Recommendations For Grounding Systems in Lightning Protection Systems
Recommendations For Grounding Systems in Lightning Protection Systems
net/publication/216859148
CITATIONS READS
8 2,074
1 author:
Johny Montana
Universidad Técnica Federico Santa María
51 PUBLICATIONS 265 CITATIONS
SEE PROFILE
All content following this page was uploaded by Johny Montana on 27 May 2014.
Johny Montaña1
Resumen— Este artículo presenta algunas recomendaciones Some technical books, standards and papers present typical
prácticas para el diseño del sistema de puesta a tierra, el cual configurations regarding earth electrodes for buildings,
hace parte del sistema integral de protección contra rayos. Estas towers, poles, houses, etc (IEEE Std-62305; Casas, 2008).
recomendaciones son el resultado de los análisis de un software Some of these configurations can be modified for obtaining
académico que se basa en el método electromagnético híbrido en
conjunto con el método de momentos. Se muestran los resultados better results concerning transient phenomenon. This paper
de la impedancia y la tensión transitoria para configuraciones presents a transient analysis of some such configurations to
como: triángulo, estrella de tres puntas, contrapesos y mallas. A ascertain how they can be modified to get better earth
partir de los resultados, se definen la aplicación y las electrode results.
características de las diferentes configuraciones, como por The results presented in this papers were obtained by means
ejemplo: longitud efectiva de los contrapesos, lugares dónde of specialised software developed using the hybrid
localizar las varillas, lugares en los cuales conectar las bajantes a
las mallas y las diferencias de potencial entre puntos de una electromagnetic method (Montaña, 2006a; Montaña, et al
misma puesta a tierra. Estas recomendaciones guían al diseñador 2006b). Impedance and voltage results are shown to provide
para obtener beneficios de las diversas configuraciones sin recommendations for geometry, injection point location, rod
desperdiciar dinero. electrode location, mesh size, etc.
5
RECOMMENDATIONS FOR GROUNDING SYSTEMS IN LIGHTNING PROTECTION SYSTEMS
IT / L
IL
j j
Figure 1. Triangle (left) and wye (right) configurations
Impedance (Ohms)
Triangle (Dry)
carried out in the frequency domain, soil parameters, skin
effect and propagation effects’ frequency dependence are 60
easily included. Such methodology is used in this paper to
find earth electrodes’ input impedance frequency response by
40
means of the voltage-current relationship. Responses in the
time domain are computed by means of the inverse Fourier
transform (IFT) (Montaña, 2006a) from the responses in the 20
frequency domain.
0
2 3 4 5 6 7
3. PARAMETERS ANALYSIS 10 10 10 10 10 10
Frequency (Hz)
Impedance in the frequency domain and voltage in the time Figure 2. Impedance of triangle and wye configurations
domain were computed using the HEM-based software to
compare different arrangements. The impedance analysis was This simulation was used for defining which of the two
performed from 100 Hz up to 3 MHz, due to most configurations presented the lower impedance values at the
representative lightning phenomenon components occurring injection point. The results showed that the wye configuration
within that range. presented the lower impedance values for wet or dry soil.
Soil was modelled by means of permittivity, permeability Taking into account that both configurations used the same
and resistivity values. Two soil models were used to carry out conductor length, it was better to build the second one (wye
the simulation (Table I) (Grcev, 1993). configuration).
Table 1. Soil models
Characteristics Wet soil Dry soil B. Counterpoise effective length
Resistivity 100 1000
Permittivity (relative) 36 9
A simulation was developed to define the maximum length
Permeability (relative) 1 1 of counterpoises to be used in grounding systems; a 100 m,
0.01 m radii counterpoise, buried 0.5 m, was modelled. The
simulations were developed in both soil types at 100 Hz and 2
A. Triangle or wye configurations MHz frequency. The injection point was at the beginning of
the counterpoise. Figure 3 shows current distribution per unit
The first configurations being studied were triangle and
throughout the counterpoise.
wye configurations; they were named according to the
geometric figure formed by their conductors (Figure 1).
6 REVISTA INGENIERÍA E INVESTIGACIÓN Vol. 31 Suplemento No. 2 (SICEL 2011), OCTUBRE DE 2011 (5-10)
MONTAÑA
1 40
100Hz (Wet) Counterpois
0.9 2MHz (Wet)
35 Rod beginning
100Hz (Dry) Rod end
0.8
2MHz (Dry) Two rods
0.7 30
Impedance (Ohms)
0.6
Current (p.u.)
25
0.5
20
0.4
0.3 15
0.2
10
0.1
0 5
0 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7
10 10 10 10 10 10
Length (m) Frequency (Hz)
Figure 3. Current distribution in counterpoise Figure 4. Counterpoise impedance – with and without rods
30
impedance magnitude. On the other hand, there is not limit to
counterpoise length in AC analysis because the current is 25
uniformly distributed. However, grounding electrodes are 20
used nowadays in AC and transient at the same time so
maximum counterpoise length should be close to 70 m in high 15
5
C. Counterpoise with or without rods 0
2 3 4 5 6 7
The impedance magnitude values of a counterpoise with 10 10 10 10 10 10
Frequency (Hz)
and without rods is presented. The rods were located at the
Figure 5. Impedance of counterpoises
beginning and in the open end. The counterpoises were
modelled with 0.01m radii, 15 m length and buried 0.6 m; the The counterpoise impedance values had no important
rods measured 2.4 m in length and had 0.01 m radii. They variations regarding counterpoise length at high frequencies,
were modelled in wet soil. meaning that the transient response of different counterpoise
lengths was the same. The voltage of four counterpoises was
Figure 4 shows the difference between impedance at the modelled in the time domain to complement this analysis;
injection point when the rods were not included, when the rod current was 1 kA and 1/20 µs. The results are shown in Figure
was included at the beginning, at the open end and at both the 6.
beginning and open ends. The results showed that better
performance was achieved when the rod was included at the Figure 6 shows injection point voltage for each
beginning of counterpoise, because including the rod at the counterpoise. The peak values for four counterpoises were the
open end led to no significant differences at high frequencies. same; the differences shown in the tails of the waveforms
explained because impedance magnitude had variations at low
frequencies but not at high frequencies. It may thus be
concluded that increased counterpoise length modified
transient voltage tail but not the peak.
REVISTA INGENIERÍA E INVESTIGACIÓN Vol. 31 Suplemento No.2 (SICEL 2011), OCTUBRE DE 2011 (5-10) 7
RECOMMENDATIONS FOR GROUNDING SYSTEMS IN LIGHTNING PROTECTION SYSTEMS
8000
1x1
2x2
6000 4x4
20
8x8
4000
Impedance (Ohms)
15
2000
10
0
0 1 2 3 4 5 6 7 8 9
Time (s) -5
x 10
Figure 6. Counterpoise voltage at injection point 5
10000
G. Injection point dependence in a mesh (impedance)
Impedance was simulated at four injection points in a
8000
24x24 m mesh having 16 inner grids to determine injection
Voltage (V)
6000
point dependence in the impedance value (see Figure 9). The
mesh was modelled in wet soil, built with conductors
4000 measuring 0.01 m radii, buried 0.5 m. The impedance for four
injection points are shown in Figure 10.
2000
-2000
0 1 2 3 4 5 6 7 8 9
Time (s) -5
x 10
Figure 7. Voltage at three different points on a 60m counterpoise
Figure 9. Mesh 24x24 m with four injection points.
Based on these results, it is shown that the concept of 25
“equipotentiality” has a different meaning in transient Corner
Inside (6,6)
analysis, since (as shown in Figure 7) there was a voltage Center (12,12)
20
difference between points on the same conductor and the Edge (0,12)
8 REVISTA INGENIERÍA E INVESTIGACIÓN Vol. 31 Suplemento No. 2 (SICEL 2011), OCTUBRE DE 2011 (5-10)
MONTAÑA
3000
2500
Voltage (V)
2000
1500
1000
500
Figure 11. 24x24 m mesh having two injection points to compute transient
voltage 0
0 1 2 3 4 5 6 7 8 9
Time (s) -5
x 10
Figure 12 shows the differences between transient voltage Figure 14. Transient voltage in three different points in a mesh 24x24 m.
when the injection point was in the centre and in a corner. The
differences mainly occurred in peak waveform not in the tail; Figure 15. Transient voltage at three different points in a 24x24 m mesh
the differences were almost twice higher when the injection
point was located in a corner. As was concluded in Figure 7, when a grounding electrode
8000 was analysed in the transient domain, it had voltage
Injection:corner differences between points within itself. Figure 14 shows that
7000 Injection:center
the differences were obvious when the observation point was
6000
moved. In this case, the difference between the centre point
and the corner was 1.5 kV when the transient voltage in the
5000 injection point was 3 kV peak.
Voltage (V)
4000
3000 4. CONCLUSIONS
2000
Based on the transient analysis of grounding configurations
it may be concluded that:
1000
0
• When there is not enough area to build grounding
0 1 2 3 4 5 6 7 8 9
Time (s) -5
electrodes, it is better to use a wye configuration instead of
x 10
the triangle configuration;
Figure 12. Transient voltage in two injection points; mesh 24x24 m.
• Effective counterpoise length was close to 70 m in high
resistivity soils and 40 m in low resistivity soils;
I. Voltage difference in a mesh
• The best performance was achieved when a rod was
Continuing mesh analysis, voltages were then found at included at the beginning of a counterpoise, not at the
different points in the same mesh (24x24m) when current was open end;
fed at the centre point to identify voltage difference in the • Increasing counterpoise length modified transient voltage
same system due to transient performance. The transient
tail, not its peak;
voltage was computed at the injection point (centre), in a
• The down conductors had to be connected in the centre of
corner and at the edge of the mesh (Figure 13).
the meshes, not in the corner or at the edges, to reduce
impedance; and
REVISTA INGENIERÍA E INVESTIGACIÓN Vol. 31 Suplemento No.2 (SICEL 2011), OCTUBRE DE 2011 (5-10) 9
RECOMMENDATIONS FOR GROUNDING SYSTEMS IN LIGHTNING PROTECTION SYSTEMS
• When a grounding electrode was analyzed in the transient Montaña, J., Grounding system, Soil electric parameters variation with
frequency and software for computing transient voltages, Thesys, National
domain, it had voltage differences between its points so University of Colombia, Doctor of Philosophy, 2006a.
that it should be mandatory to connect different devices at
the same grounding system point to avoid large voltage Montaña, J., Montanyá J., et al, Quasi-static approximation of concentrated
ground electrodes: experimental results, 28th International Conference on
differences. lightning protection, ICLP, Kanasawa – Japan, 2006b.
10 REVISTA INGENIERÍA E INVESTIGACIÓN Vol. 31 Suplemento No. 2 (SICEL 2011), OCTUBRE DE 2011 (5-10)