Harmonic Mitigation Using Hybrid Power Filter To Improve Power Quality
Harmonic Mitigation Using Hybrid Power Filter To Improve Power Quality
Mrs. Prajkta R Gangurde, Mr. Amol S Parkhe, Mr. Sushant S Aher, Mrs Swati S Sangamnere
Abstract— This paper represents a power quality improvement using harmonic mitigation method in
distribution and transmission system. This include the hybrid power filter for mitigating the harmonic in the
power system, the hybrid power filter is the combination active power filter ,passive power filter and voltage
source inverter with the passive component like a capacitor and the inductor. The drawback of the active and
the passive power filter is overcome by designing the hybrid power filter, the capability of harmonic
mitigation can be increased with dc link voltage of the voltage source inverter. in this two method of
implementation is adopted for harmonic mitigation in power system like hybrid mode and the passive mode ,
in passive mode the passive component is used in series such as capacitor and inductor and in hybrid mode
the voltage source inverter is used along with the LC-filter . The power quality improvement and the reactive
power control is also represented in this paper The analysis and MATLAB simulation give the proper
solution to mitigate the harmonic in the distribution and the transmission system to improve the power
quality and system stability .
Index Terms— ,FFT Analysis hybrid power filters, passive power filters, power system harmonics,
reactive power control., Total Harmonic Distortion, power quality, transmission and distribution network..
I. INTRODUCTION
power system and to compensate reactive power the
Today there is need of high quality power supply. Active power filter , passive power filter and hybrid
Due to wide spread used of non linear load such as power filter is used but out of this three power filter
UPS, electronic devices, power electronic devices, the passive power filter is only the series
PC etc the Harmonic is generated in the system. the combination of the inductance and the capacitance
heating of various equipment ,voltage sag ,voltage and this passive power filter is not that much
fluctuation is some of the undesirable effect will effective to mitigate the harmonic in the power
occurs in the power system due to the generation of system as its performance is depends on the
the harmonic. Also this non linear load is responsible impedance. Where as the hybrid power filter can
for the generation of the reactive power in the effectively mitigate the harmonic in the distribution
system so to avoid this undesirable effect on the and transmission System.
If the loads and transmission and distribution sinusoidal is considered as a non linear load such as
system is balanced, the three phase voltages and the computers, variable frequency drives, power
currents have identical wave shapes and are electronic devices, electronic component etc, are
separated by exactly±1/3 of fundamental period. In some common example of the non linear load. and
such a cases only characteristics harmonics exist . If due to used of this nonlinear load there is a issue
we consider 1 harmonic order with 50 Hz frequency regarding a power quality.The non-sinusoidal nature
and positive phase sequence then effect of hormonic developed due to presence of harmonic in current
on various equipment is heating of equipment If we which can cause the adverse effect on the power
consider negative sequence second order harmonics system such as distortion in voltage waveform also
with 100 Hz frequency then effect of heating plus the voltage fluctuation and voltage sag, various
motor problem is there. The aim of this paper is to power system equipment heating. voltage distortion
introduce the hybrid power filter to mitigate the that can affect both the distribution system
harmonic in distribution and transition System to equipment as well as the transmission system
improve the power quality trough the equipment and also the loads connected to it. Power
MATLAB simulation. electronic include the power converters and this
power converter considered as a large non linear load
A. Requirement of Power Quality Improvement
in the power system. The power converters are used
There is linear and non linear load will occurs in the
in the industry for different purposes, such as
power system. The load that draws the current which
adjustable speed drives, uninterruptable power
is proportional to the applied voltage is considered as
supplies etc. When the non sinusoidal current passes
a linear load ,resistive loads is one of the example of
through the system impedance which causes the
the linear load also the incandescent lamp is the
undesirable effect such as the voltage sag and the
linear load .
voltage fluctuation. Hence there is a need of power
quality improvement. Due to the presence of
harmonic in the power system the bus bars and
cables may prematurely age. Fuses and circuit
breakers will not give the better performance to
protect the entire system equipment. as a result of
this the harmonic mitigation is necessary to improve
the power quality.
amplifiers so its performance can be improved with offers a low impedance path or low resistive path to
the help of amplifier. Hence the shunt active filter the harmonic current as a result of this the harmonic
can remove the harmonic in the power system and current is pass through this low impedance path and
remove the voltage and current distortion also so the harmonic current is diverted through shunt
compensate the reactive power in the power system. passive power filter network and system is free from
with the used of active power filter voltage the distortion and current harmonics and due to this
fluctuation and the voltage sag can be remove .As maintaining the power quality. Also the system is
the name indicate that the shunt active power filter free from voltage waveform distortion as well as the
means the active power filter is connected in parallel current waveform distortion proper bypassing of the
to the system. the shunt connected active power filter current is carried out by connecting the shunt
is used to mitigate the current harmonic and the passive power filter in parallel with the harmonic
improve the power quality .The shunt active power producing load. There are different variety of passive
filter generally fabricated with help of Insulated gate filters is generally used to eliminate harmonic such
bipolar transistor ,Thyristors, bipolar junction as single tuned, double tuned, high pass and low pass
transistor , static induction thyristor ,gate turn off filter, c-type filters. But out of this all type of passive
thyristor to compensate the harmonic component of filter the most commonly used filter are the single
the load current as well as the source current. tune and double tuned passive power filter. In the
shunt connected passive power filter the combination
of capacitance and the inductance generally provide
low impedance or resistive path for tuned harmonics
but there is one drawback associated with this shunt
connected passive power filter as this power filter
doesn’t eliminate harmonics to a greater level .Figure
Figure 3: The block diagram of the shunt connected 2 shows the block diagram of shunt connected
active power filter passive power filter in which the ac source is
This shunt connected active power filter generally connected to the non linear load it can also used the
used to inject the active power to compensate the six pulse or twelve pulse ac-dc converter with R-L
voltage sag and voltage disturbances in the load .This is widely used configuration or
distribution and transmission system or grid. arrangement of shunt connected passive power
filters.
C. Shunt Passive Power Filter
The shunt passive power filter nothing but a
series parallel combination of the passive element
such the inductor ,capacitor and a resistor .Generally
this type of shunt connected passive power filter can
sequence current harmonic and this arises due to the of filter has been developed in 1920.The Kirchhoff’s
several single-phase non linear loads and are law is one of the important law which is used in the
effectively considered up in the neutral conductor design of the Low order filters by developing the
due to this the harmonic current in the neutral transfer function and this type of analysis is usually
conductor is higher than in the phase conductor and developed only to carried out for simple filters of 1st
causes the neutral conductor overload, common or 2nd order due to such design there is a advantage
mode neutral to earth voltages, increase of phase of the simplicity of approach and the ability to easily
voltage distortion, and transformers overheating and extend to higher orders. By continued-fraction or
generator overheating. partial-fraction expansions of the polynomial the
actual element values of the passive and active and
II. LITRAUTRE REVIEW
also the hybrid power filter are obtained. A different
The harmonic is nothing but an integral multiple of type of mathematical techniques or method is
the fundamental frequency there is several types of employed to analyze the behavior of a given digital
electronic filter this electronic filter is developed by filter .this paper presents a combined system of a
using only resistors and capacitors or resistors and passive filter and a small rated active filter ,both
inductors. As per the connection of the inductance connected in series or parallel and also the passive
and capacitance connection RC single-pole filters power filter is integrated with voltage source inverter
and RL single-pole filters is developed. In resent, to obtained the hybrid power filter .The passive
complex multi pole LC filters and the Hybrid filters power filter generally remove low order harmonic.
are also developed by combining the passive filter or Whereas on the other hand the hybrid power filter
the resonant cell with the voltage source inverter in improving the filtering characteristics of the passive
that generally 12 pulse or 18 pulse voltage source filters. Due to such combination there is great
inverter is used. The implementation of passive reduction in rating of the active power filter and also
power filter is generally depends on the combination eliminating all the harmonics and the limitation faced
of the resistance ,inductance, and capacitance and by using only the passive power filter, by taking into
are called as passive filters, because they do not considering a practical and economical aspect of the
depend upon an external power supply and where as system.
the active power filter contain the active element. In
passive filter the reactive elements of the filter is III. HYBRID POWER FILTER TOPOLOGY
inductors and capacitors. are The number of The resonant cells is the three single-phase
elements determines the order of the impedances in three phases and in neutral branches
filter. Historically, the design of linear analog filter of power filter are called a passive filter, and this
is mainly depend on the Q factor and this quality associated with several resonance frequencies. As
factor measure the frequency of the tuning circuit. As per the connection of the resonant cell power filter
the requirements of telecommunications the design gives two groups of resonance frequencies, in which
and the function of this notch filter is that it filter with controlled system
injected current controller block this block consist switching pulses of the Voltage Source Inverter from
of PI controller, third one is the dc link voltage the reference voltage of the Voltage Source Inverter
controller block , fourth one is the modulator block and The next important part in the configuration is
and , the main function of the grid current processing the voltage source inverter and the resonant cell The
block is that selecting the current harmonics to be resonant cells that is the passive filter of the hybrid
filtered from the grid current .the function of the power filter provide the very low impedance path to
injected current controller to sets a reference voltage positive sequence and negative sequence and zero
for the Voltage source Inverter in order to mitigate sequence currents at the particular resonance
the selected current harmonics in the distribution frequencies therefore, to inject into the grid
system. The function of the dc-link voltage controller significant levels of harmonic currents a low dc link
block is that it modifies the original reference voltage voltage is necessary in the Voltage Source Inverter.
of the Voltage Source Inverter by adding an extra As the frequency goes far away from the resonance
voltage in order to keep the dc-link voltage at its frequency then impedance offered by the resonant is
normal rated value. also increases hence hybrid power filter can
compensate only a limited range harmonics. Hence,
the grid current processing block that is the notch
filter selects those frequencies that are suitable to be
filtered from the grid current by using signal filtering
methods. As there is increase in the dc-link voltage
level of voltage source inverter the harmonics
mitigation range can also be increased but this
increases the rating of voltage source inverter and