Sub-Base Module
R8001S9001
INSTALLATION INSTRUCTIONS
Scan for more information
Application
SLATE™ brings configurable safety and programmable logic
together into one single platform. The platform can easily be
customized for almost any requirement or application–offering
virtually limitless development opportunities with far less
complexity.
The R8001S9001 SLATE Sub-Base Module provides the ability
for the SLATE system to be mounted via DIN Rail in a panel. All
SLATE modules need this sub-base except for the SLATE Base
Module.
Features
• Quick-mount to standard DIN-Rail
• Locking mechanism
• Provides bus connectivity to all modules
• Connections for remote mounted flame amplifiers (remote bus)
and remote pushbutton reset
Specifications
Electrical Ratings:
Voltage and Frequency (from the Base): 18 VDC (± 1 VDC)
Maximum Total Connected Load: 2.5A
Terminal Ratings: See Table 1
Environmental Ratings
Ambient Temperature:
Operating: -20°F to +150°F (-29°C to +66°C).
Shipping: -40°F to +150°F (-40°C to +66°C)
Humidity: 95% continuous, noncondensing.
Vibration: 0.5G environment
Dimensions:See Fig. 1.
Weight:5 oz (136 g)
Approvals
Underwriters Laboratories Inc. Listed, File: MP286
IRI acceptable.
Federal Communications Commission: Part 15, Class A
Emissions.
Mounting
DIN Rail (See Fig. 3)
Required Components
R8001A1001 SLATE Base Module
Any other SLATE modules
Optional 5-position terminal block for remote flame amplifier or
remote reset button connections (Phoenix Contact p/n 1754504
or equivalent). See Fig. 2.
4 32-00025—01
7-3/32
(180)
1-5/32
(29)
2-21/32 (67)
3-13/32 (86) M35384
TERMINAL DESCRIPTION
1 18V POWER
2 18V GROUND
3 REMOTE RESET (BURNER CONTROL AND LIMIT MODULES ONLY)
4 B (REMOTE BUS RS485)
5 A (REMOTE BUS RS485)
M35430
6 32-00025—01
Installation
WARNING
Fire or Explosion Hazard Can cause severe injury,
death, or property damage.
Verification of safety requirements must be performed
each time a control is installed on a burner to prevent
possible hazardous burner operation.
Mounting
1. The sub-base module can be mounted on type C 20 DIN rail.
2. Mount the sub-base module first. The sub-base has locking
mechanisms on both sides of the module. Pull to unlock
position. See Fig. 3.
M35378
M35386
8 32-00025—01
5. After securing the sub-base module, snap the SLATE module
into place and secure the module to the sub-base using
screws (included with SLATE module).
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or equipment damage.
IMPORTANT
This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with these
instructions, may cause interference for radio communications.
It has been tested and found to comply with the limits of a Class
A computing device of part 15 of FCC rules, which are designed
to provide reasonable protection against such interference
Signal ground
Note the 18 V system ground is not electrically connected
to earth ground. Follow local codes and appliance
recommendations to determine if this should be connected to
earth ground.
10 32-00025—01
• Enclose flame detector leadwires without armor cable in metal
cable or conduit.
• Follow directions in flame detector instructions.
Be sure loads do not exceed the terminal ratings. Refer to the
labels or terminal ratings in Table 1.
The SLATE system must be mounted in an electrical enclosure.
When mounting in an electrical enclosure, provide adequate
clearance for servicing, installation, and removal of SLATE
modules.