DC ONLINE EARTH FAULT PROTECTION SYSTEM

No. Specifications Unit

I Insulation and earth fault monitoring

1 Product name
2 Manufacturer / origin

3 Applied standard

4 Grounding type

5 General
5.1 Power Supply
5.2 Frequency
5.3 Operating temperature 0C

5.4 Humidity %

5.5 Ingress Protection

5.6 Tropicalized
6 Measurement
6.1 Resistance measurement Ω

Accuracy at 10kΩ, 1 µF

6.2 Capacitance measurement


Accuracy at 10kΩ, 1 µF

6.3 LCD display

7 Alarm feature

Detecting earth fault types: Symmetrical Faults and


7.1
Unsymmetrical Faults
Can connectivity and compatibility with Fault
7.2
Locator
Data logging: allows storing real-time alarm
7.3
information.

7.4 LED

7.5 Number of warning levels


7.5.1 Pre-Fault warning
Threshold setting

Delay time (from detection to delivery alarm signal)

7.5.2 Fault warning


Threshold setting

Delay time (from detection to delivery alarm signal)


7.6 Self-test function:
Auto
Manual
8 Other parameter
8.1 Output relay
Quantity
Mode
8.2 Protocol
8.3 Events
II Fault Locator

1 Manufacturer / origin

2 Product name

3 Applied standard

4 Feature

5 Specifications
Insulation standards:
5.1 - Normal voltage
- Pulse Endurance
Power Supply:
5.2 - Normal voltage
- Normal frequency
5.3 Number of monitoring channels
5.4 Response time

5.5 Measuring range

5.6 Output relay

5.7 Display function


- Built-in LED for indicators
- Built-in LED indicator for channel number
5.8 Protocol

Built-in communication network connecting devices


in the system together, with earth fault monitoring

III Current Transformer (CT)


1 Manufacturer / origin
2 Product name

3 Applied standard
4 Specifications
4.1 Normal voltage
4.2 Normal pulse voltage
4.3 Normal primary leakage current
4.4 CT ratio
4.5 Normal short circuit thermal current
Requirements

Detail
Detail
IEC61557-8 or equivalent
IEC61010-1 or equivalent

Compatible with isolated neutral or Ground Impedance

100 – 440 VAC/DC


50Hz
–25°C to +70°C
< 95%
Front: IP54
Rear: IP20
Yes

10Ω to 10 MΩ

< 5%

0.1µF to 500 µF
< 5%

Built-in LCD screen, allowing continuous data display


in text or trend form by hour, day, month, year

Built-in early warning function – earth fault alarm

Yes

Yes

Yes

Built-in LEDs for functions


warning, working status, errors
2

1 kΩ to 1 MΩ

0s to 7200s

1 kΩ to 1 MΩ

0s to 7200s
Yes, with cyclic is 5 hour
Yes

2
Failsafe/Standard/Mirror
Modbus RS485
Yes, 30 events

Detail

Detail
IEC61557 or equivalent
IEC61010 or equivalent
Detecting a channel warning of a earth fault
Measure and display insulation resistance and
leakage current
Incorporate measuring current transformer to locate
fault

≤ 830VAC/ 480VDC

100-440VACDC
+-15%
50 Hz
>12 channels
5s/40s/400s
200Ω…250KΩ
0.1µF…15µF
01 Output relay
Max 250VAC/6A
48VDC/1A,3mAmin. load

Yes

Built-in, RS-485 standard …

Detail
Detail
IEC 61869-2 or equivalent
IEC 60947-2 or equivalent
≥1000V
≥12kV
65A
1/1000
85 kA / 0.5 s