1 GENERATOR PROTECTION TRIPPING MATRIX

Generator protections tripping Matrix


DIGITAL OUTPUTS FROM GENERATOR PROTECTIONS PANEL LOCK OUT RELAYS

Trip to HV Trip to HV HV breaker


HV CBF start
Output digital Line Line Signal to Signal to Lock out start
Avail. Avail. from power Avail. Avail. Avail. Avail. Avail. Avail. Avail. Avail.
trips Breaker Breaker STCS PMS from power
plant
(Ch. 1) (Ch. 2) plant
Signal Type NO(1-2) NO(3-4) NO(5) NO(6) NO(7) NO(8) NO(9) NO(10) NO(11) NO(12) NO(13) NC(1) NC(2) NC(3) NC(4) NC(5)

Lock Out
Relay 86 G1 X X X X X X

Lock Out
Relay 86 G2 X X X X X X

Trip to
Trip to Trip to HV Line
Trip MV 6.6 KV
Output digital excitation excitation Signal to Signal to breaker
Avail. Avail. Breaker Unit Excitation Avail. Avail. Avail. Avail. Avail. Avail. Avail.
trips system system STCS PMS interlock
Transformer transf.
(Ch. 1) (Ch. 2) close com.
Breaker.

Signal Type NO(1) NO(2) NO(5) NO(6) NO(7) NO(8) NO(9) NO(10) NO(11) NO(12) NO(13) NC(1) NC(3) NC(3) NC(4) NC(5)

Lock Out
Relay 86 X X X X X X X
TV1

Lock Out
Relay 86 X X X X X X X
TV2

DIGITAL OUTPUTS FROM GENERATOR PROTECTION PANEL TRIP RELAYS

Trip to Trip to
Output digital Turbine Turbine Signal to
Avail.
trips (STCS) (STCS) PMS
(Ch. 1) (Ch. 2)

Signal Type NC(1) NC(2) NO(3) NO(4)

K4 T1 X X X

K4 T2 X X X

NOTE:

Regarding Generator, main & unit transformer protections system, in case of the both DC power supply failure or
both the protection relays failure (watchdog signals of the system A&B), the redundant trip signals shall be sent
to HV C.B & also Excitation system through fail safe NC contacts.
GENERATOR PROTECTION RELAY (A) TRIPPING MATRIX
Cumulative
94 X Excitation VT MCB Cumulative Alarm &
60 FL HV Line HV Line Trip to Trip to Trip to To use in Common
Normal Turbine ON Tripped Common trip to
↑ = To ↓ = From & = and Pt's CB NOT CB
STOP Tripped (Ch.1)>= (Ch.1)
lock out lock out HV Alarm to
Trip to STCS STCS
Failure Open Open 86G1/2 86TV1/2 K4T1/2 substation STCS
** 3 sec *** (digital) (serial)
(digital)
Electrical Protections Signal
Siemens 7UM6221-5EB92-OCBO+L0A
ANSI IEC En. ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↑ ↑ ↑ ↑ ↑ ↑ ↑
Type
I-Diff>>
Differential Protection 87-G - ON Trip X X X X X
I-Diff>
Overcurrent with voltage
51-V I>/U< 1st Stage ON Trip Blocked Blocked X X X X X
restrained
I>> 1st Stage ON Trip X X X X X
Definite time over current with
50 V
under voltage Seal In
V< 1st Stage ON Trip Blocked Blocked X X X X X

-32P 1 1st Stage ON Alarm X X


Reverse Power -P>
- 32P 2 2st Stage ON Trip X X X X X
59-1 1st Stage ON Trip X X X X
Overvoltage >U
59-2 2st Stage ON Trip X X X X
27-1 1st Stage ON Trip Blocked & Blocked X X X
Under voltage <U
27-2 2st Stage ON Trip Blocked & Blocked X X X
1st Stage ON Trip X X X X X
Out of Step 78
2st Stage ON Trip X X X X X
40-1 1st Stage ON Trip X X X X X
Loss of Field 40-2 1/Xd 2st Stage ON Trip X X X X X
40-3 3rd Stage ON Trip X X X X X
1st Stage ON Trip X X X
Over frequency 81> f>
2st Stage ON Trip X X X X X
1st Stage ON Trip Blocked Blocked X X X
Under frequency 81< f<
2st Stage ON Trip Blocked Blocked X X X X X
Thermal overload 49 ϴ> 1st Stage ON Alarm X X
1st Stage ON Trip Blocked Blocked X X X X X
Z<
2st Stage ON Trip Blocked Blocked X X X X X
Under impedance 21 Z1B 3rd Stage ON Trip Blocked & Blocked X X X X X
T end final
time delay 3 Blocked Blocked X X X X X
sec

59TN (100%) ΔV 1st Stage ON Trip X X X X X


Stator earth fault
59N (90%) V0 1st Stage ON Trip X X X X X
46-1 I2> 1st Stage ON Alarm X X
Negative Sequence
46-2 I2>> 2st Stage ON Trip X X X
Low forward power 32L1 Pf< 1st Stage ON Trip &* &* X(singular) X
24-1 1st Stage ON Alarm X X
Over fluxing U/f
24-2 2st Stage ON Trip X X X X
Voltage transformer failure 60FL VTS 1st Stage ON Alarm X X
Inadvertent Energization 50/27 I.En 1st Stage ON Trip Blocked X X X X
Breaker failure 50BF I>BF 1st Stage ON Trip & X X X X
Trip circuit supervision 74TC - ON Alarm X X
Relay Fault (watchdog) - ON Alarm X(singular)
Signals FROM STCS
Generator Overload
& Excitation Transf. over temp. Tripped Trip &32L1 X X X X X
(Ch.1)
Turbine Tripped (Ch.1)
(38 bearing temperature)
(26 coolant temperature) Trip &32L1 X X X X X
(39 Shaft vibration supervision)
(emergency shutdown)
Signals FROM EXCITATION SYSTEM
Trip from excitation Trip X X X X X
64-R1 U<R Alarm X X
Rotor Earth Fault
64-R2 U<<R Trip X X X X X
Signals FROM PLANT SYSTEMS
S.S CH. 1 trip command Trip X X X X X
Line prot. main protection trip Trip X X X X X
STG enclosure fire protection trip Trip X X X X X
Electrical Protections Signal
Siemens 7UT6131-5EB92-1AA0+L0A
ANSI IEC En. ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↑ ↑ ↑ ↑ ↑ ↑ ↑
Type
I-Diff>>
Overall differential 87O - ON Trip X X X X X
I-Diff>
Relay Fault (watchdog) - ON Alarm X(singular)
Signals FROM Siemens
7PA3042-1AA00-1
Trip circuit supervision( 74TC - ON Alarm X X
Plant. fire protection panel trip Trip X X X X X
Excitation transformer feeder trip Trip X X X X X
*For 94 X Normal STOP or Turbine Tripped the HV breaker will be open by STCS open command
** Signal duplicate inside protection panel
*** VT MCB serial signal to STCS
GENERATOR PROTECTION RELAY (B) TRIPPING MATRIX
Cumulative
94 X Excitation VT MCB Cumulative Alarm &
60 FL HV Line HV Line Trip to Trip to Trip to To use in Common
Normal Turbine ON Tripped Common trip to
↑ = To ↓ = From & = and Pt's CB NOT CB
STOP Tripped (Ch.2)>= (Ch.2)
lock out lock out HV Alarm to
Trip to STCS STCS
Failure Open Open 86G1/2 86TV1/2 K4T1/2 substation STCS
** 3 sec *** (digital) (serial)
(digital)
Electrical Protections Signal
Siemens 7UM6221-5EB92-OCBO+L0A
ANSI IEC En. ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↑ ↑ ↑ ↑ ↑ ↑ ↑
Type
I-Diff>>
Differential Protection 87-G - ON Trip X X X X X
I-Diff>
Overcurrent with voltage
51-V I>/U< 1st Stage ON Trip Blocked Blocked X X X X X
restrained
I>> 1st Stage ON Trip X X X X X
Definite time over current with
50 V
under voltage Seal In
V< 1st Stage ON Trip Blocked Blocked X X X X X

-32P 1 1st Stage ON Alarm X X


Reverse Power -P>
- 32P 2 2st Stage ON Trip X X X X X
59-1 1st Stage ON Trip X X X X
Overvoltage >U
59-2 2st Stage ON Trip X X X X
27-1 1st Stage ON Trip Blocked & Blocked X X X
Under voltage <U
27-2 2st Stage ON Trip Blocked & Blocked X X X
1st Stage ON Trip X X X X X
Out of Step 78
2st Stage ON Trip X X X X X
40-1 1st Stage ON Trip X X X X X
Loss of Field 40-2 1/Xd 2st Stage ON Trip X X X X X
40-3 3rd Stage ON Trip X X X X X
1st Stage ON Trip X X X
Over frequency 81> f>
2st Stage ON Trip X X X X X
1st Stage ON Trip Blocked Blocked X X X
Under frequency 81< f<
2st Stage ON Trip Blocked Blocked X X X X X
Thermal overload 49 ϴ> 1st Stage ON Alarm X X
1st Stage ON Trip Blocked Blocked X X X X X
Z<
2st Stage ON Trip Blocked Blocked X X X X X
Under impedance 21 Z1B 3rd Stage ON Trip Blocked & Blocked X X X X X
T end final
time delay 3 Blocked Blocked X X X X X
sec
27TN (100%) ΔV 1st Stage ON Trip X X X X X
Stator earth fault
59GN (90%) V0 1st Stage ON Trip X X X X X
46-1 I2> 1st Stage ON Alarm X X
Negative Sequence
46-2 I2>> 2st Stage ON Trip X X X
Low forward power 32L1 Pf< 1st Stage ON Trip &* &* X(singular) X
24-1 1st Stage ON Alarm X X
Over fluxing U/f
24-2 2st Stage ON Trip X X X X
Voltage transformer failure 60FL VTS 1st Stage ON Alarm X X
Inadvertent Energization 50/27 I.En 1st Stage ON Trip Blocked X X X X
Breaker failure 50BF I>BF 1st Stage ON Trip & X X X X
Trip circuit supervision 74TC - ON Alarm X X
Relay Fault (watchdog) - ON Alarm X(singular)
Signals FROM STCS
Generator Overload
& Excitation Transf. over temp. Tripped Trip &32L1 X X X X X
(Ch.2)
Turbine Tripped (Ch.2)
(38 bearing temperature)
(26 coolant temperature) Trip &32L1 X X X X X
(39 Shaft vibration supervision)
(emergency shutdown))
Signals FROM EXCITATION SYSTEM
Trip from excitation Trip X X X X X
64-R1 U<R Alarm X X
Rotor Earth Fault
64-R2 U<<R Trip X X X X X
Signals FROM PLANT SYSTEMS
S.S CH. 2 trip command Trip X X X X X
Line prot. Backup protection trip Trip X X X X X
STG enclosure fire protection trip Trip X X X X X
Electrical Protections Signal
Siemens 7UT6131-5EB92-1AA0+L0A
ANSI IEC En. ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↑ ↑ ↑ ↑ ↑ ↑ ↑
Type
I-Diff>>
Overall differential 87O - ON Trip X X X X X
I-Diff>
Relay Fault (watchdog) - ON Alarm X(singular)
Signals FROM Siemens
7PA3042-1AA00-1
Trip circuit supervision( 74TC - ON Alarm X X
Plant. fire protection panel trip Trip X X X X X
Excitation transformer feeder trip Trip X X X X X
*For 94 X Normal STOP or Turbine Tripped the HV breaker will be open by STCS open command
** Signal duplicate inside protection panel
*** VT MCB serial signal to STCS
FTM Doc. n. TI A512996 rev.5
2.2 MAIN TRANSFORMER PROTECTION TRIPPING MATRIX

Main Transformer protection Trip Matrix


DIGITAL OUTPUTS FROM MAIN TRASFORMER PROTECTION PANEL LOCK OUT RELAY

Trip to
Trip to HV Trip to HV Trip to Trip to HV breaker HV Line
6.6 KV HV CBF start Trip MV
Output digital Line Line excitation excitation Signal to Signal to Lock out start breaker
Excitation from power Breaker Unit Avail. Avail. Avail. Avail. Avail.
trips Breaker Breaker system system STCS PMS from power interlock
transf. plant Transformer
(Ch. 1) (Ch. 2) (Ch. 1) (Ch. 2) plant close com.
Breaker

Signal Type NO(1-2) NO(3-4) NO(5) NO(6) NO(7) NO(8) NO(9) NO(10) NO(11) NO(12) NO(13) NC(1) NC(3) NC(3) NC(4) NC(5)

Lock Out
Relay 86 X X X X X X X X X X X
MT1

Lock Out
Relay 86 X X X X X X X X X X X
MT2

DIGITAL OUTPUTS FROM MAIN TRASFORMER PROTECTION PANEL TRIP RELAYS

Trip to Trip to
Output digital Turbine Turbine Signal to
Avail.
trips (STCS) (STCS) PMS
(Ch. 1) (Ch. 2)

Signal Type NC(1) NC(2) NO(3) NO(4)

K4 T1 X X X

K4 T2 X X X

NOTE:

Regarding Generator, main & unit transformer protections system, in case of the both DC power supply failure or
both the protection relays failure (watchdog signals of the system A&B), the redundant trip signals shall be sent
to HV C.B & also Excitation system through fail safe NC contacts.
MAIN TRANSFORMER PROTECTION RELAY (A) TRIPPING MATRIX
Trip to Cumulative Cumulative Alarm &
Trip to Common Common Trip trip to
lock out Alarm to STCS to STCS STCS
K4T1/2
86MT1/2 (digital) (digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑ ↑
Type
7UT6331-5EB92-1BAO+L0A
I-Diff>> -
Differential Protection 87-T
I-Diff>
ON Trip X X X X

HV Restricted Earth Fault


87R Ido 1st Stage ON Trip X X X X
protection

HV Neutral Earth Fault


51N IE> 1st Stage ON Trip X X X X
protection
HV Inverse Time & I> 1st Stage ON Trip X X X X
Instantaneous overcurrent 50/51
I>> 2st Stage ON Trip X X X X
protection
Relay Fault (watchdog) - ON Alarm X(singular)

Trip circuit supervision 74TC ON Alarm X X


External digital Alarm/Trip
Input
Signals FROM TRANSFORMER
Winding Temperature HV
49W-1 ϴ>> 2st Stage ON Trip X X X
2ND STAGE
Winding Temperature LV
49W-2 ϴ>> 2st Stage ON Trip X X X
2ND STAGE
Oil Temperature 26 Oil ϴ>> 2st Stage ON Trip X X X
Pressure Relief Device Main
63-1 2st Stage ON Trip X X X X
Tank
Pressure Relief Device OLTC 63-2 2st Stage ON Trip X X X X
Transformer Buchholtz 80-2 2st Stage ON Trip X X X X
On Load Tap Changer
80-2 2st Stage ON Trip X X X X
Buchholtz
NON-RETURN VALVE ON Trip X X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X X
MAIN TRANSFORMER PROTECTION RELAY (B) TRIPPING MATRIX
Trip to Cumulative Cumulative Alarm &
Trip to Common Common Trip trip to
lock out Alarm to STCS to STCS STCS
K4T1/2
86MT1/2 (digital) (digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑ ↑
Type
7UT6331-5EB92-1BAO+L0A
I-Diff>> -
Differential Protection 87-T
I-Diff>
ON Trip X X X X

HV Restricted Earth Fault


87R Ido 1st Stage ON Trip X X X X
protection

HV Neutral Earth Fault


51N IE> 1st Stage ON Trip X X X X
protection
HV Inverse Time & I> 1st Stage ON Trip X X X X
Instantaneous overcurrent 50/51
I>> 2st Stage ON Trip X X X X
protection
Relay Fault (watchdog) - ON Alarm X(singular)

Trip circuit supervision 74TC ON Alarm X X


External digital Alarm/Trip
Input
Signals FROM TRANSFORMER
Winding Temperature HV
49W-1 ϴ>> 2st Stage ON Trip X X X
2ND STAGE
Winding Temperature LV
49W-2 ϴ>> 2st Stage ON Trip X X X
2ND STAGE
Oil Temperature 26 Oil ϴ>> 2st Stage ON Trip X X X
Pressure Relief Device Main
63-1 2st Stage ON Trip X X X X
Tank
Pressure Relief Device OLTC 63-2 2st Stage ON Trip X X X X
Transformer Buchholtz 80-2 2st Stage ON Trip X X X X
On Load Tap Changer
80-2 2st Stage ON Trip X X X X
Buchholtz
NON-RETURN VALVE ON Trip X X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X X
2.3 UNIT TRANSFORMER PROTECTION TRIPPING MATRIX

Unit Transformer protection Trip Matrix


DIGITAL OUTPUTS FROM UNIT TRASFORMER PROTECTION PANEL LOCK OUT RELAY

Trip to
Trip to HV Trip to HV Trip to Trip to HV breaker HV CBF HV Line
6.6 KV Trip MV
Output digital Line Line excitation excitation Signal to Signal to Lock out start from breaker
Excitation Breaker Unit Avail. Avail. Avail. Avail. Avail.
trips Breaker Breaker system system STCS PMS start from power interlock
transf. Transformer
(Ch. 1) (Ch. 2) (Ch. 1) (Ch. 2) power plant plant close com.
Breaker

Signal Type NO(1-2) NO(3-4) NO(5) NO(6) NO(7) NO(8) NO(9) NO(10) NO(11) NO(12) NO(13) NC(1) NC(3) NC(3) NC(4) NC(5)

Lock Out
Relay 86 X X X X X X X X X X X
UT1

Lock Out
Relay 86 X X X X X X X X X X X
UT2

DIGITAL OUTPUTS FROM UNIT TRASFORMER PROTECTION PANEL TRIP RELAYS

Trip to Trip to
Output digital Turbine Turbine Signal to
Avail.
trips (STCS) (STCS) PMS
(Ch. 1) (Ch. 2)

Signal Type NC(1) NC(2) NO(3) NO(4)

K4 T1 X X X

K4 T2 X X X

NOTE:

Regarding Generator, main & unit transformer protections system, in case of the both DC power supply failure or
both the protection relays failure (watchdog signals of the system A&B), the redundant trip signals shall be sent
to HV C.B & also Excitation system through fail safe NC contacts.
UNIT TRANSFORMER PROTECTION RELAY (A) TRIPPING MATRIX
Cumulative Cumulative Alarm &
Trip to
Trip to Common Alarm Common trip to
lock out to STCS Trip to STCS STCS
K4T1/2
86UT1/2 (digital) (digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑ ↑
Type
7UT6331-5EB92-1BA0+L0A
I-Diff>>
Differential Protection 87-T
I-Diff>
- ON Trip X X X X

Restricted earth fault


87R Ido 1st Stage ON Trip X X X X
protection

LV Overcurrent
Protection for Earth 50G IE> 1st Stage ON Trip X X X X
Current
HV Inverse Time & I> 1st Stage ON Trip X X X X
Instantaneous 50/51
I>> 2st Stage ON Trip X X X X
overcurrent protection
Relay Fault (watchdog) - ON Alarm X(singular)

Trip circuit supervision 74TC ON Alarm X X


External digital
Alarm/Trip Input
Signals FROM TRANSFORMER
Winding Temperature
49 W ϴ> ON Trip X X X
LV side
Oil Temperature 26 Oil ϴ> ON Trip X X X
Pressure Relief Device
63 ON Trip X X X X
Main Tank
Transformer Buchholtz 80-2 2st Stage ON Trip X X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X X

The most significant signal from the Buchholtz is the second stage trip, which is used to detect worse transformer’s failure.
UNIT TRANSFORMER PROTECTION RELAY (B) TRIPPING MATRIX
Cumulative Cumulative Alarm &
Trip to
Trip to Common Alarm Common trip to
lock out to STCS Trip to STCS STCS
K4T1/2
86UT1/2 (digital) (digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑ ↑
Type
7UT6331-5EB92-1BA0+L0A
I-Diff>>
Differential Protection 87-T
I-Diff>
- ON Trip X X X X

Restricted earth fault


87R Ido 1st Stage ON Trip X X X X
protection

LV Overcurrent
Protection for Earth 50G IE> 1st Stage ON Trip X X X X
Current
HV Inverse Time & I> 1st Stage ON Trip X X X X
Instantaneous 50/51
I>> 2st Stage ON Trip X X X X
overcurrent protection
Relay Fault (watchdog) - ON Alarm X(singular)

Trip circuit supervision 74TC ON Alarm X X


External digital
Alarm/Trip Input
Signals FROM TRANSFORMER
Winding Temperature
49 W ϴ> ON Trip X X X
LV side
Oil Temperature 26 Oil ϴ> ON Trip X X X
Pressure Relief Device
63 ON Trip X X X X
Main Tank
Transformer Buchholtz 80-2 2st Stage ON Trip X X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X X

The most significant signal from the Buchholtz is the second stage trip, which is used to detect worse transformer’s failure.
2.4 STATION TRANSFORMER PROTECTION TRIPPING MATRIX

Station Transformer protection Trip Matrix


DIGITAL OUTPUTS FROM STATION TRASFORMER PROTECTION PANEL LOCK OUT RELAY

Trip to GTG Trip to GTG Trip to GTG Trip to GTG Trip to Trip to Trip to Trip to
Generator Generator Generator Generator existing Station GTG GTG
Signal Signal
protection protection protection protection Unit Aux transfor Generator Generator
Output digital trips lock out K701 lock out K702 lock out K721 lock out K722
Avail. Avail. to to Avail. Avail. Avail. Avail. Avail. Avail.
transform mer prot. prot.
(Trip HV CB (Trip GEN CB (Trip HV CB (Trip GEN CB DCS PMS
er 6.6KV 6.6KV 7UM622 7UM622
(Ch.1)) (Ch.1)) (Ch.2)) (Ch.2)) C.B. C.B. (F11) (F21)
Signal Type NO(1) NO(2) NO(3) NO(4) NO(5) NO(6) NO(7) NO(8) NO(9) NO(10) NO(11) NO(12) NO(13) NC(1) NC(3) NC(3) NC(4) NC(5)

Lock Out Relay


86 ST1 X X X X X X X X X X

Lock Out Relay


86 ST2 X X X X X X X X X X

NOTE:

Regarding Station transformer protections system, in case of the both DC power supply failure or both the
protection relays failure (watchdog signals of the system A&B), the redundant trip signals shall be sent to GTG
lockout K701/K721 and K702/K722 through fail safe NC contacts.
STATION TRANSFORMER PROTECTION RELAY (A) TRIPPING MATRIX
Cumulative
Cumulative Common
Alarm &
Trip to
Common trip to trip to
lock out Alarm to DCS
DCS DCS
86ST1/2 (digital)
(digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑
Type
7UT6331-5EB92-1BA0+L0A
I-Diff>>
Differential Protection 87-T
I-Diff>
- ON Trip X X X

Restricted earth fault


87R Ido 1st Stage ON Trip X X X
Protection
LV Overcurrent
Protection for Earth 50G IE> 1st Stage ON Trip X X X
Current
HV Inverse Time & I> 1st Stage ON Trip X X X
Instantaneous 50/51
I>> 2st Stage ON Trip X X X
overcurrent protection
Relay Fault (watchdog) - ON Alarm X(singular)

Trip circuit supervision 74TC ON Alarm X X


External digital
Alarm/Trip Input
Signals FROM TRANSFORMER
Winding Temperature 49 W ϴ> ON Trip X X X
Oil Temperature 26 Oil ϴ> ON Trip X X X
Pressure Relief Device
63 ON Trip X X X
Main Tank
Transformer Buchholtz 80-2 2st Stage ON Trip X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X

The most significant signal from the Buchholtz is the second stage trip, which is used to detect worse transformer’s failure.
STATION TRANSFORMER PROTECTION RELAY (B) TRIPPING MATRIX
Cumulative
Cumulative Common
Alarm &
Trip to
Common trip to trip to
lock out Alarm to DCS
DCS DCS
86ST1/2 (digital)
(digital) (serial)
Electrical Protections
Signal
Siemens ANSI IEC Enabling ↑ ↑ ↑
Type
7UT6331-5EB92-1BA0+L0A
I-Diff>>
Differential Protection 87-T
I-Diff>
- ON Trip X X X

Restricted earth fault


87R Ido 1st Stage ON Trip X X X
Protection
LV Overcurrent
Protection for Earth 50G IE> 1st Stage ON Trip X X X
Current
HV Inverse Time & I> 1st Stage ON Trip X X X
Instantaneous 50/51
I>> 2st Stage ON Trip X X X
overcurrent protection
Relay Fault (watchdog) - ON Alarm X(singular)
Trip circuit supervision 74TC ON Alarm X X
External digital
Alarm/Trip Input
Signals FROM TRANSFORMER
Winding Temperature 49 W ϴ> ON Trip X X X
Oil Temperature 26 Oil ϴ> ON Trip X X X
Pressure Relief Device
63 ON Trip X X X
Main Tank
Transformer Buchholtz 80-2 2st Stage ON Trip X X X
Signals FROM PLANT SYSTEMS
Transform. fire protection panel trip ON Trip X X X

The most significant signal from the Buchholtz is the second stage trip, which is used to detect worse transformer’s failure.