CM-RQE70

PIR ‘REQUEST TO EXIT’ DETECTOR


Installation Instructions

PACKAGE CONTENTS
1 Wiring Harness 6 Wire Nuts

2 #6 x 3/4” Screws 2 MOV’s BP7175

2 3/16” Wall Plugs

Section 1: General Description FIGURE 2 - MOUNTING LOCATIONS

Camden CM-RQE-70 Request-to-Exit Sensor is a passive infrared Self-Test


(PIR) detector designed for interior use. This device is UL listed as When power is first applied to the CM-RQE70, the sensor will
an access control device under UL 294 Standard and is listed for beep once, then the unit performs a self-test to ensure its major
Class I for UL Canada under ULC-S319 when it is connected to a UL functions are within acceptable operating parameters. The self-test
approved access control system. checks the input voltage, switch operation and sensor function.
If the sensor passes all tests, there is a single beep and normal
operation begins. If the sensor fails any of the tests, the unit will
provide a series of audible beeps indicating the failure. This is take
approximately 30 seconds.

Post-Test Failure Beeps


If the sensor fails a test, the unit will perform one or more short
Section 2: Features beeps, followed by a long beep. This series of beeps is repeated
continuously.
• Compact size, designed to mount on door frames
•O
 n-board programming buttons. No dip switches # of Short
Description
Beeps
• ( 4) factory default operating modes, with the ability to customize
mode attributes The IR sensor did not settle to an acceptable level
1
during the test.
•P
 lug-in wiring harness, makes installation easy and fast
•S
 electable Fail Safe/Fail Secure One of the 3 buttons, Mode, Parameter or Select is
2
detected as being pressed.
• ( 2) Form ‘C’ contacts
•M
 omentary and latching relay modes The Source Voltage to the CM-RQE70 is outside of the
3
range of 12 – 24V.
•S
 econdary activation device input
The IR sensor is not changing over a large enough
•C
 ard/keypad input 4
range of values to reach its settle point.
•D
 oor position switch input
•R
 equest to exit input Fail Safe vs Fail Secure: Field Selectable
•B
 uilt-in sounder (adjustable) These terms are used to describe the normal operating state of
• T amper switch the output relays. In Fail Safe Mode, the relays will be normally
energized. The relays will de-energize when a person is in the
Section 3: Operation field of view (normal operation) or when the power is removed
due to an outage or other external reasons. In Fail Secure Mode,
the relays remain de-energized normally. The relays will energize
when a person is in the field of view (normal operation). The relays
remain de-energized during a power outage, therefore, keeping the
controlled device secure.

Tamper Switch
FIGURE 1 - COMPONENT LOCATIONS Dry contact outputs N/C are provided for interface to an alarm
or access control systems. The Tamper Switch is connected to a
spring that compresses and closes the switch when the housing

Page 1 of 6
CM-RQE70 PIR ‘REQUEST TO EXIT’ Detector Installation Instructions
cover is installed. Removing the cover will open the switch contacts External Disable/Enable
providing a change in state to the monitoring system.
Input: Dry
Indicator Lights: LED’s
In this mode, the REX is enabled or disabled by an external device, such as
A Red & Green LED indicates secure vs unsecure status of the REX. an access control system or security alarm panel. While this input is held
The red LED is normally lit to indicate the door is secure. When a open, the REX sensor will function normally. When this input is closed, the
person walks within the detectable range of the sensor, the green REX sensor operates the same as in Sequential Logic Input Mode.
LED will light and the red will be off.
Rex Sensor Default Modes
Access Control Input
In an effort to make installation easier, we have defined different
Input: Dry N/O installation modes. These modes will cover 90+% of the applications.
For the other 10%, there will be a Custom Mode where all settable
A dry contact closure on this input allows a card reader or keypad
functions can be adjusted.
on the secure side of the door to activate the REX sensor allowing
access through the secured door. Mode 1: Normal Latched REX Sensor
Sounder Control The most common mode, the sensor, when activated will enable the
output relay for the duration of the Relay On Time (30 seconds). If a
Input: Dry N/O door contact is connected to Input #1, when the door is sensed to be
opened, then closed, the Relay On Time is reduced to 2 seconds.
A dry contact closure from an external device will hold this sounder
on until it is released. The sounder will not affect the operation of Relay On Time: 30s (If the door is opened and closed, the
the relays or relay timers. timer is reduced to 2s)
Fail Mode: Fail Safe
Sequential Logic Input Operating Function: Latched
PIR Sensitivity: 4
Input: Dry Sound Vol: 3
This mode allows a secondary detection device to be connected Input #1: Door Contact
to the REX sensor. The REX sensor is active only while this input Input #2: Press to Exit
is opened or for 10 seconds after it has closed. For example, Input #3: Sounder Input
when the secondary activation device is activated, the REX sensor
functions normally. When a person is in the field of view, the sensor Mode 2: Door Prop Alarm
is activated and the door is released. If the secondary activation The sensor monitors the status of the door. When activated, the
device is de-activated, the REX Sensor will continue to be activated sensor enables the output relay for 30 seconds. If the door is held
if a person is in the field of view for an additional 10 seconds. open during the last 10 seconds of the Relay On Time, the piezo will
sound until the door is closed. This mode requires a Door Contact to
Door Monitor Contacts be connected to Input #1.
Input: Dry Relay On Time: 30s (If the door is opened and closed, the
timer is reduced to 2s) If the door is held open
Operating Functions during the last 10 seconds of the relay on time,
the piezo will sound until the door is closed.
Function 1: Latched Fail Mode: Fail Safe
When the REX sensor is activated, the relay will remain active as Operating Function: Door Prop Open Alarm
long as the sensor is activated. Once the sensor is deactivated, the PIR Sensitivity: 4
relay will remain on for the duration of the Relay On Time. If the door Sound Vol: 3
is opened and closed, the Relay On Time is reduced to 2 seconds. Input #1: Door Contact
Input #2: Press to Exit
Function 2: Door Prop Open Alarm Input #3: Sounder Input
The door contact input is used to monitor the status of the door. If Mode 3: Access Control
the door is held open during the last 10 seconds of the timer relay
set time, the sounder will annunciate until the door is closed again. The sensor will activate normally on motion. Input #3 is used to
If the door is opened without the REX being activated the sounder connect to an access control system. A contact closure on Input #3
will annunciate until the door is closed or someone has moved into will activate the sensor. A maintained closure on Input #3 will activate
the REX Sensor’s field of view. the sensor indefinitely.
Relay On Time: 30s (If the door is opened and closed, the
Function 3: Unauthorized Access Mode timer is reduced to 2s)
In this mode, when the REX sensor is activated but the door is not Fail Mode: Fail Safe
opened, the relay returns to a secured state in 10 seconds. If the Operating Function: Latched
REX sensor is activated and the door opens, then closes, the relay PIR Sensitivity: 4
returns to secured state in 2 seconds. Sound Vol: 3
Input #1: Door Contact
Input #2: Press to Exit
Input #3: Card Keypad
Page 2 of 6
CM-RQE70 PIR ‘REQUEST TO EXIT’ Detector Installation Instructions

Mode 4: Secondary Activation Mode 1. Using a 3/16” drill, drill 2 mounting holes 3 ¼” apart at the
desired height of installation.
The sensor requires activation of Input #3 before activating the
output relay. 2. Insert the 2 x 3/16” wall plugs into the holes
Relay On Time: 30s (If the door is opened and closed, the 3. Align the sensor back plate with the mounting holes and screw in
timer is reduced to 2s) the 2 x #6 screws, securely fastening the sensor back plate to the wall.
Operation Function: Latched, Door Prop Open Alarm or Unauthorized 4. Rotate the sensor PCB assembly into the back plate.
PIR Sensitivity: 4
Sound Vol: 3 Wiring the Sensor
Input #1: Door Contact
The Camden CM-RQE70 uses a plug-in wiring harness for all
Input #2: Press to Exit
electrical connections. The Pin out is described below.
Input #3: Sequential Input
PIN # Description Color
In this mode, the sensor would behave as described above.
1 Tamper Switch 1 Violet
2 Tamper Switch 2 Violet
Mode 5: Custom Settings
3 Input 1 Blue
The sensor may be programmed as required by the installation. 4 Input 2 Yellow
5 Input 3 Orange
Relay On Time: 5, 15, 30, 45 and 60 seconds
6 Ground Black
(unauthorized mode is 10s)
7 Relay 1a – Normally Open Green
Fail Mode: Fail Safe or Fail Secure 8 Relay 1b – Normally Open Gray
Operating Function: Latched, Door Prop Open Alarm or Unauthorized 9 Relay 1b – Normally Closed Pink
PIR Sensitivity: 1 to 5 10 Relay 1a – Normally Closed White
Sound Vol: 0 to 4 11 Relay 1b - Common Yellow/Green
Input #1: Unused, Door Contact, Sounder Input, 12 Relay 1a - Common Brown
Sequential Input, External Disable, Press to 13 Ground Black
Exit, Card Keypad 14 Power IN Red
Input #2: Unused, Door Contact, Sounder Input,
Sequential Input, External Disable, Press to Adjusting the Sensor Detectable Range
Exit, Card Keypad The sensor’s detectable range can be adjusted vertically and
Input #3: Unused, Door Contact, Sounder Input, horizontally.
Sequential Input, External Disable, Press to
Exit, Card Keypad Horizontal Adjustment

Section 4: Installation
Remove the sensor cover
1. Insert a small flat screwdriver
into the bottom end of the
housing cover and gently pry the
cover from the main assembly.
2. Loosen the sensor vertical
adjustment screw. The horizontal adjustment of the sensor is accomplished by
adjusting the 2 louvers inside the lens area. The louvers are
3. Rotate the sensor PCB
adjusted using a small flat head screwdriver. On the bottom of the
assembly until it is removed
sensor housing there are 2 adjustment screws. Turning the screws
from the back plate. adjusts the louvers left and right horizontally, therefore changing
the beam direction and width. Once the horizontal adjustment is
Install the Back Plate complete, place the tamper label (provided) over the set screws to
avoid accidental adjustment.

Vertical Adjustment
The sensor beam is vertically
adjusted by rotating the PCB
assembly barrel within the
mounting back plate. Once the
vertical adjustment is complete,
tighten the lock down screw to
prevent the barrel from moving.
Once all adjustments are made,
install the sensor cover and
install the set screw provided.
Page 3 of 6
CM-RQE70 PIR ‘REQUEST TO EXIT’ Detector Installation Instructions

Programming Buttons Red LED


There are no DIP switches to set on this Rex Sensor. 3 buttons are Mode Beeps Description
Flashes
used for all setup and programming.
1 1 1 Latched Mode

2 2 2 Door Prop Alarm Mode

3 3 3 Access Control Mode

The MODE Button (top): 4 4 4 Secondary Activation Mode

The MODE button is used to select 1 of 4 pre-set modes or a fully


configurable custom Mode. Pressing the MODE button for the first 5 5 5 Custom Settings Mode
time will indicate which Mode the REX sensor is currently in. The
REX sensor will BEEP and the LED will flash red the number of times The Adjust Button (Bottom)
equal to the MODE number. I.E. 1 Beep/Flash = Mode 1.
The adjust button is used to change the value of the Parameter.
The Parameters Button (Middle) Once a Parameter is selected, use the Adjust button to cycle
through the available options for each parameter as described in
This button selects the available parameters in each mode that can
the below table.
be customized. From within any Mode, press this button to cycle
through the parameters.

Parameter 1 beep 2 beeps 3 beeps 4 beeps 5 beeps 6 beeps 7 beeps LED

Relay On Time 5 seconds 15 seconds 30 45 60 Yellow Solid

Red/Yellow
Fail Mode Safe Secure
Flashing

Operation Door Prop Unauthorized Green/Yellow


Latched
Mode Open Alarm Access Flashing

PIR Red/Green
1 2 3 4 5
Sensitivity Flashing

Red/Green/
Sound Volume 0 1 3 3 4
Yellow Flashing

Sequential External
Input #1 Unused Press to Exit Card/Keypad Door Contact Sounder Input Red Flashing
Input Disable

Sequential External
Input #2 Unused Press to Exit Card/Keypad Door Contact Sounder Input Green Flashing
Input Disable

Sequential External
Input #3 Unused Press to Exit Card/Keypad Door Contact Sounder Input Yellow Flashing
Input Disable

Factory Reset Regulatory Information


The Camden CM-RQE70 Request to Exit sensor can be reset to The unit shall be installed in accordance with National Electrical
factory defaults by pressing and holding the MODE and ADJUST Code ANSI/NFPA 70 and part 1 of the Canadian Electrical Code CSA
buttons. The Sensor will start to beep. Continue holding the MODE C22.1, Safety Standard for Electrical Installations.
and ADJUST buttons while the beeping gets progressively faster until
it reaches a steady tone. When the tone stops, the REX sensor has
been reset to factory defaults and the MODE and ADJUST buttons
may be released.

Page 4 of 6
CM-RQE70 PIR ‘REQUEST TO EXIT’ Detector Installation Instructions

14 13 12 11 10 9 8 7 6 5 4 3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1
MOV MOV

12 - 24 V + Sounder
Request to Exit
12 - 24 V + 1 2 3
Request to Exit
DC Control
Push Button DC Access 4 5 6 Push Button
Door Contact
Power - Power - Control 7 8 9
Door Contact
Keypad/
Reader

MOV Maglock MOV Maglock

MODE 1&2 WIRING DIAGRAM MODE 3 WIRING DIAGRAM

PIN# Description Color


1 Tamper Switch 1 Violet
2 Tamper Switch 2 Violet
3 Input 1 - Door Contact Blue
14 13 12 11 10 9 8 7 6 5 4 3 2 1 4 Input 2 - Request to Exit Yellow
5 Input 3 - Sounder Control Orange
MOV
6 Ground Black
OPTIONAL
12 - 24 V + REX Sensor
DC Keypad
Request to Exit 7 Relay 1a– Normally Open Green
Push Button
Power - Eye Beams Door Contact 8 Relay 1b– Normally Open Grey
9 Relay 1b– Normally Closed Pink
10 Relay 1a– Normally Closed White
11 Relay 1b- Common Yellow/Green
MOV
12 Relay 1a- Common Brown
Maglock
13 Ground Black
14 Power IN Red
MODE 4 WIRING DIAGRAM

Section 5: Specifications
Voltage: 12 /24V DC operation Piezo Buzzer: 92db.@ 10cm. UL 294 Access Control Performance
Current Draw:
50mA (max) Indicator: Activation LED Levels
Relays: (2) Form ‘C’ (DPDT) Card or 1) Access Controls, Destructive Attack -
Contact Rating:
3A @ 30VDC Keypad Input: (1) N/O Level I (No Attack)
Programming:
On-board push buttons Door Position 2) Line Security - Level I (No Line Security)
and status LED Switch Input: (1) N/O
Request to 3) Endurance - Level IV (100,000 cycles)
Modes: - (4) Factory Default
- (1) Fully Custom Exit Input: (1) N/O 4) Standby Power - Level I (No Stand by
- Selectable Fail Safe/ Tamper Switch Power)
Fail Secure Contact Rating: 50mA @ 12VDC
Coverage: - Max. 10’ W x 10’ H Temp Operating
- Horizontal & vertical Range: 32°F - 120°F (0 - 50°C)
adjustment (mechanical) Humidity Range: 0 - 93% non-condensing
- Sensor sensitivity/range Dimensions: 7” W x 1 3/4” D x 1 3/4”H
(electronic) (176mm x 43mm x 43mm)
Time Delay: Adjustable, 5, 15, 30, 45 Weight: 0.25 lbs. (0.12kg.)
& 60 second Colors: White and black models
Sounder: On/Off, with adjustable
volume
Page 5 of 6
CM-RQE70 PIR ‘REQUEST TO EXIT’ Detector Installation Instructions

Section 6: Coverage Information


The detection area changes depending on the mounting height and in a larger detection area typically. The illustrations show the REX
angle of the lens of the REX sensor. If the REX sensor is mounted on sensor mounted at 7.5 (2.3m) Feet on a wall with the lens pointing
the wall above a door with the lens pointing straight, the detection straight down and at 8 Feet (2.4m) on a ceiling with the lens pointing
areas against the wall are not detected and not shown in the straight down.
illustrations. Mounting the REX sensor at higher heights,results
7’5” Ceiling - Above Single Door 8’ Ceiling - Over the Ceiling
Front View Front View

Bird’s-Eye View Bird’s-Eye View

11’ 6”
(3.5m)

12’
(3.6m)

Side View
Side View

2 ft. 3 ft.
(0.6m) (0.9m)

Push Buttons Key Pads Strikes Magnetic Locks Key Switches Relays & Timers Access Control

File: CM-RQE70 Detector Manual.indd


DISCOVER THE BEST IN DOOR ACTIVATING www.camdencontrols.com Rev. Label/Date: 1/07-26-17
AND LOCKING PRODUCTS! Toll Free: 1.877.226.3369 Part No: 40-82B203