Spec Earth Fault
Spec Earth Fault
1 Product name
2 Manufacturer / origin
3 Applied standard
4 Grounding type
5 General
5.1 Power Supply
5.2 Frequency
5.3 Operating temperature 0C
5.4 Humidity %
5.6 Tropicalized
6 Measurement
6.1 Resistance measurement Ω
Accuracy at 10kΩ, 1 µF
7 Alarm feature
7.4 LED
1 Manufacturer / origin
2 Product name
3 Applied standard
4 Feature
5 Specifications
Insulation standards:
5.1 - Normal voltage
- Pulse Endurance
Power Supply:
5.2 - Normal voltage
- Normal frequency
5.3 Number of monitoring channels
5.4 Response time
3 Applied standard
4 Specifications
4.1 Normal voltage
4.2 Normal pulse voltage
4.3 Normal primary leakage current
4.4 CT ratio
4.5 Normal short circuit thermal current
Requirements
Detail
Detail
IEC61557-8 or equivalent
IEC61010-1 or equivalent
10Ω to 10 MΩ
< 5%
0.1µF to 500 µF
< 5%
Yes
Yes
Yes
1 kΩ to 1 MΩ
0s to 7200s
1 kΩ to 1 MΩ
0s to 7200s
Yes, with cyclic is 5 hour
Yes
2
Failsafe/Standard/Mirror
Modbus RS485
Yes, 30 events
Detail
Detail
IEC61557 or equivalent
IEC61010 or equivalent
Detecting a channel warning of a earth fault
Measure and display insulation resistance and
leakage current
Incorporate measuring current transformer to locate
fault
≤ 830VAC/ 480VDC
100-440VACDC
+-15%
50 Hz
>12 channels
5s/40s/400s
200Ω…250KΩ
0.1µF…15µF
01 Output relay
Max 250VAC/6A
48VDC/1A,3mAmin. load
Yes
Detail
Detail
IEC 61869-2 or equivalent
IEC 60947-2 or equivalent
≥1000V
≥12kV
65A
1/1000
85 kA / 0.5 s