Commissioning 5

Frequency converters, also known as variable frequency drives (VFDs), are pivotal in modern motor control and
motion applications.Note
These devices regulate the speed and torque of electric motors by varying the frequency and
voltage of the powerFor
supplied to them.
a detailed This capability
description enables
of parameter precise
settings for thecontrol over motor operation,
quick commissioning, refer to theleading to
enhanced efficiency,topic "Quick
energy commissioning
savings, (Pageperformance
and improved 60)". in various industrial and commercial settings.
How to use the frequency converter in motor motion control?

5.1 The built-in Basic Operator Panel (BOP)

5.1.1 Introduction to the built-in BOP

SINAMICS V20 Inverter


Operating Instructions, 09/2014, A5E34559884 49
Commissioning
5.1 The built-in Basic Operator Panel (BOP)

Button functions

Stops the inverter


Single press OFF1 stop reaction: the inverter brings the motor to a standstill in the ramp-
down time set in parameter P1121.
Note:
If configured to be an OFF1 stop, this button is inactive in AUTO mode.
Double press (< 2 s) or OFF2 stop reaction: the inverter allows the motor to coast to a standstill
long press ( > 3 s) without using any ramp-down times.
Starts the inverter

If the inverter is started in HAND / JOG mode, the inverter running icon ( ) displays.
Note:
This button is inactive if the inverter is configured for control from terminals (P0700 = 2, P1000 = 2) and
is in AUTO mode.
Multi-function button
Short press ( < 2 s) • Enters the parameter setting menu or moves to the next screen
• Restarts the digit by digit editing on the selected item
• Returns to the fault code display
• If pressed twice in digit by digit editing, returns to the previous screen
without changing the item being edited
Long press ( > 2 s) • Returns to the status screen
• Enters the setup menu
Short press ( < 2 s) • Switches between status values
• Enters edit value mode or change to the next digit
• Clears faults
• Returns to the fault code display
Long press ( > 2 s) • Quick parameter number or value edit
• Accesses fault information data
Hand/Jog/Auto
+ Press to switch between different modes:

Note:
Jog mode is only available if the motor is stopped.

SINAMICS V20 Inverter


50 Operating Instructions, 09/2014, A5E34559884
Commissioning
5.5 Quick commissioning

Connection macro Cn001 - BOP as the only control source

Connection macro settings:

Parameter Description Factory default Default for Cn001 Remarks


P0700[0] Selection of command source 1 1 BOP
P1000[0] Selection of frequency 1 1 BOP MOP
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
P0771[0] CI: Analog output 21 21 Actual frequency
P0810[0] BI: CDS bit 0 (Hand/Auto) 0 0 Hand mode

SINAMICS V20 Inverter


Operating Instructions, 09/2014, A5E34559884 65
Commissioning
5.5 Quick commissioning

Connection macro Cn002 - Control from terminals (PNP/NPN)


External control - Potentiometer with setpoint

● Hand/Auto switch between the BOP and terminals by pressing +


● Both NPN and PNP can be realized with the same parameters. You can change the
connection of the digital input common terminal to 24 V or 0 V to decide the mode.

Connection macro settings:

Parameter Description Factory default Default for Cn002 Remarks


P0700[0] Selection of command source 1 2 Terminal as command source
P1000[0] Selection of frequency 1 2 Analog as speed setpoint
P0701[0] Function of digital input 1 0 1 ON/OFF
P0702[0] Function of digital input 2 0 12 Reverse
P0703[0] Function of digital input 3 9 9 Fault acknowledgement
P0704[0] Function of digital input 4 15 10 JOG forward
P0771[0] CI: Analog output 21 21 Actual frequency

SINAMICS V20 Inverter


66 Operating Instructions, 09/2014, A5E34559884
Commissioning
5.5 Quick commissioning

Connection macro Cn010 - USS control

Connection macro settings:

Parameter Description Factory default Default for Cn010 Remarks


P0700[0] Selection of command 1 5 RS485 as the command source
source
P1000[0] Selection of frequency 1 5 RS485 as the speed setpoint
P2023[0] RS485 protocol selection 1 1 USS protocol
P2010[0] USS/MODBUS baudrate 6 8 Baudrate 38400 bps
P2011[0] USS address 0 1 USS address for inverter
P2012[0] USS PZD length 2 2 Number of PZD words
P2013[0] USS PKW length 127 127 Variable PKW words
P2014[0] USS/MODBUS telegram off 2000 500 Time to receive data
time

Connection macro Cn011 - MODBUS RTU control

Connection macro settings:

Parameter Description Factory default Default for Cn011 Remarks


P0700[0] Selection of command source 1 5 RS485 as the command source
P1000[0] Selection of frequency 1 5 RS485 as the speed setpoint
P2023[0] RS485 protocol selection 1 2 MODBUS RTU protocol
P2010[0] USS/MODBUS baudrate 6 6 Baudrate 9600 bps
P2021[0] MODBUS address 1 1 MODBUS address for inverter

SINAMICS V20 Inverter


74 Operating Instructions, 09/2014, A5E34559884
Commissioning
5.5 Quick commissioning

5.5.1.5 Setting common parameters

Functionality
This menu provides some common parameters for inverter performance optimization.

Text menu
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.

Setting parameters

Parameter Access Function Text menu Parameter Access Function Text menu
level (if P8553 = 1) level (if P8553 =1)
P1080[0] 1 Minimum motor P1001[0] 2 Fixed frequency
frequency setpoint 1

(MIN F) (FIX F1)


P1082[0] 1 Maximum motor P1002[0] 2 Fixed frequency
frequency setpoint 2

(MAX F) (FIX F2)


P1120[0] 1 Ramp-up time P1003[0] 2 Fixed frequency
setpoint 3

(RMP UP) (FIX F3)


P1121[0] 1 Ramp-down time P2201[0] 2 Fixed PID frequen-
cy setpoint 1

(RMP DN) (PID F1)


P1058[0] 2 JOG frequency P2202[0] 2 Fixed PID frequen-
cy setpoint 2

(JOG P) (PID F2)


P1060[0] 2 JOG ramp-up time P2203[0] 2 Fixed PID frequen-
cy setpoint 3

(JOG UP) (PID F3)

SINAMICS V20 Inverter


78 Operating Instructions, 09/2014, A5E34559884
Commissioning
5.4 Starting the motor for test run

5.4 Starting the motor for test run


This section describes how to start the motor for a test run to check that the motor speed
and rotation direction are correct.

Note
To run the motor, the inverter must be in the display menu (default display) and power-on
default state with P0700 (selection of command source) = 1.
If you are now in the setup menu (the inverter displays "P0304"), press for over two
seconds to exit the setup menu and enter the display menu.

You can start the motor in HAND or JOG mode.

Starting the motor in HAND mode


1. Press to start the motor.

2. Press to stop the motor.

Starting the motor in JOG mode


1. Press + to switch from HAND to JOG mode (the . icon flashes).

2. Press to start the motor. Release to stop the motor.

5.5 Quick commissioning

5.5.1 Quick commissioning through the setup menu

5.5.1.1 Structure of the setup menu

Functionality of the setup menu


The setup menu guides you through the steps required for quick commissioning of the
inverter system. It consists of the following four sub-menus:

Sub-menu Functionality
1 Motor data Sets nominal motor parameters for quick commissioning
2 Connection macro selection Sets macros required for standard wiring arrangements

SINAMICS V20 Inverter


60 Operating Instructions, 09/2014, A5E34559884