module fixing screw (M3 13 screw) 0.36 to 0.48 N•m
Module fixing screw (M3 12 screw) 0.36 to 0.48 N•m
I/O module terminal block screw (M3 screw) 0.42 to 0.58 N•m
I/O module terminal block fixing screw (M3.5 screw) 0.68 to 0.92 N•m
Power supply module terminal screw (M3.5 screw) 0.68 to 0.92 N•m
4-1
4 INSTALLATION AND WIRING
(4) Be sure to install a power supply module on the main base unit and extension
base unit. Even if the power supply module is not installed, when the I/O modules
and intelligent function module installed on the base units are light load type, the
modules may be operated. In this case, because a voltage becomes unstable, we
cannot guarantee the operation.
(5) When using an extension cable, keep it away from the main circuit cable (high
voltage and large current).
Keep a distance of 100mm or more from the main circuit.
(6) Be sure to fix a main base unit to the panel using fixing screws. Not doing so could
result in vibration that may cause erroneous operation.
Panel
(b) Place the right-hand side notch of the base unit onto the right-hand side
screw.
Panel
(c) Place the left-hand side pear-shaped hole onto the left-hand side screw.
Panel
(d) Fit the mounting screws into the holes at the bottom of the base unit, and
then retighten the all mounting screws.
(Note) : Mount a main base unit to a panel, with no module installed in the right-
end slot.
Remove the base unit after removing the module from the right-end slot.
4-2
4 INSTALLATION AND WIRING
When mounting the Motion controller to an enclosure or similar, fully consider its
operability, maintainability and environmental resistance.
OUT
5V
SG
Hs 2
H
POWER CPU I/O0 I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7 I/O8 I/O9 I/O10 II/O11
/ O11
FG Q312DB
Hs1
Ws1 Ws2 Ws3
4-3
4 INSTALLATION AND WIRING
40mm
Motion CPU module Motion CPU module
(1.58inch)
MELSEC
Q61P
POWER
Q03DCPU
MODE
Q173DCPU
QX40
01 2 3 4 5 6 7
89 AB CDE F
QX40
0 1 2 3 45 6 7
8 9 A B CDE F
Q172DEX
SY. ENC TREN
1 1
Q173DPX
PLS.A PLS. B TREN
1 1 1
or more
RUN 2 2
2 2 2
ERR. 3 3 3
USER SW
BAT. 1 2
BOOT STOP RUN
CAUTION
EMI
SY. ENC1
PULSER II/O11
/ O1 1
PULL
Q312DB
CN1
USB
PULL
Panel Door
CN2
RS-232
FRONT
BAT
Q172DEX Q173DPX
100mm
(3.94inch)
100mm 123.5mm or more
(3.94inch) (4.86inch)
or more
5mm(0.20inch) 5mm(0.20inch)
or more (Note-1) or more
(Note-1) : 20mm (0.79 inch) or more when the adjacent module is not removed and the extension cable is connected.
4-4
4 INSTALLATION AND WIRING
(5) Mounting of unit in an area where the other devices are mounted
Avoid mounting base unit in proximity to vibration sources such as large
magnetic contractors and no-fuse circuit breakers; mount those on a separate
panel or at a distance).
50mm(1.97inch)
or more
100mm(3.94inch)
50mm(1.97inch)
or more
or more
Contactor, relay, etc.
4-5
4 INSTALLATION AND WIRING
This section explains how to install and remove a power supply module, PLC CPU
module, Motion CPU module, Motion module, I/O module, intelligent function module
or another module to and from the base unit.
Module
fixing hook
Using the module fixing hole Module loading
as a fulcrum, push the module Module lever
in the direction of arrow to Module fixing hole
install it into the base unit.
Module Module
fixing hook fixing hook
Unit fixing
END projection
Module
fixing hook
(Note): Screw the Motion CPU module to the main base unit.
4-6
4 INSTALLATION AND WIRING
POINTS
(1) When installing the module, always insert the module fixing projection into the
module fixing hole of the base unit.
At that time, securely insert the module fixing projection so that it does not
come off from the module fixing hole.
If the module is forcibly installed without the latch being inserted, the module
connector and module will be damaged.
(2) When using the modules in a place where there is large vibration or impact,
screw the module to the base unit.
Module fixing screw : M3 12 (user-prepared)
Screw the Motion CPU module to the main base unit using supplied fixing
screws.
(3) Do not install/remove the module onto/from base unit or terminal block more
than 50 times, after the first use of the product. Failure to do so may cause the
module to malfunction due to poor contact of connector.
CAUTION
Insert the module fixing projection into the fixing hole in the base unit to install the module.
Incorrect installation could result in malfunction, failure, or a drop of the module.
When using the modules in a place where there is large vibration or impact, screw the module
to the base unit.
Tighten the screws within the specified torque range.
If the screw is too loose, it may cause a drop of the module, a short circuit or malfunctions.
If too tight, it may cause damage to the screws and/or module, resulting in an accidental drop of
the module, short circuit or malfunctions.
4-7
4 INSTALLATION AND WIRING
Push
When using the module fixing
screws, remove them.
Module Module
connector
Pull the module based on the
supporting point of module
bottom while pressing the
module fixing hook. Module fixing hole
Pull
Completion
POINT
When the module fixing screw is used, always remove the module by removing the
module fixing screw and then taking the module fixing latch off the module fixing
hole of the base unit.
Attempting to remove the module by force may damage the module fixing latch.
CAUTION
Do not touch the heat radiating fins of controller or servo amplifier's, regenerative resistor and
servomotor, etc. while the power is ON and for a short time after the power is turned OFF. In
this timing, these parts become very hot and may lead to burns.
Remove the modules while paying attention.
4-8
4 INSTALLATION AND WIRING
When mounting the battery holder unit (Q170DBATC) to an enclosure or similar, fully
consider its mounting position and orientation.
(Correct) (Wrong)
CPU
Q170DBATC
BATTERY
LITHIUM BATTERY
MITSUBISHI
LITHIUM BATTERY
MITSUBISHI
BATTERY
Q170DBATC
CPU
Q170DBATC
BATTERY
CPU
LITHIUM BATTERY
MITSUBISHI MITSUBISHI
LITHIUM BATTERY
BATTERY
CPU
Q170DBATC
4-9
4 INSTALLATION AND WIRING
Motion CPU
module
CN1
CN2
4 - 10
4 INSTALLATION AND WIRING
POINTS
(1) Forcibly removal the SSCNET cable from the Motion CPU module will
damage the Motion CPU modules and SSCNET cables.
(2) After removal of the SSCNET cable, be sure to put a cap on the SSCNET
connector. Otherwise, adhesion of dirt deteriorates in characteristic and it may
cause malfunctions.
(3) Do not remove the SSCNET cable while turning on the power supply of
Multiple CPU system and servo amplifier.
Do not see directly the light generated from SSCNET connector of Motion
CPU module or servo amplifier and the end of SSCNET cable. When the
light gets into eye, may feel something is wrong for eye. (The light source of
SSCNET cable complies with class1 defined in JISC6802 or
IEC60825-1.)
(4) If the SSCNET cable is added a power such as a major shock, lateral
pressure, haul, sudden bending or twist, its inside distorts or brakes, and
optical transmission will mot be available.
Be sure to take care enough so that the short SSCNET cable is added a
twist easily.
(5) Be sure to use the SSCNET cable within the range of operating temperature
described in this manual. Especially, as optical fiber for MR-J3BUS M and
MR-J3BUS M-A are made of synthetic resin, it melts down if being left near
the fire or high temperature. The cable part and code part melt down if being
left near the fire or high temperature. Therefore, do not make it touched the
part which becomes high temperature, such as radiator or regenerative brake
option of servo amplifier, or servomotor.
(6) When laying the SSCNET cable, be sure to secure the minimum cable bend
radius or more.
(7) SSCNET cable is used a optical cables or optical codes little affected by
plasticizer. However, come migrating plasticizer may affect the optical
characteristic of SSCNET cable as shown below.
SSCNET cable Code Cable
MR-J3BUS M
MR-J3BUS M-A
MR-J3BUS M-B
Cable is not affected by plasticizer.
Phthalate ester plasticizer such as DBP and DOP may affect optical characteristic
of cable.
4 - 11
4 INSTALLATION AND WIRING
POINTS
(8) Put the SSCNET cable in the duct or fix the cable at the closest part to the
Motion CPU module with bundle material in order to prevent SSCNET cable
from putting its own weight on SSCNET connector.
When laying cable, the optical cord should be given loose slack to avoid from
becoming smaller than the minimum bend radius, and it should not be twisted.
Also, fix and hold it in position with using cushioning such as sponge or rubber
which does not contain plasticizing material.
(9) If the adhesion of solvent and oil to the code part of SSCNET cable may
lower the optical characteristic and machine characteristic. If it is used such an
environment, be sure to do the protection measures to the cord part.
(10) When keeping the Motion CPU or servo amplifier, be sure to put on a cap to
connector part so that a dirt should not adhere to the end of SSCNET
connector.
(11) SSCNET connector is put a cap to protect light device inside connector from
dust. For this reason, do not remove a cap until just before connecting
SSCNET cable. Then, when removing SSCNET cable, make sure to put a
cap.
(12) Be sure to keep a cap and the tube for protecting light code end of SSCNET
cable in a plastic bag with a zipper of SSCNET cable to prevent them from
becoming dirty.
(13) When exchanging the servo amplifier or Motion controller, make sure to put a
cap on SSCNET connector. When asking repair of servo amplifier or Motion
controller for some troubles, make also sure to put a cap on SSCNET
connector. When the connector is not put a cap, the light device may be
damaged at the transit. In this case, exchange and repair of light device is
required.
4 - 12
4 INSTALLATION AND WIRING
Bottom
Front
Control panel
Do not hold
lead wire
4 - 13
4 INSTALLATION AND WIRING
Do not hold
lead wire
Q6BAT
Battery holder unit
(Q170DBATC)
POINT
(1) Forcibly removal the battery cable or battery lead wire from the battery holder
unit will damage the battery holder unit, battery cable or battery lead wire.
(2) As for the battery cable, the shape of connector is different on Motion CPU
side and battery holder side. Be sure to connect after confirming shape.
(3) The programs, parameters, absolute position data, and latch data of SRAM
built-in Motion CPU module are backed up if the battery connector is not
connect correctly.
4 - 14
4 INSTALLATION AND WIRING
Removal
1)
2)
POINTS
Forcibly removal the forced stop input cable from the CPU module will damage the
Motion CPU unit or forced stop input cable.
4 - 15
4 INSTALLATION AND WIRING
This section describes precautions for handling the serial absolute synchronous
encoder (Q170ENC).
(1) If the serial absolute synchronous encoder is linked to a chain, timing belt, or
gears, the machine rotating shaft should be supported by a separate bearing
and connected to Q170ENC through a coupling. Ensure that excessive force
(greater than the permitted shaft load) is not applied to the shaft of Q170ENC.
(2) Excessive load is applied to the shaft of Q170ENC by the large mounting errors in
eccentricity and angle of deviation As a result, it might damage the machine or
shorten extremely the life.
Minimize loads applied to the shaft such that they make within the permitted shaft
load range.
4 - 16
4 INSTALLATION AND WIRING
CAUTION
The Q170ENC contains a glass disk and precision mechanism. Take care when handling it. The
encoder performance may deteriorate if it is dropped or subjected to shocks or vibration exceeding the
prescribed limits.
Do not connect the shaft of Q170ENC directly to machine side rotary shaft. Always after connecting
the shaft of Q170ENC to another bearing once, connect the shaft through a flexible coupling.
Gear
Bearing
Q170ENC
Coupling
Fig 4.2 Connecting the shaft of Q170ENC to a machine side rotary shaft.
Never hit the end of the Q170ENC coupling shaft with a hammer when connecting the coupling to it.
The large loads applied to Q170ENC will damage it.
The Q170ENC uses optical parts. Mount it in an atmosphere where there are extremely few water
drops and little oil and dust.
In any place where the Q170ENC is exposed to water and/or oil, provide protection from oil and water,
e.g. install a cover. In addition, run the cable downward to prevent oil and/or water from running on the
cable into the Q170ENC. When it is inevitable to mount the Q170ENC vertically or obliquely, trap for
the cable.
Use the Q170ENC within the specified temperature range (-5 to 55°C (23 to 131°F) ).
4 - 17
4 INSTALLATION AND WIRING
4.4 Wiring
DANGER
Completely turn off the externally supplied power used in the system before installation or removing
the module. Not doing so could result in electric shock or damage to the product.
When turning on the power supply or operating the module after wiring, be sure that the module's
terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.
CAUTION
Be sure to ground of the earth terminal FG and LG. Not doing so could result in electric shock or
operation failure. (Ground resistance: 100 or less)
When wiring in the Motion controller, be sure that it is done correctly by checking the product's rated
voltage and the terminal layout. Connecting a power supply that is different from the rating or
incorrectly wiring the product could result in fire or damage.
External connections shall be crimped or pressure welded with the specified tools, or correctly
soldered. Imperfect connections could result in short circuit, fire, or operation failure.
Tighten the terminal screws within the specified torque range. If the terminal screws are loose, it could
result in short circuit, fire, or operation failure. Tightening the terminal screws too far may cause
damages to the screws and/or the module, resulting in drop, short circuit, or operation failure.
Be sure there are no foreign matters such as sawdust or wiring debris inside the module. Such debris
could cause fire, damage, or operation failure.
The module has an ingress prevention label on its top to prevent foreign matter, such as wiring debris,
from entering the module during wiring.
Do not remove this label during wiring.
Before starting system operation, be sure to remove this label because of heat dissipation.
This section described instructions for the wiring of the power supply.
(1) Power supply wiring
(a) 100VAC, 200VAC and 24VDC wires should be twisted as dense as possible
respectively. Connect the modules with the shortest distance.
Also, to reduce the voltage drop to the minimum, use the thickest wires (Up
2
to 2.0mm ) possible.
Use the wires of the following core size for wiring.
Application Recommended core size
100VAC, 200VAC, 24VDC wires 2.0mm2 or less
2
0.3 to 0.75mm
I/O equipment
(Outside diameter 2.8mm (0.11inch) or less)
Ground wire 2.0mm2 or more
4 - 18
4 INSTALLATION AND WIRING
(b) Do not bundle the 100VAC and 24VDC wires with, or run them close to, the
main circuit (high voltage, large current) and I/O signal lines (including
common line).
Reserve a distance of at least 100mm (3.94inch) from adjacent wires.
Multiple CPU
AC
system
E2
POINTS
(1) Separate the ground of the surge absorber for lighting (E1) from that of the
Multiple CPU system (E2).
(2) Select a surge absorber for lighting whose power supply voltage does no
exceed the maximum allowable circuit voltage even at the time of maximum
power supply voltage elevation.
(b) The wires used for connection to the terminal block should be 0.3 to
2
0.75mm in core and 2.8mm (0.11inch) or less in outside diameter.
(c) Run the input and output lines away from each other.
(d) When the wiring cannot be run away from the main circuit and power lines,
use a batch-shielded cable and ground it on the Motion controller side.
In some cases, ground it in the opposite side.
Multiple CPU system
Shield cable
Input
RA
Output Shield
DC
(e) Where wiring runs through piping, ground the piping without fail.
(f) Run the 24VDC input line away from the 100VAC and 200VAC lines.
4 - 19
4 INSTALLATION AND WIRING
(g) Wiring of 200m (656.17ft.) or longer distance will give rise to leakage
currents due to the line capacity, resulting in a fault.
Refer to the troubleshooting chapter of the I/O Module User's Manual.
(h) As a countermeasure against the power surge due to lightning, separate the
AC wiring and DC wiring and connect a surge absorber for lightning (Refer
to Section 4.4.1(1)).
Failure to do so increases the risk of I/O device failure due to lightning.
(3) Grounding
For grounding, follow the steps (a) to (c) shown below.
(a) Use a dedicated grounding wire as far as possible.
(Ground resistance: 100 or less)
grounding grounding
(1) Independent grounding.....Best (2) Common grounding.....Good (3) Joint grounding.....Not allowed
2
(c) For grounding a cable, use the cable of 2 mm or more.
Position the ground-contact point as nearly to the Multiple CPU system as
possible, and reduce the length of the grounding cable as much as possible.
4 - 20
4 INSTALLATION AND WIRING
The following diagram shows the wiring example of power lines, grounding lines, etc.
to the main and extension base units.
Fuse
(Note-1)
ERR
AC
DC FG
24VDC
LG
INPUT
100-240VAC
Ground
Connect to 24VDC terminals wire
of I/O module that requires Grounding
24VDC internally.
Extension base unit
Extension cable (Q68B)
Q61P I/O module
100VAC
(Note-1)
ERR
FG
LG
INPUT
100-240VAC
Ground
wire
Grounding
4 - 21
4 INSTALLATION AND WIRING
POINT
2
(1) Use the thickest possible (up to 2mm ) wires for the 100/200 VAC and 24 VDC
power cables. Be sure to twist these wires starting at the connection terminals.
To prevent a short circuit should any screws loosen, use solderless terminals
with insulation sleeves of 0.8 mm (0.03 inch) or less.
Also, only two solderless terminals can be connected per terminal block.
Terminal
block
Solderless terminals
with insulation sleeves
(3) No system error can be detected by the ERR terminal of an extension base
unit. (The ERR terminal is always set off.)
4 - 22
4 INSTALLATION AND WIRING
SSCNET cable is made from optical fiber. If optical fiber is added a power such as a
major shock, lateral pressure, haul, sudden bending or twist, its inside distorts or
breaks, and optical transmission will not be available. Especially, as optical fiber for
MR-J3BUS M, MR-J3BUS M-A is made of synthetic resin, it melts down if being left
near the fire or high temperature. Therefore, do not make it touched the part, which
becomes high temperature, such as radiator or regenerative brake option of servo
amplifier.
Be sure to use optical fiber within the range of operating temperature described in this
manual.
Read described item of this section carefully and handle it with caution.
(2) Tension
If tension is added on the SSCNET cable, the increase of transmission loss
occurs because of external force which concentrates on the fixing part of
SSCNET cable or the connecting part of SSCNET connector. At worst, the
breakage of SSCNET cable or damage of SSCNET connector may occur.
For cable laying, handle without putting forced tension. (Refer to "APPENDIX1.1
SSCNET cables" for the tension strength.)
4 - 23
4 INSTALLATION AND WIRING
(4) Twisting
If the SSCNET cable is twisted, it will become the same stress added condition
as when local lateral pressure or bend is added. Consequently, transmission loss
increases, and the breakage of optical fiber may occur at worst.
(5) Disposal
When incinerating optical cable (cord) used for SSCNET , hydrogen fluoride gas
or hydrogen chloride gas which is corrosive and harmful may be generated. For
disposal of optical fiber, request for specialized industrial waste disposal services
who has incineration facility for disposing hydrogen fluoride gas or hydrogen
chloride gas.
40mm
Motion CPU module Motion CPU module
(1.58inch)
MELSEC
Q61P
POWER
Q03DCPU
MODE
Q173DCPU
QX40
01 2 3 4 5 6 7
89 AB CDE F
QX40
0 1 2 3 45 6 7
8 9 A B CDE F
Q172DEX
SY. ENC TREN
1 1
Q173DPX
PLS.A PLS. B TREN
1 1 1
or more
RUN 2 2
2 2 2
ERR. 3 3 3
USER SW
BAT. 1 2
BOOT STOP RUN
CAUTION
EMI
SY. ENC1
PULSER II/O11
/ O1 1
PULL
Q312DB
CN1
USB
PULL
Panel Door
CN2
RS-232
FRONT
BAT
Q172DEX Q173DPX
100mm
(3.94inch)
100mm 123.5mm or more
(3.94inch) (4.86inch)
or more
5mm(0.20inch) 5mm(0.20inch)
or more (Note-1) or more
(Note-1) : 20mm (0.79 inch) or more when the adjacent module is not removed and the extension cable is connected.
4 - 24
4 INSTALLATION AND WIRING
• Bundle fixing
Optical cord should be given loose slack to avoid from becoming smaller than the minimum bend radius, and it
should not be twisted. When laying cable, fix and hold it in position with using cushioning such as sponge or
rubber which does not contain plasticizing material.
Control panel
Code
Loose slack
4 - 25
4 INSTALLATION AND WIRING
MEMO
4 - 26
5 TRIAL OPERATION AND ADJUSTMENT
5-1
5 TRIAL OPERATION AND ADJUSTMENT
5-2
5 TRIAL OPERATION AND ADJUSTMENT
Check wiring and module installation Refer to Section 2.1.4 for installation method and
installation position.
(1) Check the installation position and
condition of each modules. Refer to Section 4.1.3 for installation of module.
(2) Check the connecting condition of
connectors. DANGER
(3) Check that all terminal screws are tight. Be sure to ground the Motion controllers, servo
(4) Check the ground wires of servo amplifiers and servomotors.
amplifier, etc.. (Ground resistance: 100 or less)
(5) Check the servomotor wiring (U, V, W). Do not ground commonly with other devices.
(6) Check the regenerative resistor wiring.
(7) Check the circuit of emergency stop or CAUTION
forced stop.
Check that the installation position of modules
and combination of modules are correct.
Wrong installation and combination may damage
the modules.
[Installation mode]
Install operating system software Refer to Section 5.3
Motion CPU : The operating system software is not installed at
Install the operating system software to
the CPU module using MT Developer. the time of Motion CPU module purchase.
Be sure to install the operating system software to
be used before a system start.
Servo amplifier setting Refer to Section 2.4.8(4)
Servo amplifier
Set the axis number of servo amplifier.
CAUTION
When using a regenerative resistor, shut the
Turn ON power supply power OFF with an error signal. The
regenerative resistor may abnormally overheat
PLC CPU Set the RUN/STOP/RESET switch of PLC
CPU module to STOP, and turn ON the due to a fault in the regenerative transistor, etc.,
Motion CPU and may lead to fires.
Multiple CPU power supply.
Always take heat measure such as flame
proofing for the inside of the control panel where
[System setting] the servo amplifier or regenerative resistor is
Multiple CPU parameters setting mounted and for the wires used. Failing to do so
may lead to fires.
Set the following positioning parameters
Motion CPU using MT Developer.
(1) Multiple CPU setting
(2) Automatic refresh setting
(3) System setting
[Parameter setting]
PLC parameter setting
PLC CPU Set the parameter setting using
GX Developer.
1)
5-3
5 TRIAL OPERATION AND ADJUSTMENT
1)
(Note) : An error may occur if the power is turned on
before system setting. In the case, reset the
Turn ON power supply again Multiple CPU system after system setting.
Turn ON again the power supply or reset Refer to the "Q173DCPU/Q172DCPU Motion
of Multiple CPU system. controller Programming Manual (COMMON)"
at the system setting error occurrence.
2)
5-4
5 TRIAL OPERATION AND ADJUSTMENT
2) DANGER
Never open the front case or terminal cover at
[Programming] times other than wiring work or periodic
inspections even if the power is OFF. The
Create Motion programs insides of the Motion controller and servo
Motion CPU Create the Motion programs using amplifier are charged and may lead to electric
shocks.
MT Developer.
When performing wiring work or inspections,
turn the power OFF, wait at least ten minutes,
[Programming] and then check the voltage with a tester, etc..
Create PLC programs Failing to do so may lead to electric shocks.
Create the PLC programs to start of Wire the units after mounting the Motion
Motion programs using GX Developer. controller, servo amplifier and servomotor.
Failing to do so may lead to electric shocks or
damage.
PLC CPU
Write the positioning data and Motion Use the program commands for the program
Motion CPU with the conditions specified in the instruction
programs created to the Motion CPU
module. manual.
Some devices used in the program have fixed
applications, so use these with the conditions
specified in the programming manual.
Turn ON power supply again
Turn ON again or reset the Multiple CPU
system power supply .
CAUTION
If safety standards (ex., robot safety rules, etc., )
apply to the system using the Motion controller,
servo amplifier and servomotor, make sure that
Turn ON servo amplifiers power supply
the safety standards are satisfied.
Check the emergency stop ON and forced Construct a safety circuit externally of the
stop ON, and turn ON the power supply of Motion controller or servo amplifier if the
servo amplifiers and servomotors. abnormal operation of the Motion controller or
servo amplifier differ from the safety directive
[Test mode operation in the system.
servo start-up
(Initial check) ]
Check servo am plifier Axis No. and error description of servo amplifier which
detected errors are displayed on initial check screen.
Check that the mounted servo amplifiers
operate correctly.
[Test mode
Motion CPU servo start-up
(Upper/lower stroke
limit check) ]
Check upper/lower stroke limits
Check that the upper/lower stroke limits
operate correctly.
3)
5-5
5 TRIAL OPERATION AND ADJUSTMENT
3)
[Test mode
JOG operation ]
Check machine operation
CAUTION
Check the followings by making the machine
operate with the JOG operation of The system must have a mechanical
MT Developer. allowance so that the machine itself can stop
(1) Machine operates correctly
even if the stroke limits switch is passed
(no vibration, hunting, etc. )
(2) Stroke limits operate correctly through at the max. speed.
(3) Machine stops by the emergency stop Execute the test operation in the system that
or forced stop. it is low-speed as much as possible and put
forced stop, and confirm the operation and
[Test mode safety.
home position return ]
Check home position return
Check the followings by executing the home
position return.
(1) Home position return direction
(2) Home position return data
(3) Proximity dog position
Motion CPU
[Programming]
Check Motion program
Set the RUN/STOP/RESET switch of PLC
CPU module to RUN and the RUN/STOP
switch of Motion CPU module to RUN, and
check that all positioning controls by Motion
programs are correct.
[Monitor]
Check by automatic operation
END
POINTS
(1) Make note of motor module names before the motor is mounted on a machine.
The motor name plate may not be visible after the motor is mounted.
(2) When the servo amplifier, servomotor is first turned on, check the operation
before the servomotor is mounted on a machine to avoid an unexpected
accidents such as machine breakage.
5-6
5 TRIAL OPERATION AND ADJUSTMENT
The operating system software must be installed to the Motion CPU module by using
the peripheral device and MT Developer.
The installation procedure is shown below.
START
END
POINTS
(1) The operating system software was not installed at the time of Motion CPU
module purchase. Be sure to install the operating system software to be used
before a system start.
(2) Be sure to change a rotary switch after turning off the power supply.
(3) Even if the operating system software is installed, the programs, parameters
and absolute position data written in the Motion CPU module does not be
rewritten.
(4) Do not turn off the power supply during installation. Doing so could result
damage the Motion CPU module.
(5) When the operating system software is installed at set the multiple Motion
CPU modules not installed in one base unit, be sure to set to installation mode
(set a rotary switch1 (SW1) to "A" position.) of all not installed Motion CPU
modules to install.
(Note): If the power supply is turned ON without setting all Motion CPU module
not installed to installation mode, it does not operate normally.
Be sure to install the operating system software before system start.
5-7
5 TRIAL OPERATION AND ADJUSTMENT
At the worksite, copy the following table for use as a check sheet.
Work Step Item Trial Operation and Adjustment Confirmation Check
Check that the each module is installed correctly.
Check that the each connector is connected correctly.
Check the each terminal screw for looseness.
Check that the earth wires of power supply module or servo amplifiers, etc. are
Installation of
Before power supply correct.
unit/module
ON Check that the servomotor wiring is correct.
and basic wiring
Check that the regenerative option wiring is correct.
Check that the circuit of emergency stop and forced stop are correct.
Check that the wiring of each power supply and I/O are correct.
Check that the rotary switch setting is correct.
Installation of OS Check that the operating system software is compatible.
System setting Check that the system setting is correct.
Power supply ON/
Check that the upper/lower stroke limit inputs are correct.
Q172LX external
Check that the STOP signal input is correct.
Motion CPU module signal
Check that the proximity dog and speed/position switching signal input are correct.
in STOP status/
Program/ Check that the Motion program, PLC program and positioning data are stored in the
positioning data PLC/Motion CPU module correctly.
PLC CPU module in
Check the communications with servo amplifiers.
STOP status
Check that the rotation direction for JOG operation is correct.
Check that the upper/lower limit switches operate correctly.
Basic axis Check that the rotation at maximum command speed is motor rating or less.
Motion CPU module
operations Check that the machine operates correctly by the JOG operation.
in RUN status/
(Check each axis) Check that the machine stops by the upper/lower stroke limit.
Check that the machine stops by the emergency stop or forced stop.
PLC CPU module in
Check that the home position return is executed correctly.
STOP status
Check that each positioning control of Motion program is operates correctly.
Check the each operation in manual operation mode of system during Motion program
execution.
Check that the machine operation stops immediately by the emergency stop or
forced stop.
Manual operation
Check the operation of each actuator and confirmation limit switch.
Check that the emergency stop, forced stop and equipment alarm signals are
correct.
Checks in compliance with control specifications specific to system and equipment.
Motion CPU module Check the each operation in manual operation mode of system during Motion program
in RUN status/ execution.
Check that the automatic operation motions.
PLC CPU module in
Check that the machine operation stops immediately by the emergency stop or
RUN status
Automatic forced stop.
operation Check that the module or equipment alarm causes an immediate stop or cycle
stop.
Check that the restoring operation can be performed after an alarm stop.
Make other checks in compliance with control specifications specific to system and
equipment.
Check that the acceleration/deceleration torque is maximum torque or less.
Torque check
Check that the continuous effective load torque is rated torque or less.
5-8
6 INSPECTION AND MAINTENANCE
DANGER
Do not touch the terminals while power is on. Doing so could cause electric shock.
Correctly connect the battery. Also, do not charge, disassemble, heat, place in fire, short circuit, or
solder the battery.
Mishandling of a battery may cause overheating, cracks or ignition which could result in injury and fire.
Switch off all phases of the externally supplied power used in the system when cleaning the
module or retightening the terminal or module mounting screws.
Not doing so could result in electric shock.
Under tightening of terminal screws can cause a short circuit or malfunction.
Over tightening of screws can cause damages to the screws and/or the module, resulting in
fallout, short circuits, or malfunction.
The capacitor is mounted to the modules. Do not incinerate the modules so that the incineration of
capacitor may cause burst.
CAUTION
Read the manual carefully and pay careful attention to safety for the on-line operation (especially
program change, forced stop or operation change) performed by connecting peripheral devices to the
CPU module during operation. 6
Erroneous operation may cause machine breakage or accident.
Never try to disassemble or modify module. It may cause product failure, operation failure, injury or fire.
Use any radio communication device such as a cellular phone or a PHS phone more than 25cm (9.85
inch) away in all directions of the Motion controller.
Failure to do so may cause a malfunction.
Completely turn off the externally supplied power used in the system before installation or removing
the module. Not doing so could result in damage to the product.
Do not install/remove the module on to/from base unit or terminal block more than 50 times, after the
first use of the product. Failure to do so may cause the module to malfunction due to poor contact of
connector.
Do not drop or impact the battery installed to the module. Doing so may damage the battery, causing
battery liquid to leak in the battery.
Do not use the dropped or impacted battery, but dispose of it.
Before touching the module, always touch grounded metal, etc. to discharge static electricity from
human body. Failure to do so may cause the module to fail or malfunction.
Do not directly touch the module's conductive parts and electronic components. Touching them could
cause an operation failure or give damage to the module.
In order that you can use the Motion controller in normal and optimal condition at all times, this
section describes those items that must be maintained or inspected daily or at regular intervals.
6-1
6 INSPECTION AND MAINTENANCE
In order that can use the Motion controller in safety and normal, those items that must
be inspected list below.
DANGER
Never open the front case or terminal covers while the power is ON or the unit is running, as this may
lead to electric shocks.
Never run the unit with the front case or terminal cover removed. The high voltage terminal and
charged sections will be exposed and may lead to electric shocks.
Never remove the front case or terminal cover at times other than wiring work or periodic inspections
even if the power is OFF. The insides of the Motion controller and servo amplifier are charged and
may lead to electric shocks.
When performing wiring work or inspections, turn the power OFF, wait at least ten minutes, and then
check the voltage with a tester, etc.. Failing to do so may lead to electric shocks.
Never operate the switches with wet hands, as this may lead to electric shocks.
Do not damage, apply excessive stress, place heavy things on or sandwich the cables, as this may
lead to electric shocks or fire.
Do not touch the Motion controller, servo amplifier or servomotor terminal blocks while the power is
ON, as this may lead to electric shocks.
Do not touch the built-in power supply, built-in grounding or signal wires of the Motion controller and
servo amplifier, as this may lead to electric shocks.
CAUTION
Be sure to ground the Motion controller, servo amplifier and servomotor. Do not ground
commonly with other devices. (Ground resistance : 100 or less)
The wiring work and inspections must be done by a qualified technician.
Wire the units after mounting the Motion controller, servo amplifier and servomotor. Failing to do so
may lead to electric shocks or damage.
Perform the daily and periodic inspections according to the instruction manual.
Perform maintenance and inspection after backing up the program and parameters for the Motion
controller and servo amplifier.
Do not place fingers or hands in the clearance when opening or closing any opening.
Periodically replace consumable parts such as batteries according to the instruction manual.
Do not touch the lead sections such as ICs or the connector contacts.
Do not place the Motion controller or servo amplifier on metal that may cause a power leakage or
wood, plastic or vinyl that may cause static electricity buildup.
Do not perform a megger test (insulation resistance measurement) during inspection.
When replacing the Motion controller or servo amplifier, always set the new unit settings correctly.
After maintenance and inspections are completed, confirm that the position detection of the
absolute position detector function is correct.
6-2
6 INSPECTION AND MAINTENANCE
CAUTION
Do not short circuit, charge, overheat, incinerate or disassemble the batteries.
The electrolytic capacitor will generate gas during a fault, so do not place your face near the Motion
controller or servo amplifier.
The electrolytic capacitor and fan will deteriorate. Periodically change these to prevent secondary
damage from faults. Replacements can be made by our sales representative.
If an error occurs in the self diagnosis of the Motion controller or servo amplifier, confirm the check
details according to the instruction manual, and restore the operation.
If a dangerous state is predicted in case of a power failure or product failure, in order to prevent that
state, use a servomotor with electromagnetic brakes for maintenance or mount a brake mechanism
externally.
Use a double circuit construction so that the electromagnetic brake operation circuit can be operated
by emergency stop signals set externally.
Shut off with the
Shut off with servo ON signal OFF, emergency stop
alarm, electromagnetic brake signal. signal (EMG).
Servomotor
RA1 EMG
Electromagnetic
brakes
24VDC
If an error occurs, remove the cause, secure the safety and then resume operation after alarm
release.
The unit may suddenly restart after a power failure is restored, so do not go near the machine. (Design
the machine so that personal safety can be ensured even if the machine restarts suddenly.)
Confirm and adjust the program and each parameter before operation. Unpredictable movements may
occur depending on the machine.
Extreme adjustments and changes may lead to unstable operation, so never make them.
Do not apply a voltage other than that specified in the instruction manual on any terminal.
Doing so may lead to destruction or damage.
Do not mistake the terminal connections, as this may lead to destruction or damage.
Do not mistake the polarity ( + / - ), as this may lead to destruction or damage.
Do not touch the heat radiating fins of controller or servo amplifier, regenerative resistor and
servomotor, etc., while the power is ON and for a short time after the power is turned OFF. In this
timing, these parts become very hot and may lead to burns.
Always turn the power OFF before touching the servomotor shaft or coupled machines, as these parts
may lead to injuries.
Do not go near the machine during test operations or during operations such as teaching. Doing so
may lead to injuries.
Do not bunch the control wires or communication cables with the main circuit or power wires, or
lay them closely. They should be installed 100 mm (3.94 inch) or more from each other.
Trying to bunch or install could result in noise that would cause operation failure.
6-3
6 INSPECTION AND MAINTENANCE
Battery error
"BT1" does not display.
warning
(Abnormal if steady "BT1" display.)
(2.7V or less) Refer to Section
Battery error 6.5
"BT2" does not display.
warning
(Abnormal if steady "BT2" display.)
(2.5V or less)
" . . . " does not display.
WDT error
(Abnormal if steady " . . ." display.)
Refer to Section
2.4.1(2)
" AL" does not flash.
Others
(Abnormal if " . . ." flashes.)
Check that the LED is The LED must be OFF when the input power is turned OFF.
Input LED ON/OFF. (Abnormal if the LED does not turn ON or turn OFF as Refer to
I/O module
6-4
6 INSPECTION AND MAINTENANCE
The items that must be inspected one or two times every 6 months to 1 year are listed
below. When the equipment is moved or modified, or layout of the wiring is changed,
also implement this inspection.
Looseness, rattling
looseness and rattling. solidly. module is loose, fix it with
3
screws.
Adhesion of dirt and Dirt and foreign matter must not
Check visually. Remove and clean.
foreign matter be present.
Looseness of terminal Try to further tighten screws with a
Screws must not be loose. Retighten the terminal screws.
screws screwdriver.
Connection
6-5
6 INSPECTION AND MAINTENANCE
6.4 Life
(1) The life of the capacitor greatly depends on ambient temperature and operating
conditions. The capacitor will reach the end of its in 10 years of continuous
operation in normal air-conditioned environment.
(2) Change the bearings in 20,000 to 30,000 hours as a guideline under rated speed.
This differs on the operating conditions, The bearings must also be changed if
unusual noise or vibration is found during inspection.
6-6
6 INSPECTION AND MAINTENANCE
The battery installed in the Motion CPU module is used for data retention during the
power failure of the program memory and latch device. Special relays SM51 or SM58
turn on due to the decrease of battery voltage. Even if the special relays turn on, the
program and retained data are not erased immediately.
However, if these relays are overlooked, the contents may be erased.
After relay SM51 or SM58 turns on, replace the battery quickly within the data
retention time for power failure (3 minutes).
POINT
(1) SM51 or SM58 turns on when the battery voltage falls below the specified
value, and remains ON even after the voltage is recovered to the normal
value. SM51 or SM58 turns off by power supply on again or reset.
(2) After SM51 or SM52 turns on, replace the battery quickly.
• SM51 turns on at the battery voltage 2.5V or less.
• SM58 turns on at the battery voltage 2.7V or less.
(3) If SM51 turns on, the details of the programs, parameters and absolute
position data cannot be guaranteed.
It is recommended to back-up the battery periodically.
6-7
6 INSPECTION AND MAINTENANCE
6-8
6 INSPECTION AND MAINTENANCE
POINT
(1) Do not use the battery exceeding its guaranteed life.
(2) When the battery hours (total power failure time) may exceed its guaranteed
value, take the following measure.
• Perform ROM operation to protect a program even if the battery dies at the
Multiple CPU system power-OFF.
• If SM51 or SM52 turns on, the contents of programs, parameters and
absolute position data cannot be guaranteed.
It is recommended to back-up the battery periodically.
(3) When the battery-low special relay SM52 turns on, immediately change the
battery. Even if the alarm has not yet occurred, it is recommended to replace
the battery periodically according to the operating condition
(4) The self-discharge influences the life of battery without the connection to
Q173DCPU/Q172DCPU/Q172DEX. The external battery should be exchanged
approximately every 4 or 5 years.
And, exchange the battery with a new one in 4 to 5 years even if a total power
failure time is guaranteed value or less.
6-9
6 INSPECTION AND MAINTENANCE
POINTS
When replacing the battery, pay attention to the following.
(1) Back up the data using MT Developer before starting replacement.
(2) Firstly back up the data stored in the Motion CPU to the personal computer
which is installed MT Developer then replace the battery with a new one. After
setting the battery in the Battery holder unit, verify the backing up the data to
the personal computer which is installed MT Developer and the data in the
Motion CPU module, confirm the data is not changing.
In the following status, the backup time after power OFF is 3 minutes.
• The battery connector/Q6BAT lead connector is disconnected.
• The battery cable/lead wire of Q6BAT is broken.
Lead wire
END
6 - 10
6 INSPECTION AND MAINTENANCE
POINT
When replacing the battery, pay attention to the following.
(1) The Multiple CPU power supply must be on for 10 minutes or longer before
dismounting the battery.
(2) Encoder data in the memory are backed up for a while by a capacitor even
after the battery is removed. However, since data in the memory may be
erased if the time for replacement exceeds the backup time shown the
following guaranteed value, replace the battery quickly.
• Backup time by capacitor : 3 minutes
Replacing Battery
Battery Connector
(A6BAT/MR-BAT) (BATTERY)
Connect the encoder cable to the
Q172DEX.
END
6 - 11
6 INSPECTION AND MAINTENANCE
When the operation is to be resumed after being stored with the battery removed or
the battery has gone flat during storage, the contents of programs, parameters,
absolute position data and latch data cannot be guaranteed.
Before resuming operation, write the contents of programs, parameters, absolute
position data and latch data backed up prior to storage to SRAM built-in Motion CPU
module.
POINT
Before storing the Motion controller, always back up the contents of programs,
parameters, absolute position data and latch data to SRAM built-in Motion CPU
module.
6 - 12
6 INSPECTION AND MAINTENANCE
6.6 Troubleshooting
This section describes the various types of trouble that occur when the system is
operated, and causes and corrective actions of these troubles.
The basic three points that must be followed in the troubleshooting are as follows.
After checking (a) to (g), monitor the operating conditions of servomotors and
error code using MT Developer and GX Developer.
6 - 13
6 INSPECTION AND MAINTENANCE
This section describes the contents of troubles for the error codes and corrective
actions of the troubles.
As for troubleshooting of PLC CPU, refer to the QCPU User's Manual (Hardware
Design, Maintenance and Inspection) of their respective modules.
POINT
Check that the operating system software is installed before starting the Motion
CPU module.
Error-occurrence description
(a)
"POWER" LED turns off
"Flowchart for when "POWER" LED turns off"
(c)
"A00" displays on 7-segment LED
"Flowchart for when "A00" displays on 7-segment LED"
(f)
"BT " displays on 7-segment LED
"Flowchart for when "BT " displays on 7-segment LED"
(g)
" . . ." displays on 7-segment LED
"Flowchart for when " . . ." displays on 7-segment LED"
(h)
Servo amplifier does not start
"Flowchart for when servo amplifier does not start"
6 - 14
6 INSPECTION AND MAINTENANCE
The following shows the flowchart when "POWER" LED of the power
supply module turns off at the power supply ON or during operation.
NO
Is there a power supply? Supply power.
YES
YES
Is the power NO
supply voltage within the The supply voltage should be within
rated range? the rated range.
YES
YES
NO YES
Does "POWER"
LED turn on?
1) END
6 - 15
6 INSPECTION AND MAINTENANCE
1)
YES
NO
Install all modules that removed from
the base unit to the base unit. H/W fault
Explain the error symptom and get
advice from out sales representative.
NO
H/W fault
Check operation in the order starting
END
with the minimum system.
If the module will not work, explain
the error symptom and get advice
from out sales representative for the
modules with failure.
6 - 16
6 INSPECTION AND MAINTENANCE
(b) Flowchart for when " ." does not flash in the first digit of
7-segment LED
YES
Is the
connecting direction
of extension cable correctly? NO
Connect the extension cable correctly.
(Isn't IN-IN or OUT-OUT
connection?)
YES
NO Does " . " flash YES
in the first digit of 7-segment
LED?
Is the "RESET"
RUN/STOP/RESETand
RUN/STOP switch of CPU Set the RUN/STOP/RESET and
No.1 and target CPU Module RUN/STOP switch to "STOP"
set to STOP?
"STOP"
H/W fault
Check operation in the order starting END
with the minimum system.
If the module will not work, explain
the error symptom and get advice
from out sales representative for the (Note) : Normally, " . " flashes in the first digit of
modules with failure. 7-segment LED.
6 - 17
6 INSPECTION AND MAINTENANCE
Is the
operating system NO
software installed to Motion
CPU module?
YES
6 - 18
6 INSPECTION AND MAINTENANCE
NO
NO
Is ROM operation executed?
YES
Set a rotary switch1 (SW1) to "0", a Set a rotary switch1 (SW1) to "0", a
rotary switch2 (SW2) to "6" of Motion rotary switch2 (SW2) to "0" of Motion
CPU module, and then execute ROM CPU module.
writing. (Mode operated by RAM)
NO
YES
END
6 - 19
6 INSPECTION AND MAINTENANCE
(e) Flowchart for when "AL" "A1" " " displays on 7-segment
LED.
""AL" (flashes 3 times) Steady "A1" display " "" displays at the self-
diagnosis error occurrence.
The following shows the flowchart when the ""AL" (flashes 3 times)
Steady "L01" display " "" display" displays during operation.
: 4-digits error code is displayed in two sequential flashes of 2-digits each.
YES
Hardware cause fault?
NO
NO
Noise cause?
Correct each Multiple CPU system
setting based on the error causes .
YES
Reset the Multiple CPU system. Explain the error symptom and get
advice from out sales representative.
YES
END
6 - 20
6 INSPECTION AND MAINTENANCE
"BT1" or "BT1" displays when the external battery voltage of battery holder
unit is lowered.
"BT1" or "BT1" displays at the following cases.
• BT1: Battery voltage 2.7V or less
• BT2: Battery voltage 2.5V or less
The following shows the flowchart when the "BT " displays.
END
H/W fault
Explain the error symptom and get
advice from out sales representative.
REMARK
If SM51,SM58 turns on, the details of the programs, parameters, absolute position
data and latch data cannot be guaranteed.
It is recommended to back-up the battery periodically.
6 - 21
6 INSPECTION AND MAINTENANCE
Is the error NO
code of Motion CPU WDT
cause "1"?
YES
Is the error NO
code of Motion CPU WDT
Correct the main cycle not to exceed cause "2"?
1.0[s] by the following methods, and
write it to Motion CPU.
1) Change the operation cycle to
YES
large value in the system setting. Is the error NO
2) Reduce the number of execution to code of Motion CPU WDT
the event task program and NMI Correct the Motion operating time to cause "301"?
task program in the Motion SFC shorten by the following methods,
program. and write it to Motion CPU.
3) Reduce the number of execution to 1) Change the operation cycle to YES
the normal task program executed large value in the system setting.
simultaneously 2) Reduce the number of execution to Correct the servo program so that the
in the Motion SFC program. the event task program and NMI number of CPSTART instructions of
4) Reduce the number of automatic task program in the Motion SFC 8 or more points should not exceed
refresh points of CPU shared program. the number of simultaneous startable
memory. programs (14 or less), and write it to
Motion CPU.
YES
END
Explain the error symptom and get
advice from out sales representative.
6 - 22
6 INSPECTION AND MAINTENANCE
The following shows the flowchart when servo amplifier does not start.
YES NO YES
Does servo amplifier start?
YES
NO YES
Does servo amplifier start?
Is the connection of NO
SSCNET cable correct? Connect the SSCNET cable correctly.
YES
NO YES
Does servo amplifier start?
YES
NO YES
Does servo amplifier start?
YES
NO YES
Does servo amplifier start?
6 - 23
6 INSPECTION AND MAINTENANCE
""AL" (flashes 3 times) Steady "S01" display" displays at the servo error
occurrence.
The following shows the flowchart when the ""AL" (flashes 3 times)
Steady "S01" display" displays during operation.
YES
END
6 - 24
6 INSPECTION AND MAINTENANCE
The error code and error message can be read using MT Developer.
The procedure for reading error is as follows.
(1) Connect the PLC CPU module to personal computer (IBM PC/AT).
(2) Start MT Developer.
(3) Select [Online] - [Read from CPU] Menu of MT Developer, and read the project
data from Motion CPU.
(4) Start the monitor screen of MT Developer and select [Motion CPU error batch
monitor] menu.
(5) Confirm the error codes and error messages displayed on screen.
6 - 25
6 INSPECTION AND MAINTENANCE
This section describes possible problems with I/O circuits and their corrective actions.
Leakage AC input
is not Input module
current
turned
OFF. Input module
Power supply
separately.
is not
turned Leakage Input module
current
OFF.
Power supply
• Leakage current due to line capacity of wiring • Same as Example 1.
cable. (However, leakage current is not generated
(Line capacity C of twisted pair wire is approx. when the power supply is located in the input
Input signal 100 pF/m). equipment side as shown below.)
Example 3
is not
Leakage
turned current Resistor R
Input module Input module
OFF.
6 - 26
6 INSPECTION AND MAINTENANCE
is not
turned E1 E2 Input module
OFF. E1 E2 Input module
E1 >E2
Depending on response time setting, noise is Change the response time setting.
imported as input. Example : 1 [ms] 5[ms]
(When excessive noise is cyclic, shorter
response time setting may produce a higher
Example 6
False input effect.) When the above action does not have
due to an effect, take measures against noise to block
noise excessive noise, e.g. avoid tying the power
cables and control cables in a bundle, and add
surge absorbers to the noise sources such as
the relays and contactors used with the same
power supply.
Leakage
Motion CPU
current 4[mA]
module
3.6[k ]
24[VDC]
(a) Because the condition for OFF voltage (18[mA]) of Q172DLX is not
satisfied. Connect a resistor as shown below.
Q172DLX
4[mA]
Iz=0.18[mA]
R<264 [ ].
Assuming that resistor R is 220 [ ], the power capacity W of resistor R is:
2 2
W = (Input voltage) ÷ R = 26.4 ÷ 220 = 3.168 [W]
6 - 27
6 INSPECTION AND MAINTENANCE
(c) The power capacity of the resistor selected is 3 to 5 times greater than the
actual current consumption. 220 [ ], 10 to 15 [W] resistor may therefore be
connected to the terminal in question.
Load
Load
Excessive
voltage is 2)
Example 1
Load
Load does
not turn OFF Resistor
Leakage current
(Triac output).
Load
6 - 28
APPENDICES
APPENDICES
APPENDIX 1 Cables
In this cable connection diagram, maker names of connectors are omitted. Refer to
"APPENDIX 2.7 Connector" for maker names of connectors.
(Note-1) : For the cable of less than 30[m](98.43[ft.]), contact your nearest Mitsubishi sales representative.
(2) Specifications
Description
SSCNET cable model MR-J3BUS M MR-J3BUS M-A MR-J3BUS M-B
0.15 0.3 to 3 5 to 20 30 to 50
SSCNET cable length [m(ft.)]
4.4 0.4
(0.09 0.008)
2.2 0.2
(0.09 0.003)
(0.17 0.016)
2.2 0.07
4.4 0.1
Optical cable
(0.09 0.003)
2.2 0.07
(0.17 0.004)
(Code)
External appearance
[mm(inch)]
(Note-1): This temperature range for use is the value for optical cable (cord) only.
App - 1
APPENDICES
POINTS
(1) If the end face of code tip for the SSCNET cable is dirty, optical transmission
is interrupted and it may cause malfunctions. If it becomes dirty, wipe with a
bonded textile, etc. Do not use solvent such as alcohol.
(2) If the end face of code tip for SSCNET cable is dirty, optical transmission is
interrupted and it may cause malfunctions. If it becomes dirty, wipe with a
bonded textile, etc. Do not use solvent such as alcohol.
(3) When incinerating the SSCNET cable (optical fiber), hydrogen fluoride gas or
hydrogen chloride gas which is corrosive and harmful may be generated. For
disposal of the SSCNET cable (optical fiber), request for specialized
industrial waste disposal services who has incineration facility for disposing
hydrogen fluoride gas or hydrogen chloride gas.
(a) MR-J3BUS M
1) Model explanation
Type: MR-J3BUS M-
Symbol Cable type
None Standard code for inside panel
A Standard cable for outside panel
B Long distance cable
2) Exterior dimensions
• MR-J3BUS015M
[Unit: mm(inch)]
15 13.4 37.65
6.7(0.26) (0.59) (0.53) (1.48)
Protective tube
20.9(0.82)
150 +50
-0
(5.91)
(0.31)
8+0
2.3(0.09)
1.7(0.07)
App - 2
APPENDICES
• MR-J3BUS03M to MR-J3BUS3M
[Unit: mm(inch)]
Refer to the table of this section (1) for cable length (L).
100 100
(3.94) L (3.94)
• MR-J3BUS5M-A to MR-J3BUS20M-A,MR-J3BUS30M-B to
MR-J3BUS50M-B
Refer to the table of this section (1) for cable length (L).
Variation [mm(inch)]
SSCNET cable
A B
MR-J3BUS5M-A to MR-J3BUS20M-A 100(3.94) 30(1.18)
MR-J3BUS30M-B to MR-J3BUS50M-B 150(5.91) 50(1.97)
[Unit: mm(inch)]
Protective tube
(Note)
POINTS
Keep the cap and the tube for protecting light code end of SSCNET cable in a
plastic bag with a zipper of SSCNET cable to prevent them from becoming dirty.
App - 3
APPENDICES
Generally use the serial absolute synchronous encoder cables available as our
products. If the required length is not found in our products, fabricate the cable on the
customer side.
(1) Selection
The following table indicates the serial absolute synchronous encoder cables
used with the serial absolute synchronous encoder.
Connector sets (Q170ENCCNS) are also available for your fabrication.
Table 1 Wire models
Type Length [m(ft.)] Wire model
2(6.56), 5(16.40), 10(32.81), 20(65.62),
Q170ENCCBLM M14B0023 12 pair (BLACK)
30(98.43), 50(164.04)
Use the following or equivalent twisted pair cables as the serial absolute
synchronous encoder cables.
Table 2 Connector sets
Connector sets type Description
Insulation sheath
Conductor
! CAUTION
When fabricating the encoder cable, do not make incorrect connection. Wrong connection will
cause runaway or explosion.
App - 4
APPENDICES
(2) Q170ENCCBL M
(a) Model explanation
Type: Q170ENCCBL M
P5 19 S
LG 11 R
P5 20
LG 12
P5 18
LG 2
BAT 9 E
LG 1
MR 7 K
MRR 17 L
MD 6 H
MDR 16 J
SD plate N
:Twisted pair cable
App - 5
APPENDICES
Generally use the battery cable available as our products. If the required length is not
found in our products, fabricate the cable on the customer side. Make the battery cable
within 0.5m(1.64ft.).
(1) Q170DBATCBL M
(a) Model explanation
Type : Q170DBATCBL M
1 3
+ 4 1 +
2 N.C.
- 3 3 -
N.C. 2
FG 1
App - 6
APPENDICES
Generally use the forced stop input cable available as our products. If the required
length is not found in our products, fabricate the cable on the customer side. Make the
forced stop input cable within 30m(98.43ft.).
(1) Q170DEMICBL M
(a) Model explanation
Type : Q170DEMICBL M
2
1
5556TL (Terminal)
5557-02R (Connector)
EMI.COM 2 EMI.COM
EMI 1 EMI
App - 7
APPENDICES
F01 F01
SW
AB E
CDE
23 6
23 6
CD
45
45
AB
1 2
789 789
STOP RUN
CAUTION
EMI
98(3.86)
CN1
FRONT
BAT
119.3(4.70) 27.4(1.08)
F01 F01
SW
AB E
CDE
23 6
23 6
CD
45
45
AB
1 2
789 789
STOP RUN
CAUTION
EMI
98(3.86)
CN1
CN2
FRONT
BAT
119.3(4.70) 27.4(1.08)
App - 8
APPENDICES
[Unit: mm (inch)]
Q172DLX
98(3.86)
CTRL
Q172DLX
[Unit: mm (inch)]
Q172DEX
SY.ENC TREN
1 1
2 2
SY.ENC1
98(3.86)
LITHIUM BATTERY
MITSUBISHI
SY.ENC2
Q172DEX
4.2(0.17)
90(3.54) 39(1.54) 27.4(1.08)
App - 9
APPENDICES
[Unit: mm (inch)]
Q173DPX
PLS.A PLS.B TREN
1 1 1
2 2 2
3 3 3
98(3.86)
PULSER
ON
1 2 3 4 5 6
KSD06S
Q173DPX
App - 10
APPENDICES
APPENDIX 2.5 Power supply module (Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P)
[Unit: mm (inch)]
(1) Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P
Q61P
POWER
98(3.86)
PULL
90(3.54) 55.2(2.17)
(2) Q64P
[Unit: mm (inch)]
Q64P
POWER
98(3.86)
PULL
115(4.53) 55.2(2.17)
App - 11
APPENDICES
BATTERY
CPU
45(1.77)
60(2.36)
(0.30)
40(1.57)
7.5
80(3.15)
18.4(0.72)
30(1.18)
(0.46)
11.6
App - 12
APPENDICES
22.0 14.0
(0.87) (0.55)
39.0(1.54)
23.8(0.94)
33.3 12.7
(1.31) (0.50)
27.4(1.08)
22.0(0.87) 14.0(0.55)
39.0(1.54)
23.8(0.94)
33.3(1.31) 12.7
(0.22)
5.7
(0.50)
App - 13
APPENDICES
11.5(0.45)
6.7
42.0(1.65)
33.0(1.30)
29.7(1.17)
4.8(0.19)
(0.53)
13.4
1.7
(0.07)
(0.59)
15
2.3
9.3(0.37)
(0.26)
(0.09)
6.7
17.6 0.2 8
(0.69 0.01) (0.31)
20.9 0.2
(0.82 0.01)
App - 14
APPENDICES
6.5 (0.26)
(0.21)
5.4
10.5 (0.41)
19.6 (0.77)
8.5
(0.25)
6.3
3.5
(0.14)
(0.38)
9.6
App - 15
APPENDICES
[Unit: mm (inch)]
NP
50(1.97)
70(2.76)
80(3.15) 1
60(2.36) 0.5
20
80
5 to
12V 0V A B
30
70
60
40
50
M3 6
Space
) 2
-0
44
(2.
72(2.8
3)
62
0.2
[Unit: mm (inch)]
84(3.31) 58.5(2.30)
70.7(2.78) 28(1.10) 30(1.18)
45
7(0.28) 2(0.08)
40(1.57)
14(0.55)
8.72(0.34)
9.52(0.37)
75(2.95)
A
70.7(2.78)
(0.34)
8.72
122.5(4.82)
4- 5.5(0.22)
22.5(0.89)
40(1.57) 36.5(1.44)
App - 16
APPENDICES
MEMO
App - 17
WARRANTY
Please confirm the following product warranty details before using this product.
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad.
If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance.
4. Delivery Term
In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or
adjustments to the customer and Mitsubishi is not liable for on site adjustment or test run of the product.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
MODEL Q173D-U-E
MODEL 1XB927
CODE
When exported from Japan, this manual does not require application to the
IB(NA)-0300133-A(0801)MEE Ministry of Economy, Trade and Industry for service transaction permission.
MITSUBISHI
ELECTRIC Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Straße 8 /// D-40880 Ratingen /// Germany
FACTORY AUTOMATION Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// [email protected] /// www.mitsubishi-automation.com