Sample Cover Page

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

H-

S
Mechanical Services
DRAWING INDEX
M-01 COVER SHEET, DRAWING INDEX, NOTES AND DETAILS
M-02 GROUND FLOOR - AIR CONDITIONING AND VENTILATION LAYOUT
SEAL BETWEEN DUCT SHEETMETAL
AND OVERFLASHING OVERFLASHING BY
WITH WATERPROOF MECHANICAL
AIR CONDITIONING UNITS SCHEDULE SEALANT CONTRACTOR
SUPPORT AROUND APRON FLASHING -
DUCTWORK TO PREVENT MIN 100mm UPSTAND BY
ROOF SHEETS FROM ROOF CONTRACTOR
COLLAPSING AROUND
DUCTWORK ROOF FINISH

LEGEND OF SYMBOLS
ACC AIR CONDITIONING OUTDOOR UNIT 300 300
ACU AIR CONDITIONING INDOOR UNIT
AF AIR FILTER
GEF GENERAL EXHAUST FAN
OAF OUTSIDE AIR FAN
A/P
TEF
ACCESS PANEL
TOILET EXHAUST FAN
TYPICAL DUCTWORK ROOF
O/A OUTSIDE AIR INTAKE PENETRATION DETAIL
SAD, EAG, RAG SUPPLY AIR DIFFUSER, EXHAUST AIR GRILLE, RETURN AIR GRILLE NOT TO SCALE
SAG, ARG, OAG SUPPLY AIR GRILLE, AIR RELIEF GRILLE, OUTSIDE AIR GRILLE,
T/B, F/A, F/B, T/A TO BELOW, FROM ABOVE, FROM BELOW, TO ABOVE

GALVANISED SHEET METAL DUCT. ALL SUPPLY AND RETURN AIR


DUCT TO BE THERMAL INSULATION OF R 2.0 (75mm THK NOM)
EXTERNALLY INSULATED U.N.O. NO INSULATION REQUIRED TO
DUCTWORK SERVING VENTILATION ONLY U.N.O.

THERMAL INSULATION OF R 1.2 INTERNAL; 50 THICK NOM.


MAINTAIN MANUFACTURERS
MINIMUM CLEARANCE
THERMAL INSULATION OF R 2.0 INTERNAL; 75 THICK NOM.
NOTE: PROVIDE METAL CLADDING TO
DUCT AIR WAY DIMENSIONS IN mm. FIRST DIMENSION IS SIDE ALL EXPOSED REFRIGERANT
400x200 PIPEWORK AND ELECTICAL CONDUITS
VIEWED SECOND DIMENSION IS SIDE NOT VIEWED

DIRECTION OF FLOW: S/A = SUPPLY AIR R/A = RETURN AIR ACC


O/A = OUTSIDE AIR E/A = EXHAUST AIR TYPICAL OUTDOOR UNIT
PROVIDE MANUFACTURES
FLEXIBLE DUCTWORK - SIZES AS SHOWN: PROPRIETARY DRAIN KIT FOR
0-90 L/s Ø200 211-290 L/s Ø350 481-550 L/s Ø500 CONDENSATE DRAIN CONNEC
NEOPRENE VIBRATION ISOLATION
91-150 L/s Ø250 291-380 L/s Ø400 MOUNTS AS SPECIFIED REFRIGERANT PIPEWORK
151-210 L/s Ø300 381-480 L/s Ø450
PLANT PLATFORM OFF ON PROVIDE UPSTAND FOR
ROOF SHEET CREST CONDENSING UNIT ISOLATOR.
SPIRAL/OVAL DUCTWORK
DUCTWORK TO MATCH SYSTEM INSULATION
Ø25 CONDENSATE DRAIN TO
RETURN/EXHAUST AIR GRILLE LENGTH x WIDTH AS SHOWN IN NEAREST DRAIN POINT
SCHEDULE ROOF DECK

RETURN AIR GRILLE WITH 75MM INTERNAL INSULATION TYPICAL OUTDOOR CONDENSING UNIT
CEILING SUPPLY SWIRL DIFFUSER PLANT PLATFORM MOUNTING DETAIL
NOT TO SCALE
1 OUTLET SCHEDULE NUMBER

REFRIGERANT PIPEWORK NEW


DOOR GRILLE SCHEDULE
R

REFRIGERANT PIPEWORK JUNCTION


TYPE SIZE AIR QUANTITY
A 600mm x 150mm 0-120 L/s
NON-CONNECTED PIPE CROSSING B 600mm x 200mm 120-160 L/s
PIPEWORK DOWN C 600mm x 250mm 160-200 L/s
D 600mm x 300mm 200-250 L/s
PIPEWORK UP
E 600mm x 450mm 250-400 L/s
D CONDENSATE DRAIN PIPEWORK RV F 600mm x 600mm 400-550 L/s
ROOF COWL / VENT
T TEMPERATURE SENSOR SHEETMETAL OVERFLASHING BY FD INDICATES DOOR GRILLE COMPLETE WITH GALVANISED SHEETMETAL
MECHANICAL CONTRACTOR INTUMESCENT FIRE DAMPER DUCT SLEEVE
CP PROPRIETARY CONTROL PANEL
PENETRATION AND UPSTAND BY DUCT SLEEVE TO FIT OVER
ROOF CONTRACTOR ROOF UPSTAND BY
CP/T PROPRIETARY CONTROL & THERMOSTAT PANEL
MECHANICAL CONTRACTOR

A AIR TRANSFER DOOR GRILLE, REFER SCHEDULE FOR DOOR GRILLE SIZE PROVIDE SUPPORTS TO ROOF
PROVIDED BY MECHANICAL SERVICES CONTRACTOR TO BE INSTALLED BY BUILDER SHEETING AROUND
PENETRATION
U AIR TRANSFER 20mm DOOR UNDERCUT

ROOF
TUNDISH & WALL TUNDISH BY HYDRAULIC SERVICES CONTRACTOR
ROOF PURLIN
T WT
GALVANISED MILD STEEL ANGLE
TRIMMERS BOLTED AND BRACKETED
TO PURLIN
TRANSITION DUCTWORK TO SUIT
FAN CONNECTION
PENETRATION AND UPSTAND
BY ROOFING CONTRACTOR
TYPICAL ROOF MOUNTED OUTSIDE
AIR INTAKE COWL DETAIL TYPICAL ROOF PIPEWORK
NOT TO SCALE
PENETRATION DETAIL
NOT TO SCALE